This document contains configuration parameters for a UPC (Turbine Speed Governor Controller). It includes parameters grouped into sections for general configuration, PID control, turbine actuator control, speed thresholds, head measurement, simulation mode, generator control, Modbus communication, timeouts, turbine speed settings, local manual control ramp time, frequency coupling threshold, PID gains for synchronization and load control, isolation mode settings, output settings, power input settings, power limitation settings, and speed variation thresholds. The values for each parameter are also provided.
This document contains configuration parameters for a UPC (Turbine Speed Governor Controller). It includes parameters grouped into sections for general configuration, PID control, turbine actuator control, speed thresholds, head measurement, simulation mode, generator control, Modbus communication, timeouts, turbine speed settings, local manual control ramp time, frequency coupling threshold, PID gains for synchronization and load control, isolation mode settings, output settings, power input settings, power limitation settings, and speed variation thresholds. The values for each parameter are also provided.
This document contains configuration parameters for a UPC (Turbine Speed Governor Controller). It includes parameters grouped into sections for general configuration, PID control, turbine actuator control, speed thresholds, head measurement, simulation mode, generator control, Modbus communication, timeouts, turbine speed settings, local manual control ramp time, frequency coupling threshold, PID gains for synchronization and load control, isolation mode settings, output settings, power input settings, power limitation settings, and speed variation thresholds. The values for each parameter are also provided.
CONFIG T.SLG General configuration Access=4 Value = 69
> POW_FDB Power Feedback Value = 1 > WIR_INP Wired input Value = 0 > HEAD_MSR Head measurement Value = 1 > LO_4/20 Opening limiter in 4/20mA Value = 0 > R6 Synchronisation choice by R6 Value = 0 > WIRE_LA Wired LOCAL AUTO control Value = 0 > SV Speed Thresholds Value = 1 > SPC_AUTM SPC autonomous mode enable Value = 0 PID_CNF PID bloc configuration Access=0 Value = 0 > SY_AUTO Automatic synchronisation Value = 0 TAC_CNF TAC bloc configuration Access=4 Value = 2 > FG1 TCTT FG1 measurement on sensor Value = 0 > FG2 AVAI FG2 on sensor available Value = 1 > FG1_LOST FG1 desable lost detection Value = 0 > FG2_LOST FG2 desable lost detection Value = 0 > FR_LOST FR desable lost detection Value = 0 SPT_CFG Speed threshold Access=3 Value = 1 > SP_TH1 Output #1 inverted Value = 1 > SP_TH2 Output #2 inverted Value = 0 > SP_TH3 Output #3 inverted Value = 0 > SP_TH4 Output #4 inverted Value = 0 HED_CNF Head measurement configuration Access=4 Value = 1 > MDB_MSR MODBUS measurement Value = 1 > UP_DOWN Upstream and downstream level Value = 0 SIMUL Simulation mode Access=4 Value = 0 > SIMUL T.SLG in simulation mode Value = 0 > Isolated Simulation réseau isolé Value = 0 GBF_CNF GBF bloc configuration Access=3 Value = 0 > SINUS Sinus Value = 0 > SQUARE Square Value = 0 > TRI Triangle Value = 0 > FG Unit frequency Value = 0 > PI PI bloc Value = 0 > CSC CSC (before dispatching) Value = 0
TO_TPLC Time out of TPLC link (s) Access=3 Value=5.0 (min=0.05,max=60.0) RPM_NOM Turbine RPM at nominal frequency Access=0 Value=300.0 (min=0.0,max=10000.0) RPM_MIN RPM display lowest value (rpm) Access=0 Value=0.0 (min=0.0,max=10000.0) RPM_MAX RPM display highest value (rpm) Access=0 Value=600.0 (min=0.0,max=10000.0) LM_RMPTI LOCAL MANU - Ramp time (s) Access=0 Value=60.0 (min=0.0,max=1499.0) FQ_CPL Freq. coupling threshold (Norm) Access=3 Value=0.9 (min=0.0,max=2.0) Sn_Kd Differential gain Access=0 Value=9.0 (min=0.0,max=10.0) Sync_Kp Prop gain - Synchronisation Access=0 Value=2.0 (min=0.0,max=10.0) Sync_Td Deriv time - Synchronisation(s) Access=0 Value=0.17 (min=0.0,max=10.0) Sync_Ti Integr time - Synchronisat. (s) Access=0 Value=30.0 (min=0.0,max=2500.0) Intd_Kp Prop gain - Interconnected Access=0 Value=4.0 (min=0.0,max=10.0) Intd_Td Deriv time - Interconnected (s) Access=0 Value=0.1 (min=0.0,max=10.0) Intd_Ti Integr time - Interconnected(s) Access=0 Value=12.0 (min=0.0,max=2500.0) Intd_BP Permanent droop - Interconnected Access=0 Value=0.038 (min=0.0,max=0.2) Isol_Kp Prop gain - Isolated Access=0 Value=1.23 (min=0.0,max=10.0) Isol_Td Deriv time - Isolated (s) Access=0 Value=0.53 (min=0.0,max=10.0) Isol_Ti Integr time - Isolated(s) Access=0 Value=4.3 (min=0.0,max=2500.0) Isol_BP Permanent droop - Isolated Access=0 Value=0.053 (min=0.0,max=0.2) Sync_TCF Frequ. setter evolution time (s) Access=0 Value=60.0 (min=1.0,max=2000.0) SpLd_TCF Load setter evolution time (s) Access=0 Value=180.0 (min=1.0,max=2000.0) SpLd_LLM Load setter Low limitation Access=3 Value=-1.0 (min=-1.0,max=1.0) VT_RPAR Sluice evolution time (s) Access=3 Value=50.0 (min=1.0,max=2999.0) LA_POSA Start stop evolution (Norm) Access=3 Value=0.05 (min=0.0,max=1.0) LA_POSF Stop threshold detection (Norm) Access=3 Value=0.01 (min=0.0,max=1.0) CF_PLAG Freq. modification width (Norm) Access=3 Value=0.1 (min=0.05,max=1.0) VT_OMAV Opening in speed no load Access=3 Value=0.0 (min=0.0,max=1.0) RV_TMAV Delay on speed no load (s) Access=3 Value=0.5 (min=0.0,max=5.0) RES_GLI Slide coefficient (s) Access=3 Value=-10.0 (min=-100.0,max=100.0) VT_ITA0 Default insensitivity (Norm) Access=0 Value=0.0 (min=0.0,max=1.0) VT_ITA1 Insensitivity with R4 (Norm) Access=0 Value=0.0 (min=0.0,max=1.0) RV_SEP1 Fast load intak thres. 1(Norm) Access=3 Value=4.0E-4 (min=0.0,max=0.1) RV_SEP2 Fast load intak thres. 2(Norm) Access=3 Value=8.0E-4 (min=0.0,max=0.1) LO_DEM Opening limit on start up Access=0 Value=0.15 (min=0.0,max=1.0) LO_RABT Closing limit opening Access=0 Value=0.14 (min=0.0,max=1.0) LO_RPLI Fallback limit opening Access=0 Value=1.0 (min=0.0,max=1.0) LO_TIM Ramp time of incremental LO (s) Access=3 Value=60.0 (min=5.0,max=500.0) VT_SRA Closing speed threshold (Norm) Access=3 Value=0.75 (min=0.0,max=2.0) VT_PID OL disabling threshold (Norm) Access=3 Value=0.995 (min=0.0,max=2.0) FREQ_REF Frequency main reference (Hz) Access=3 Value=60.0 (min=1.0,max=120.0) FG_TGR FG filter time (s) Access=3 Value=0.1 (min=0.0,max=20.0) FG_PRFQ Freq. threshold prediv. (Norm) Access=3 Value=0.9 (min=0.0,max=2.0) FG2_PRD Measurement number by period Access=3 Value=30.0 (min=1.0,max=200.0) FG2_FRN Sens. freq. at nominal speed(Hz) Access=3 Value=150.0 (min=1.0,max=3500.0) FG_DIFMX Max FG1/2 freq. difference (Hz) Access=3 Value=5.0 (min=0.0,max=50.0) FG_DISC Freq. min discrepancy detect(Hz) Access=3 Value=20.0 (min=0.0,max=100.0) FG_TDEM Speed appearance time delay (s) Access=3 Value=15.0 (min=0.0,max=999999.0) FG_SLDF No speed threshold (Norm) Access=3 Value=0.05 (min=0.0,max=2.0) FR_TGR FR filter time (s) Access=3 Value=0.1 (min=0.0,max=20.0) FG_TFD FG Thres. fault detection (norm) Access=3 Value=0.2 (min=0.0,max=3.0) PW_MAX Max unit power (MW) (max head) Access=0 Value=237.0 (min=0.0010,max=1000.0) IN_PW_TF Power filter time constant (s) Access=0 Value=0.5 (min=0.0,max=20.0) IN_PW_LC Power Input low raw value Access=3 Value=0.0 (min=-1.0,max=2.0) IN_PW_HC Power Input high raw value Access=3 Value=1.0 (min=-1.0,max=2.0) IN_PW_LV Power Input low value (MW) Access=3 Value=-50.0 (min=-1000.0,max=100.0) IN_PW_HV Power Input high value (MW) Access=3 Value=250.0 (min=0.0,max=1000.0) IN_PW_TL Power fail. detect. time lag (s) Access=3 Value=5.0 (min=0.0,max=1000.0) OU_PW_4 Power value for 4mA output (MW) Access=3 Value=-50.0 (min=-1000.0,max=1000.0) OU_PW_20 Power val. for 20mA output (MW) Access=3 Value=250.0 (min=0.0,max=1000.0) PW_LIND Power min indicator scale (MW) Access=3 Value=-50.0 (min=-1000.0,max=100.0) PW_HIND Power max indicator scale(MW) Access=3 Value=250.0 (min=0.0,max=2000.0) LW_TF Pw lim - Closing mov. time (s) Access=3 Value=10.0 (min=1.0,max=200.0) LW_KP Power limiter - Prop. gain Access=3 Value=0.1 (min=0.1,max=10.0) LW_TI Pw lim - Integ. action time (s) Access=3 Value=100.0 (min=0.0,max=2999.0) LW_LIM Power limitation (MW) Access=0 Value=236.0 (min=0.0,max=1000.0) OU_FL_4 Freq. setpoint 4mA out. (Norm) Access=3 Value=0.9 (min=0.0,max=2.0) OU_FL_20 Freq. setpoint 20mA out. (Norm) Access=3 Value=1.1 (min=0.0,max=2.0) OU_LD_4 Load order for 4mA out. (Norm) Access=3 Value=-1.0 (min=-2.0,max=2.0) OU_LD_20 Load order for 20mA out. (Norm) Access=3 Value=1.0 (min=-2.0,max=2.0) OU_LO_4 LO for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0) OU_LO_20 LO for 20mA output (Norm) Access=3 Value=1.0 (min=-1.0,max=2.0) OU_FG_4 Unit freq. for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0) OU_FG_20 Unit freq. for 20mA outpt (Norm) Access=3 Value=2.0 (min=-1.0,max=3.0) OU_FR_4 Grid freq. for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0) OU_FR_20 Grid freq. for 20mA outpt (Norm) Access=3 Value=2.0 (min=-1.0,max=3.0) SV_SD1 Falling threshold SV1 (Norm) Access=3 Value=0.25 (min=0.0,max=3.0) SV_SM1 Rising threshold SV1 (Norm) Access=3 Value=0.3 (min=0.0,max=3.0) SV_SD2 Falling threshold SV2 (Norm) Access=3 Value=0.5 (min=0.0,max=3.0) SV_SM2 Rising threshold SV2 (Norm) Access=3 Value=0.4 (min=0.0,max=3.0) SV_SD3 Falling threshold SV3 (Norm) Access=3 Value=1.51 (min=0.0,max=3.0) SV_SM3 Rising threshold SV3 (Norm) Access=3 Value=1.53 (min=0.0,max=3.0) SV_SD4 Falling threshold SV4 (Norm) Access=3 Value=0.01 (min=0.0,max=3.0) SV_SM4 Rising threshold SV4 (Norm) Access=3 Value=3.0 (min=0.0,max=3.0) FO_1_NB Channel 1 - Test point Id Access=0 Value=1.0 (min=0.0,max=255.0) FO_1_TF Channel 1 - Filter time const(s) Access=0 Value=0.0 (min=0.0,max=1000.0) FO_1_MIN Channel 1 - Min val Access=0 Value=-1.0 (min=-1000.0,max=1000.0) FO_1_MAX Channel 1 - Max val Access=0 Value=1.0 (min=-1000.0,max=1000.0) FO_2_NB Channel 2 - Test point Id Access=0 Value=1.0 (min=0.0,max=255.0) FO_2_TF Channel 2 - Filter time const(s) Access=0 Value=0.0 (min=0.0,max=1000.0) FO_2_MIN Channel 2 - Min val Access=0 Value=-1.0 (min=-1000.0,max=1000.0) FO_2_MAX Channel 2 - Max val Access=0 Value=1.0 (min=-1000.0,max=1000.0) CH_REPLI Head - Fallback value (m) Access=0 Value=327.17 (min=0.0,max=9999.0) CH_LIND Head min indicator scale Access=3 Value=0.0 (min=0.0,max=1000.0) CH_HIND Head max indicator scale Access=3 Value=400.0 (min=0.0,max=1000.0) LW_SCND Conditioning threshold Access=3 Value=0.05 (min=0.0,max=1.0) CS_TCF Compensator evolution time (s) Access=0 Value=30.0 (min=1.0,max=2999.0) CS_POSC Turb - Compensator positioning Access=0 Value=0.0 (min=0.0,max=1.0) PM_POSC Pump - Compensator positioning Access=0 Value=0.0 (min=0.0,max=1.0) VT_TMRI Delay for freq netw isolation Access=0 Value=2.0 (min=0.0,max=1000.0) ISOL_FTH Freq Threshold to isolated netw Access=0 Value=0.1 (min=0.0,max=1.0) ISOL_VAR Freq varaition to isolated netw Access=0 Value=0.1 (min=0.0,max=1.0) ISOL_VTM Time for ISOL_VAR detect (s) Access=0 Value=5.0 (min=1.0,max=7.0) GBF_PER Signal period (s) Access=3 Value=9999.0 (min=1.0,max=9999.9) GBF_MIN Minimal signal value (Norm) Access=3 Value=0.0 (min=-0.1,max=0.1) GBF_MAX Maximal signal value (Norm) Access=3 Value=0.0 (min=-0.1,max=0.1)
LO_RBCH Fallback opening limit. / head Access=0 Lois Parameter Type
> Value : x y x min x max y min y max 0.5 9999.0 0.0 1.0 5.0 0.5 10.0 0.75 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 LO / CH Opening limitation versus head Access=0 Lois Parameter Type > Value : x y x min x max y min y max 0.85 9999.0 0.0 1.0 5.0 0.9 10.0 0.95 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 40.0 1.0 LW_W/CH Power limitation versus head Access=3 Lois Parameter Type > Value : x y x min x max y min y max 0.0 1000.0 10.0 1000.0 20.0 1000.0 30.0 1000.0 40.0 1000.0 40.0 1000.0 40.0 1000.0 40.0 1000.0 40.0 1000.0 40.0 1000.0 PW_O/nW Opening versus nominal power Access=3 Lois Parameter Type > Value : x y x min x max y min y max 0.0 1.0 0.25 0.5 1.0 1.0 1.0 1.0 1.0 1.0 1.0
SPC01
CONFIG_A SPC Alstom configuration Access=4 Value = 144
> DUAL_CA Dual Can Value = 0 > DIST_VA Distributing valve Value = 0 > SE_RED Servomotor sensor redundancy Value = 0 > VA_RED Valve sensor redundancy Value = 0 > POW_2Q 2Q power output Value = 1 > POW_4Q 4Q power output Value = 0 > POW_MAV mA/V power output Value = 0 > MAN_CTR Manual control Value = 1 CONFIG_B SPC Maintenance configuration Access=3 Value = 0 > KD_INV Actuator control inversion Value = 0 > Value = 0 > SAT_OFF Saturation fault not signalled Value = 0 > SSR_GRAD Fast deviation detection Value = 0 > SSR_DEV Slow deviation detection Value = 0
KP Proportional gain Access=0 Value=20.0 (min=0.0,max=200.0)
TD Derivative time (s) Access=0 Value=0.0 (min=0.0,max=2000.0) TI Integral time (s) Access=0 Value=20.0 (min=0.0,max=200.0) KD Derivative action Access=0 Value=1.0 (min=1.0,max=20.0) RTA Electrical zero Access=0 Value=0.59 (min=-1.0,max=1.0) VA_KP Distr. valve loop - Prop gain Access=0 Value=0.0 (min=0.0,max=200.0) VA_MIN Distr. valve - Min limitation Access=0 Value=-2.0 (min=-2.0,max=0.0) VA_MAX Distr. valve - Max limitation Access=0 Value=2.0 (min=0.0,max=2.0) VA_OSP Distr. valve - Equilib. Pos. Access=0 Value=0.0 (min=-1.0,max=1.0) SE_FILT Servomotor filter constant (s) Access=0 Value=0.0 (min=0.0,max=10.0) SE1_GAI Servomotor sensor 1 - Gain Access=0 Value=1.02040816E-4 (min=-10.0,max=10.0) SE1_OFF Servomotor sensor 1 - Offset Access=0 Value=-0.012142858 (min=-10.0,max=10.0) SE2_GAI Servomotor sensor 2 - Gain Access=0 Value=1.0E-4 (min=-10.0,max=10.0) SE2_OFF Servomotor sensor 2 - Offset Access=0 Value=0.0 (min=-10.0,max=10.0) SE_DISC Servomotor discrep. threshold Access=0 Value=0.01 (min=0.0,max=1.0) VA_FILT Distr. valv filter constant (s) Access=0 Value=0.0 (min=0.0,max=10.0) VA1_GAI Distr. valv sensor 1 - Gain Access=0 Value=2.0E-4 (min=-10.0,max=10.0) VA1_OFF Distr. valv sensor 1 - Offset Access=0 Value=-1.0 (min=-10.0,max=10.0) VA2_GAI Distr. valv sensor 2 - Gain Access=0 Value=2.0E-4 (min=-10.0,max=10.0) VA2_OFF Distr. valv sensor 2 - Offset Access=0 Value=-1.0 (min=-10.0,max=10.0) VA_DISC Distr. valv discrep. threshold Access=0 Value=0.01 (min=0.0,max=1.0) DIT_AMP Dither effect amplitude Access=0 Value=0.35 (min=0.0,max=1.0) TRK_THR Tracking error threshold (alarm) Access=0 Value=0.02 (min=0.0,max=2.0) TRK_TIM Tracking error detect time(s) Access=0 Value=30.0 (min=0.0,max=2000.0) OR_GAIN Servomotor position output- Gai Access=0 Value=10000.0 (min=-10000.0,max=20000.0) OR_OFFS Servomotor posit output-Offset Access=0 Value=0.0 (min=-10000.0,max=10000.0) MAN_RAM Manual control ramp (s) Access=0 Value=60.0 (min=0.0,max=200.0) INT_LIM Integral action limitation Access=0 Value=0.01 (min=0.0,max=1.0) PWM_MIN PWM minimum value Access=0 Value=500.0 (min=500.0,max=9500.0) PWM_MAX PWM maximum value Access=0 Value=9500.0 (min=500.0,max=9500.0) TRK_TRIP Tracking error threshold (trip) Access=0 Value=0.05 (min=0.0,max=1.0) RED_HOLD Max time to hold setpoint (s) Access=0 Value=2000.0 (min=0.0,max=2000.0)
SE_LINE Servomotor sensor linearisation Access=0 Lois Parameter Type
> Value : x y x min x max y min y max 0.0 1.0 0.08133 0.1 0.19143 0.2 0.30153 0.3 0.41102 0.4 0.51622 0.5 0.61561 0.6 0.71551 0.7 0.9001 0.9 0.9702 1.0