UPC

CONFIG T.SLG General configuration Access=4 Value = 69


> POW_FDB Power Feedback Value = 1
> WIR_INP Wired input Value = 0
> HEAD_MSR Head measurement Value = 1
> LO_4/20 Opening limiter in 4/20mA Value = 0
> R6 Synchronisation choice by R6 Value = 0
> WIRE_LA Wired LOCAL AUTO control Value = 0
> SV Speed Thresholds Value = 1
> SPC_AUTM SPC autonomous mode enable Value = 0
PID_CNF PID bloc configuration Access=0 Value = 0
> SY_AUTO Automatic synchronisation Value = 0
TAC_CNF TAC bloc configuration Access=4 Value = 2
> FG1 TCTT FG1 measurement on sensor Value = 0
> FG2 AVAI FG2 on sensor available Value = 1
> FG1_LOST FG1 desable lost detection Value = 0
> FG2_LOST FG2 desable lost detection Value = 0
> FR_LOST FR desable lost detection Value = 0
SPT_CFG Speed threshold Access=3 Value = 1
> SP_TH1 Output #1 inverted Value = 1
> SP_TH2 Output #2 inverted Value = 0
> SP_TH3 Output #3 inverted Value = 0
> SP_TH4 Output #4 inverted Value = 0
HED_CNF Head measurement configuration Access=4 Value = 1
> MDB_MSR MODBUS measurement Value = 1
> UP_DOWN Upstream and downstream level Value = 0
SIMUL Simulation mode Access=4 Value = 0
> SIMUL T.SLG in simulation mode Value = 0
> Isolated Simulation réseau isolé Value = 0
GBF_CNF GBF bloc configuration Access=3 Value = 0
> SINUS Sinus Value = 0
> SQUARE Square Value = 0
> TRI Triangle Value = 0
> FG Unit frequency Value = 0
> PI PI bloc Value = 0
> CSC CSC (before dispatching) Value = 0

SEL_MDB Modbus : RS485 (>=0) TCP/IP (<0) Access=4 Value=-1.0 (min=-1.0,max=1.0)


TO_TPLC Time out of TPLC link (s) Access=3 Value=5.0 (min=0.05,max=60.0)
RPM_NOM Turbine RPM at nominal frequency Access=0 Value=300.0 (min=0.0,max=10000.0)
RPM_MIN RPM display lowest value (rpm) Access=0 Value=0.0 (min=0.0,max=10000.0)
RPM_MAX RPM display highest value (rpm) Access=0 Value=600.0 (min=0.0,max=10000.0)
LM_RMPTI LOCAL MANU - Ramp time (s) Access=0 Value=60.0 (min=0.0,max=1499.0)
FQ_CPL Freq. coupling threshold (Norm) Access=3 Value=0.9 (min=0.0,max=2.0)
Sn_Kd Differential gain Access=0 Value=9.0 (min=0.0,max=10.0)
Sync_Kp Prop gain - Synchronisation Access=0 Value=2.0 (min=0.0,max=10.0)
Sync_Td Deriv time - Synchronisation(s) Access=0 Value=0.17 (min=0.0,max=10.0)
Sync_Ti Integr time - Synchronisat. (s) Access=0 Value=30.0 (min=0.0,max=2500.0)
Intd_Kp Prop gain - Interconnected Access=0 Value=4.0 (min=0.0,max=10.0)
Intd_Td Deriv time - Interconnected (s) Access=0 Value=0.1 (min=0.0,max=10.0)
Intd_Ti Integr time - Interconnected(s) Access=0 Value=12.0 (min=0.0,max=2500.0)
Intd_BP Permanent droop - Interconnected Access=0 Value=0.038 (min=0.0,max=0.2)
Isol_Kp Prop gain - Isolated Access=0 Value=1.23 (min=0.0,max=10.0)
Isol_Td Deriv time - Isolated (s) Access=0 Value=0.53 (min=0.0,max=10.0)
Isol_Ti Integr time - Isolated(s) Access=0 Value=4.3 (min=0.0,max=2500.0)
Isol_BP Permanent droop - Isolated Access=0 Value=0.053 (min=0.0,max=0.2)
Sync_TCF Frequ. setter evolution time (s) Access=0 Value=60.0 (min=1.0,max=2000.0)
SpLd_TCF Load setter evolution time (s) Access=0 Value=180.0 (min=1.0,max=2000.0)
SpLd_LLM Load setter Low limitation Access=3 Value=-1.0 (min=-1.0,max=1.0)
VT_RPAR Sluice evolution time (s) Access=3 Value=50.0 (min=1.0,max=2999.0)
LA_POSA Start stop evolution (Norm) Access=3 Value=0.05 (min=0.0,max=1.0)
LA_POSF Stop threshold detection (Norm) Access=3 Value=0.01 (min=0.0,max=1.0)
CF_PLAG Freq. modification width (Norm) Access=3 Value=0.1 (min=0.05,max=1.0)
VT_OMAV Opening in speed no load Access=3 Value=0.0 (min=0.0,max=1.0)
RV_TMAV Delay on speed no load (s) Access=3 Value=0.5 (min=0.0,max=5.0)
RES_GLI Slide coefficient (s) Access=3 Value=-10.0 (min=-100.0,max=100.0)
VT_ITA0 Default insensitivity (Norm) Access=0 Value=0.0 (min=0.0,max=1.0)
VT_ITA1 Insensitivity with R4 (Norm) Access=0 Value=0.0 (min=0.0,max=1.0)
RV_SEP1 Fast load intak thres. 1(Norm) Access=3 Value=4.0E-4 (min=0.0,max=0.1)
RV_SEP2 Fast load intak thres. 2(Norm) Access=3 Value=8.0E-4 (min=0.0,max=0.1)
LO_DEM Opening limit on start up Access=0 Value=0.15 (min=0.0,max=1.0)
LO_RABT Closing limit opening Access=0 Value=0.14 (min=0.0,max=1.0)
LO_RPLI Fallback limit opening Access=0 Value=1.0 (min=0.0,max=1.0)
LO_TIM Ramp time of incremental LO (s) Access=3 Value=60.0 (min=5.0,max=500.0)
VT_SRA Closing speed threshold (Norm) Access=3 Value=0.75 (min=0.0,max=2.0)
VT_PID OL disabling threshold (Norm) Access=3 Value=0.995 (min=0.0,max=2.0)
FREQ_REF Frequency main reference (Hz) Access=3 Value=60.0 (min=1.0,max=120.0)
FG_TGR FG filter time (s) Access=3 Value=0.1 (min=0.0,max=20.0)
FG_PRFQ Freq. threshold prediv. (Norm) Access=3 Value=0.9 (min=0.0,max=2.0)
FG2_PRD Measurement number by period Access=3 Value=30.0 (min=1.0,max=200.0)
FG2_FRN Sens. freq. at nominal speed(Hz) Access=3 Value=150.0 (min=1.0,max=3500.0)
FG_DIFMX Max FG1/2 freq. difference (Hz) Access=3 Value=5.0 (min=0.0,max=50.0)
FG_DISC Freq. min discrepancy detect(Hz) Access=3 Value=20.0 (min=0.0,max=100.0)
FG_TDEM Speed appearance time delay (s) Access=3 Value=15.0 (min=0.0,max=999999.0)
FG_SLDF No speed threshold (Norm) Access=3 Value=0.05 (min=0.0,max=2.0)
FR_TGR FR filter time (s) Access=3 Value=0.1 (min=0.0,max=20.0)
FG_TFD FG Thres. fault detection (norm) Access=3 Value=0.2 (min=0.0,max=3.0)
PW_MAX Max unit power (MW) (max head) Access=0 Value=237.0 (min=0.0010,max=1000.0)
IN_PW_TF Power filter time constant (s) Access=0 Value=0.5 (min=0.0,max=20.0)
IN_PW_LC Power Input low raw value Access=3 Value=0.0 (min=-1.0,max=2.0)
IN_PW_HC Power Input high raw value Access=3 Value=1.0 (min=-1.0,max=2.0)
IN_PW_LV Power Input low value (MW) Access=3 Value=-50.0 (min=-1000.0,max=100.0)
IN_PW_HV Power Input high value (MW) Access=3 Value=250.0 (min=0.0,max=1000.0)
IN_PW_TL Power fail. detect. time lag (s) Access=3 Value=5.0 (min=0.0,max=1000.0)
OU_PW_4 Power value for 4mA output (MW) Access=3 Value=-50.0 (min=-1000.0,max=1000.0)
OU_PW_20 Power val. for 20mA output (MW) Access=3 Value=250.0 (min=0.0,max=1000.0)
PW_LIND Power min indicator scale (MW) Access=3 Value=-50.0 (min=-1000.0,max=100.0)
PW_HIND Power max indicator scale(MW) Access=3 Value=250.0 (min=0.0,max=2000.0)
LW_TF Pw lim - Closing mov. time (s) Access=3 Value=10.0 (min=1.0,max=200.0)
LW_KP Power limiter - Prop. gain Access=3 Value=0.1 (min=0.1,max=10.0)
LW_TI Pw lim - Integ. action time (s) Access=3 Value=100.0 (min=0.0,max=2999.0)
LW_LIM Power limitation (MW) Access=0 Value=236.0 (min=0.0,max=1000.0)
OU_FL_4 Freq. setpoint 4mA out. (Norm) Access=3 Value=0.9 (min=0.0,max=2.0)
OU_FL_20 Freq. setpoint 20mA out. (Norm) Access=3 Value=1.1 (min=0.0,max=2.0)
OU_LD_4 Load order for 4mA out. (Norm) Access=3 Value=-1.0 (min=-2.0,max=2.0)
OU_LD_20 Load order for 20mA out. (Norm) Access=3 Value=1.0 (min=-2.0,max=2.0)
OU_LO_4 LO for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0)
OU_LO_20 LO for 20mA output (Norm) Access=3 Value=1.0 (min=-1.0,max=2.0)
OU_FG_4 Unit freq. for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0)
OU_FG_20 Unit freq. for 20mA outpt (Norm) Access=3 Value=2.0 (min=-1.0,max=3.0)
OU_FR_4 Grid freq. for 4mA output (Norm) Access=3 Value=0.0 (min=-1.0,max=2.0)
OU_FR_20 Grid freq. for 20mA outpt (Norm) Access=3 Value=2.0 (min=-1.0,max=3.0)
SV_SD1 Falling threshold SV1 (Norm) Access=3 Value=0.25 (min=0.0,max=3.0)
SV_SM1 Rising threshold SV1 (Norm) Access=3 Value=0.3 (min=0.0,max=3.0)
SV_SD2 Falling threshold SV2 (Norm) Access=3 Value=0.5 (min=0.0,max=3.0)
SV_SM2 Rising threshold SV2 (Norm) Access=3 Value=0.4 (min=0.0,max=3.0)
SV_SD3 Falling threshold SV3 (Norm) Access=3 Value=1.51 (min=0.0,max=3.0)
SV_SM3 Rising threshold SV3 (Norm) Access=3 Value=1.53 (min=0.0,max=3.0)
SV_SD4 Falling threshold SV4 (Norm) Access=3 Value=0.01 (min=0.0,max=3.0)
SV_SM4 Rising threshold SV4 (Norm) Access=3 Value=3.0 (min=0.0,max=3.0)
FO_1_NB Channel 1 - Test point Id Access=0 Value=1.0 (min=0.0,max=255.0)
FO_1_TF Channel 1 - Filter time const(s) Access=0 Value=0.0 (min=0.0,max=1000.0)
FO_1_MIN Channel 1 - Min val Access=0 Value=-1.0 (min=-1000.0,max=1000.0)
FO_1_MAX Channel 1 - Max val Access=0 Value=1.0 (min=-1000.0,max=1000.0)
FO_2_NB Channel 2 - Test point Id Access=0 Value=1.0 (min=0.0,max=255.0)
FO_2_TF Channel 2 - Filter time const(s) Access=0 Value=0.0 (min=0.0,max=1000.0)
FO_2_MIN Channel 2 - Min val Access=0 Value=-1.0 (min=-1000.0,max=1000.0)
FO_2_MAX Channel 2 - Max val Access=0 Value=1.0 (min=-1000.0,max=1000.0)
CH_REPLI Head - Fallback value (m) Access=0 Value=327.17 (min=0.0,max=9999.0)
CH_LIND Head min indicator scale Access=3 Value=0.0 (min=0.0,max=1000.0)
CH_HIND Head max indicator scale Access=3 Value=400.0 (min=0.0,max=1000.0)
LW_SCND Conditioning threshold Access=3 Value=0.05 (min=0.0,max=1.0)
CS_TCF Compensator evolution time (s) Access=0 Value=30.0 (min=1.0,max=2999.0)
CS_POSC Turb - Compensator positioning Access=0 Value=0.0 (min=0.0,max=1.0)
PM_POSC Pump - Compensator positioning Access=0 Value=0.0 (min=0.0,max=1.0)
VT_TMRI Delay for freq netw isolation Access=0 Value=2.0 (min=0.0,max=1000.0)
ISOL_FTH Freq Threshold to isolated netw Access=0 Value=0.1 (min=0.0,max=1.0)
ISOL_VAR Freq varaition to isolated netw Access=0 Value=0.1 (min=0.0,max=1.0)
ISOL_VTM Time for ISOL_VAR detect (s) Access=0 Value=5.0 (min=1.0,max=7.0)
GBF_PER Signal period (s) Access=3 Value=9999.0 (min=1.0,max=9999.9)
GBF_MIN Minimal signal value (Norm) Access=3 Value=0.0 (min=-0.1,max=0.1)
GBF_MAX Maximal signal value (Norm) Access=3 Value=0.0 (min=-0.1,max=0.1)

LO_RBCH Fallback opening limit. / head Access=0 Lois Parameter Type


> Value : x y x min x max y min y max
0.5 9999.0 0.0 1.0
5.0 0.5
10.0 0.75
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
LO / CH Opening limitation versus head Access=0 Lois Parameter Type
> Value : x y x min x max y min y max
0.85 9999.0 0.0 1.0
5.0 0.9
10.0 0.95
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
40.0 1.0
LW_W/CH Power limitation versus head Access=3 Lois Parameter Type
> Value : x y x min x max y min y max
0.0 1000.0
10.0 1000.0
20.0 1000.0
30.0 1000.0
40.0 1000.0
40.0 1000.0
40.0 1000.0
40.0 1000.0
40.0 1000.0
40.0 1000.0
PW_O/nW Opening versus nominal power Access=3 Lois Parameter Type
> Value : x y x min x max y min y max
0.0 1.0
0.25
0.5
1.0
1.0
1.0
1.0
1.0
1.0
1.0

SPC01

CONFIG_A SPC Alstom configuration Access=4 Value = 144


> DUAL_CA Dual Can Value = 0
> DIST_VA Distributing valve Value = 0
> SE_RED Servomotor sensor redundancy Value = 0
> VA_RED Valve sensor redundancy Value = 0
> POW_2Q 2Q power output Value = 1
> POW_4Q 4Q power output Value = 0
> POW_MAV mA/V power output Value = 0
> MAN_CTR Manual control Value = 1
CONFIG_B SPC Maintenance configuration Access=3 Value = 0
> KD_INV Actuator control inversion Value = 0
> Value = 0
> SAT_OFF Saturation fault not signalled Value = 0
> SSR_GRAD Fast deviation detection Value = 0
> SSR_DEV Slow deviation detection Value = 0

KP Proportional gain Access=0 Value=20.0 (min=0.0,max=200.0)


TD Derivative time (s) Access=0 Value=0.0 (min=0.0,max=2000.0)
TI Integral time (s) Access=0 Value=20.0 (min=0.0,max=200.0)
KD Derivative action Access=0 Value=1.0 (min=1.0,max=20.0)
RTA Electrical zero Access=0 Value=0.59 (min=-1.0,max=1.0)
VA_KP Distr. valve loop - Prop gain Access=0 Value=0.0 (min=0.0,max=200.0)
VA_MIN Distr. valve - Min limitation Access=0 Value=-2.0 (min=-2.0,max=0.0)
VA_MAX Distr. valve - Max limitation Access=0 Value=2.0 (min=0.0,max=2.0)
VA_OSP Distr. valve - Equilib. Pos. Access=0 Value=0.0 (min=-1.0,max=1.0)
SE_FILT Servomotor filter constant (s) Access=0 Value=0.0 (min=0.0,max=10.0)
SE1_GAI Servomotor sensor 1 - Gain Access=0 Value=1.02040816E-4
(min=-10.0,max=10.0)
SE1_OFF Servomotor sensor 1 - Offset Access=0 Value=-0.012142858
(min=-10.0,max=10.0)
SE2_GAI Servomotor sensor 2 - Gain Access=0 Value=1.0E-4 (min=-10.0,max=10.0)
SE2_OFF Servomotor sensor 2 - Offset Access=0 Value=0.0 (min=-10.0,max=10.0)
SE_DISC Servomotor discrep. threshold Access=0 Value=0.01 (min=0.0,max=1.0)
VA_FILT Distr. valv filter constant (s) Access=0 Value=0.0 (min=0.0,max=10.0)
VA1_GAI Distr. valv sensor 1 - Gain Access=0 Value=2.0E-4 (min=-10.0,max=10.0)
VA1_OFF Distr. valv sensor 1 - Offset Access=0 Value=-1.0 (min=-10.0,max=10.0)
VA2_GAI Distr. valv sensor 2 - Gain Access=0 Value=2.0E-4 (min=-10.0,max=10.0)
VA2_OFF Distr. valv sensor 2 - Offset Access=0 Value=-1.0 (min=-10.0,max=10.0)
VA_DISC Distr. valv discrep. threshold Access=0 Value=0.01 (min=0.0,max=1.0)
DIT_AMP Dither effect amplitude Access=0 Value=0.35 (min=0.0,max=1.0)
TRK_THR Tracking error threshold (alarm) Access=0 Value=0.02 (min=0.0,max=2.0)
TRK_TIM Tracking error detect time(s) Access=0 Value=30.0 (min=0.0,max=2000.0)
OR_GAIN Servomotor position output- Gai Access=0 Value=10000.0 (min=-10000.0,max=20000.0)
OR_OFFS Servomotor posit output-Offset Access=0 Value=0.0 (min=-10000.0,max=10000.0)
MAN_RAM Manual control ramp (s) Access=0 Value=60.0 (min=0.0,max=200.0)
INT_LIM Integral action limitation Access=0 Value=0.01 (min=0.0,max=1.0)
PWM_MIN PWM minimum value Access=0 Value=500.0 (min=500.0,max=9500.0)
PWM_MAX PWM maximum value Access=0 Value=9500.0 (min=500.0,max=9500.0)
TRK_TRIP Tracking error threshold (trip) Access=0 Value=0.05 (min=0.0,max=1.0)
RED_HOLD Max time to hold setpoint (s) Access=0 Value=2000.0 (min=0.0,max=2000.0)

SE_LINE Servomotor sensor linearisation Access=0 Lois Parameter Type


> Value : x y x min x max y min y max
0.0 1.0
0.08133 0.1
0.19143 0.2
0.30153 0.3
0.41102 0.4
0.51622 0.5
0.61561 0.6
0.71551 0.7
0.9001 0.9
0.9702 1.0