Abstract—Power System stability is an essential study in the not meeting active/reactive power demanded and acceptable
planning and operation of an efficient, economic, reliable and voltage at each systems bus. This state can further lead to
secure electric power system because it encompasses all the voltage collapse when all the voltage profile after
facet of power systems operations, from planning, to disturbance is below acceptable limits in an important part of
conceptual design stages of the project as well as during the the power systems such that the different part of the systems
systems operating life span. This paper presents different controllers are stressed beyond their operational limit. Thus,
scenario of power system stability studies on a modified IEEE ability of the systems to remain practically intact and regain
30-bus system which is subjected to different faults conditions. a state of operating equilibrium makes the system voltage
A scenario whereby the longest high voltage alternating
stable.
current (HVAC) line is replaced with a high voltage direct
current (HVDC) line was implemented. The results obtained Much research has been done on voltage stability
show that the HVDC line enhances system stability more analysis [1] , [2]. Improvement through the use of FACT
compared to the contemporary HVAC line. Dynamic analysis devices was discussed in [3]-[5]. The effect of the automatic
using RMS simulation tool was used on DigSILENT voltage regulator (AVR), on-load tap changers and power
PowerFactory. systems stabilizer (PSS) on voltage stability was discussed in
[6] and [7], while [8] and [9] discusses the impact of HVDC
Keywords—HVDC, CCT, dynamic voltage stability
links on voltage stability.
P + jQ = P 0 ¨¨ ¸¸ + Q 0 ¨¨ ¸¸
case of small disturbance around a steady state equilibrium ©U 0 ¹ ©U 0 ¹
point (xo, yo) and further eliminated to give (3). Static (4)
bifurcation, capable of causing voltage collapse will occur
when D is zero. Thus an assumption of D0 is always made
for dynamic bifurcation studies.
⋅
x = f (x, y) (1)
0 = g ( x, y ) (2)
dΔx −1
= ( A − BD C ) = A'Δx
dt (3)
Dynamic voltage stability can then be performed by
analysing the eigenvalues of Aǯ. (A, B, C and D are
appropriate dimensioned matrices) [1], [13], [14].
3 2α I V tI cos γ I − 3 X C I d
V dI =
π (5)
3 2α R V tR cos α R − 3 X C I d
V dR =
π (6)
B. Time-Domain Stability Simulation Fig. 7. Voltage Plot during fault on ‘Line 3_1’, cleared by switching off
the line after 100ms. (Without HVDC line)
Two operational scenarios were considered in this study.
The first scenario is when the power is being transmitted
using AC lines only, and the second scenario is when an
existing longest AC line is replaced with an HVDC line and
the results are depicted on a graph. Bus voltage and
generator excitation current are the main object of focus for
this study.
For the bus voltage magnitude graph, specific busbar that
are prone to voltage instability was selected rather than use
all the 30 buses of the network.
1) First scenario (without HVDC)
Different study cases was carried out while using the
time domain simulation to investigate the weakest area of the
network. This involve the use of critical clearing time to
observe the maximum time a fault can stay on each of the
element on the network (busbar and lines). Three phase short
circuit fault was placed on each of the busbar once at a time
and their CCT was estimated. It was observed that bus 8 has
the least critical time. The same process was also carried out
on the line (placing the fault at the beginning of the line) and
cleared by switching off the line. Fig. 8. Generators rotor angle (Without HVDC line)
The same three phase fault was carried out on ‘Line 3_1’
and the fault cleared by isolating the line after 120ms while
using HVDC line to interconnect ‘bus 1’ to ‘bus 28’, it was
found out that the system was stable even until it reaches a
maximum time of 150ms. Further increase of fault duration
resorted in convergence error. Fig. 15-17 shows the bus
voltage magnitude, generator rotor angle and excitation
current respectively.
A case of commutation failure occur at the inverter side
of the HVDC link during fault period, but with the help of
the converter selection mode by blocking the fault current
from transferring into the HVDC link, the systems was able
to maintain stability. HVDC systems thus help to increase
the time duration a fault can stay on the line before being
isolated from the systems.
All different study cases carried out on the systems prove
Fig. 11. Generator Rotor angle fault (Without HVDC line) the efficacy of HVDC link in power systems stability and
control during system disturbance.
that HVDC lines improve dynamic voltage stability of power
systems.
Though different FACTs devises and a well modelled
generator controller helps in enhancing voltage stability of a
system but cannot be compared to the benefit which HVDC
systems offers, such as; little line losses, long distance bulk
power transfer, immunity to cascading effect, bi-direction
power transfer, small right of way, asynchronous
interconnection etc. cost of constructing converter station
might be a little expensive for now, but the cost saved by
transmission line construction with associated losses in DC
systems outweigh the latter. And with the emergence of new
power electronic converter and well rugged controller,
HVDC system will be the best mode to transmit power due
to high efficiency and economics of transmission that it
offers.
REFERENCES
Fig. 14. Voltage Plot during fault on ‘Line 3_1’, cleared by switching off [1] G. Morison, B. Gao, and P. Kundur, "Voltage stability analysis using
the line after 150ms. (With HVDC line) static and dynamic approaches," Power Systems, IEEE Transactions
on, vol. 8, pp. 1159-1171, 1993.
[2] T. Van Cutsem and C. Vournas, Voltage stability of electric power
systems vol. 441: Springer Science & Business Media, 1998.
[3] M. Noroozian, L. Ängquist, M. Ghandhari, and G. Andersson,
"Improving power system dynamics by series-connected FACTS
devices," Power Delivery, IEEE Transactions on, vol. 12, pp. 1635-
1641, 1997.
[4] Y.-H. Song and A. Johns, Flexible ac transmission systems (FACTS):
IET, 1999.
[5] S. Gasperic and R. Mihalic, "The impact of serial controllable FACTS
devices on voltage stability," International Journal of Electrical
Power & Energy Systems, vol. 64, pp. 1040-1048, 2015.
[6] C. Vournas and M. Karystianos, "Load tap changers in emergency
and preventive voltage stability control," Power Systems, IEEE
Transactions on, vol. 19, pp. 492-498, 2004.
[7] Y. Wang, D. J. Hill, R. H. Middleton, and L. Gao, "Transient stability
enhancement and voltage regulation of power systems," Power
Systems, IEEE Transactions on, vol. 8, pp. 620-627, 1993.
Fig. 15. Generators rotor angle (With HVDC line) [8] D. L. H. Aik and G. Andersson, "Power stability analysis of multi-
infeed HVDC systems," Power Delivery, IEEE Transactions on, vol.
13, pp. 923-931, 1998.
[9] Hammad, "Stability and control of HVDC and AC transmissions in
parallel," Power Delivery, IEEE Transactions on, vol. 14, pp. 1545-
1554, 1999.
[10] DigSILENT PowerFactory: Power System Stability Seminar
DigSILENT Buyisa (Pty) Ltd.
[11] W. A. Oyekanmi, G. Radman, A. A. Babalola, and T. O. Ajewole,
"Effects of STATCOM on the critical clearing time of faults in multi-
machine power systems during transient stability analysis studies," in
Adaptive Science & Technology (ICAST), 2014 IEEE 6th
International Conference on, 2014, pp. 1-6.
[12] R. Kamdar, M. Kumar, and G. Agnihotri, "Transient stability analysis
and enhancement of ieee-9 bus system. Electrical & Computer
Engineering: An International Journal (ECIJ) Volume 3, Number 2,
June 2014"
[13] J. Chow and A. Gebreselassie, "Dynamic voltage stability analysis of
a single machine constant power load system," in Decision and
Fig. 16. Excitation current. (With HVDC line) Control, 1990., Proceedings of the 29th IEEE Conference on, 1990,
pp. 3057-3062.
[14] B. H. Lee and K. Y. Lee, "Dynamic and static voltage stability
V. CONCLUSION enhancement of power systems," Power Systems, IEEE Transactions
Impact of HVDC scheme on AC systems short term on, vol. 8, pp. 231-238, 1993.
voltage stability study was investigated in this study, and [15] DigSILENT PowerFactory: Technical Reference Documentation -
based on this study; it was found out that HVDC systems General Load, Gomaringen, Germany, 2013.
helps in enhancing voltage stability than the AC line, in that
it helps to improve the critical clearing/ isolating time for
disturbances on the systems. The effect of VDCOL in HVDC
link during systems disturbance was also analyzed. The
strategies for improving voltage stability are thus proposed;