Professional Documents
Culture Documents
Bayelsa State
Nigeria
May 2013
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 1
Executive Summary
TEKS Geotechnical Consultancy (Nigeria) Limited, Port Harcourt, Rivers State was commissioned by
HAALP Consult Limited Associates Limited provide specialist advice regarding a geotechnical
investigation of the subsurface at the proposed site of the Federal University, Otuoke, Bayelsa State for
the purpose of providing up to date information about soil conditions that could assist with the physical
planning of the university campus site and the design of appropriate foundation system for building
structures and infrastructure to be developed within the site . The field investigations commenced on
Wednesday 27 February 2013 and were completed on Friday 15 March 2013 with the demobilization of
SPT Rigs and Hand Augers as well as geophysical tools from the project site.
Field investigations involved conducting detailed geotechnical drilling totalling eighteen (18 ) borings to
a depth of thirty (30) meters using percussion rigs and twenty-nine (29) borings using the Hand Auger to
3-meters in depth. The geotechnical drilling involved conducting a Standard Penetration Tests (SPT) and
taking both disturbed and undisturbed samples and testing these in laboratories to study their
geotechnical engineering parameters. A detailed geophysical study was also carried out. This comprised
of Vertical Electrical Sounding (VES) and Constant Separation Traversing (CST) to determine various soil
types and their corresponding apparent resistivity. Moreover, chemical analyses of the soil samples
were carried to ascertain their corrosivity.
The results of geotechnical investigations and laboratory testing carried out on the soil samples
obtained from the project site, suggest that basically about FIVE (5) identifiable soil horizons are present
and these are namely:
(i) Brownish Clayey layer (CL) - [Top Soil]
(ii) Greyish Organic Silty Clays (OL)
(iii) Greyish Clayey Silty Sands (SM) and (SC-SM)
(iv) Yellowish to whitish Silty Sands (SM)
(v) Well-graded Sands and Gravels (SW)
Groundwater was encountered during the investigation at depths ranging from 2.40m to 3.50m. The
various geotechnical engineering properties of each of the sub-soils are summarized in Tables 8a-8r of
this report. Tables E1 and E2 , below, show the summary of bearing capacity values derived from Field
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 2
SPT soundings and the results of chemical tests on soil samples collected from the Federal University
Otuoke project site.
Table E1: Summary of Bearing Capacity Values derived from Field SPT Soundings at the Federal University Otuoke
Project Site, Ogbia, Bayelsa State
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 3
Table E2: Results of Chemical Tests on the Soils at the Project Site
S/No. Site BH # Sample Depth of pH Cl- SO4-2 Organic
No. Sample value (g/g) (g/g) Matter
(m) (%)
1. Federal ZONE A
University,
Otuoke, Otuoke, BH #s A 2m 4.5 8.9 126.3 0.41
Bayelsa Site. 1,2,3,4,5 &9
2. Federal ZONE B
University,
BH #s
Otuoke, Otuoke, 6,7,8,12 B 4m 4.5 12.8 278.2 0.52
Bayelsa Site. &13
3. Federal ZONE C
University,
BH #s
Otuoke, Otuoke, 10,11,14,15, C 3m 4.7 13.2 298.2 0.64
Bayelsa Site. 16, 17 &18
4. Baseline Data
(far from site). BH2 BL3 3m 4.6 26.7 2.4 Not Detected
Allowable Code
5. Standards, - - - 7.00 2% of 5% of 0.00
[ ACI Code] concrete concrete
On the basis of the computations carried out on data retrieved from the field, the following conclusions
and recommendations are made:
(1) The obtained value for the Bearing Capacity for Isolated Footings to be used at the project site is
about 195.35 + 1.1867B [kPa] where B = Width of the Structure to be built. For a B = 5.00
meters, the Bearing Capacity has been found to be 201.284 kPa. The recommended depth of
emplacement of Isolated Footings is 1.50 meters. This value represents the bearing capacity of
the upper bearing Lateritic Clayey Sands at the Project Site.
(2) The obtained value for the Bearing Capacity for Continuous Strip Footings to be used at the
project site is about 153.35 + 1.483B [kPa] where B = Width of the Structure to be built. For a B =
5.00 meters, the Bearing Capacity has been found to be 160.76 kPa. The recommended depth of
emplacement of Continuous Strip Footings is 0.75 meters. This value represents the bearing
capacity of the upper bearing Lateritic Clays and Silty-Clays at the project site.
(3) The range of values obtained for the Bearing Capacity for Raft Footings at the Project Site, based
on the methods of Meyerhof (1974); Bowles (1988); Terzaghi & Peck (1967); Brinch Hansen
(1968) and the conventional SPT Method is between 76.55 and 208.86 kPa with an average of
122.85 kPa. The recommended depth of emplacement of Raft Footings is 1.50 meters. This
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 4
value represents the bearing capacity of the upper bearing Lateritic Clays and Silty-Clays at the
project site.
(4) A value of qallowed = [14.4] + [(9.964T)/( B x L)] kN / m2 can be used as the allowable Soil Pressure
on the soil at the project site, since this value should be less than the average value of the
allowable soil pressure (bearing capacity ), q(allow) of the soils at site. [Note: B = breadth; L =
Length of structures at site].
(5) The computed settlement data for the project area indicate that the Immediate Settlement
value for the Project Site is estimated to be about i = 0.0000132(T) (B) (meters), where T = the
Dead weight of the Buildings at site. This is the settlement expected to take place during the
construction phase of the Buildings at the project site.
(6) The computed settlement data for the project area indicate that the Long-Term Settlement
value for the buildings at the site is estimated to be about 0.000132 T + {(0.520) Log 10 (1
+0.01498 T)} (meters), where T = the estimated Dead Weight of the buildings. This is the
settlement expected to take place long after the construction phase of the buildings at the
various zones at the project sites.
(7) About 50% of the settlements will have taken place about 3.70 years after construction, while
90% of the settlement will take place after about 15.728 years after the completion of the
buildings at the University Complex.
(8) Since the buildings at a University Campus are subjected to live loads from the movements of
different numbers of students in a continuous day-to-day fashion over the years, the potential
of the silty soils becoming liquefied as a result of human traffic-induced vibration was also
assessed during this investigation, since this is a permanent structure for the foreseeable future.
Soil dynamics analysis carried out by us indicate that there will be no possibility of Soil
Liquefaction at the project site as a result of vibration from live loads and structures. This is
considered not to be possible, even though the groundwater table was found to be near the
surface, because of the absence of totally silty soils beneath the ground surface.
(9) Foundation concrete should be dense and impermeable for protection against Sulphate attack
especially in areas likely to be in contact with surface or groundwater.
(10) The pH value of 4.5 is low and therefore may enhance corrosion of buried pipes and metals.
(11) Generally the resistivity in the project area is quite high, which could have entailed non-
corrosive environment. However, for the slightly lower resistivity that could be expected during
the rainy season, it may therefore be recommended that some precautions be taken on the
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 5
pipe-works e.g. bonded Coatings of the pipes or better still a Cathodic Protection could be
incorporated.
(12) Sulphate-resistant Cement may be used for the foundation concrete (cement content not less
than 330 kg/m, Max. W/C 0.50 or Sulphate-resisting cement with cement content not less than
290 kg/m, Max. W/C 0.50)
(13) The specific values obtained at this site are higher than those recommended values by IEEE
Green Book (1992). Hence irrespective of the point chosen for Earthing at the project sited, the
earth conductivity must be improved upon by the addition of ground enhancement material
such as mixing charcoal and coke with salts like sodium chloride or magnesium chloride or
better still some of the artificial gels, and buried at depths of between 4 – 5 meters.
(14) The apparent resistivity values obtained for the specific depths are somehow high so that the
conductivity of the soil needs to be improved upon for any effective earthing facility to be put in
place. The area in terms of resistivity does not pose any problem as a corrosive soil. However,
due to seasonal changes especially during the wet season, the Resistivity is expected to be
lowered, the percentage of which depends on the amount of moisture available.
(15) The subsurface layers delineated consist of the topsoil, sand-and-clay, intercalating with each
other. The clay layer is deep in some of the areas investigated thus negating the use of shallow
foundations. Pile foundation will suffice for the area or any other design that will adequately take
care of the clay layers such as Raft Foundation.
(16) On the basis of the geotechnical considerations for structures such as the proposed University
single or multiple office Blocks; laboratory buildings and various categories and sizes of
Residential Buildings at the Campus site, the Geotechnical Consultants highly recommend that
the above findings be strictly adhered to.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 6
Acknowledgements
We wish to register our profound gratitude to the management of HAALP Consult for the opportunity
given us to make our modest contributions to the Federal University Otuoke Project by carrying out
detailed, integrated Geotechnical and Geophysical investigations at the proposed site. In this vein, we
would like to appreciate the immense assistance we received during our field investigations from E.Z
Chmara (Director, HAALP Consult), Mr. Opiriba Ikiriko (HAALP Supervisor on site) and representatives of
the Director of Works (Dr. Oloye and his team) Federal University Otuoke. They were very helpful in
providing details about our scope of work during the field operations of our study.
The approval of the Vice Chancellor of the Federal University Otuoke, Bayelsa State is most graciously
acknowledged. The assistance of the Chief Security Officer (and his team) of the Federal university
Otuoke is also appreciated. TEKS Geotechnical Consultancy (Nigeria) Limited, would like to thank the
various field staff of TGCL for their execution of this work (supervisors, technicians/technologists, drillers
and assistant drillers especially Mr. Brown Otuma, the senior driller and his assistant drillers; laboratory
personnel, field assistants and drivers). Their contributions are also highly appreciated.
We also wish to acknowledge the wonderful cooperation of the Civil Engineering Department of the
Rivers State University of Science and Technology, Port Harcourt, where the soil samples were analysed
for geotechnical property evaluations. In this regard we are especially grateful to Venerable Dr.
(Engineer) Chukuigwe of the Petroleum/Petrochemical Department and Mr. Eferigbo of the Civil
laboratory. In the same vein, we sincerely thank the Laboratory staff of the Institute of Pollution Studies
(IPS), especially Mr. Ikoro, who undertook the careful chemical analyses of the soils from the project
site. Above all, we thank all staff of TEKS Geotechnical Consultancy (Nigeria) Limited, especially Ms.
Oghoin-Olem Cletus Oruene who did almost all the computer-graphics in the Report, Ms. Gift Nsirimaobi
and other staff for all their co-operations in the timely execution of this important project.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 7
List of Consultants
Data Collection
Senior Consultant: Sir(Prof.)S.C. Teme Ph.D; FNMGS; COMEG
Consultants Ms. O.Cletus Oruene.B.Sc.(Geology); M.Sc.(Geol)
Mr. Jacob Ori-itemem.B.Sc.(AUE PHC.)
Geology
Senior Consultants: Sir(Prof.) S.C. Teme FNMGS; COMEG.
Consultants Ms. O.Cletus Oruene.B.Sc. (Geology); M.Sc.(Geol)
Mr. Prosper Ogbunie.B.Sc.(Geol); M.Phil.(Env. Mgt)
Geotechnical
Senior Consultant: Sir(Prof.) S.C. Teme FNMGS; COMEG.
Consultants Ms. O.Cletus Oruene B.Sc.(Geology); M.Sc.(Geol)
Mr. Prosper Ogbunie.B.Sc.(Geol); M.Phil.(Env. Mgt)
Mr. Alex Jamani. B.Sc.(Geol)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 8
Table of Contents
Page
Cover Page
Executive Summary… … … … … … … … … I
Acknowledgements… … … … … … … … … … vi
List of Consultants… … … … … … … … … … vii
Table of Contents… … … … … … … … … … viii
List of Figures… … …. … … … … … … … … xiv
List of Tables… … … … … … … … … … … xvi
List of Appendices … … …. … … … … … … … xix
1.0 Introduction… … … … … … … … … 15
9.0 Discussion of Results of Investigations In Relation to Foundation System Design and Construction 118
Appendices… … … … … … .. … … .. … 154
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 9
List of Figures
Figure 1: A Site Assessment Chart (Modified after Andrew-SatCom-Africa)… … … … 16
Figure 2a: Vertical Satellite imagery of the site of the Federal University, Otuoke, Bayelsa State,
showing the distribution of the Boring points… … … … … … 17
Figure 2b: Orthogonal Satellite Imagery of Federal University Otuoke, Bayelsa State, showing the
distribution of the Boring points… … … … … … … 18
Figure 2c: Another Orthogonal view of the Satellite Imagery of Federal University Site, Otuoke
Bayelsa State, showing the distribution of the Boring points… … … … … 18
Figure 3: Topography and the Vegetation Pattern at the site of the Federal University, Otuoke,
Bayelsa State… … … … … … … … … 19
Figure 3b: Vegetation Pattern at the site of the Teaching Core of the Federal University, Otuoke,
Bayelsa State… … … … … … … … … 20
Figure 3c: Another Vegetation Pattern at the site of the Teaching Core of the Federal University,
Otuoke, Bayelsa State… … … … … … … … 20
Figures 4b: Soil retrieval process by a combined team of two rigs during the Percussion drilling
at the project site… … … … … … … … … 23
Figure 5a: Schematic Fence Diagram showing the Borings in ZONE A at the Project Site…. … 31
Figure 5b: Schematic Fence Diagram showing the Borings in ZONE B at the Project Site… … 32
Figure 5c: Schematic Fence Diagram showing the Borings in ZONE C at the Project Site … 33
Figure 6a: Outline of Geophysical Sounding Profiles at the Federal University Otuoke … 35
Figure 6b: General Outlay of the Federal University, Otuoke showing Field Boring Locations… … 36
Figure 8b: The Photograph of the Geophysical Survey Group during Investigation… … … 39
Figure 8c: Mud-cracks at the Site Showing the Clayey Nature of the Soil in the Bulldozed Areas… 39
Figure 9a: The Schlumberger Depth Sounding Curves beneath VES 1... … … … 44
Figure 9b: The Schlumberger Depth Sounding Curves beneath VES 2... … … … 45
Figure 9c: The Schlumberger Depth Sounding Curves beneath VES 3... … … … 46
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 10
Figure 9d: The Schlumberger Depth Sounding Curves beneath VES 4... … … … 47
Figure 9e: The Schlumberger Depth Sounding Curves beneath VES 5... … … … 48
Figure 9f: The Schlumberger Depth Sounding Curves beneath VES 6... … … … 49
Figure 9g: The Schlumberger Depth Sounding Curves beneath VES 7... … … … 50
Figure 9h: The Schlumberger Depth Sounding Curves beneath VES 8... … … … 51
Figure 9i: The Schlumberger Depth Sounding Curves beneath VES 9... … … … 52
Figure 9j: The Schlumberger Depth Sounding Curves beneath VES 10... … … … 53
Figure 9k: The Schlumberger Depth Sounding Curves beneath VES 11... … … … 54
Figure 9l: The Schlumberger Depth Sounding Curves beneath VES 12... … … … 55
Figure 9m: The Schlumberger Depth Sounding Curves beneath VES 13... … … … 56
Figure 9n: The Schlumberger Depth Sounding Curves beneath VES 14... … … … 57
Figure 9o: The Schlumberger Depth Sounding Curves beneath VES 15... … … … 58
Figure 9p: The Schlumberger Depth Sounding Curves beneath VES 16... … … … 59
Figure 14: Net Pressure on footing with backfill (assuming top of Raft footing above ground surface)… 111
Figure 15: Factors for Calculating the Average Immediate Settlement of Loaded Area… … … 114
Figure 16a: Plot of Pile Load Vs Depth for Pile Diameters of 400mm and 600mm at the Federal
University Otuoke Zone A [BH# 1, 2, 3, 4, 5 and 9]… … … … … 127
Figure 16b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal
University Otuoke Zone A [BH# 1, 2, 3, 4, 5 and 9]… … … … … 128
Figure 17a: Plot of Pile Load Vs Depth for Pile Diameters of 400mm and 600mm at the Federal
University Otuoke Zone B [BH# 6, 7, 8, 12 and 13]. .. … … … … 133
Figure 17b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal
University Otuoke Zone B [BH# 6, 7, 8, 12 and 13]… … … … … 134
Figure 18a: Plot of Pile Load Vs Depth for Pile Diameters of 400mm and 600mm at the Federal
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 11
University Otuoke Zone C [BH# 10, 11, 14, 15, 16, 17 and 18]… … … … 139
Figure 18b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal
University Otuoke Zone C[BH# 10, 11, 14, 15, 16, 17 and 18]… … … … 140
Figure 19: Correlation between field Liquefaction behavior of sands for level ground conditions and
penetration resistance, supplemented by data from large scale tests (after Seed, 1979)… 143
Figure 20: Range of Values of r/d for different soil profiles in Liquefaction Potentials analyses
(after Seed & Idriss, 1971)…. … … … … … … … 145
List of Tables
Table 1: Visual Inspection for Site Assessment… … … … … … … 16
Table 2: Ground Elevations and Ground Water Tables at Boring Locations at Project Site… .. 21
Table 4a: Schlumberger Depth Sounding Data at Federal University Otuoke, Bayelsa State… … 67
Table 4b: Schlumberger Depth Sounding Data at Federal University Otuoke, Bayelsa State… … 68
Table 4c: The Geographical Coordinates of the Investigated Profiles at Federal University Otuoke,
State using Geographical Positioning Systems (GPS) Map 76s… … … … 68
Table 5: Summary of Bearing Capacity Values derived From Field SPT Soundings at the Federal
University Otuoke Project Site, Ogbia, Bayelsa State… … … … … 74
Table 6: Consolidation, Bearing and Drainage Characteristics of Materials of the Federal
University, Otuoke Site, Bayelsa State… … … … … … … 76
Table 7: Results of Chemical Tests on the Soils at the Project Site… … … … … 77
Table 8a: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.1] … … … … … … … 79
Table 8b: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 2]… … … … … … … 80
Table 8c: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 3] … … … … … … … 81
Table 8d: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.4] … … … … … … … 82
Table 8e: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 5] … … … … … … … 83
Table 8f: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.6]… … … … … … … 84
Table 8g: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 7] … … … … … … … 85
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 12
Table 8h: Summary Of Geotechnical Properties For The Sub-Soils At The Federal University
Otuoke, Bayelsa State [Boring No. 8] … … … … … … … 86
Table 8i: Summary Of Geotechnical Properties For The Sub-Soils At The Federal University
Otuoke, Bayelsa State [Boring No.9] … … … … … … … 87
Table 8j: Summary Of Geotechnical Properties For The Sub-Soils At The Federal University
Otuoke, Bayelsa State [Boring No.10] … … … … … … … 88
Table 8k: Summary Of Geotechnical Properties For The Sub-Soils At The Federal University
Otuoke, Bayelsa State [Boring No.11] … … … … … … … 89
Table 8l: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.12] … … … … … … … 90
Table 8m: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.13] … … … … … … … 91
Table 8n: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.14]… … … … … … … 92
Table 8o: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No.15] … … … … … … … 93
Table 8p: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 16] … … … … … … … 94
Table 8q: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 17] … … … … … … … 95
Table 8r: Summary of Geotechnical Properties for the Sub-Soils at the Federal University
Otuoke, Bayelsa State [Boring No. 18] … … … … … … … 96
Table 10: Meyerhof’s And Bowles’ Equations for Computing Footing Bearing Capacity… … … 106
Table 11: Values of Bearing Capacities of Project Site Sub-Soils, Based On SPT N-Values… … 107
Table 12: Bearing Capacity Values for the Federal University Otuoke, Bayelsa State Foundation
[Df = 1.50m], (Based On F.S = 3.0)… … … … … … … 109
Table 13: A Sensitivity Analysis of Bearing Capacities of Project Site Soils for Isolated and Raft
Foundations, Federal University Otuoke, Bayelsa State… … … … … 110
Table 14: The Final Average Values of Bearing Capacity for Isolated and Raft Foundations at
different Foundation Depths… … … … … … … … 110
Table 16: Summary of the Computed Rates of Settlements for the Site at the Federal University
Otuoke, Bayelsa State… … … … … … … … … 117
Table 17: Values of Pile Bearing Capacities for Various Pile Diameters for the Buildin Foundations… 122
Table 18a: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 13
the Federal University Otuoke, Bayelsa State Project [Zone A- Casing Diameter: 400mm]… 123
Table 18b: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone A- Casing Diameter: 600mm]… 124
Table 18c: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke Bayelsa State Project [Zone A- Casing Diameter: 800mm]… 125
Table 18d: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone A- Casing Diameter: 1000mm]… 126
Table 19a: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone B- Casing Diameter: 400mm]… 129
Table 19b: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone B- Casing Diameter: 600mm]… 130
Table 19c: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone B- Casing Diameter: 800mm]… 131
Table 19d: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone B- Casing Diameter: 1000mm]… 132
Table 20a: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone C- Casing Diameter: 400mm]… 135
Table 20b: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone C- Casing Diameter: 600mm]… 136
Table 20c: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke, Bayelsa State Project [Zone C- Casing Diameter: 800mm]… 137
Table 20d: Geotechnical Design of Pile Foundation for Proposed 2 or More Storey Buildings at
the Federal University, Otuoke Bayelsa State Project [Zone C- Casing Diameter: 1000mm]… 138
List of Appendices
Appendix Ai' - Borehole Logs … … … … … … … … … 155
Appendix Aii '- Hand Auger Borings … … … … … … … … 176
Appendix B - Geophysical Data … … … … … … … … … 106
Appendix C - Particle Size Distribution … … … … … … … … 210
Appendix D - Consistency Limits (Atterberg Limits) … … … … … … 232
APPENDIX E - Direct Shear Tests … … … … … … … … … 239
APPENDIX F - Unconsolidated-Undrained (U-U) Triaxial Compression Tests … … … … 246
APPENDIX G - Oedometer Consolidation Tests … … … … … … … 253
APPENDIX H - California Bearing Ratio (CBR) Test Results … … … … … … 259
APPENDIX I - Standard Compaction Test Results … … … … … … … 291
APPENDIX J - Refrences … … … … … … … … …
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 14
1. Introduction
TEKS Geotechnical Consultancy (Nigeria) Limited was sub-contracted by HAALP Consult Limited
to, among other things, carry out a geotechnical investigation of the subsurface at the proposed
site of the Federal University, Otuoke, Bayelsa State for the purpose providing specialist
technical advice that will assist with the detailed planning of the land-uses and the of design of
appropriate foundation systems for buildings and other infrastructure within the campus. This
study was undertaken with a view to determining the suitability of the sub-soils as bearing
media for the proposed project and where found unsuitable, recommend methods of improved
foundation systems for the structures envisaged for the area.
Soon after commissioning, a team comprising members from TEKS Geotechnical Consultancy
(Nigeria) Limited undertook a field survey that involved boring, sounding and soil samplings.
Eighteen (18) borings were made to final depths of 30.00 meters as directed by the client. The
boring employed the Shell-and-Auger Rig. The Standard Penetration Tests ( SPT ) were carried
out at appropriate depth intervals of 1.00 meters or where a change in lithology was observed
during the boring process. Both undisturbed samples (using Split Spoon Samplers and U-4 tubes)
and slightly disturbed soil samples (using shelling augers) were obtained during the boring
process.
The recovered soil samples were subjected to both field and laboratory visual examinations as
well as detailed laboratory testing. The overall investigation is intended to provide a geologic-
and geotechnical engineering investigation which will form the basis for the effective planning of
land-uses and sound engineering design of foundation systems for the proposed buildings and
infrastructure at the Federal University Otuoke Campus Site, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 15
1.2.1 Methodology Of Site Investigation
The methodology of site investigation adopted included Visual Site Inspection and Soil Boring
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 16
If the answers to all the questions above are no, then type a soil investigation method is
recommended. if the answers to all the questions are yes, then Type C Soil Investigation Method
is recommended. If the site is situated in an area where there are signs of no excess water, the
materials are not imported and the in-situ materials are more of Clayey sands as against sands
and gravel then Type B Soil Investigation Method must be used.
Based on the site assessment derivable from Figure 1 above, it was observed that Site
Investigation Type B (Method 2) was the most appropriate method to be used at this site and it
was so employed.
Figure 2a: Vertical Satellite imagery of the site of the Federal University Otuoke,
Bayelsa State, showing the distribution of the Boring points.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 17
Figure 2b: Orthogonal Satellite Imagery of Federal University Site Otuoke, Bayelsa State,
showing thedistribution of the Boring points.
Figure 2c: Another Orthogonal view of the Satellite Imagery of Federal University Site,
Otuoke Bayelsa State , showing the distribution of the Boring points
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 18
2.2 Topography and Vegetation
The general topography of the proposed project site at the Federal University Otuoke, Bayelsa
State Is relatively flat lying and situated in an undeveloped area of Otuoke Community in Ogbia
Local Government Area of Bayelsa State. The project area is a low-lying, relatively flat-lying
terrain that had at the time of investigation an elevation ranging between 0.8m and 10.5m
above sea level.
The vegetation around the general area consists mostly of primary vegetation of tall trees
underlain by an undergrowth of shrubs, grasses and other forms of secondary vegetal growths
in places where the primary forest have been cleared for farming.
The general character of the vegetation around the project site at the time of the investigation is
shown in Figs. 3a to 3c.
Figure 3a: Topography and the Vegetation Pattern at the site of the Federal University,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 19
Figure 3b: Vegetation Pattern at the site of the Teaching Core of the Federal University,
Otuoke, Bayelsa State.
Figure 3c: Another Vegetation Pattern at the site of the Teaching Core of the Federal
University, Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 20
3.0 Subsurface Condition
The Subsurface conditions at the project site were studied by sounding in the form of Standard
Penetration Testing (SPT) and boring holes with the aid of Shell-and-Auger Percussion Rig (Fig. 4)
while retrieving soil samples at specific depth intervals of 1.00 meters for purposes of visual
examination of soil samples, laboratory testing and classifications, as the case may be. The
bearing capabilities of the various soil horizons at the project site were assessed using the
Standard Penetration Test data. These methods provided valuable information about the
subsurface characteristics in the project area.
Table 2: Ground Elevations and Ground Water Table at Boring Locations at the Federal University
Project Site
ZONE BH # Ground Water Table Remarks
Elevation (m) [bgl]* *
.m (asl)*
1 5.30m 3.00m Elevation effect [as at 04 /03/13]
2 3.00m 3.10m Elevation effect [as at 04 /03/13]
3 4.00m 2.40m Elevation effect [as at 04 /03/13]
A 4 10.50m 2.50m Elevation effect [as at 04 /03/13]
5 3.00m 2.50m Elevation effect [as at 04 /03/13]
9 4.00m 3.50m Elevation effect [as at 04 /03/13]
6 4.00m 2.40m Elevation effect [as at 07 /03/13]
7 5.30m 3.00m Elevation effect [as at 07 /03/13]
B 8 2.10m 3.1m Elevation effect [as at 08 /03/13]
12 3.10m 3.20m Elevation effect [as at 09 /03/13]
13 3.00m 2.90m Elevation effect [as at 04 /03/13]
10 3.60m 3.30m Elevation effect [as at 04 /03/13]
11 4.00m 3.10m Elevation effect [as at 04 /03/13]
14 3.00m 2.30m Elevation effect [as at 04 /03/13]
15 4.00m 2.70m Elevation effect [as at 04 /03/13]
C 16 0.80m 2.80m Elevation effect [as at 04 /03/13]
17 6.00m 2.50m Elevation effect [as at 04 /03/13]
18 3.00m 2.90m Elevation effect [as at 04 /03/13]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 21
3.3 Subsurface Explorations
The subsurface exploration programme at the project site comprised Shell-and-Auger borings
and soil samplings. The Standard Penetration Testing (SPT) was carried out during the Shell-and-
Auger boring exercise.
3.3.1 Borings
A total of eighteen (18) deep borings were made, each to a depth of 30.00 meters at this
project site, as shown on Figs. 5a - 5c.
3.3.2 Soundings
Standard Penetration Tests (SPTs) were carried out during the subsurface exploration-sounding
programme at the project site. The SPT curves are shown in Appendix ‘A’ of this report.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 22
Figures 4b: Soil retrieval process by a combined team of two rigs during the Percussion
drilling at the Project Site.
3.3.3 Samplings
In general, disturbed samples were obtained during the drilling programme using the Shell-and-
Auger equipment. Within the zone of cohesive materials such as clays or sandy clays,
undisturbed soil samples were obtained during the percussion drilling with the aid of split-
spoons and U4-tubes. Disturbed soils taken during the drilling process are shown in Figure 4b
above. Sampling intervals during the drilling were 1.00-meters apart down to the end of the
boring. All the depths mentioned in this report are in relation to ground level at the time of
investigations.
The individual descriptions of the soil samples retrieved from the borings at the project site are
set out in the following sections of the report. The Project site has been sub-divided into three
(3) Zones, each representing a segment of the University Campus, for ease of project description
and implementation, especially during the Construction Phase.
The three (3) Zones and the boring numbers (#) represented are as follows:
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 23
ZONE A: The Campus Phase 1 Area BH# 1
Junior Staff Quarters Area BH# 2
University Commercial Centre Area BH# 3
Sports and Recreation Area BH# 4
Engineering & Maintenance Area BH# 5
Garden / Parks Area HA Hole # 7, 8, 9, 10 & 11
Research Area. BH# 9
Total number of borings in this Zone Six (6) and Five (5) Hand Auger
ZONE B: The Teaching Core Area BH# 6; 7 & 8
Student Accommodation Area BH# 12 & 13.
Total number of borings in this Zone Five (5)
ZONE C: The Central Administration Area BH# 10 & 11
University Centre Area BH# 18
Senior Staff Housing Area BH# 17
Registrar Housing Area BH# 16
Guest Cottages Area BH# 15
Pitch Putt Golf Area HA Hole # 19, 20, 21, 22 & 23
Vice-Chancellor’s Residential Area. BH# 14
Total number of borings in this Zone Seven (7)
The soil descriptions (below) are given in accordance with the groups as zoned above.
The Ground elevations and the attendant Ground Water Tables at the time of field
investigations at the project site [4th to 12th of March, 2013] are tabulated under the various
Zones. For Zone A, Table 2 shows the observed Water Tables and the Ground Elevations (using
the Hand-held GPS) for the height elevations, with a margin of error of about +.05m.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 24
Brownish Clay Layer (CL) – Top Soil
These materials represent the Top soil in all the Five (5) borings in this Zone at the
project site and was found to range in thickness between 0.50 meter and 1.00 meter
and is entirely made up of plastic Clays.The materials of this first upper layer have
moisture contents of between 5.5 – 8.4%. Under the Unified Soil Classification System
(USCS), the materials in this layer have been classified as Clays low to medium
consistencies (CL). Unconsolidated – Undrained (U-U) tri-axial test results on samples
from this layer indicate that the undrained friction angles (u) vary from 4° to 6° with
corresponding undrained cohesion (Cu) values of 45.60 to 60.50 KPa
These materials represent the second layer of the subsurface in Zone A at the project
site This layer was encountered at in five of the six borings within the zone and was
found to be between 2.00 m to 4.00m thick and is entirely made up of Grey Silty Clays .
The materials of this layer have moisture contents of between 7.50 – 8.5% and can be
classified as OL (Organic Silty Clays) under the USC system of Nomenclature.
Unconsolidated – Undrained (U-U) tri-axial test results on samples from this layer
indicate that the undrained friction angles (u) are between 6.0° and 8.0° with
corresponding cohesion (Cu) values of between 42.50 and 68.50 KPa.
These materials represent the third layer in this Zone at the project site and are found
to range in thickness between 2.50 meters and 6.00 meters and is entirely made up of
greyish Clayey Sands. The materials of this third layer have moisture contents of
between 4.0 – 6.5% Under the Unified Soil Classification System (USCS), the materials in
this layer have been classified as Silty Clays and Clayey Sands of low consistencies (SC).
Unconsolidated – Undrained (U-U) tri-axial test results on samples from this layer
indicate that the undrained friction angles (u) vary from 8°to 10°with corresponding
undrained cohesion (Cu) values of 44.80 to 50.50 KPa.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 25
Whitish Silty Sands Layer (SM)
These materials represent the Fourth layer of the subsurface at Zone A at the project
site and was encountered at five (5) of the six (6) borings at depths ranging from 3.00m
to 11.00m with thicknesses ranging between 4.00m and 11.00m. The layer is entirely
made up of whitish Silty Sands. The materials of this layer have moisture contents of
between 4.40 – 9.4%. Materials of this layer can be classified as SM (Silty Sands) under
the USC system of Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test
results on samples from this layer indicate that the undrained friction angles (u) are
between 28. 0° and 30.0°with corresponding cohesion (Cu) values of 0.00 KPa.
These materials represent the Fifth layer of the subsurface in five of the six borings
carried out in Zone A at the project site. The layer was encountered at the six (6) borings
at depths ranging between 7.00m and 21m. This layer was found to be between 9.00 m
to 23.00m thick and is entirely made up of well-graded Sands and gravels to the final
depth of boring (ie 30.00m). The materials of this layer have moisture contents of
between 5.5 – 6.5%. Materials of this layer can be classified as SW (Well- Graded Sands)
under the USC system of Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test
results on samples from this layer indicate that the undrained friction angles (u) are
between 34.0° and 36.0° with corresponding cohesion (Cu) values of 0.00 KPa.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 26
Brownish Clay Layer (CL) – Top Soil
These materials represent the Top soil in all the Five (5) borings in this Zone at the
project site and was found to range in thickness between 0.50 meter and 1.00 meter
and is entirely made up of plastic Clays.The materials of this first upper layer have
moisture contents of between 5.5 – 8.4%. Under the Unified Soil Classification System
(USCS), the materials in this layer have been classified as Clays low to medium
consistencies (CL). Unconsolidated – Undrained (U-U) tri-axial test results on samples
from this layer indicate that the undrained friction angles (u) vary from 4° to 6°with
corresponding undrained cohesion (Cu) values of 45.60 to 60.50 KPa
These materials represent the second layer of the subsurface in ZONE B at the project
site This layer was encountered at in two of the five borings within the zone and was
found to be between 3.00 m to 6.00m thick and is entirely made up of Grey Silty Clays .
The materials of this layer have moisture contents of between 8.50 – 8.8% and can be
classified as OL (Organic Silty Clays) under the USC system of Nomenclature.
Unconsolidated – Undrained (U-U) tri-axial test results on samples from this layer
indicate that the undrained friction angles (u) are between 6.0° and 8.0° with
corresponding cohesion (Cu) values of between 44.50 and 65.50 KPa.
These materials represent the third layer in this Zone at the project site and are found to
occur in only four out of the five borings [#7.8,12 & 13] in this Zone. It is found to range
to range in thickness between 5.0 meters and 9.00 meters and is entirely made up of
greyish Clayey Silty-Sands. These materials represent the third layer in this Zone at the
project site and are found to occur in only four out of the five borings [#7.8,12 & 13] in
this Zone. It is found to range to range in thickness between 5.0 meters and 9.0 meters.
The materials of this third layer have moisture contents of between 5.0 – 8.5% Under
the Unified Soil Classification System (USCS), the materials in this layer have been
classified as Silty Clays and Clayey Silty Sands of low consistencies (SC). Unconsolidated –
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 27
Undrained (U-U) tri-axial test results on samples from this layer indicate that the
undrained friction angles (u) vary from 8° to 10°with corresponding undrained cohesion
(Cu) values of 44.80 to 50.50 KPa
These materials represent the Fourth layer of the subsurface at Zone A at the project
site and was encountered at all the borings at depths ranging from 35.00m to 15.00m
with thicknesses ranging between 1.00m and 11.00m. The layer is entirely made up of
whitish Silty Sands. The materials of this layer have moisture contents of between 4.00 –
7.5%. Materials of this layer can be classified as SM (Silty Sands) under the USC system
of Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test results on samples
from this layer indicate that the undrained friction angles (u) are between 28. 0°and
30.0° with corresponding cohesion (Cu) values of 0.00 KPa.
These materials represent the Fifth layer of the subsurface in all of the five borings
carried out in ZONE B at the project site. The layer was encountered at the five (5)
borings at depths ranging between 5.00m and 20m. This layer was found to be between
10.00 m to 25.00m thick and is entirely made up of well-graded Sands and gravels to the
final depth of boring (ie 30.00m). The materials of this layer have moisture contents of
between 6.0 – 7.5%. Materials of this layer can be classified as SW (Well- Graded Sands)
under the USC system of Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test
results on samples from this layer indicate that the undrained friction angles (u) are
between 34.0°and 36.0° with corresponding cohesion (Cu) values of 0.00 KPa.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 28
(ii) Greyish Organic silty Clayey Sands (SC-SM)
(iii) Greyish Silty- Sands (SM) and
(iv) Well-graded Gravelly-Sands (SW)
These materials represent the second layer of the subsurface in ZONE C at the project
site This layer was encountered at four borings [# 10, 16, 17 and 18] within the zone and
was found to be between 3.00 m to 8.00m thick and is entirely made up of Grey Silty
Clays . The materials of this layer have moisture contents of between 6.50 – 8.0% and
can be classified as SC-SM (Silty Clayey Sands) under the USC system of Nomenclature.
Unconsolidated – Undrained (U-U) tri-axial test results on samples from this layer
indicate that the undrained friction angles (u) are between 5.0° and 10.0°with
corresponding cohesion (Cu) values of between 35.50 and 48.00 KPa.
These materials represent the Third layer of the subsurface at Zone C at the project site
and was encountered at three borings at depths ranging from 10.00m to 17.00m with
thicknesses ranging between 4.00m and 9.00m. The layer is entirely made up of greyish
Silty Sands. The materials of this layer have moisture contents of between 4.00 – 6.5%.
Materials of this layer can be classified as SM (Silty Sands) under the USC system of
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 29
Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test results on samples from
this layer indicate that the undrained friction angles (u) are between 28. 0° and 30.0°
with corresponding cohesion (Cu) values of 0.00 KPa.
These materials represent the Fourth layer of the subsurface in all of the Seven borings
carried out in Zone C at the project site. The layer was encountered at the Seven (7)
borings at depths ranging between 6.00m and 23m. This layer was found to be between
8.00 m to 14.00m thick and is entirely made up of well-graded Sands and gravels to the
final depth of boring (ie 30.00m). The materials of this layer have moisture contents of
between 5.0 – 8.0%. Materials of this layer can be classified as SW (Well- Graded Sands)
under the USC system of Nomenclature. Unconsolidated – Undrained (U-U) tri-axial test
results on samples from this layer indicate that the undrained friction angles (u) are
between 34.0° and 36.0°with corresponding cohesion (Cu) values of 0.00 KPa.
These basic soil types are found in these three Zones used in this study, as detailed in the Fence
Diagrams of each Zone (Figures 5a, 5b and 5c ).
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 30
3.5.1 Fence Diagrams of Project Site
The Fence Diagrams of the project site as derived from the eighteen (18) borings made at the site are shown in Figures 5b, 5c and 5d respectively
BH 5 BH 1
OH
OH BH 2
T
SC CL TT
OL OL
BH 9
SP BH 4 BH 3
TT OH
T
CL
CL SC
OL SC CL
SM SC-SM
SM SM
SM
SM SM
SM
S
W
S S S
W S W
W W
S
W
Topsoil (T) Organic silts and Organic Clayey Sands, Sand-Clay Silty Clayey Sands Mixtures (SC-SM)
silty clays (OL) Mixtures (SC)
Organic Clays Poorly-graded Sands
(OH) Inorganic clays, silty clays, Silty Sands, Sand-Silt
gravelly clays and lean clays Mixtures (SM) Well-graded Sands
(CL)
Figure 5a: Schematic Fence Diagram showing the Borings in ZONE A at the Project Site.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 31
BH 13 BH 7 BH 6
T T T
CL BH 8
OH CL
BH 12 OL SM
T
SC-
OL CL
SM
SP SC-
SC- SM
SM SC-
SM
SM
SW
SM SP SM
SW SW
SW SW
Topsoil (T) Organic silts and Organic Clayey Sands, Sand-Clay Silty Clayey Sands Mixtures (SC-SM)
silty clays (OL) Mixtures (SC)
Figure 5b: Schematic Fence Diagram showing the Borings in ZONE B at the Project Site
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 32
BH 14
BH 15
T
T BH 18
BH 16
OH
BH 17 OH BH 10
OH
T BH 11
CL
T
OH OH CL OL
CL
SC-SM OL
CL
SM SC SC-SM
SC-SM
SM
SC-SM
SP
SP SP SM
SP
SP
SP
SW
SW SW SW
SW
SW
SW
Topsoil (T) Organic silts and Organic silty Clayey Sands, Sand-Clay Silty Clayey Sands Mixtures (SC-SM)
clays (OL) Mixtures (SC)
Organic Clays Poorly-graded Sands
(OH) Inorganic clays, silty clays, Silty Sands, Sand-Silt Mixtures
gravelly clays and lean clays (CL) (SM)
Well-graded Sands
Figure 5c: Schematic Fence Diagram showing the Borings in ZONE C at the Project Site.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 33
4.0 Geophysical Investigation
4.1 Introduction
Geophysical methods have become an important tool to complement direct methods of investigation
in geotechnical investigations (Ed Wightman, Frank Jalinoos, Philip Sirles, Kanaan Hanna 2003,
Adepelumi, A.A and Olorunfemi, M.O 2000). The methods are capable of producing information about
the subsurface without invading it and can go farther into a subsurface where direct drilling is not
capable of reaching.
One of the methods routinely used is the electrical resistivity method. It is capable of showing the
stratigraphic sequence of site, identification of hazard zones, delineation of hydrogeological regimes
and proffering the engineering properties of the subsurface. In general, the subsurface
characterization provided by geophysical exploration methods is valuable indicator for the
geotechnical evaluation for the following reasons:
They allow collection of data over large areas in very much shorter times than
most destructive methods.
They can offer accurate and timely information for design quality and
performance.
TEKS Geotechnical Consultants (Nig) Ltd. carried out a geophysical survey involving an electrical
resistivity method at the site. The objectives of the survey were:
(i) To delineate the various layers that underlie the area vis-à-vis their resistivity
and thickness.
(ii) To recommend appropriate depth for foundation footings.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 34
A A’
B’
Figure 6a: Outline of Geophysical Sounding Profiles at the Federal University Site, Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 35
Figure 6b: General Outlay of the Federal University, Otuoke, Bayelsa State showing Field Boring Locations.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 36
Legend
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 37
Study Area (Clays Sand And Mangrove Swamps)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 38
Figure 8a: Photograph Of The Geophysical Survey Group During Investigation.
Figure 8c: Mud-cracks at the Site Showing the Clayey Nature of the Soil in the Bulldozed
Areas
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 39
4.2.1 Electrical Resistivity
The electrical resistivity method of geophysical investigations had been used on many occasions to
characterize the suitability of earth materials as an earthing media as it combines speed, accuracy and
cost-effectiveness in the determination of the various lithologic sequences within the subsurface.
The electrical resistivity of soil or rock is a property which depends on lithology and fluid content, thus
depending on the soil type and texture in conjunction with the type of fluid content, earth materials
respond to the passage of electric current differently. The method inject very low frequency current
into the earth mass through two stainless steel electrodes called the current electrodes and resulting
potential difference is measured by another pair of stainless steel electrodes called the potential
electrodes.
The Vertical Electrical Sounding (VES) technique was used to acquire the data in this investigation. The
VES is used to determine the variation in the electrical properties of the earth with depth and this
consists of taking a succession of apparent resistivity values for increasing electrode spacing. The
general norm is that large electrode spacing corresponds to increased depth of investigation.
The full Schlumberger and the half Schlumberger electrode array were utilized for data acquisition.
Sixteen Vertical Electrical Sounding (VES) profiles were occupied. The sounding stations are as shown
in Figure 6b. The inter-electrode spacing was varied from 1m to 50m which gives the specific depth
varying from 20m that is believed to be adequate for any earthing depth
The electrical resistivity survey data was acquired using Super Mini-Res Earth Resisitivity Meter. High
resolution instrument using a synchronous detection for the receiver, so that data in noisy
environment could be effectively taking , it gives a continuous readout of resistance or induced
polarization depending on the button pressed. It has auto-ranging capability i.e. it automatically adapt
the instrument range to the signal value to measure. It also has the capability to create energetic wave
based upon the parameters supplied by the user. It has automatic filtering device (notch filters
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 40
50/60Hz). It is automatically calibrated at every switch-on. At the end of each cycle, the spontaneous
potential is dynamically deducted and the result displayed digitally as resistance in Ohms.
where,
R = resistance (Ohms)
a = apparent resistivity (Ohm-m)
a = distance between active current electrodes and the reference point (m)
MN
where:-
2πa
2
is called the geometric factor for half schlumberger
MN
R = resistance (Ohms)
AB = distance between current electrodes (m)
MN = distance between potential electrodes (m)
Л = Constant
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 41
4.4 Data Interpretation
The Vertical Electrical Sounding (VES) data was interpreted both qualitatively and quantitatively. For
the quantitative interpretation, the VES field data are presented as sounding curves-plots of apparent
resistivity as a function of the half electrode spacing. The quantitative interpretation of the sounding
curves involved partial curve matching (Orellana and Mooney, 1966) and computer iteration using
WINRESIST package (Vander Velpen 2004, ITC, 1T-RSG/CSD) and Winglink The interpretation results
are presented as in the graphs below.
Sixteen (16) Vertical Electrical Soundings (VES) were carried out and two (2) Constant Separation
Traversing (CST) were also run across the property bringing the number of tests carried out to be
eight. The VES was run for the Earthing and Corrosivity tests while the CST was run across the site
for Cathodic protection tests.
An electrical resistivity method has been employed at the site to detect the Corrosivity of the soil; the
Cathodic protection procedure for the underground pipe works and verifies the electrical quality of
the soil within this property as an Earthing medium for the Earthing System for the .
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 42
The specific depth of investigation is defined as that depth, which contributes most to the total signal,
measured on the ground surface (Beck A.E 1981). This specific depth of investigation for Schlumberger
configuration is got through the formula:
D = 0.125 x (AB) … … … … … … … (2)
where:
D = specific depth of investigation
AB = the total distance between the two current electrodes
The results are presented as Table 4a and 4b below.
The Resistivity trend indicates an initial decrease with depth, to about 5m but later pick up and
increase in value with an increase in depth to the maximum depth explored. However the Resistivity
values are generally high implying that the conductivity is low.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 43
Figure 9a: The Schlumberger Depth Sounding Curves beneath VES 1.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 44
Figure 9b: The Schlumberger Depth Sounding Curves beneath VES 2.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 45
Figure 9c: The Schlumberger Depth Sounding Curves beneath VES 3.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 46
Figure 9d: The Schlumberger Depth Sounding Curves Beneath VES 4.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 47
Figure 9e: The Schlumberger Depth Sounding Curves Beneath VES 5.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 48
Figure 9f: The Schlumberger Depth Sounding Curves Beneath VES 6.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 49
Figure 9g: The Schlumberger Depth Sounding Curves Beneath VES 7
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 50
Figure 9h: The Schlumberger Depth Sounding Curves Beneath VES 8.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 51
Figure 9i: The Schlumberger Depth Sounding Curves Beneath VES 9.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 52
Figure 9j: The Schlumberger Depth Sounding Curves Beneath VES 10
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 53
Figure 9k: The Schlumberger Depth Sounding Curves Beneath VES 11.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 54
Figure 9l: The Schlumberger Depth Sounding Curves Beneath VES 12
Figure 9l: The Schlumberger Depth Sounding Curves Beneath VES 12.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 55
Figure 9m: The Schlumberger Depth Sounding Curves Beneath VES 13
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 56
Figure 9n: The Schlumberger Depth Sounding Curves Beneath VES 14.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 57
Figure 9o: The Schlumberger Depth Sounding Curves Beneath VES 15.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 58
Figure 9p: The Schlumberger Depth Sounding Curves Beneath VES 16.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 59
5.0 Discussion Of Geophysical Results
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 60
The earthing of an electrical installation has two purposes:
To provide protection for persons or animals against the danger of electric
shock.
To maintain the proper function of the electrical system.
The effectiveness of any earthing system is therefore dependent on the following:-
the resistivity of the soil surrounding the earth rod,
the contact resistance between the earthen rod and the surrounding soil and,
the resistance of the earthen rod and connecting conductors.
Therefore, the resistivity of the soil in the vicinity of the earthen rod is very important. The soil
should be able to accept and dissipate the unwanted energy without raising the potential of the
earthing system. Low resistivity is required.
(2) Climate
Obviously, arid and good rainfall climates are at opposite extremes for conditions
of soil resistivity. The more moisture there is in the soil system, the lower the
resistivity and higher the higher the conductivity of electrical currents through such
soils.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 61
Given all the above factors, there is a large variation of soil resistivity between different soil
types and moisture contents.
Every earth is an individual and the only way to know that an earthing installation meets code
requirements is to carry out proper resistance measurements on site, which has been carried
out on this site. The Resistivity values got for the area surveyed from surface to a depth of
about 12.5m indicates a generally consistent high resistivity values (all greater than 1000 Ohm-
m) as indicated by all the figures drawn and this resistivity range is very high for any earthing
system to be put in place. Furthermore, the specific resistance at any of the sounded stations is
greater than 5 Ohms. According to the IEEE Green Book (1992), the grounding electrode
resistance of large electrical sub-stations for commercial and industrial sites should be in the
range of 2-5 Ohms. The specific values got at this site are higher than these suggested values.
Hence irrespective of the point chosen for Earthing at this area, the earth conductivity must be
improved upon by the addition of ground enhancement material, this is to enhance its
absorption power and increase its richness with charge carrying ions. This could be done by
mixing charcoal and coke with salts like sodium chloride or magnesium chloride or better still
some of the artificial gels. The depth recommended for any earthing system is 4m to 5m, this
depth lies within the low resistivity layer.
Soil resistivity
Presence of chlorides and sulfates.
Oxygen content.
pH.
The chief among them is the resistivity of the soil. Variations in soil properties and
characteristics across three dimensions can have a major impact on corrosion of buried
structures. Typically, the most corrosive soils are those with low resistivity, low pH (for
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 62
steel/ductile iron), and the highest concentration of Chlorides and Sulphates. Wet conditions
are particularly difficult since these can result in concentration of corrosive species and
mechanical action that tend to break down protective corrosion films and coatings on metal
surfaces.
The following criteria were adopted for the interpretation of the of the soil resistivity (after
Davenport et al, 1981 and ANSI/AWWA C105/A21.5, 1993).
5 – 10 Corrosive
10 – 20 Moderately corrosive
The progressively high resistivity values indicate increasing sand content. Therefore sandy soils with
high resistivity values are considered the least corrosive. The resistivity values obtained for the area
survey irrespective of the depth are very high when compared with this table.
The minimum resistivity value is in the range of 1442 Ohm-m to 2755 Ohm-m. Therefore, the soil is
practically non-Corrosive relative to the resistivity values found in the area at the time the test was
carried out. However, the resistivity is expected to change during the wet season, it is expected to be
lower in value. The percentage change cannot be predicted now, but it is not expected to fall into the
range of very corrosive soil, because the soil around the campus site is expected to be well drained
due to its sandy nature.
The entire resistivity values overview however shows that there is no clay infilling, apart from pockets
of high Resistivity values as depicted by the apparent resistivity sections (Figures 10a & b) at shallow
depth, the resistivity values relative to horizontal distribution is fairly uniform.
Therefore except for increase in moisture content due to seasonal changes effect (which could not be
predicted at the time this test was being carried out), the Cathodic Protection need not be carried out,
ab initio. However, for the explanation of the changes that may occur during the wet season, when
the moisture content is expected to rise, the Cathodic Protection option could be done to take care of
these changes. The recommended method of Cathodic Protection should be the “impressed current
Method” because the resistivity of the area is generally high (greater than 50 Ohm-m) which is the
threshold value between using the “Sacrificial Anode method” and the “Impressed Current method”.
The subsurface had been processed into geoelectric sections along two major profiles named as AA’
and BB” The lithologies consists of clay and sand of varying textures. The geo-electric layer is as shown
in Figures 10a & b below.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 64
Pitch and putt Student Teaching core Garden park Campus phase 1
DEPTH (M) Guest cottages golf accommodation
0 TOPSOIL
5 Clay
Medium Grained Sand To Coarse Sand
10
20
25
CLAY
30
35
50
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 65
University Sports/recreation Uni Comm
Senior staff Central Admin Research
DEPTH (M) center Centre
housing
0 Topsoil
Clay
5
Univ. comm.
10 center
15
Fi f Fine Grained Sand Silty in Some Medium Grained Sand To Coarse Sand
Places Places
20
25
30
Medium Grained Sand To Coarse Sand CLAY
35
Clay/Sandyclay/Clayey Sand
40
Medium grained sand to coarse sand
45
50
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 66
6.0 Conclusions and Recommendation Based On Geophysical Investigation
The data got had been processed into specific depth of investigation profiles, apparent resistivity
sections and geo-electric sections. The apparent resistivity values got for the specific depths are
somehow high so that the conductivity of the soil needed to be improved upon for any earthing
facility to be put in place. The area in terms of resistivity does not pose any problem as a corrosive soil.
However, due to seasonal changes especially during the wet season, the Resistivity is expected to be
lowered, the percentage of which depends on the amount of moisture available. Therefore, a Cathodic
Protection could be done for buried pipe works. The criterion used is mostly based on current density
required and soil resistivity. Since the soil resistivity is much higher than 50 Ohm-m, the best method
to be used for the Cathodic Protection is the impressed current method.
The subsurface layers delineated consist of the topsoil, sand-and-clay, intercalating with each other.
The clay layer is deep in some of the areas investigated thus negating the use of shallow foundations.
Pile foundation will suffice for the area or any other design that will adequately take care of the clay
layers such as Raft Foundation.
TABLE 4a: Schlumberger Depth Sounding Data At Federal University Otuoke, Bayelsa State.
Half App. App. App. App. App. App. App. App. Resistivity
current Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Ohm-m
electrode Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m
spread
VES 1 VES 2 VES 3 VES 4 VES 5 VES 6 VES 7 VES 8
________________________________________________________________________________________________________
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 67
\
TABLE 4b: Schlumberger Depth Sounding Data at Federal University Otuoke, Bayelsa State
Half current App. App. App. App. App. App. App. App. Resistivity
electrode Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Ohm-m
spread Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m
TABLE 4c: The Geographical Coordinates of the Investigated Profiles at Federal University Otuoke, Bayelsa State using
Geographical Positioning Systems (GPS)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 68
\
The following Chemical Tests were carried out on the subsurface materials of the Project site, namely:
o pH Values (Soils and Water, where applicable)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 69
\
The following laboratory tests were carried out on selected samples recovered from the borings.
Visual Classification of Soil Samples
Grain Size Analysis
Consistency Limits (Atterberg Limits)
Unit Weights determinations
Unconsolidated-Undrained Tri-axial Tests
Direct Shear Tests on Block samples
Oedometer Consolidation Tests
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 70
\
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 71
\
In the Undrained-Unconsolidated Triaxial Tests, values of both undrained cohesion (Cu) and undrained
friction angle (u) were obtained as indices of strength of the c- materials at the site. Each specimen
of 35mm diameter and 110mm height was prepared from slightly disturbed samples obtained with U-4
shelby tubes of 120mm diameter and tested in unconsolidated-undrained (U-U) compression using cell
pressures of 50.0, 100.0 and 200KPa, respectively.
The values of cohesion (Cu) and friction angles (u) are contained in Tables 8a-8r and Appendix D of the
report.
(i) The coefficient of volume compressibility (Mv); This determines the area that is likely to be
compressible under a given amount of load; and
(ii) The coefficient of consolidation (Cv), which is an indication of the likely rate of settlement per
annum under the given loading conditions.
These values of SPT N-values when converted to Allowable Net Soil Pressures (qllow ) according to the
method of Peck, Hanson and Thornburn (1974) employing the modified relationship:
.qa = 1/F.S{ 0.22 N (0.1073(1000)} kPa --- --- --- --- (3)
where:
F.S = Factor of Safety = 3.0
gives the following approximate allowable net soil pressures for the various soil layers as:
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 73
\
Table 5: Summary of Bearing Capacity Values Derived from Field SPT Soundings at the Federal
University Otuoke Project Site, Ogbia, Bayelsa State
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 74
\
The California bearing Ratios CBR) tests were carried out on Twenty-Nine (29) soil samples obtained
from the project Sites for both soaked and un-soaked tests. These tests were conducted in accordance
with specifications contained in ASTM D1883.
The results of these tests are contained in Appendix “G” of this report.
The samples from the project area were subjected to 24 – hour soaked CBR test, to evaluate the
influence of submergence of the materials to water.
Results indicate that the soils from the project area have a range of CBR (soaked) values of between
18.00% to 32.30 %. These values are very adequate for use as sub-base materials for road pavements.
[Overseas Road Note 31].
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 75
\
How these affect drainage and consolidation characteristics of the various soil profiles at the project
site at the Federal University Otuoke, Project Site are shown in Table 6 above of this report.
Table 6: Consolidation, Bearing and Drainage Characteristics of Materials of the Federal University,
Otuoke Site, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 76
\
The summary of all test results obtained from the project site are contained in Tables 8a-8r of this
Report.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 77
\
8.10 Discussion Of Results Of Investigations In Relation To Foundation Systems Design And Construction For
The Federal University, Otuoke Site, Bayelsa State.
8.10.1 General
A total of eighteen (18) Shell-and-Auger borings were made at the project site to a depth of 30.00
meters as previously mentioned. Also, two (2) geophysical profiles were completed at the project site
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 78
\
TABLE 8a: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
[BORING No.1]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 1/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
1/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
1/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 1/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 1/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 1/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
1/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 1/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
#1 Sand layer (SC) 1/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
110 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
1/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
1/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 1/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 1/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
1/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
1/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
1/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
1/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
1/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
1/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
1/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
1/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 1/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 1/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 1/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
1/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
1/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
1/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 79
\
TABLE 8b: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
[BORING No. 2]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 2/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
2/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
2/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 2/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 2/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 2/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
2/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 2/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
#2 Sand layer (SC) 2/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
210 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
2/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
2/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 2/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 2/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
2/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
2/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
2/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
2/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
2/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
2/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
2/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
2/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 2/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 2/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 2/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
2/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
2/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
2/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 80
\
TABLE 8c: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No. 3]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 3/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
3/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
3/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 3/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 3/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 3/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
3/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 3/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
#3 Sand layer (SC) 3/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
310 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
3/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
3/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 3/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 3/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
3/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
3/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
3/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
3/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
3/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
3/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
3/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
3/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 3/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 3/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 3/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
3/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
3/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
3/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 81
\
TABLE 8d: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.4]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 4/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
4/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
4/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
4/4 3.00 CL 4.5 42.0 16.8 17.8 4 46.8 - - - -
Whitish Silty 4/5 12.0 SM 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands (SM) 4/6 13.0 SM 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
4/7 14.0 SM 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
4/8 15.0 SM 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 - 24 13 7
BH 4
#4 Well-graded 4/9 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 4/10 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 4/11 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
4/12 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8
2
4/13 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6
4/14 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
4/15 30.0 SP 5.0 NP NP 24.6 24.8 0.0 - - - - - - 42 20 14 8 1
4/16 29.0 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - - 28 10 9 2
4/17 28.8 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 26 11 6 5
4/18 28.0 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - 45 28 12 8 2
4/19 28.0 SP 5.2 NP NP 24.6 24.82 0.0 - - - - - - - 24 10 6 2
4/20 27.6 SP 5.0 NP NP 24.6 4.8 0.0 - - - - - - 38 20 14 5 1
4/21 28.8 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - 42 28 10 9
2
4/22 29.0 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 26 11 6
4/23 28.0 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - - 28 12 8 5
4/24 28.0 SP 5.2 NP NP 24.6 24.82 0.0 - - - - - - 45 24 10 6 2
4/25 24.0 SP 5.0 NP NP 24.6 4.8 0.0 - - - - - - - 20 14 6 2
4/26 24.0 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - 38 28 10 9 1
4/27 28.6 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - 42 26 11 6 2
4/28 28.8 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - - 28 12 8 5
4/29 28.8 SP 5.2 NP NP 24.6 24.8 0.0 - - - - - - - 24 10 6 2
4/30 26.8 SP 5.2 NP NP 25.2 25.4 0.0 - - - - - - 45 20 09 8
2
4/31 28.8 SP 4.8 NP NP 24.8 24.8 0.0 - - - - - - - 18 08 4
- - 38 12 02 2 1
-
-
-
Water Table(WT) = >2.5 meters from the ground surface
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 82
\
TABLE 8e: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No. 5]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 5/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
5/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
5/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 5/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 5/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 5/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
5/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
Greyish Clayey 5/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
Sand layer (SC) 5/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
510 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
5/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
BH 5/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
#5
Poorly graded 5/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 5/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
5/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
5/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
5/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
5/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
5/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
5/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
5/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
5/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 5/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 5/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 5/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
5/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
5/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
5/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 83
\
TABLE 8f: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.6]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 6/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
6/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
6/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
6/4 3.00 CL 4.5 42.0 16.8 17.8 4 46.8 - - - -
Whitish Silty 6/5 12.0 SM 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands (SM) 6/6 13.0 SM 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
6/7 14.0 SM 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
6/8 15.0 SM 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 - 24 13 7 4
BH
#6 Well-graded 6/9 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 6/10 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 6/11 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
6/12 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
6/13 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
6/14 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
6/15 30.0 SP 5.0 NP NP 24.6 24.8 0.0 - - - - - - 42 20 14 8 2
6/16 29.0 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - - 28 10 9 5
6/17 28.8 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 26 11 6 2
6/18 28.0 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - 45 28 12 8 2
6/19 28.0 SP 5.2 NP NP 24.6 24.82 0.0 - - - - - - - 24 10 6 1
6/20 27.6 SP 5.0 NP NP 24.6 4.8 0.0 - - - - - - 38 20 14 5 2
6/21 28.8 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - 42 28 10 9 5
6/22 29.0 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 26 11 6 2
6/23 28.0 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - - 28 12 8 2
6/24 28.0 SP 5.2 NP NP 24.6 24.82 0.0 - - - - - - 45 24 10 6 1
6/25 24.0 SP 5.0 NP NP 24.6 4.8 0.0 - - - - - - - 20 14 6 2
6/26 24.0 SP 4.0 NP NP 24.8 24.6 0.0 - - - - - - 38 28 10 9 5
6/27 28.6 SP 5.2 NP NP 23.8 24.8 0.0 - - - - - - 42 26 11 6 2
6/28 28.8 SP 5.4 NP NP 24.8 24.6 0.0 - - - - - - - 28 12 8 2
6/29 28.8 SP 5.2 NP NP 24.6 24.8 0.0 - - - - - - - 24 10 6 1
6/30 26.8 SP 5.2 NP NP 25.2 25.4 0.0 - - - - - - 45 20 09 8 -
6/31 28.8 SP 4.8 NP NP 24.8 24.8 0.0 - - - - - - - 18 08 4 -
- - 38 12 02 2 -
Water Table(WT) = >2.4 meters from the ground surface
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 84
\
TABLE 8g: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No. 7]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 7/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
7/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
7/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 7/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 7/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 7/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
7/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 7/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
#7 Sand layer (SC) 7/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
710 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
7/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
7/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 7/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 7/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
7/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
7/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
7/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
7/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
7/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
7/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
7/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
7/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 7/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 7/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 7/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
7/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
7/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
7/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 85
\
TABLE 8h: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No. 8]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 8/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
8/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
8/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 8/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 8/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 8/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
8/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
Greyish Clayey 8/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
Sand layer (SC) 8/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
810 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
8/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
BH 8/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
#8
Poorly graded 8/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 8/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
8/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
8/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
8/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
8/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
8/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
8/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
8/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
8/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 8/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 8/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 8/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
8/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
8/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
8/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 86
\
TABLE 8i: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.9]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 9/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
9/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
9/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 9/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 9/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 9/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
9/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 9/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
#9 Sand layer (SC) 9/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
910 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
9/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
9/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 9/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 9/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
9/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
9/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
9/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
9/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
9/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
9/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
9/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
9/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 9/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 9/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 9/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
9/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
9/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
9/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 87
\
TABLE 8j: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.10]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 10/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
10/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
10/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
10/4 3.00 CL 4.5 42.0 16.8 17.8 4 46.8 - - - -
Greyish Silty- 10/5 4.0 SM 4.4 NP NP 24.6 5.0 8.0 - - - - 12.5 24.6 35 34 12 10 2
Clayey Sands (SC- 10/6 5.0 SM 5.8 NP NP 24.8 6.0 9.0 - - - - - - - 28 14 10 1
SM) 10/7 6.0 SM 5.2 NP NP 23.8 6.0 8.0 - - - - - - 32 26 14 8 -
10/8 7.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
BH 10/9 8.00 SM 4.4 NP NP 24.6 5.0 - - - - - 12.5 24.6 35 34 12 10 2
# 10 10/10 9.00 SM 5.8 NP NP 24.8 6.0 - - - - - - - - 28 14 10 1
10/11 10.0 SM 5.2 NP NP 23.8 6.0 - - - - - - - 32 26 14 8 -
10/12 11.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
- -
Greyish poorly- 10/13 12.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 10/14 13.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
10/15 14.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
10/16 15.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 28 24 13 7 4
10/17 16.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
10/18 17.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 30 24 13 7 4
Well-graded 10/19 18.0 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 10/20 19.0 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 10/21 20.0 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
10/22 21.0 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
10/23 22.0 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
10/24 23.0 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
10/25 24.0 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
10/26 25.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
10/27 26.8 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
10/28 27.0 SW 5.4 NP NP 24.8 24.6 0.0 - - - - - - 38 28 10 9 5
10/29 28.0 SW 5.2 NP NP 24.6 24.82 0.0 - - - - - - 42 26 11 6 2
10/30 29.0 SW 5.0 NP NP 24.6 4.8 0.0 - - - - - - - 28 12 8 2
10/31 30.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 88
\
TABLE 8k: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.11]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 11/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
11/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
11/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
11/4 3.00 CL 4.5 42.0 16.8 17.8 4 46.8 - - - -
Greyish Silty- 11/5 4.0 SM 4.4 NP NP 24.6 5.0 8.0 - - - - 12.5 24.6 35 34 12 10 2
Clayey Sands (SC- 11/6 5.0 SM 5.8 NP NP 24.8 6.0 9.0 - - - - - - - 28 14 10 1
SM) 11/7 6.0 SM 5.2 NP NP 23.8 6.0 8.0 - - - - - - 32 26 14 8 -
11/8 7.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
BH 11/9 8.00 SM 4.4 NP NP 24.6 5.0 - - - - - 12.5 24.6 35 34 12 10 2
# 11 11/10 9.00 SM 5.8 NP NP 24.8 6.0 - - - - - - - - 28 14 10 1
11/11 10.0 SM 5.2 NP NP 23.8 6.0 - - - - - - - 32 26 14 8 -
11/12 11.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
- -
Greyish poorly- 11/13 12.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 11/14 13.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
11/15 14.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
11/16 15.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 28 24 13 7 4
11/17 16.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
11/18 17.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 30 24 13 7 4
Well-graded 11/19 18.0 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 11/20 19.0 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 11/21 20.0 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
11/22 21.0 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
11/23 22.0 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
11/24 23.0 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
11/25 24.0 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
11/26 25.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
11/27 26.8 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
11/28 27.0 SW 5.4 NP NP 24.8 24.6 0.0 - - - - - - 38 28 10 9 5
11/29 28.0 SW 5.2 NP NP 24.6 24.82 0.0 - - - - - - 42 26 11 6 2
11/30 29.0 SW 5.0 NP NP 24.6 4.8 0.0 - - - - - - - 28 12 8 2
11/31 30.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 89
\
TABLE 8l: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.12]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 12/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
12/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
12/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
12/4 3.00 CL 4.5 42.0 16.8 17.8 4 46.8 - - - -
Whitish Silty 12/5 4.0 SM 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands (SM) 12/6 5.0 SM 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
12/7 6.0 SM 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
12/8 7.0 SM 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 - 24 13 7 4
BH
# 12 Whitish poorly- 12/9 8.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 12/10 9.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
Well-graded 12/11 10.0 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 12/12 11.0 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 12/13 12.0 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
12/14 13.0 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
12/15 14.0 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
12/16 15.0 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
12/17 16.0 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
12/18 17.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
12/19 18.8 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
12/20 19.0 SW 5.4 NP NP 24.8 24.6 0.0 - - - - - - 38 28 10 9 5
12/21 20.0 SW 5.2 NP NP 24.6 24.82 0.0 - - - - - - 42 26 11 6 2
12/22 21.0 SW 5.0 NP NP 24.6 4.8 0.0 - - - - - - - 28 12 8 2
12/23 22.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - - 24 10 6 1
12/24 23.0 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - 45 20 14 6 2
12/25 24.0 SW 5.4 NP NP 24.8 24.6 0.0 - - - - - - - 28 10 9 5
12/26 25.0 SW 5.2 NP NP 24.6 24.82 0.0 - - - - - - 38 26 11 6 2
12/27 26.0 SW 5.0 NP NP 24.6 4.8 0.0 - - - - - - 42 28 12 8 2
12/28 27.0 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - - 24 10 6 1
12/29 28.0 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 09 8 -
12/30 29.0 SW 5.4 NP NP 24.8 24.6 0.0 - - - - - - 45 18 08 4 -
12/31 30.0 SW 5.2 NP NP 24.6 24.8 0.0 - - - - - - - 12 02 2 -
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 90
\
TABLE 8m: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.13]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Clayey 13/1 0.00 CL 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
13/2 1.00 CL 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Layer ( CL)
13/3 2.00 CL 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
Greyish Organic 13/4 3.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 13/5 4.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 13/6 5.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
13/7 6.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
BH Greyish Clayey 13/8 7.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - 34 36 18 4
# 13 Sand layer (SC) 13/9 8.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - 22 34 16 2
13/10 9.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - 22 22 14 -
13/11 10.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 0.54 0.25 - 10 25 12 -
13/12 11.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.60 0.24 - 06 22 10 -
Poorly graded 13/13 12.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 13/14 13.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
13/15 14.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
13/16 15.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
13/17 16.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - - 20 14 8 2
13/18 17.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
13/19 18.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 29 26 11 6 2
13/20 19.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 14.2 25.6 - 28 12 8 2
13/21 20.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
13/22 21.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 32 26 09 8 1
12.5 24.8
Well-graded 13/23 22.0 SP 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 13/24 23.0 SP 4.0 NP NP 24.8 24.8 0.0 - - - - - - - 28 10 9 5
layer 13/28 27.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 11 6 2
13/29 28.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 45 28 12 8 2
13/30 29.0 SP 5.2 NP NP 24.6 24.6 0.0 - - - - - - - 24 10 6 1
13/31 30.0 SP 5.0 NP NP 24.8 24.8 0.0 - - - - - - 38 26 09 8 1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 91
\
TABLE 8n: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.14]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Organic 14/1 0.00 OH 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
14/2 1.00 OH 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Silty Clayey Layer
14/3 2.00 OH 4.5 44.0 18.2 17. 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
(OH) 14/4 3.00 OH 4.0 48.2 12.8 17.8 4 52.8 - - - -
14/5 4.00 OH 4.5 46.0 15.6 17.8 - 50.2 - - - -
Greyish Organic 14/6 5.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 14/7 6.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 14/8 7.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
BH 14/9 8.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
# 14
Greyish Silty Sand 14/10 9.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - - - 34 36 18 4
layer (SM) 14/11 10.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - - - 22 34 16 2
1412 11.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - - - 22 22 14 -
14/13 12.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 - - - - - 10 25 12 -
14/14 13.00 SC 8.0 16.4 6.4 18.8 10 14.8 - - - - - - - 06 22 10 -
14/15 14.00 SC 6.2 15.5 8.5 19.8 8 12.5 - - - - - - -
14/16 15.00 SC 7.4 16.5 6.5 19.4 - - - - - - - - -
14/17 16.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.46 0.26 - - -
Poorly graded 14/18 17.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 14/19 18.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
14/20 19.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
14/21 20.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 92
\
TABLE 8o: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No.15 ]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Brownish Organic 15/1 0.00 OH 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
15/2 1.00 OH 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Silty Clayey Layer
15/3 2.00 OH 4.5 44.0 18.2 17. 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
(OH) 15/4 3.00 OH 4.0 48.2 12.8 17.8 4 52.8 - - - -
15/5 4.00 OH 4.5 46.0 15.6 17.8 - 50.2 - - - -
Greyish Organic 15/6 5.00 OL 6.4 48.2 12.8 17.8 4 48.2 0.14 0.38 0.60 0.88 - 64 36 18 4
Silty Clay layer 15/7 6.00 OL 6.8 46.0 15.6 17.8 - 46.5 -- -- - - - 62 34 16 2
(OL) 15/8 7.00 OL 10.0 44.0 18.2 17.8 4 38.8 0.16 0.34 0.72 0.76 - 42 22 14 4
15/9 8.00 OL 10.2 47.5 14.6 18.4 8 40.2 - 0.28 0.54 0.65 - 30 25 12 4
Greyish Silty Sand 15/10 9.00 SC 6.4 20.6 10.4 20.8 8 5.00 - 0.28 0.60 0.24 - - - 34 36 18 4
layer (SM) 15/11 10.00 SC 6.8 16.5 9.5 18.8 - - - -- - - - - - 22 34 16 2
BH 1512 11.00 SC 6.2 15.5 8.5 19.8 8 12.5 - 0.14 0.72 0.46 - - - 22 22 14 -
# 15/13 12.00 SC 7.4 16.5 6.5 19.4 - - - 0.28 - - - - - 10 25 12 -
15/14 13.00 SC 8.0 16.4 6.4 18.8 10 14.8 - - - - - - - 06 22 10 -
15
15/15 14.00 SC 6.2 15.5 8.5 19.8 8 12.5 - - - - - - -
15/16 15.00 SC 7.4 16.5 6.5 19.4 - - - - - - - - -
15/17 16.00 SC 8.0 16.4 6.4 18.8 10 14.8 - 0.22 0.46 0.26 - - -
Poorly graded 15/18 17.0 SP 4.4 NP NP 24.6 23.8 0.0 - - - - 12.5 24.6 35 34 12 10 2
Sands 15/19 18.0 SP 5.8 NP NP 24.8 24.8 0.0 - - - - - - - 28 14 10 1
15/20 19.0 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
15/21 20.0 SP 5.4 NP NP 24.8 24.8 0.0 - - - - 13.8 26.8 32 24 13 7 4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 93
\
TABLE 8p: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[BORING No. 16]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Greyish Organic 16/1 0.00 OH 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
16/2 1.00 OH 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Clay Layer (OH)
16/3 2.00 OH 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
16/4 3.00 OH 4.5 42.0 16.8 17.8 4 46.8 - - - -
16/5 4.00 OH 4.5 46.0 18.2 17.8 - - - - - -
Greyish Silty- 16/6 5.0 SM 4.4 NP NP 24.6 5.0 8.0 - - - - 12.5 24.6 35 34 12 10 2
Clayey Sands (SC- 16/7 6.0 SM 5.8 NP NP 24.8 6.0 9.0 - - - - - - - 28 14 10 1
SM) 16/8 7.0 SM 5.2 NP NP 23.8 6.0 8.0 - - - - - - 32 26 14 8 -
BH 16/9 8.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
# 16 16/10 9.00 SM 4.4 NP NP 24.6 5.0 - - - - - 12.5 24.6 35 34 12 10 2
16/11 10.00 SM 5.8 NP NP 24.8 6.0 - - - - - - - - 28 14 10 1
16/12 11.00 SM 5.2 NP NP 23.8 6.0 - - - - - - - 32 26 14 8 -
16/13 12.00 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
- -
Greyish poorly- 16/14 13.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 16/15 14.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
16/16 15.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
16/17 16.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 28 24 13 7 4
16/18 17.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
16/19 18.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 30 24 13 7 4
16/20 19.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 32 26 14 8 -
16/21 20.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 24 13 7 4
16/22 21.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 26 14 8 -
Well-graded 16/23 22.00 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 16/24 23.00 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 16/25 24.00 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
16/26 25.00 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
16/27 26.00 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
16/28 27.00 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
16/29 28.00 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
16/30 29.00 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
16/31 30.00 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 94
\
TABLE 8q: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[ BORING No. 17]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Greyish Organic 17/1 0.00 OH 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
17/2 1.00 OH 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Clay Layer (OH)
17/3 2.00 OH 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
17/4 3.00 OH 4.5 42.0 16.8 17.8 4 46.8 - - - -
17/5 4.00 OH 4.5 46.0 18.2 17.8 - - - - - -
Greyish Silty- 17/6 5.0 SM 4.4 NP NP 24.6 5.0 8.0 - - - - 12.5 24.6 35 34 12 10 2
Clayey Sands (SC- 17/7 6.0 SM 5.8 NP NP 24.8 6.0 9.0 - - - - - - - 28 14 10 1
SM) 17/8 7.0 SM 5.2 NP NP 23.8 6.0 8.0 - - - - - - 32 26 14 8 -
BH 17/9 8.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
# 17 17/10 9.00 SM 4.4 NP NP 24.6 5.0 - - - - - 12.5 24.6 35 34 12 10 2
17/11 10.00 SM 5.8 NP NP 24.8 6.0 - - - - - - - - 28 14 10 1
17/12 11.00 SM 5.2 NP NP 23.8 6.0 - - - - - - - 32 26 14 8 -
17/13 12.00 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
- -
Greyish poorly- 17/14 13.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 17/15 14.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
17/16 15.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
17/17 16.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 28 24 13 7 4
17/18 17.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
17/19 18.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 30 24 13 7 4
17/20 19.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 32 26 14 8 -
17/21 20.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 24 13 7 4
17/22 21.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 26 14 8 -
Well-graded 17/23 22.00 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 17/24 23.00 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 17/25 24.00 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
17/26 25.00 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
17/27 26.00 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
17/28 27.00 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
17/29 28.00 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
17/30 29.00 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
17/31 30.00 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 95
\
TABLE 8r: SUMMARY OF GEOTECHNICAL PROPERTIES FOR THE SUB-SOILS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
[ BORING No. 18]
Soil Type Sam Depth USC Soil Consistency Sat. U –U triaxial Oedometer AASHTO Soun- Grain size Distribution Pattern
No. (m) Class Unit Tests Compaction dings
Consolidation Tests (% Passing Sieve Sizes)
Wt
.wn LL PI Mv Cv
(%) (%) (%) kN/m3 u Cu (m2 / MN) x 10-4 (m2 / yr.) OMC MDD SPT > 4.75 75 2
(o ) kPa 50.00 400.00 50.00 400. (N ) 4.75 mm
kPa kPa kPa kPa mm
Greyish Organic 18/1 0.00 OH 4.0 48.2 12.8 17.8 4 52.8 0.14 0.38 0.60 0.88 88 44 38 24
18/2 1.00 OH 4.5 46.0 15.6 17.8 - 50.2 -- -- - - 74 42 36 22
Clay Layer (OH)
18/3 2.00 OH 4.5 44.0 18.2 17.8 6 46.8 0.16 0.34 0.72 0.76 72 40 36 20
18/4 3.00 OH 4.5 42.0 16.8 17.8 4 46.8 - - - -
18/5 4.00 OH 4.5 46.0 18.2 17.8 - - - - - -
Greyish Silty- 18/6 5.0 SM 4.4 NP NP 24.6 5.0 8.0 - - - - 12.5 24.6 35 34 12 10 2
Clayey Sands (SC- 18/7 6.0 SM 5.8 NP NP 24.8 6.0 9.0 - - - - - - - 28 14 10 1
SM) 18/8 7.0 SM 5.2 NP NP 23.8 6.0 8.0 - - - - - - 32 26 14 8 -
BH 18/9 8.0 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
# 18 18/10 9.00 SM 4.4 NP NP 24.6 5.0 - - - - - 12.5 24.6 35 34 12 10 2
18/11 10.00 SM 5.8 NP NP 24.8 6.0 - - - - - - - - 28 14 10 1
18/12 11.00 SM 5.2 NP NP 23.8 6.0 - - - - - - - 32 26 14 8 -
18/13 12.00 SM 5.4 NP NP 24.8 6.0 - - - - - 13.8 26.8 - 24 13 7 4
- -
Greyish poorly- 18/14 13.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - 32 26 14 8 -
graded sands 18/15 14.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 24 13 7 4
18/16 15.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
18/17 16.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 28 24 13 7 4
18/18 17.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 14 8 -
18/19 18.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 30 24 13 7 4
18/20 19.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - 32 26 14 8 -
18/21 20.00 SP 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 24 13 7 4
18/22 21.00 SP 5.4 NP NP 24.8 24.8 0.0 - - - - - - - 26 14 8 -
Well-graded 18/23 22.00 SW 5.0 NP NP 24.6 23.8 0.0 - - - - - - 42 20 14 8 2
gravelly sands 18/24 23.00 SW 4.0 NP NP 24.8 24.8 0.0 - - - - - - 45 24 10 6 1
layer 18/25 24.00 SW 5.2 NP NP 23.8 24.6 0.0 - - - - - - - 26 09 8 1
18/26 25.00 SW 5.4 NP NP 24.8 24.8 0.0 - - - - - - 38 20 14 8 2
18/27 26.00 SW 5.2 NP NP 24.6 24.6 0.0 - - - - - - 42 28 10 9 5
18/28 27.00 SW 5.0 NP NP 24.8 24.8 0.0 - - - - - - - 26 11 6 2
18/29 28.00 SW 5.0 NP NP 24.6 24.8 0.0 - - - - - - - 28 12 8 2
18/30 29.00 SW 4.0 NP NP 24.8 24.6 0.0 - - - - - - 45 24 10 6 1
18/31 30.00 SW 5.2 NP NP 23.8 24.8 0.0 - - - - - - - 20 14 5 2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 96
8.10.2 Soil Bearing Pressures
On the basis of field investigations and laboratory tests performed, we have the following
observations about the safe bearing pressures that can be borne by each of the identified subsoil
layers at the project site. In making these comments, account has been taken of comparative
values of bearing pressures obtained in similar soil conditions elsewhere within the Niger Delta sub-
region and adjoining flanks (Teme, 1989, 1994, 1995, 1997, 1998, 1999a, 1999b, 1999c, 1999d,
1999e, 2000a, 2000b, 2001a, 2001b, 2001c, 2002a, 2003a,b and c; 2004 a-n; 2005 a-z; 2006 a-d;
2007 a-e; 2008 a-e; 2009a-c; 2010 a-b; 2011 1-d; 2012 a-b and 2013 a-b). The soil pressures that
can be borne by each soil horizon identified at the project site have been provided in Section 8.5 of
this Report and need not be mentioned here.
Shallow Foundations
It is recommended that Shallow Foundations should be adopted at the project siteson the
basis of the Lithologic configuration of the subsurface there. (see Logs in Appendix A1 of
this Report).
Isolated Footings
It is being proposed that Office buildings, Residential buildings and Classrooms of less than
one storey at the project site should employ the use of Isolated Footings and possibly Rafts
as foundations. In this regard, the bearing capacities of the proposed Isolated Footings are
being calculated in this section of the Report to serve as applicable values for the Isolated
Footings that would be used in the service life of the such buildings.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 97
Depth of foundation below ground surface (Df)
The depth of the foundation below ground surface is taken to be that depth from the
ground surface to the base of the foundation level, as shown in the Figure 11. For this
project site, the recommended depth of isolated footings for Office Buildings is taken as
1.50 meters.
Width x
Length
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 98
The Net Ultimate Bearing Capacity for Isolated Footings is given as follows (according to Tomlinson
(1980)):-
where:
c = cohesion of soil at site, ~ 50 kPa.
N = Terzaghi Bearing Capacity factor with respect to unit weight, (available in Table 9)
po = effective pressure of overburden soil at foundation level, = ‘Df. = (17.8 kN/m3) ( 1.50m)
= 26.70kPa
1.3 = shape factor of footing with respect to cohesion.
(degrees) Nc N Nq
0 5.14 0 1.00
5 6.5 0.10 1.60
10 8.40 0.50 2.50
15 11.00 1.40 4.00
20 14.8 3.50 6.40
25 20.70 8.10 10.70
30 30.00 18.10 18.40
35 46.00 41.10 33.30
40 75.30 100.00 64.20
45 134.00 254.00 135.00
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 99
At a depth of 1.50m (recommended by the Geotechnical Consultants) at this site, we have the
following soil properties:
.c = 50.00 kPa = 10.0o N = 0.50
= 17.8 kN/m3 Nc = 8.40 Nq = 2.50
Assuming a Factor of Safety (F.S) = 3.0 Also assuming that B/L ~ 1.00 = 5/5
we have:
qallow = 1/3 {(1.3)(50.00) ( 8.4) + ( 26.70 kPa) ( 2.50 – 1) + ( 0.4) ( 17.8 kN/m3) ( B m) (0.50) }
= 1/3 { 1.3 x 420} + { 40.05} + { 3.56 B} ]
= 195.35 + 1.1867 B kPa
Hence, the Net Ultimate Bearing Capacity for the Isolated footing of B meter square for office
buildings at the Federal University Otuoke project site in Bayelsa State is found to be about 195.35
+ 1.1867 B kPa.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 100
Depth of Foundation below ground surface (Df)
The depth of the foundation below ground surface is taken to be that depth from the
ground surface to the base of the foundation level, as shown in the Figure 12. From boring
and sounding records obtained at the project site, the Continuous Strip Footing should be
borne at depths of 0.75 meter below the ground level. This depth range coincides with the
lateritic Clayey Sands (SC) layer. This will necessitate the removal of about 0.75 meter of
this overburden at the site during the foundation construction phase of the project.
8.10.7 Calculation Of Ultimate Bearing Capacities For The Continuous Strip Footing Foundations At the Site
The Net Ultimate Bearing Capacity for Continuous Strip Footings is given by the following according
to Tomlinson (1980):-
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 101
qnf = cNc + po (Nq – 1 ) + (B/2) N . … … … (5)
where:
c = cohesion of soil at site, ~ 50 kPa.
Nc , Nq and N = Terzaghi Bearing Capacity factors obtainable in Table 9 above.
B = width or breadth of the Isolated footing, = 1.50 meters (assumed)
= unit weight of the soil materials at site. = 17.8 kN/m3
po = effective pressure of overburden soil at foundation level, = ‘Df. = (17.8 kN/m3)
( 1.50m)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 102
.c = 50.00 kPa = 10.0o N = 0.50
= 17.8 kN/m3 Nc = 8.40 Nq = 2.50
Assuming a Factor of Safety (F.S) = 3.0 we have from equation (5) above:
q allow = 1/3 {(50.00) ( 8.4) + ( 26.70 kPa) ( 2.50 – 1) + ( 0.5) ( 17.8 kN/m3) ( B) (0.50) }
= 1/3 {{ 420} + { 40.05} + { 4.45 B}}
= 153.35 + 1.483B kPa
The Net Ultimate Bearing Capacity for Continuous Strip Footing of B meters length for Residential
Buildings at the Federal University Otuoke Project Site, Bayelsa State is found to be about 153.35 +
1.483B kPa [compared with q(allow) = 195.35 + 1.1867 B kPa obtained for the Isolated Footing for
Offices]. Settlement considerations are by the virtue of the inherent use of these equations limited
to 25.4 mm. The use of the Factor of Safety of 3.0 takes care of any unexpected high settlement
values that may likely be obtained for this site.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 103
P = Weight of Super Structures
Depth of Raft
Beneath ground
Surface Df = 1.50m
x Width of Footing, y x
Width of Foundation, B
The Length of the Raft footing is the same as the length of the building in question. This is
to be provided by Client.
8.13 Computations of Bearing Capacities for The Federal University, Otuoke Project Site, Bayelsa State.
In computing the bearing capacities of the soils at the various boring sites at the project site, several
classical computational methods have been used. These methods include the following:-
a) SPT Method
b) Terzaghi’s Method
c) Meyerhof’s Method
d) Bowles Method
e) Brinch Hansen’s Method.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 104
8.13.1 Bearing Capacity Based on the “SPT Method”
The allowable net soil pressure for the design of Rigid Raft based on the “SPT” field data, may with
sufficient accuracy be taken as:
qa (tons / sq. ft ) = 0.22 N --- --- --- --- --- --- (1)
where: N = SPT value (corrected for Water Table effects)
At a depth of 1.50 meters at the project site, an average value of SPT N-value of 17 was obtained.
Thus,
qa (tons / sq. ft) = 0.22 ( 17 ) = 3.74 tons / sq. ft
= ( 3.74 ) ( 0.1073) = 0.4013 MPa
= 401.302 KPa.
For a Safety Factor of 3.0 the allowable Bearing Capacity ( based on The SPT- Method ) = 133.77
kPa
[Note: This value of bearing capacity can be conveniently used for a depth range of 1.50 - 2.50
meters.]
qu = qc / F.S = 1/F.S {{ ( 1-0.2 B/L ) B/L.N } + { (1 + 0.20 B/L) c Nc} + { ( Df Nq )}} --- ( 6 )
where,
B = width of Raft Foundation = 5.00m; L = Length of Raft Foundation = 10.00m (assumed)
= unit weight of soil at foundation level
N, Nc, Nq = Terzaghi bearing Capacity Factors obtainable from Table 5 above.
qu = qc / F.S = 1/3 { { ( 0.80 x 0.50) 17.8kPa x 0.50 } + { (1.20 x 0.50) 50.00kPa x 8.40
+ {(17.8kPa) ( 1.50m) ( 2.50).
= 1/3 { 322.31 } = 107.44 Kpa.
qa = 12N B + 0.305 2
qa = 12.5 N B + 0.305 2
kd B 1.22 m --- (7b)
B B
2
qa = 12 N B + 0.305 --- --- --- --- --- --- --- ( 7b )
B
where: N= SPT value (corrected for water table effects).
Meyerhof’s Method
At a depth of the proposed 1.50 meters at the project site, an SPT N-value of 17 minimum was
obtained,
qu (kN/m2) = ( 12 x 17 ) { ( 5.00 + 0.305) / 5.00 } 2 = 229.647 kN/m2 [where B ~ 5.00m,
assumed]
Hence,
.qu ( kN/m2 ) = 229.647 kPa
Applying a factor of safety of 3.0 gives,
8.13.4 Bearing Capacity of the Federal University Otuoke Project Site, Bayelsa State Foundation Based on
the Bowles’ Method
Bowles (1988) modified Meyerhof’s equation is shown for some boundary conditions in Table 10
above.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 106
At a depth of the proposed 1.50 meters at the project site, a minimum SPT N-value of 17. was
obtained. Thus,
For B 1.22 m, the following relationship (eqn. 7b of Bowles) is applicable,
qa = 12.5N B + 0.305 2 kd --- --- --- --- --- --- --- (7b)
B
where,
Kd = 1 + 0.33 ( D/B ) 1.33 --- --- --- --- --- (8)
= 1 + 0.33 ( 1.50 / 5.00 )
= 1.099
= 262.898 kPa
Table 11: Values of Bearing Capacities of Project Site Sub-soils, based on SPT N-values.
* = for B = 5.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 107
Qu = - c Cot. + (q + c Cot. ) Nq sq dq + 0.5 B N s d --- --(9)
where,
parameters are as defined in Equations (6) above.
For horizontal ground surface, horizontal footing base, the ground and inclination factors all equal
to unity (1)
Hence, assuming a q = 200 kPa, substituting the same soil conditions and the relevant factors into
Equation (9) gives:
qu = { -50.00 kPa [ Cot 10o ]} + { (200 kPa + 50.00kPa (Cot 10o )) (2.50)(1)(1)}
+ { 0.50(5.00)(0.50)(1)(1)}
= 626.586 kPa
q(allowable) = qu / F.S = 208.862 KPa
The Brinch Hansen equation for the ultimate Bearing Capacity for the project site soils is given by
the following:-
.qf = cNc scdcicbcgc + po Nq sqdqiqbqgq + 0.50 γ B Nγ s γ d γ i γ b γ g γ … … … …( 10a )
Where:
γ = density of soil below foundation level,
B = width of foundation,
c = undrained cohesion of soil
po = [γsoil - γwater ] Df = [ 17.80 – 1.00] Df = effective pressure of overburden soil at
foundation level
Df = Depth of foundation [ variable ]
Nγ, Nq, and Nc are bearing capacity factors,
s γ, sq and sc are shape factors
d γ dq, dc, are depth factors
i γ iq, ic are load inclination factors
b γ bq bc are base inclination factors
g γ gq, gc are ground surface inclination factors
Since the project site is relatively flat, we can conveniently assume that the depth, shape, load
inclination and ground surface inclination factors = 1.00. Results of a sensitivity analysis of bearing
capacities of the various analytical methods with depth are shown in Table 12. In summary
therefore, the values of the bearing capacity based on Raft type (at foundation bearing level of 1.50
meters) for the Federal University Otuoke, Bayelsa State Foundation based on the various classical
geotechnical computation methods are as given in Table 12 below, for purposes of comparison and
analysis.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 108
Table 12: Bearing Capacity Values For The Federal University Otuoke, Bayelsa State Foundation [Df =
1.50m], (Based On F.S = 3.0 )
(1967) (1968)
Depth of Foundation (m)
1.50m 0.75m 1.50m
On the
OK OK OK OK OK High side OK Acceptable
These values are however, below the upper values for bearing capacity (380 to 470 kPa) cautioned
for use by Bowles (1977, page 124).
Settlement considerations are by the virtue of the inherent use of these equations limited to 25.4
mm. The use of the Factor of safety of 3.0 takes care of any unexpected high settlement values that
may likely be obtained for this site.
From the above, it could be observed that the range of Soil Bearing Capacity values useable at the
proposed Federal University Otuoke, Bayelsa State, based on a foundation depth (Df ) of 1.50
meters for a B value = 5.00 meters = 76.549 to 208.86 kPa with an average of 139.47 kPa.
The above values of bearing capacity are based on the empirical methods of Bowles (1988),
Meyerhof (1974), Terzaghi and Peck (1967); Hansen ( 1968 ) and proven field methods using the
SPT techniques (Peck, Hansen and Thornburn, 1974).
The soil profiles at the given Project site are quite homogeneous as shown in the Fence diagrams
given in Figures 5a; 5b; and 5c, respectively.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 109
A Sensitivity Analysis of the Bearing Capacity of the soils for both Isolated and Raft Footings for
depths ranging from 0.50m; 1.00m; 1,50m; 2,00m and 2,50 meters was carried out and the results
are as shown in Table 13.
Table 13: A Sensitivity Analysis of Bearing Capacities of Project Site soils for Isolated and Raft Foundations,
Federal University Otuoke, Bayelsa State
S/No. Foundation Bearing Capacity Values for Foundation Types Remarks
Depth [ kPa]
(m) Foundation Types
Isolated RAFT FOUNDATION
Footings
Analytical Methods adopted
Meyerhof’s Bowles’ Terzaghi Brinch
(1974) (1988) & Hansen’s
Peck (1968)
(1967)
Table 14: The Final Average Values of Bearing Capacity for Isolated and Raft Foundations at
Different Foundation Depths.
S/No. Foundation Final Average Bearing Capacity Values Remarks
Depth [kPa]
(m) Foundation Types
Isolated Footing Raft Foundations
8.14 Re-Assessment if Allowable Bearing Capacity at 1.5m Depth At The Site Of The Federal University,
Otuoke, Bayelsa State.
A re-assessment of both the Net Soil Pressure (q net ) and the allowable bearing capacity ( qallow ) at
the specified depth of foundation of 2.50 meters for the Federal University, Otuoke, Bayelsa State
is as follows:
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 110
8.14.1 ZONE A.
.qnet = Dc ( c - s ) + P / Af … … … … … (10)
= {[ 14.4 ] + [9.964T/( B x L ) ]} kN / m2
where:
For stability of the Foundation, q net q allow. [14.4] + [(9.964T)/( B x L)] kN / m2… (11)
We can recommend that a qnet = [1.44] + [(9.964T)/( B x L)] kN / m2 be used in the design of the
Raft Foundation at the Federal University, Otuoke, Bayelsa State.
P
Ground Surface
.
(concrete) Df = 1.70m
d = 1.50m
q
.a
Af = b x l B
q
Af = B x L
L
Figure 14: Net Pressure on footing with backfill (assuming top of Raft footing above ground
surface).
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 111
8.14.2 On the basis of the computations carried out above, the following recommendations are hereby
made:-
(1) A range of values of between 76.549 to 208.86 kPa with an average of 139.47 kPa. has
been found to be the bearing capacity of the upper bearing Lateritic Clayey Sand (SC) layer for
purposes of supporting the 1-2 storey buildings at the Federal University Otuoke, Bayelsa State.
(2) A depth of about 1.50 meters should be excavated before placement of building Foundation
at the Project Site.
(3) The width of the Raft Foundation in all cases should be taken as ( B + 2x ) meters, where: B
= width of the base of the building, and x = 1.00 m as allowance around the perimeter of the
excavation.
(4) A value of qnet = [1.44] + [(9.964T)/( B x L)] kN / m2 can be used as the Net Soil Pressure on
the soil at the project site, since this value should be less than the average value of the allowable
soil pressure, q(allow) (bearing capacity ) of the soils at site. [Note: B = breadth; L = Length of
structures at site ].
Settlement considerations are by the virtue of the inherent use of these equations limited to 25.4
mm. The use of the Factor of safety of 3.0 takes care of any unexpected high settlement values that
may likely be obtained for this site.
8.15.1 Estimation of Settlements of More Than 2- Storey Building Foundations on The Clayey Sand Stratum
at a Depth Of 0.75 Meters or 1.50 Meters.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 112
where:
the factors µ1 and µ0 are related to the depth (Df ) of the foundation, the thickness of the H
of the compressible layer and Length /Width (L/B) ratio of the foundation. Values of these
factors are shown in the Figure 15 below.
where,
mv = average coefficient of volume compressibility obtainable
from laboratory tests on soils from the site. = 0.16 x 10-4 m2 / MN
H = thickness from bottom of Foundation to
competent layer below [ eg. Sandy layer] = 7.50 m [ from Boring # 1
at site ]
B = Width of the foundation.
qn = Imposed load on the soil .
µ1 = 0.50
µ0 = 0.96
Ed = 1/ mv = 1 /( 0.16 x 10 -4) m2 /MN
= 62,500 MN/ m2
i = (0.50 x 0.96 x qn (kN/ m2 )x B (m)) / 62,500 MN/ m2
= 7. 68 x 10-6 qn B [in meters]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 113
I = 7. 68 x 10-6 qn B [in meters]
Figure 15: Factors for Calculating the Average Immediate Settlement Of Loaded Area.
(after Christian and Carrier (1978)
8.5.2 Computation of Immediate Settlements in the Clayey Sand Stratum at The Site.
The stresses transmitted to the surface of the Clayey Sands Layer at the project site can be given
as:
{ immediate settlement, I + final settlement , Sc }
where:
immediate settlement, I , can be computed from laboratory Oedometer data.
Using the method of Skempton and Bjerrum (1957) we observe that the oedometer settlement
(oed ) at the point of foundation level is given as:
oed = mv . z . H … … … … … … … … (13a)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 114
where,
mv = average coefficient of volume compressibility obtainable
from laboratory tests on soils from the project site.
z = average effective vertical stress imposed on the soil by the superstructure,
H = thickness of the compressible layer from bottom of foundation to competent layer.
When we represent the vertical stress distribution pattern by a triangular distribution, the above
equation becomes:-
Oedometer settlement, i = mv . z . H
= mv x 0.55 qn x 1.5 B … … … … (13b)
But,
mv = 0.16 x 10-4 m2 / MN
B = [Width of the Production Building]
.qn = imposed load = T (MPa)
i = (0.16 x 10-4 m2/MN ) ( 0.55) (T MPa) (1.5 x B m )
=
I = 0.0000132(T)(B) m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 115
= { 0.520 } log10 {1 + T / 66.75} cm
Sc = { 0.520} log10 {1 + 0.01498T}
The summary of the computed estimated values of settlements for the project site is shown in
Table 15.
Table 15: Summary of Computed Settlements at the Project Site
Project Site Computed Settlements (cm) Remarks
Immediate Long-term Total
settlement Settlement (Hf) Settlement
(i) ( total)
Federal
University, 0.000132T { 0.520} log10 {1 + 0.000132T + Compressible layer
Otuoke, m 0.01498T }m { 0.520} log10 {1 + beneath foundation
Bayelsa 0.01498T }m level = 7.50 m
State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 116
= 0.76 m2 / yr.
T = time factor which for the given condition
of loading and drainage at the project site corresponds to
T 50 = 0.20 and T 90= 0.85
From equation ( 16 ) above, the time period required for a 50% of final foundation settlement for
the brownish Lateritic Clayey Sand (SC) layer is estimated at:-
. t 50 = ( 0.20 ) ( 3.75) 2
0.76
t 50 = 3.700 years
A summary of the Rates of Settlements computed for the site at The Federal University Otuoke Campus Site
is shown in the Table 16.
Table 16: Summary of the computed Rates of Settlements for the site at the Federal University Otuoke, Bayelsa
State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 117
9.0 Discussion of Results of Investigations in Relation to Foundation System Design
and Construction for The Proposed Structures at The Federal University,
Otuoke, Bayelsa State.
9.1 General
A total of Eighteen (18) Shell-and-Auger borings and Twenty-Nine (29) Hand-Auger borings were
made at the project site to a depth of 30.00 meters and 3.00meters, respectively as previously
mentioned.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 118
9.3.1 Storey Buildings With Two or More Floors, at the Federal University Complex, Otuoke, Bayelsa State
The design of the Concrete Reinforced Steel Hollow Cylindrical Piles Foundation on the basis of the
detailed field investigations carried out at the project site should take the following into
considerations.
For the recommended pile under consideration, the Ultimate Carrying Capacity, Qu , can be
assessed using equation (---) above as follows:-
For a Steel Pipe diameter of 400mm and a Factor of Safety (F.S) of 3.0.
Assuming the total Load of the Superstructure, = (T) Tons, and Area of each Pier = (As ), then
the Total imposed Net soil pressure (q net) is:
.q net = Dc ( c - s ) + ( hf ) ( ’ ) + T /As --- --- --- --- (18)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 119
where:
T = Weight of Super structure.
= (42.99 +7.34 x 10 -7 T)
Qu = Q b + Qs … … … … … … …(20)
Where:
Qb = base resistance of tip of pile
Qs = Skin Friction of pile
For a pile depth of 24.00 meters, for Borehole #1 at the project site we have:
Pd = 37.8kN/m2
Qb = 37.8 (24.36 - 1)
= 0.883 MN
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 120
f = Ks. Pd. tan --- --- --- --- … --- (22)
However, the failure load of the pile Qu = load at failure applied to the pile Q’u + Wt of the
Pile (Wp)
.ie:
Qu ’ = Qu - W p = Q b + Q s
= Ab Pd (Nq –1) + Qs
= A b P d N q - A b P d + Qs
where:
Ab = cross-sectional area of pile
As = embedded surface area of pile
Pd = average effective overburden pressure over embedded depth of pile
Qs = Pd{{ ( . r2 ) (24.36)} + { 1.1 x tan (2/3 (30.00)) ( D.24.00)}}
Qs = {0.662r2 + 0.254 D} MN
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 121
Table 17: Values of Pile Bearing Capacities for various Pile Diameters for the Building Foundations
(Qu' )(MN)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 122
Table 18a: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT.
[AVERAGE BORING PARAMETERS - [ Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
Lithology Thickness Depth Frictional Cohension (c) Effective Ks =0.5tan 2 q0 =γb n Diameter Perimeter (P) δ =2/3ф TAN δ
[∆L] [m] At Angleф [kPa] Density(γsat) [450 + ф/2] ∆Ln (D) m 2pr (0o)
Bottom [deg] [kN/m3] [kN/m2]
(m)
CL 2 2 4 45.6 12.19 0.0078 6.095 0.4 1.25664 2.66667 0.046576
OL 4 6 6 65 4.5 0.72 8.83 0.4 1.25664 4 0.069927
SC 6 12 18 12.8 9.79 0.227 18.62 0.4 1.25664 12 0.212557
SP 10 22 32 0 16.5 7.006 47.99 0.4 1.25664 21.3333 0.390555
SP 4 26 32 0 16.5 7,006 89.96 0.4 1.25664 21.3333 0.390555
SW 4 30 36 0 28.6 0.0144 161.9 0.4 1.25664 24 0.44523
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 123
Table 18b: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 124
Table 18c: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
Ab m Nc Nq Nγ ΣqoKsTAN Pile Shaft Pile End Qu = Qb + Q (allowed) Σ Total Pile Load (allowable) [F.S = 2.50]
δ∆L Load (Qf ) Load Qf [kN] = Qu/F.S [MN]
[kN] (qb)[kN] [F.S =
(P*ΣqoKst (cNc+q0N 2.50]
anδ∆L) q)Ab
0.50266 43.2 30.86 0 0.00443 0.01113 1084.74 1084.75 433.899 0.4339
0.50266 9.36 3.12 54 1.77827 4.46929 319.664 324.133 129.653 0.13009
0.50266 7.44 1.86 0 5.39054 13.5479 65.2775 78.8255 31.5302 0.03166
0.50266 40.8 29.14 54 1313.12 3300.23 702.929 4003.16 1601.26 1.60129
0.50266 30.8 19.8 26 984605 2474587 895.335 2475482 990193 990.195
0.50266 43.2 30.86 54 4.15196 10.435 2511.39 2521.82 1008.73 1.99892
Pile Diameter = 800mm = 0.800m
FEDERAL UNIVERSITY, OTUOKE BAYELSA STATE - ZONE A - 800mm DIAMETER PILE - TGCL - 28 - 04- 2013.
[ BH#s: 1, 2, 3, 4, 5, & 9 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 125
Table 18d: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
Lithology Thickness Depth At Frictional Cohension (c) Effective Density Ks =0.5tan 2 q0 =γb n Diameter Perimeter δ =2/3ф TAN δ (0o)
[∆L] [m] Bottom (m) Angleф [kPa] (γsat) [kN/m3] [450 + ф/2] ∆Ln (D) m (P) 2pr
[deg] [kN/m2]
BH#s: 1, 2, 3, 4, 5, & 9 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 126
Depth 400mm Pile Diameter - Federal University Depth 600mm Pile Diameter- Federal University
(m) ZONE # A. (m) ZONE # A.
0 0 0 0
0 0.0224692 0 0.05015648
4 0.0576352 4 0.12121825
8 0.263772 8 0.51066881
14 0.8160352 14 1.50340727
22 2.1035707 22 3.76618006
30 3.8943775 30 6.9134243
Figure 16a: Plot of Pile Load Vs Depth for Pile Diameters of 400mm and 600mm at the Federal University Otuoke Zone A.
[ BH# 1, 2, 3, 4, 5 and 9 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 127
800mm Pile Diameter- Federal University Depth 1000m Pile Diameter- Federal University
Depth ZONE # A. (m) ZONE # A.
(m)
0 0.088812 0 0.138436
4 0.207978 4 0.317915
8 0.834239 8 1.234484
14 2.377016 14 3.436861
22 5.836005 22 8.313047
30 10.64704 30 15.09523
Figure 16b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal University Otuoke Zone A
[ BH# 1, 2, 3, 4, 5 and 9 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 128
Table 19a: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
0.13192789
0.125664 43.2 30.86 0 0.00442853 0.00556506 329.8141781 329.8197 131.9279 7
0.03293010
0.125664 9.36 3.12 54 1.65477993 2.07946265 79.91597053 81.99543 32.798173 1
0.125664 7.44 1.86 0 4.49211743 5.64497444 14.07552411 19.7205 7.8881994 0.00792113
0.46632822
0.125664 40.8 29.14 54 787.869737 990.068627 175.7321316 1165.801 466.3203 5
0.58491722
0.125664 30.8 19.8 26 984.604592 1237.29351 223.8337221 1461.127 584.45089 3
0.25641938
0.125664 43.2 30.86 54 9.34191976 11.73943 627.8467494 639.5862 255.83447 9
Diameter = 400mm = 0.4m ZONE # B SOILS [CASING DIAMETER ( B) = 400mm]
{BORING # 6,7,8,12& 13}
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 129
Table 19b: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE PROJECT
[ AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
Depth
At Frictional TAN δ
Lithology δ =2/3ф
Thickness Bottom Angleф Cohension (c) Effective Density Ks =0.5tan 2 q0 =γb n ∆Ln Diameter Perimeter (0o)
[∆L] [m] (m) [deg] [kPa] (γsat) [kN/m3] [450 + ф/2] [kN/m2] (D) m (P) 2pr
CL 2 2 4 56.4 9.85 0.0078 6.095 0.6 1.88496 2.666667 0.046576
OL 4 6 6 65 4.5 0.67 8.83 0.6 1.88496 4 0.069927
SC 5 11 18 10.4 10.6 0.227 18.62 0.6 1.88496 12 0.212557
SP 6 17 32 0 22.3 7.006 47.99 0.6 1.88496 21.33333 0.390555
SP 4 21 32 0 22.5 7 89.96 0.6 1.88496 21.33333 0.390555
SW 9 30 36 0 27.8 0.0144 161.9 0.6 1.88496 24 0.44523
Σ Total
Pile Load
Pile Shaft Load
Q (allowed) = (allowable)
Ab m ΣqoKsTANδ∆L (Qf ) [kN]
Pile End Load Qu/F.S [F.S =
(P*ΣqoKstanδ∆L)
Nc Nq Nγ (qb)[kN] Qu = Qb + Q f [F.S = 2.50]
(cNc+q0Nq)Ab [kN] 2.50] [MN]
0.282744 43.2 30.86 0 0.004429 0.008348 742.0819 742.0902 296.8361 0.296836
0.282744 9.36 3.12 54 1.65478 3.119194 179.8109 182.9301 73.17205 0.073469
0.282744 7.44 1.86 0 4.492117 8.467462 31.66993 40.13739 16.05496 0.016128
0.282744 40.8 29.14 54 787.8697 1485.103 395.3973 1880.5 752.2001 0.752216
0.282744 30.8 19.8 26 984.6046 1855.94 503.6259 2359.566 943.8265 0.944579
0.282744 43.2 30.86 54 9.34192 17.60915 1412.655 1430.264 572.1057 0.57305
Diameter = 600mm = 0.6m ZONE # B SOILS [CASING DIAMETER ( B) = 600mm]
{BORING # 6,7,8,12& 13}
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 130
Table 19c: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[ AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 131
Table 19d: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[ AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
Effective
Depth At
Frictional Density
Layer Bottom Δ =2/3ф TAN δ (0o)
Thickness Angleф Cohension (γsat) Ks =0.5tan 2 q0 =γb n ∆Ln Diameter Perimeter
(m)
[∆L] [m] [deg] (c) [kPa] [kN/m3] [450 + ф/2] [kN/m2] (D) m (P) 2pr
CL 2 2 4 56.4 9.85 0.0078 6.095 1 3.1416 2.666667 0.046576
OL 4 6 6 65 4.5 0.67 8.83 1 3.1416 4 0.069927
SC 5 11 18 10.4 10.6 0.227 18.62 1 3.1416 12 0.212557
SP 6 17 32 0 22.3 7.006 47.99 1 3.1416 21.33333 0.390555
SP 4 21 32 0 22.5 7 89.96 1 3.1416 21.33333 0.390555
SW 9 30 36 0 27.8 0.0144 161.9 1 3.1416 24 0.44523
Nc Nq Nγ Σ Total
Pile Shaft
Pile End Pile Load
Load (Qf )
ΣqoKsTANδ∆ Load Q (allowed) = (allowable)
Ab m [kN]
L (qb)[kN] Qu/F.S [F.S =
(P*ΣqoKstan
(cNc+q0Nq)A
Qu = Qb + Qf [F.S = 2.50]
δ∆L)
b [kN] 2.50] [MN]
0.7854 7.44 1.86 0 0.004429 0.013913 338.4703 338.4842 135.3937 0.135394
0.7854 28 18 54 1.65478 5.198657 1554.259 1559.458 623.7833 0.623919
0.7854 9.33 3.36 0 4.492117 14.11244 125.3461 139.4585 55.7834 0.056407
0.7854 43.2 30.86 54 787.8697 2475.172 1163.155 3638.327 1455.331 1.455387
0.7854 30.8 19.8 26 984.6046 3093.234 1398.961 4492.195 1796.878 1.798333
0.7854 43.2 30.86 54 9.34192 29.34858 3924.042 3953.391 1581.356 1.583155
Diameter = 1000mm =1.0m ZONE # B SOILS [CASING DIAMETER ( B) = 1000mm]
{BORING # 6,7,8,12& 13}
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 132
Depth (m) 400mm Pile Diameter- Federal University Depth 600mm Pile Diameter- Federal University
ZONE # B. (m) ZONE # B.
2 0.025838 2 0.05688602
4 0.0613 4 0.12852234
8 0.268393 8 0.51977963
11 0.562201 11 1.08568312
18 1.516965 18 2.78500138
30 3.904754 30 6.82820574
Figure 17a: Plot of Pile Load vs. Depth for Pile Diameters of 400mm and 600mm at the Federal University Otuoke Zone B
[ BH# 6, 7, 8, 12 and 13 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 133
Depth 800mm Pile Diameter- Federal University Depth 1000mm Pile Diameter- Federal University
(m) ZONE # B. (m) ZONE # B.
2 0.100021 2 0.155241
4 0.220126 4 0.336112
8 0.849293 8 1.256933
11 1.770753 11 2.61741
18 4.392741 18 6.340183
30 10.39904 30 14.61726
Figure 17b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal University Otuoke Zone B
[ BH# 6, 7, 8, 12 and 13 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 134
Table 20a: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
ZONE # C SOILS {BORING # 10,11,14,15, 16, 17 & 18} [CASING DIAMETER ( B) = 400mm]
Depth At Frictional Effective q0 =γb n
Layer Thickness Bottom Angleф Cohension Density (γsat) Ks =0.5tan 2 ∆Ln Diameter Perimeter (P) δ =2/3ф TAN δ (0o)
[∆L] [m] (m) [deg] (c) [kPa] [Kn/m3] [450 + ф/2] [kN/m2] (D) m 2pr
CL 5 5 4 56.4 8.4 0.72 6.095 0.4 1.25664 2.66667 0.046576
OL 8 13 6 65 6.7 0.7201 8.83 0.4 1.25664 4 0.069927
SC 5 18 18 10.4 10.6 0.34 18.62 0.4 1.25664 12 0.212557
SP 4 22 32 0 22.3 7.006 0.756 0.4 1.25664 21.3333 0.390555
SP 4 26 32 0 22.5 7 89.96 0.4 1.25664 21.3333 0.390555
SW 4 30 36 0 27.8 2 161.9 0.4 1.25664 24 0.44523
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 135
Table 20b: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
ZONE # C SOILS {BORING # 10,11,14,15, 16, 17 & 18} [CASING DIAMETER ( B) = 600mm]
Lithology Thickness [∆L] Depth At Frictional Cohension (c) Effective Ks =0.5tan 2 q0 =γb n Diameter Perimeter δ =2/3ф TAN δ (0o)
[m] Bottom Angleф [kPa] Density (γsat) [450 + ф/2] ∆Ln (D) m (P) 2pr
(m) [deg] [kN/m3] [kN/m2]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 136
Table 20c: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE,
BAYELSA STATE PROJECT
[ AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
ZONE # C SOILS {BORING # 10,11,14,15, 16, 17 & 18} [CASING DIAMETER ( B) = 800mm]
Lithology Thickness [∆L] Depth At Frictional Cohension Effective Ks =0.5tan 2 q0 =γb n Diameter Perimeter δ =2/3ф TAN δ (0o)
[m] Bottom Angleф (c) [kPa] Density (γsat) [450 + ф/2] ∆Ln (D) m (P) 2pr
(m) [deg] [kN/m3] [kN/m2]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 137
Table 20d: GEOTECHNICAL DESIGN OF PILE FOUNDATION FOR PROPOSED 2 OR MORE STOREY BUILDINGS AT THE FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE
PROJECT
[AVERAGE BORING PARAMETERS - [Based on the Berezantsev’s Method for soils with Cohesion (c) and Friction ()]
ZONE # C SOILS {BORING # 10,11,14,15, 16, 17 & 18} [CASING DIAMETER ( B) = 1000mm]
Lithology Thickness Depth Frictional Cohension Effective Ks =0.5tan 2 q0 =γb n Diameter Perimeter δ =2/3ф TAN δ (0o)
[∆L] [m] At Angleф (c) [kPa] Density (γsat) [450 + ф/2] ∆Ln (D) m (P) 2pr
Bottom [deg] [kN/m3] [kN/m2]
(m)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 138
Depth 400mm Pile Diameter- Federal University, Otuoke ZONE # C. Depth 600mm Pile Diameter- Federal University, Otoke
(m) (m) ZONE # C.
0 0 0
2.5 0.0141545 2.5 0.03083482
3.9 0.0712164 3.9 0.14961423
5.9 0.1955823 5.9 0.39806665
9.9 0.5636482 9.9 1.09099955
19.9 1.9364009 19.9 3.45291834
30 4.0656774 30 7.11319815
Figure 18a: Plot of Pile Load vs. Depth for Pile Diameters of 400mm and 600mm at the Federal University Otuoke Zone C
[BH# 10, 11, 14, 15, 16, 17 and 18]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 139
Depth 800mm Pile Diameter- Federa University, Otuoke ZONE Depth 1000mm Pile Diameter- Federal University, Otuoke
(m) C (m) ZONE # C.
0 0 0 0
2.5 0.053917 2.5 0.083401
3.9 0.256538 3.9 0.391989
5.9 0.670346 5.9 1.012422
9.9 1.782036 9.9 2.636757
19.9 5.33498 19.9 7.582587
30 10.83717 30 15.2376
Figure 18b: Plot of Pile Load vs. Depth for Pile Diameters of 800mm and 1000mm at the Federal University Otuoke Zone C.
[ BH# 10, 11, 14, 15, 16, 17 and 13 ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 140
Table 21: Summary Of Pile Bearing Capacities at Different Pile Diameters in each Zone of the Project Site at the
Federal University Otuoke, Bayelsa State.
Based on the soil properties observed at the various Zones of the University Complex, the Bearing
Capacities of the Piles to maximum depths of 30.00 meters at different Pile diameters are as shown
above. These values will guide the Contractors during constructions of the various buildings in the
process of expansion of the University with time.
The factors that affect the liquefaction potentials of sands and silts are:-
Grain Size Distribution
Density of sand and silt deposits ( initial relative density)
Vibration characteristics strain history
Location of drainage and dimensions of deposit,
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 141
Magnitude and nature of superimposed loads
Method of soil formation (soil structure)
Period under sustained loads
Previous strain history
Entrapped air, and
In-situ moisture content.
The steps recommended for computations leading to evaluations of liquefaction potentials are:
1) Determine the shear stress [av ] to be caused by expected earthquakes using the relationship:
av ~ 0.65 x [h / g ]amax x r/d … …. … … …. (26)
where:
= Unit weight of soil
h = depth of overburden
g = acceleration due to gravity
amax = maximum earthquake acceleration expected
r/d = factor obtainable from charts (see Figure 19)
2) Determine [o / v’ ] from Figure 19 and compute o .
3) A comparison of av and o shows if liquefaction occurs or not for a given site.
If av > o , then Liquefaction occurs
If not, then Liquefaction does not occur.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 142
Figure 19: Correlation between field Liquefaction behaviour of sands for level ground conditions
and penetration resistance, supplemented by data from large scale tests (after Seed, 1979).
9.3.2.2 Soil Liquefaction Potentials At The Federal University Site, Otuoke, Bayelsa State.
Using the Standard Penetration Tests (SPT) values obtained at the Eighteen (18) borings at the Project site
and adopting an average Saturated Unit Weight of 2.76 Mg/m3 at three magnitudes of earthquake Intensities
of M = 6, 7.5 and 8.25, the estimated / calculated liquefaction potentials of the soils at the Federal University
Otuoke project site are as follows:
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 143
(a) Liquefaction Potentials for Earthquake Intensity, of M = 6.0
__________________________________________________________________________________________________
Depth
(m) v’ CN* N N1 = o / v’ o
N x CN [ Fig. 18] [Col. 2 x
Col.6]kPa
1. 2. 3. 4. 5. 6. 7.
__________________________________________________________________________________________________
_
where:
p = effective overburden pressure at the elevation of the SPT (kPa).
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 144
ii) Computation of Shear Stress developed during earthquake, av
where:
av ~ 0.65 . [h ] . [amax /g] . [ r/d]
_____________________________________________________________________________________________
Depth
(m) amax/g r/d av
[ t / ft3 ] [kPa]
1. 2. 3. 4. 5.
________________________________________________________________________________________________
Figure 20: Range of Values of r/d for different soil profiles in Liquefaction Potentials analyses
(after Seed & Idriss, 1971).
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 145
(b) Liquefaction Potentials for Earthquake Intensity, of M = 7.5
__________________________________________________________________________________________________
Depth
(m) v’ CN* N N1 = o / v’ o
N x CN [ Fig. 18] [Col. 2 x Col.6]kPa
1. 2. 3. 4. 5. 6. 7.
__________________________________________________________________________________________________
2.50 1.95 0.778 17 13.226 0.16 0.312
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 146
(c) Liquefaction Potentials for Earthquake Intensity, of M = 8.25
1. 2. 3. 4. 5. 6. 7.
__________________________________________________________________________________________________
9.3.3 Summary of Results on Soil Liquefaction Potentials at the Federal University Otuoke Project Site, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 147
(ii) Earthquake Intensity M = 7.5
_____________________________________________________________________________________________
__________________________________________________________________________________________________
At all Intensities of Earthquake [M = 6.0; 7.50 and 8.25 ], there is little possibility of any Liquefaction occurring
at the Federal University, Otuoke site in Bayelsa State, Nigeria. This can be explained by the fact that the
Water Table at site is about 3.00 meters below the ground surface. Most Liquefaction occurs when Water
Table is near ground surface.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 148
9.4 Other Recommendations
Some soil properties that were determined during the oedometer tests sample evaluations included the
following:
(i) Poisson’s ratio of between 0.45 to 0.50
(ii) Shear Modulus, G of 4.50 MPa
(iii) Modulus of Elasticity Es of 62,500 MN/ m2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 149
Table 21: Critical Heights (Hc) corresponding to various Consistencies [after: Tomlinson, 1980].
___________________________________________________________________________________________
Very soft Soft Firm
_______________________________________________________________________________________________
Cohesion (kN.m2 ) 0.00 – 17.50 17.50 – 35.00 35.00 - 70.00
Critical height (m) 4.00 4–8 8 - 16
_______________________________________________________________________________________________
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 150
9.4.3.2 Retaining Walls And Dykes
Embankments and dykes surrounding Gas Storage tanks at the project site need to be constructed on the
basis of available engineering properties of site soils. For adequate compaction purposes, the Optimum
Moisture Content (OMC) and the Maximum Dry density (MDD) of the earth materials provide data for
engineered embankment compactions. Values of OMC and MDD obtained for the site soils are contained in
Appendix H of this Report. Values of Optimum Moisture Contents (OMC) for the soils range from 14.50% to
16.00 %, while values of Maximum Dry Densities (MDD) for these soils ranged from 1.98 Mg/m 3 to 2.90
Mg/m3 .
On the basis of field investigations and laboratory testing carried out on the soil samples obtained from the
project site, it is observed that basically about FIVE (5) identifiable soil horizons are present and this are
namely:
(i) Brownish Clayey layer (CL) - [TOP SOIL]
(ii) Greyish Organic Silty Clays (OL)
(iii) Greyish Clayey Silty Sands (SM) and (SC-SM)
(iv) Yellowish to whitish Silty Sands (SM)
(v) Well-graded Sands and Gravels (SW)
The various geotechnical engineering properties of each of the sub-soils are summarized in Table 8a-8r of this
report.
On the basis of the computations carried out above, the following recommendations are hereby made:-
(1) The obtained value for the Bearing Capacity for Isolated Footings to be used at the Project Site is
about 195.35 + 1.1867B [kPa] where B = Width of the Structure to be built. For a B = 5.00 meters,
the Bearing Capacity has been found to be 201.284 kPa. The recommended depth of emplacement
of Isolated Footings is 1.50 meters. This value represents the bearing capacity of the upper bearing
Lateritic Clayey Sands at the project site.
(2) The obtained value for the Bearing Capacity for Continuous Strip Footings to be used at the Project
Site is about 153.35 + 1.483B [kPa] where B = Width of the Structure to be built. For a B = 5.00
meters, the Bearing Capacity has been found to be 160.76 kPa. The recommended depth of
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 151
emplacement of Continuous Strip Footings is 0.75 meters. This value represents the bearing
capacity of the upper bearing Lateritic Clays and Silty-Clays at the project site.
(3) The range of values obtained for the Bearing Capacity for Raft Footings at the project site, based on
the methods of Meyerhof (1974); Bowles (1988); Terzaghi & Peck (1967); Brinch Hansen (1968) and
the conventional SPT Method is between 76.55 and 208.86 kPa with an average of 122.85 kPa. The
recommended depth of emplacement of Raft Footings is 1.50 meters. This value represents the
bearing capacity of the upper bearing Lateritic Clays and Silty-Clays at the project site.
(4) A value of qallowed = [14.4] + [(9.964T)/( B x L)] kN / m2 can be used as the allowable Soil Pressure on
the soil at the project site, since this value should be less than the average value of the allowable
soil pressure (bearing capacity ), q(allow) of the soils at site. [ Note: B = breadth; L = Length of
structures at site ].
(5) The computed settlement data for the project area indicate that the Immediate Settlement values
for the Project Site is estimated to be about i = 0.0000132(T)(B) (meters) , where T = the Dead
weight of the Buildings at site. This is the settlement expected to take place during the construction
phase of the Buildings at the Project site.
(6) The computed settlement data for the project area indicate that the Long-Term Settlement value
for the Buildings at the Site is estimated to be about 0.000132 T + {(0.520) Log 10 (1 +0.01498 T)}
(meters) , where T = the estimated Dead Weight of the Buildings. This is the settlement expected to
take place long after the construction phase of the Buildings at the various zones at the Project
sites.
(7) About 50% of the settlements must have taken place about 3.70 years after construction, while
90% of the settlement will take place after about 15.728 years after the completion of the Buildings
at the University Complex.
(8) Since the buildings at a University Campus are subjected to Live Loads from the movements of
different numbers of students in a continuously day-to-day fashion over the years, the potentials of
the silty soils becoming liquefied as a result of human traffic-induced vibration was also assessed
during this investigation, since this is a permanent structure for ages to come. Soil dynamics
analysis carried out by us indicate that there will be no possibility of Soil Liquefaction at the Project
Site as a result of vibration from Live Loads and structures. This was found not to be possible even
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 152
though the groundwater table was found near the ground surface because of the absence of totally
silty soils beneath the ground surface.
(9) Foundation concrete should be dense and impermeable for protection against Sulphate Attack
especially in areas likely to be in contact with surface or groundwater.
(10) The pH value of 4.5 is low and therefore may enhance corrosion of buried pipes and metals.
(11) Generally the resistivity in the project area is quite high which could have entailed non-
corrosive environment. However, for the slightly lower resistivity that could be expected
during the rainy season, it may therefore be recommended that some precautions be
taken on the pipe-works e.g. bonded Coatings of the pipes or better still a Cathodic
Protection could be done.
(12) Sulphate-resistant Cement may be used for the foundation concrete (cement content not
less than 330 kg/m3, Max. W/C 0.50 or Sulphate-resisting cement with cement content not
less than 290 kg/m3, Max. W/C 0.50)
(13) The specific values got at this site are higher than those recommended values by IEEE Green
Book (1992). Hence irrespective of the point chosen for Earthing at the project sited, the
earth conductivity must be improved upon by the addition of ground enhancement
material such as mixing charcoal and coke with salts like sodium chloride or magnesium
chloride or better still some of the artificial gels, and buried at depths of between 4 – 5
meters.
(14) Finally, on the basis of the geotechnical considerations for structures such as the proposed
University single or multiple Office Blocks; Laboratory Buildings and various categories and
sizes of Residential Buildings at the Campus site, the Geotechnical Consultants highly
recommend that the above findings be strictly adhered to.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 153
Appendices
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 154
Appendix ‘A1’
Borehole Logs
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 155
LOCATIONS OF BORING POINTS AT THE FEDERAL UNIVERSITY OTUOKE PROJECT SITE
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 156
Figure A1: Sub-surface Log of BH# 1 (Built-up Area) at the Federal University Campus, Otuoke.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 157
Figure A2: Sub-surface Log of BH# 2 (Junior Staff Qtrs) at the Federal University Campus, Otuoke.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 158
Figure A3: Sub-surface Log of BH# 2 (Junior Staff Qtrs) at the Federal University Campus, Otuoke .
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 159
Figure A4: Sub-surface Log of BH# 3 (University Commercial Centre) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 160
Figure A5: Sub-surface Log of BH# 4 (Sports / Recreation Centre) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 161
Figure A6: Sub-surface Log of BH# 5 (Engineering & Maintenance) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 162
Figure A7: Sub-surface Log of BH# 6 (Teaching Core) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 163
Figure A8: Sub-surface Log of BH# 7 (Teaching Core) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 164
Figure A9: Sub-surface Log of BH# 8 (Teaching Core) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 165
Figure A10: Sub-surface Log of BH# 8 (Research Centre) at the Federal University Campus,
Otuoke, Bayelsa State
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 166
Figure A11: Sub-surface Log of BH# 10 (Central admin) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 167
Figure A12: Sub-surface Log of BH# 11 (Central Admin) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 168
Figure A13: Sub-surface Log of BH# 12 (Student Accommodation) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 169
Figure A14: Sub-surface Log of BH# 13 (Student Accommodation) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 170
Figure A15: Sub-surface Log of BH# 14 (Vice-Chancellor’s Lodge) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 171
Figure A16: Sub-surface Log of BH# 15 (Guest Cottages) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 172
Figure A17: Sub-surface Log of BH# 16 (Registrar’s Residence) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 173
Figure A17: Sub-surface Log of BH# 17 (Senior Staff Housing) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 174
Figure A18: Sub-surface Log of BH# 17 (University Centre) at the Federal University Campus,
Otuoke, Bayelsa State.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 175
Appendix Aii
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 176
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 177
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 178
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 179
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 180
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 181
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 182
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 183
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 184
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 185
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 186
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 187
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 188
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 189
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 190
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 191
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 192
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 193
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 194
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 195
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 196
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 197
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 198
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 199
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 200
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 201
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 202
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 203
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 204
APPENDIX ‘A3’
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 205
Appendix B
Geophysical Data
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 206
TABLE B1: SCHLUMBERGER DEPTH SOUNDING DATA AT FEDERAL UNIVERSITY OTUOKE
Half cur App. App. App. App. App. App. App. App.
electrode Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity
spread Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 207
TABLE B2 SCHLUMBERGER DEPTH SOUNDING DATA AT FEDERAL UNIVERSITY OTUOKESTATE (cont’d)
Half cur App. App. App. App. App. App. App. App.
electrode Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity Resistivity
spread Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m Ohm-m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 208
TABLE B3: THE GEOGRAPHICAL COORDINATES OF THE INVESTIGATED PROFILES AT
FEDERAL UNIVERSITYOTUOKE USING GEOGRAPHICAL POSITIONING
SYSTEMS (GPS )
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 209
Appendix C
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 210
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY PROJECT,
OTUOKE, BAYELSA STATE.
PARTICLE SIZE DISTRIBUTION PATTERN
( BOTH SIEVE ANALYSIS AND HYDROMETER ANALYSIS )
(BOREHOLE # 1)
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 1/1 0.00 4.0 88 44 38 24
1/2 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately stiff ] 1/3 2.00 4.5 72 40 36 20
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 211
- Continued -
(BOREHOLE # 2)
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 2/1 0.00 4.0 88 44 38 24
2/2 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately
2/3 2.00 4.5 72 40 36 20
stiff ]
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 212
- Continued -
(BOREHOLE # 3)
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 3/1 0.00 4.0 88 44 38 24
3/2 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately stiff ] 3/3 2.00 4.5 72 40 36 20
- Continued -
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 213
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY PROJECT,
OTUOKE, BAYELSA STATE.
PARTICLE SIZE DISTRIBUTION PATTERN
( BOTH SIEVE ANALYSIS AND HYDROMETER ANALYSIS )
(BOREHOLE # 4)
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 4/1 0.00 4.0 88 44 38 24
4/2 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately stiff ] 4/3 2.00 4.5 72 40 36 20
4/4 3.00 4.4 68 42
- Continued –
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 214
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY PROJECT,
OTUOKE, BAYELSA STATE.
PARTICLE SIZE DISTRIBUTION PATTERN
( BOTH SIEVE ANALYSIS AND HYDROMETER ANALYSIS )
(BOREHOLE # 5)
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 5/1 0.00 4.0 88 44 38 24
5/2 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately stiff ] 5/3 2.00 4.5 72 40 36 20
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 215
- Continued -
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY PROJECT,
OTUOKE, BAYELSA STATE.
PARTICLE SIZE DISTRIBUTION PATTERN
( BOTH SIEVE ANALYSIS AND HYDROMETER ANALYSIS )
(BOREHOLE # 6 )
Soil Type Sample Depth Natural % Passing sieves sizes by wt and hydrometer tests
No. (m) Moisture
Content >4.75mm 4.75mm 75 2
(NMC)
% Dry Wt.
Brownish Clayey layer (CL) 6/1 0.00 4.0 88 44 38 24
6/3 1.00 4..5 74 42 36 22
[ Slightly plastic, moderately
6/4 2.00 4.5 72 40 36 20
stiff ] 3.00 4.4 68 42
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 216
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring#: 1 Sample # 8; Depth: 7.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 217
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring#: 3 Sample # 9; Depth: 8.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 218
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring#: 5 Sample # 10; Depth: 9.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 219
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring#: 7 Sample # 11; Depth: 10.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 220
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 8: Sample # 23; Depth: 22.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 221
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 9: Sample # 6; Depth: 5.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 222
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 10: Sample # 6; Depth: 5.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 223
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 11: Sample # 7; Depth: 6.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 224
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 12: Sample # 8; Depth: 7.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 225
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 13: Sample # 4; Depth: 3.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 226
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 14: Sample # 11; Depth: 10.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 227
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 15: Sample # 9; Depth: 8.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 228
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 16: Sample # 6; Depth: 5.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 229
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 17: Sample # 8; Depth: 7.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 230
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
GRAIN SIZE ANALYSIS – ASTM D422-90. Boring# 18: Sample # 4; Depth: 3.00m
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 231
Appendix D
Consistency Limits (Atterberg Limits)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 232
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY PROJECT, OTUOKE, BAYELSA STATE.
(BOREHOLE # 1)
Greyish Clayey Sands (SC) 1/8 7.00 20.8 6.4 20.6 10.4
1/9 8.00 18.8 6.8 16.5 9.5
1/10 9.00 19.8 6.2 15.5 8.5
1/11 10.00 19.4 7.4 16.5 6.5
1/12 11.00 18.8 8.0 16.4 6.4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 233
- Continued -
(BOREHOLE # 2)
Greyish Clayey Sands (SC) 2/8 7.00 20.8 6.4 20.6 10.4
2/9 8.00 18.8 6.8 16.5 9.5
2/10 9.00 19.8 6.2 15.5 8.5
2/11 10.00 19.4 7.4 16.5 6.5
2/12 11.00 18.8 8.0 16.4 6.4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 234
- Continued -
(BOREHOLE # 3)
Greyish Clayey Sands (SC) 3/8 7.00 20.8 6.4 20.6 10.4
3/9 8.00 18.8 6.8 16.5 9.5
3/10 9.00 19.8 6.2 15.5 8.5
3/11 10.00 19.4 7.4 16.5 6.5
3/12 11.00 18.8 8.0 16.4 6.4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 235
- Continued -
(BOREHOLE # 4)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 236
- Continued -
(BOREHOLE # 5)
Greyish Organic Silty Clays (OL) 5/4 3.00 17.8 6.4 48.2 12.8
5/5 4.00 17.8 6.8 46.0 15.6
5/6 5.00 17.8 10.0 44.0 18.2
5/7 6.00 18.4 10.2 47.5 14.6
Greyish Clayey Sands (SC) 5/8 7.00 20.8 6.4 20.6 10.4
5/9 8.00 18.8 6.8 16.5 9.5
510 9.00 19.8 6.2 15.5 8.5
511 10.00 19.4 7.4 16.5 6.5
5/12 11.00 18.8 8.0 16.4 6.4
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 237
- continued -
(BOREHOLE # 6)
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 238
Appendix E
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 239
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY OTUOKE PROJECT, BAYELSA STATE.
Soil Type Sample No. Depth Residual Cohesion Residual Friction Angle
(m)
( Cr) (residual)
(KN/m2.)
Brownish Clayey Layer (CL)
1/3 2.00 52.8 4
[ Slightly plastic, moderately stiff ]
3/6 5.00 38.8 8
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 240
Stress – Strain Curves and Shear Strength versus Normal Stress Plots are given in Appendix D.
C r = 52.80 KPa
KPa φr= 4.0 o
Tan φ = 1.1578
130.0
100.0
50.00 Φ = 4.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE E1/3: Direct Shear Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 241
C r = 38.80 KPa
KPa φr= 8.0 o
Tan φ = 0.1578
130.0
100.0
50.00 Φ = 8.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE E3/6: Direct Shear Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 242
C r = 46.80 KPa
KPa φr= 4.0 o
Tan φ = 0.1578
130.0
100.0
50.00 Φ = 4.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE E6/4: Direct Shear Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 243
C r = 40.20 KPa
KPa φr= 8.0 o
Tan φ = 0.1578
130.0
100.0
50.00 Φ = 8.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE E8/7: Direct Shear Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 244
C r = 46.80 KPa
KPa φr= 4.0 o
Tan φ = 0.1578
130.0
100.0
50.00 Φ = 4.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE E12/4: Direct Shear Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 245
Appendix F
Unconsolidated-Undrained
(U-U) Triaxial
Compression Tests.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 246
SUBSURFACE INVESTIGATION OF THE FEDERAL UNIVERSITY, OTUOKE PROJECT, BAYELSA STATE.
Soil Type Sample Depth Natural U-U Friction Undrained Shear Poisson’s Ratio
No. (m) Moisture Angle ( ) Cohesion Modulus
content (o) ( Cu ) G ( )
(NMC) Kpa MPa)
{% Dry Wt.}
Brownish lateritic 1/2 0.00 5.5 8.0 50.20 4.5 0.4
Clayey Sand layer
3/4 3.00 6.4 4.0 48.20 4.5 0.4
(SC)
[ Slightly plastic, 6/5 4.00 4.4 24.0 0.00 4.5 0.4
moderately stiff ]
NOTE: The specimens were tested in Undrained Compression using Cell Pressures of 50, 100 and 200
KN/m2 respectively.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 247
C = 50.20 KPa
KPa φ = 8.0 o
Tan φ = 0.06992
130.0
100.0
50.00 Φ = 8.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE F1/2: Quick Triaxial Compression Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 248
C = 48.20 KPa
KPa φ = 4.0 o
Tan φ = 0.06992
130.0
100.0
50.00 Φ = 4.0o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 24.9% 24.9% 24.9%
%
200.00
Dry Density gm/cc γd 1.86 1.86 1.86
Saturation (%) So 76.8 76.2 76.5
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 24.8% 24.8% 24.8%
100.00 shear Dry density (gm/cc) γd 1.72 1.72 1.72
Saturation (% ) So 62.2 62.1 61.7
Void ratio eo 0.71 0.70 0.70
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress ( Kpa) (σ1 - σ3 ) max 140.0 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 15.0 18.0 28.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE F 3/4: Quick Triaxial Compression Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 249
C = 0.00 KPa
φ = 34.0 o
KPa
Tan φ = 1.6745
130.0
100.0
50.00
Φ = 34o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 12.00 12.0% 12.0%
% %
200.00
Dry Density gm/cc γd 2.64 264 2.64
Saturation So 62.6 62.3 61.7
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 11.8% 11.8% 11.6%
100.00 shear Dry density gm/cc γd 2.64 2.64 1.42
Saturation So 62.2 62.1 61.7
Void ratio eo 0.72 0.70 0.71
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress KPa (σ1 - σ3 ) max 138 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 35.0 46.0 60.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE F 6/5: Quick Triaxial Compression Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 250
C = 0.00 KPa
φ = 34.0 o
KPa
Tan φ = 1.6745
130.0
100.0
50.00
Φ = 34o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 12.00 12.0% 12.0%
% %
200.00 Dry Density gm/cc γd 2.64 264 2.64
Saturation So 62.6 62.3 61.7
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 11.8% 11.8% 11.6%
100.00 shear Dry density gm/cc γd 2.64 2.64 1.42
Saturation So 62.2 62.1 61.7
Void ratio eo 0.72 0.70 0.71
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress KPa (σ1 - σ3 ) max 138 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 35.0 46.0 60.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE F 6/5: Quick Triaxial Compression Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 251
C = 0.00 KPa
φ = 34.0 o
KPa
Tan φ = 1.6745
130.0
100.0
50.00
Φ = 34o
0.00
. . . . . .
50 100 150 200 250 300
kPa Normal Stress KPa
240.00 Specimen No. 1 2 3
c Initial Water Content (%) Wn 12.00 12.0% 12.0%
% %
200.00
Dry Density gm/cc γd 2.64 264 2.64
Saturation So 62.6 62.3 61.7
Void ratio .e o 0.76 0.70 0.80
Before Water content % wn 11.8% 11.8% 11.6%
100.00 shear Dry density gm/cc γd 2.64 2.64 1.42
Saturation So 62.2 62.1 61.7
Void ratio eo 0.72 0.70 0.71
Minor Principal Stress KPa σ3 50.0 100.0 200.0
a Max. Dev. Stress KPa (σ1 - σ3 ) max 138 180.0 200.0
0.00 b Time to ( 1 - 2 ) max ( min ) .t1 35.0 46.0 60.00
5 10 15 Ultimate deviator stress ( 1 - 3 ) ult. KPa 50.0 120.0 140.0
Axial Strain mm Initial Diameter ( mm) Do 35.0 35.0 35.00
Controlled Strained Test Initial Height ( mm ) Ho 11.0 11.0 11.0
FIGURE F 18/14: Quick Triaxial Compression Test Report on soils from FEDERAL UNIVERSITY, OTUOKE, BAYELSA
STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 252
Appendix G
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 253
SUBSURFACE INVESTIGATION THE FEDERAL UNIVERSITY, OTUOKE BAYELSA STATE
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 254
OEDOMETER CONSOLIDATION TEST
Ro ( 0% U )
-- 0.00
o
-- 0.10
o
o R 90 = 90 % U Consolidation
-- 0.20
-- 0.30 o
o
o
o
--0.40 o
o
.t90 = (60.705)2
= 7.79min
-- 0.50
. . . . . . . . . . . . . . . . .
2.00 4.00 6.00 8.00 10.00 12.00 1 4.00 16.00 18.00
√ Time (Min ) 1/2
Figure G 1/ 6 : Determination of Coefficient of Consolidation ( Cv ) on soils from the Federal University Complex, Otuoke,
Bayelsa State, using Taylor's (1948) "Square Root of Time "Method.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 255
OEDOMETER CONSOLIDATION TEST
Ro ( 0% U )
-- 0.00
o
-- 0.10
o
o R 90 = 90 % U Consolidation
-- 0.20
-- 0.30 o
o
o
o
--0.40 o
o
.t90 = (60.705)2
= 7.79min
-- 0.50
. . . . . . . . . . . . . . . . .
2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00
√ Time (Min ) 1/2
Figure G 5/ 5 : Determination of Coefficient of Consolidation ( Cv ) on soils from the Federal University Complex, Otuoke,
Bayelsa State, using Taylor's (1948) "Square Root of Time "Method.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 256
OEDOMETER CONSOLIDATION TEST
Ro ( 0% U )
-- 0.00
o
-- 0.10
o
o R 90 = 90 % U Consolidation
-- 0.20
-- 0.30 o
o
o
o
--0.40 o
o
.t90 = (60.705)2
= 7.79min
-- 0.50
. . . . . . . . . . . . . . . . .
2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00
√ Time (Min ) 1/2
Figure G 7/ 6 : Determination of Coefficient of Consolidation ( Cv ) on soils from the Federal University Complex, Otuoke,
Bayelsa State, using Taylor's (1948) "Square Root of Time "Method.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 257
OEDOMETER CONSOLIDATION TEST
Ro ( 0% U )
-- 0.00
o
-- 0.10
o
o R 90 = 90 % U Consolidation
-- 0.20
-- 0.30 o
o
o
o
--0.40 o
o
.t90 = (60.705)2
= 7.79min
-- 0.50
. . . . . . . . . . . . . . . . .
2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00
√ Time (Min ) 1/2
Figure G 17/ 13 : Determination of Coefficient of Consolidation ( Cv ) on soils from the Federal University Complex, Otuoke,
Bayelsa State, using Taylor's (1948) "Square Root of Time "Method.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 258
Appendix H
Tests Results.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 259
SUBSURFACE INVESTIGATION AT THE FEDERAL UNIVERSITY, OTUOKE PROJECT, BAYELSA STATE.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 260
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Date: 24th March, 2013
Material: Brownish Lateritic Silty Sandy Clay (SC) Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA1/1
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READING ECTED kN % READING ECTED kN % READING ECTED kN %
READI READING READING
NG
0.625
1.250
1.880
2.50 13.34 8.10 0.81 0.97 7.27 7.40 0.74 0.90 6.75
3.75
5.00 20.02 13.93 1.39 1.71 8.54 13.30 1.33 1.64 8.19
6.250
7.500 16.00 1.60 1.96 9.80 15.40 1.54 1.88 9.40
8.800
10.00
11.25
12.50
1.5
Penetration CBR %
1 0.1 in 7.27 6.75
0.2 in 8.54 8.19
0.5
(Selected) Average
0
0 1 2 3 4 5 6 7 8
CBR – 7.01 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 261
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 2/2
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED Kn % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 8.40 0.84 1.10 8.25 7.20 0.72 0.96 7.20
3.75
5.00 20.02 16.00 1.600 1.97 9.80 14.2 1.42 1.92 9.60
6.250
7.500 18.60 1.86 2.29 11.40 17.7 1.77 2.19 10.90
8.800
10.00
11.25
12.50
1 kN = 224.84 lb
2
1.5
1 Penetration CBR %
0.5 0.1 in 8.25 7.20
0.2 in 9.80 9.60
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 7.73 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 262
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 1/2
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READIN G READING READING
G
0.625
1.250
1.880
2.50 13.34 17.50 1.75 2.00 14.99 16.50 1.65 1.90 14.24
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.78 13.88
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3 1 kN = 224.84 lb
2.5
2 Penetration CBR %
1.5 0.1 in 14.99 14.24
1
0.2 in 14.78 13.88
0.5
(Selected) Average
0
0 1 2 3 4 5 6 7 8
CBR – 14.62 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 263
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA1/4
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 11.10 1.11 1.44 10.79 9.70 0.97 1.20 9.00
3.75
5.00 20.02 21.60 2.16 2.41 12.04 18.10 1.81 2.15 10.74
6.250
7.500 22.90 2.29 2.52 12.59 20.90 2.09 2.29 11.44
8.800
10.00
11.25
12.50
1 Penetration CBR %
0.5 0.1 in 10.79 9.00
0.2 in 12.04 10.74
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (mm)
CBR – 9.90 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 264
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA1/4
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 12.00 1.20 1.46 11.00 9.80 0.98 1.21 9.10
3.75
5.00 20.02 21.90 2.19 2.42 12.08 18.20 1.82 2.17 10.84
6.250
7.500 23.00 2.30 2.54 12.70 20.90 2.09 2.29 11.44
8.800
10.00
11.25
12.50
2 1 kN = 224.84 lb
0 (Selected) Average
0 1 2 3 4 5 6 7 8 CBR – 10.05 %
Penetration of Plunger(m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 265
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 1/6
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READING ECTED kN % READIN ECTED kN % READING ECTED kN %
READING G READING READING
0.625
1.250
1.880
2.50 13.34 15.70 1.57 1.77 13.30 13.90 1.39 1.59 11.92
3.75
5.00 20.02 22.40 2.24 2.75 13.74 20.30 2.03 2.54 12.69
6.250
7.500 26.40 2.64 3.00 14.99 24.90 2.49 2.86 14.29
8.800
10.00
11.25
12.50
2.5
2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 266
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 1/7
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READING ECTED kN % READING ECTED kN %
G READIN READING READING
G
0.625
1.250
1.880
2.50 13.34 11.10 1.11 1.46 10.95 9.90 0.99 1.30 9.70
3.75
5.00 20.02 21.80 2.18 2.54 12.69 18.10 1.81 2.20 10.99
6.250
7.500 22.90 2.29 2.72 13.59 20.90 2.09 2.39 11.94
8.800
10.00
11.25
12.50
1 Penetration CBR %
0.5 0.1 in 10.95 9.70
0.2 in 12.69 10.99
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (mm)
CBR – 10.33 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 267
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 2/1
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READING ECTED kN % READING ECTED kN %
G READING READING READING
0.625
1.250
1.880
2.50 13.34 8.40 0.84 1.06 8.00 7.20 0.72 0.93 6.97
3.75
5.00 20.02 16.00 1.600 1.90 9.49 14.2 1.42 1.82 9.09
6.250
7.500 18.60 1.86 2.29 11.40 17.7 1.77 2.19 10.90
8.800
10.00
11.25
12.50
1 kN = 224.84 lb
2
1.5
1 Penetration CBR %
0.5 0.1 in 8.00 6.97
0.2 in 9.49 9.09
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 7.73 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 268
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZA 2/8
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READING ECTED kN % READING ECTED kN %
G READING READING READING
0.625
1.250
1.880
2.50 13.34 14.00 1.40 1.71 12.84 11.90 1.19 1.47 11.01
3.75
5.00 20.02 24.20 2.42 2.96 14.80 21.20 2.12 2.47 12.33
6.250
7.500 27.10 2.71 3.28 16.38 25.50 2.55 3.14 15.68
8.800
10.00
11.25
12.50
2.5
Penetration CBR %
2
0.1 in 12.84 11.01
1.5 0.2 in 14.80 12.33
1
(Selected) Average
0.5
CBR – 11.93 %
0
0 1 2 3 4 5 6 7 8
Penetration of Plunger(m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 269
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/9
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 27.10 2.71 3.00 22.49 25.50 2.55 2.72 20.40
3.75
5.00 20.02 43.10 4.31 4.62 23.08 40.09 4.09 4.36 21.78
6.250
7.500 46.08 4.08 4.79 23.93 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
3 Penetration CBR %
0.1 in 22.49 20.40
2
0.2 in 23.08 21.78
1
(Selected) Average
0
0 1 2 3 4 5 6 7 8
CBR – 21.46 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 270
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/10
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 8.10 0.81 0.97 7.27 7.40 0.74 0.90 6.75
3.75
5.00 20.02 13.93 1.39 1.71 8.54 13.30 1.33 1.64 8.19
6.250
7.500 16.00 1.60 1.96 9.80 15.40 1.54 1.88 9.40
8.800
10.00
11.25
12.50
1.5
Penetration CBR %
1
0.1 in 7.27 6.75
0.5
0.2 in 8.54 8.19
0 (Selected) Average
0 1 2 3 4 5 6 7 8 CBR – 7.01 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 271
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/11
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 8.40 0.84 1.10 8.25 7.20 0.72 0.96 7.20
3.75
5.00 20.02 16.00 1.600 1.97 9.80 14.2 1.42 1.92 9.60
6.250
7.500 18.60 1.86 2.29 11.40 17.7 1.77 2.19 10.90
8.800
10.00
11.25
12.50
1 kN = 224.84 lb
2
1.5
1 Penetration CBR %
0.5 0.1 in 8.25 7.20
0.2 in 9.80 9.60
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 7.73 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 272
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/12
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 17.50 1.75 2.00 14.99 16.50 1.65 1.90 14.24
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.78 13.88
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2 Penetration CBR %
1.5 0.1 in 14.99 14.24
1
0.2 in 14.78 13.88
0.5
(Selected) Average
0
0 1 2 3 4 5 6 7 8
CBR – 14.62 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 273
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/13
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 11.10 1.11 1.44 10.79 9.70 0.97 1.20 9.00
3.75
5.00 20.02 21.60 2.16 2.41 12.04 18.10 1.81 2.15 10.74
6.250
7.500 22.90 2.29 2.52 12.59 20.90 2.09 2.29 11.44
8.800
10.00
11.25
12.50
1 Penetration CBR %
0.5 0.1 in 10.79 9.00
0.2 in 12.04 10.74
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (mm) CBR – 9.90 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 274
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/14
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READIN
G
0.625
1.250
1.880
2.50 13.34 12.00 1.20 1.46 11.00 9.80 0.98 1.21 9.10
3.75
5.00 20.02 21.90 2.19 2.42 12.08 18.20 1.82 2.17 10.84
6.250
7.500 23.00 2.30 2.54 12.70 20.90 2.09 2.29 11.44
8.800
10.00
11.25
12.50
Surcharge 22.24N(5lb)
PLOT OF DIAL LOAD Vs PENETRATION OF
Proving Ring No KDF 606 A
PLUNGER
3 Proving Ring Factor 1.225/Div
1 kN = 224.84 lb
2.5
Dial Load(KN)
0 (Selected) Average
0 1 2 3 4 5 6 7 8 CBR – 10.05 %
Penetration of Plunger(m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 275
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT,
RIVERS STATE B.S 1377 Test No. 15
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/15
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 15.70 1.57 1.77 13.30 13.90 1.39 1.59 11.92
3.75
5.00 20.02 22.40 2.24 2.75 13.74 20.30 2.03 2.54 12.69
6.250
7.500 26.40 2.64 3.00 14.99 24.90 2.49 2.86 14.29
8.800
10.00
11.25
12.50
2.5
2
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 276
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/16
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READIN G READING READING
G
0.625
1.250
1.880
2.50 13.34 11.10 1.11 1.46 10.95 9.90 0.99 1.30 9.70
3.75
5.00 20.02 21.80 2.18 2.54 12.69 18.10 1.81 2.20 10.99
6.250
7.500 22.90 2.29 2.72 13.59 20.90 2.09 2.39 11.94
8.800
10.00
11.25
12.50
1 Penetration CBR %
0.5 0.1 in 10.95 9.70
0.2 in 12.69 10.99
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (mm) CBR – 10.33 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 277
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/17
PENET STD
R- LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
ATION (kN)) READIN ECTED kN % READING ECTED kN % READING ECTED kN %
(mm) G READIN READING READIN
G G
0.625
1.250
1.880
2.50 13.34 8.40 0.84 1.06 8.00 7.20 0.72 0.93 6.97
3.75
5.00 20.02 16.00 1.600 1.90 9.49 14.2 1.42 1.82 9.09
6.250
7.500 18.60 1.86 2.29 11.40 17.7 1.77 2.19 10.90
8.800
10.00
11.25
12.50
2 1 kN = 224.84 lb
1.5
1 Penetration CBR %
0.5 0.1 in 8.00 6.97
0.2 in 9.49 9.09
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 7.73 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 278
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/18
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READING ECTED kN % READIN ECTED kN %
G READING READING G READING
0.625
1.250
1.880
2.50 13.34 14.00 1.40 1.71 12.84 11.90 1.19 1.47 11.01
3.75
5.00 20.02 24.20 2.42 2.96 14.80 21.20 2.12 2.47 12.33
6.250
7.500 27.10 2.71 3.28 16.38 25.50 2.55 3.14 15.68
8.800
10.00
11.25
12.50
2.5
2
1.5
1 Penetration CBR %
0.5 0.1 in 12.84 11.01
0.2 in 14.80 12.33
0
0 1 2 3 4 5 6 7 8
Penetration of Plunger(m m ) (Selected) Average
Top Bottom CBR – 11.93 %
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 279
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/19
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 27.10 2.71 3.00 22.49 25.50 2.55 2.72 20.40
3.75
5.00 20.02 43.10 4.31 4.62 23.08 40.09 4.09 4.36 21.78
6.250
7.500 46.08 4.08 4.79 23.93 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
3 Penetration CBR %
0.1 in 22.49 20.40
2
0.2 in 23.08 21.78
1
(Selected) Average
0
0 1 2 3 4 5 6 7 8
CBR – 21.60 %
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 280
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZB 2/20
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 16.20 1.62 1.92 14.39 15.60 1.56 1.86 13.94
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.78 13.88
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2
Penetration CBR %
1.5
0.1 in 14.39 13.94
0.2 in 14.78 13.88
1
0.5
(Selected) Average
0 CBR – 14.10 %
0 1 2 3 4 5 6 7 8
Penetration of Plunger (m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 281
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/21
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 27.20 2.72 3.03 22.71 25.80 2.58 2.86 21.44
3.75
5.00 20.02 43.10 4.31 4.64 23.18 40.00 4.00 4.37 21.83
6.250
7.500 46.10 4.61 4.80 23.98 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
5 1 kN = 224.84 lb
Dial Reading (KN)
2 Penetration CBR %
0.1 in 22.71 21.44
1
0.2 in 23.18 21.87
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 22.08 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 282
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/22
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 27.10 2.71 3.00 22.49 25.5S 2.55 2.82 21.14
0
3.75
5.00 20.02 43.20 4.32 4.65 23.23 40.10 4.10 4.37 21.83
6.250
7.500 46.10 4.61 4.80 23.98 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
2
Penetration CBR %
0.1 in 22.49 21.14
1 0.2 in 23.18 21.87
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 21.81 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 283
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/23
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 12.00 1.20 1.46 11.00 9.80 0.98 1.21 9.00
3.75
5.00 20.02 23.00 2.30 2.54 12.70 20.90 2.09 2.29 11.44
6.250
7.500 27.00 2.70 3.30 16.50 22.90 2.29 2.80 14.00
8.800
10.00
11.25
12.50
Surcharge 22.24N(5lb)
PLOT OF DIAL LOAD Vs PENETRATION OF
Proving Ring No KDF 606 A
PLUNGER
3 Proving Ring Factor 1.225/Div
1 kN = 224.84 lb
2.5
Dial Load(KN)
0 (Selected) Average
0 1 2 3 4 5 6 7 8 CBR – 10.00 %
Penetration of Plunger(m m )
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 284
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/24
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 17.50 1.75 2.00 14.99 16.50 1.65 1.90 14.24
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.78 13.88
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2
1.5 Penetration CBR %
1 0.1 in 14.99 14.24
0.5 0.2 in 14.78 13.88
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 14.52 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 285
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/25
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 16.20 1.62 1.91 14.32 15.60 1.56 1.86 13.88
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.85 14.24
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2
1.5 Penetration CBR %
1 0.1 in 14.32 13.88
0.5
0.2 in 14.78 14.24
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (m m ) CBR – 14.14 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 286
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/26
PENETR STD
-ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 16.20 1.62 1.91 14.32 15.60 1.56 1.86 13.88
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.85 14.24
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2
1.5 Penetration CBR %
1 0.1 in 14.32 13.88
0.5
0.2 in 14.78 14.24
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (m m ) CBR – 14.14 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 287
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/27
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 16.20 1.62 1.91 14.32 15.60 1.56 1.86 13.88
3.75
5.00 20.02 24.60 2.46 2.96 14.78 22.10 2.21 2.85 14.24
6.250
7.500 30.10 3.01 3.48 17.38 28.10 2.81 3.24 16.18
8.800
10.00
11.25
12.50
3
2.5
2
1.5 Penetration CBR %
1 0.1 in 14.32 13.88
0.5
0.2 in 14.78 14.24
0
0 1 2 3 4 5 6 7 8
(Selected) Average
Penetration of Plunger (m m ) CBR – 14.14 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 288
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/28
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READIN ECTED kN %
G READING G READING G READIN
G
0.625
1.250
1.880
2.50 13.34 27.20 2.72 3.03 22.71 25.80 2.58 2.86 21.44
3.75
5.00 20.02 43.10 4.31 4.64 23.18 40.00 4.00 4.37 21.83
6.250
7.500 46.10 4.61 4.80 23.98 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
5 1 kN = 224.84 lb
Dial Reading (KN)
2 Penetration CBR %
0.1 in 22.71 21.44
1
0.2 in 23.18 21.87
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 22.08 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 289
TEKS GEOTECHNICAL CONSULTANCY (NIG.) LTD.
15 CHURCHILL ROAD CBR TEST
P.O.BOX 9587, PORT HARCOURT, B.S 1377 Test No. 15
RIVERS STATE
NIGERIA.
Contract ----------------------------
Source: Federal University, Otuoke, Bayelsa State No: ----------------------------
Material: Brownish Lateritic Silty Sandy Clay (SC) Date: 24th March, 2013
Location: Federal University, Otuoke, Bayelsa State
Sample #: ZC 2/29
PENETR- STD
ATION LOAD
TEST No. 1 TEST No. 2 TEST No. 3
DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR DIAL CORR- LOAD CBR
(mm) (kN)) READIN ECTED kN % READIN ECTED kN % READING ECTED kN %
G READING G READING READING
0.625
1.250
1.880
2.50 13.34 27.10 2.71 3.00 22.49 25.5S 2.55 2.82 21.14
0
3.75
5.00 20.02 43.20 4.32 4.65 23.23 40.10 4.10 4.37 21.83
6.250
7.500 46.10 4.61 4.80 23.98 42.80 4.28 4.42 22.08
8.800
10.00
11.25
12.50
2
Penetration CBR %
0.1 in 22.49 21.14
1 0.2 in 23.18 21.87
0
0 1 2 3 4 5 6 7 8 (Selected) Average
Penetration of Plunger (m m ) CBR – 21.81 %
Top Bottom
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 290
Appendix I
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 291
PROJECT: SUBSURFACE INVESTIGATION AT THE FEDERAL UNIVERSITY COMPLEX, OTUOKE,
BAYELSA STATE.
NOTE: The Dry Density Versus Moisture Content Plots for all samples tested are shown in Figure H1
through H10.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 292
PROJECT: SUBSURFACE INVESTIGATION AT THE FEDERAL UNIVERSITY COMPLEX, OTUOKE,
BAYELSA STATE.
NOTE: The Dry Density Versus Moisture Content Plots for all samples tested are shown in Figure H1
through H17.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 293
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
ZAV
2.60
OZR
(Mg / m3 )
2.20
Density
Dry
1.80
BPA 1/9
1.40
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 294
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20 o
o
Density
o o
o
o
Dry
1.80 o o
BPA1/9
BPA1/6
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 295
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20
Density
o
Dry
1.80 o
o
o
1.40
BPC 1/1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 296
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20
o
Density
o
Dry
1.80
o
BPC 1/6
1.40
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
o
2.20
Density
o
o
Dry
1.80
BPC 1/10
1.40
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
o
2.20
o
Density
o
o
o
Dry
1.80 o
BPC 1/10
o
BPC 1/6 o
o
1.40
BPC 1/1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 299
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
ZAV
2.60
OZR
(Mg / m3 )
2.20 o
o
Density
o
Dry
1.80
BPC3/10
1.40
COMPACTION TEST.
3.00
ZAV
2.60
OZR
(Mg / m3 )
2.20
Density
Dry
1.80
BPA 1/9
1.40
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 301
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
o
2.20
o
Density
o o
o
o
Dry
1.80 o o
BPA1/9
BPA1/6
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20
Density
o
Dry
1.80 o
o
o
1.40
BPC 1/1
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 303
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20
o
Density
o
Dry
1.80
o
BPC 1/6
1.40
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 304
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
o
2.20
Density
o
o
Dry
1.80
BPC 1/10
1.40
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 305
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
o
2.20
o
Density
o
o
o
Dry
1.80 o
BPC 1/10
o
BPC 1/6 o
o
1.40
BPC 1/1
COMPACTION TEST.
3.00
ZAV
2.60
OZR
(Mg / m3 )
2.20 o
o
Density
o
Dry
1.80
BPC3/10
1.40
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20 o
o
o
Density
o
o
o
o
Dry
1.80 o
BPC 3/10
o
BPC 3/6
BPC 3/3
1.40
COMPACTION TEST.
3.00
ZAV
2.60
OZR
(Mg / m3 )
2.20
o
Density
o
o
Dry
1.80
BPD 3/6
1.40
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 309
TEKS GEOTECHNICAL CONSULTANCY (NIGERIA) LIMITED.
15 CHURCHILL ROAD, PORT HARCOURT.
COMPACTION TEST.
3.00
OZR
ZAV
2.60
(Mg / m3 )
2.20
o
o
Density
o
o
o
o o
Dry
1.80 o
BPD 3/9 o
BPD 3/6
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 310
Appendix J
References
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 311
REFERENCES.
ANSI/AWWA C105/A21.5 (1993), American National Standard for Polyethylene Encasement for
Ductile Iron Pipe Systems. American Water Works Association (Publishers). Denver, Colorado.
ANSI / IEEE Green Book Standard, pp 142-1982.
Beck A.E. (1981), Physical Principles of Exploration Methods, Ontario, Canada, 234pp
Christian, J.T. and Carrier, W.D.,Janbu, Bjerrun and Kjaernsli’s chart reinterpretation, Canadian
Geotechnical Journal, 15,v123v128 )1978 and discussion , 15 436 – (1978)
Davenport et al, (1981), Geotechnical investigations for corrosive soils. UNAM Proceedings
De Beer, E. and Martens, A (1957), A method of computation of an Upper limit for the Influence of the
Heterogeneity of Sand Layers in The Settlement of Bridges, Proc. 4th Int. Conference, Soil Mech. London
vol. 1 pp 275 – 282.
Bowles, J.E. ( 1977 ), Foundation Analysis and Design. 2nd Edition. McGraw-Hill Book Company, New
York., 750 pages.
Butler, F.G. ( 1974), Review Paper: Heavily consolidated Clays, in: Proc. Conf. On Settlement of
Structures Pentech Press, Cambridge, p 531 – 578.
Cernica, J.N, (1995), Geotechnical Engineering: Foundation Design. John Wiley & Sons Inc. 486 pages.
Christian J.T. and Carrier, W.D. (1978) Janbu, Bjerrum and Kjaernsli’s chart Re-interpreted. Canadian
Geotechnical Journal, Vol. 15, pp 123-128.
Hansbo, S. (1994), Foundation Engineering. Developments in Geotechnical Series No. 75. Elsevier
Amsterdam. 519 pages.
Hansen, J.B., (1968), A revised extended formular for bearing capacity, Danish Geotechnical Institute
Bulletin, No. 28.
Janbu, N., Bjerrum, L. and Kjaernsli, B (1956) Norwegion Geotechnical Institute Publication No. 16.
Meyerhof, G.G., (1963), Some recent research on bearing capacity of foundations Canadian
Geotechnical Journal. Vol. 1 pp 16 – 26.
Orellana E. and Mooney H.M. (1966), Master Table and Curves for Vertical Electrical Sounding over
layered structures,Madrid, 33pp
Overseas Road Note 31(1993), Guide to the Structural Design of Bitumen-Surfaced Roads in Tropical
andSub-Tropical Countries. Overseas Centre, Transport Research Laboratory [TRL], Crownthorne
Berkshire
Peck, R.B; Hansen, W.E; Thornburn, T.H. (1974), Foundation Engineering.
2nd Edition. John Wiley & Sons Inc. New York; 514 pages.
Skempton, A.W. and MacDonald, H.H (1956), The allowable Settlement of Buildings, Proc. Of Civil
Engineers, part 3, vol. 5 pp 727 – 784.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 312
Teks Geotechnical Consultancy (Nigeria) Limited. (1989), Geotechnical Investigation for the foundation
of the UF85 Plant at the National Fertilizer Company of Nigeria, (NAFCON), Onne, Rivers State. Technical
Report to NAFCON Ltd.
Teks Geotechnical Consultancy (Nigeria) Limited. (1992), Subsurface Investigations for the Control of
Gully Erosion at Agulu-Nanka, Anambra State of Nigeria. Technical Report submitted to
SCHWARTZ KRISTOFFEL ENGINEERING SERVICES (NIG.) Ltd, 126 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, and Edet, A.E. (1995), Report on Geotechnical
Investigations for the Structures at the NIBS Complex, Onne. Technical report.
Teks Geotechnical Consultancy (Nigeria) Limited, ( 1997 ), Report on the Geotechnical Investigations for
the Skid-Mounted N2 Plant at the N.N. P.C Refinery, Eleme, near Port Harcourt, Rivers State. Technical
Report submitted to Morpol Industrial Corporation Ltd. 67 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, ( 1998 ), Report on Geotechnical investigations for the
Provision of Additional Mixed LPG
Loading Facilities for Butanisation Project, Port Harcourt Refinery Complex, Alesa-Eleme, Rivers State.
Technical Report submitted to Morpol Industrial Corporation Ltd. 73 pages.
Teks Geotechnical Consultancy (Nigeria) Limited. ( 1999a), Report on Geotechnical Investigations for the
Submersible Pump Foundation at the Additional Mixed LPG Loading Facilities for Butanisation Project,
Port Harcourt Refinery Complex,
Alesa-Eleme, Rivers State. Technical Report submitted to Morpol Industrial Corporation Ltd., 53 pages.
Teks Geotechnical Consultancy (Nigeria) Limited. ( 1999b), Report on Geotechnical Investigations for
The Rehabilitation Project No. 18 – NEW RAW
WATER TANK AND FACILITIES, Port Harcourt Refinery Company, Alesa-Eleme, Rivers State. Technical
Report submitted to CHROME CONSORTIUM, PHRC Premises, Alesa-Eleme, June. 88 pages
Teks Geotechnical Consultancy (Nigeria) Limited, ( 1999c ), Report on Geotechnical Investigations for
the Foundation Design for A Residential
Building at Amassoma, Southern Ijaw Local Government Area, Bayelsa State, Nigeria. Technical Report
submitted to HFP Engineering Nigeria Limited, Ahoada Industrial Estate, Rivers State, July. 29 pages.
Teme, S.C., ( 1999d ), Report on Geotechnical Investigations for the Foundation Design for the Unipole
Advertisement Tower at the Oil Mill Junction Eleme, Port Harcourt, Rivers State, Nigeria. Technical
Report submitted to ALB SALAH ASSOCIATES, Lagos. September. 68 pages.
Teks Geotechnical Consultancy (Nigeria) Limited., ( 1999e ), Report on Geotechnical Investigations for
the Foundation Design for the Unipole Advertisement Tower at Upper Iweka by Police Station by Niger
Bridge, Onitsha, Anambra State, Nigeria. Technical Report submitted to ALB SALAH ASSOCIATES, Lagos.
October. 68 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, ( 2000a ), Report on Geotechnical Investigations for
the Foundation Design for the Bridge Abutments Along The Proposed Gwara – Sii – Iyanorom – Nkoro –
Kalaibiama – Opobo Road. Rivers State, Nigeria. Technical Report submitted to TOM-JAJA ASSOCIATES,
6 Uyo Street, Rumuomasi Port Harcourt. July. 130 pages.
Teks Geotechnical Consultancy (Nigeria) Limited , (2000b), Report on Geotechnical Investigations for
the Foundation Design of the NAL MERCHANT BANK PLC Building Complex, Trans-Amadi Industrial
Area, Port Harcourt. Technical Report submitted to NAL Merchant Bank Plc, Port Harcourt, 95 pages.
Teks Geotechnical Consultancy (Nigeria) Limited S.C., (2001a), Report on Geotechnical Investigations for
the Foundation Design of the Students’ Cafeteria Building Complex, Niger Delta University (NDU),
Wilberforce Island, Bayelsa State. Technical Report submitted to Bayelsa State Government, Niger Delta
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 313
University, Port Harcourt, 65 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2001b), Report on Geotechnical Investigations for the
Foundation Design of the Hostel (East Wing) Building Complex, Niger Delta University (NDU),
Wilberforce Island, Bayelsa State.. Technical Report submitted to Bayelsa State Government, Niger
Delta University, Port
Harcourt, 52 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2001c), Report on Geotechnical Investigations for the
Foundation Design of A residential Building Complex at the Naval Base, Onura Onne, Rivers State..
Technical Report submitted to Echikwa Phillips Partnership, 32 Trans-Amadi Industrial Layout, Port
Harcourt, 52 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2002, Report on Geotechnical Investigations and
Foundation designs for Elevated water Tanks (ORO-N-WT-4) for the Akwa Ibom State Water
Corporation: UKUKO-ORON Local Government Area. Technical Reports submitted to MotherCat Limited,
Kaduna, 54 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2002c), Report on Sand search for Civil Works at the
Etekwuru I & II Link Road – Phase I, Imo State, Nigeria. Technical Reports submitted to ChrisBrown
International Limited, Port Harcourt. 56 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2002d), Report on Geotechnical Investigation and
Foundation Design for Agape Bible Church Building, Presidential Estate, Port Harcourt. Technical
Reports submitted to Agape Bible Church, Port Harcourt.58 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2002e), Report on Geotechnical Investigation for the
Unwana Erosion and Flood Control Project Unwana Beach, Afikpo, Ubeyi LGA Ebonyi State. Technical
Reports
submitted to Anambra-Imo River Basin & Rural Development Authority, Owerri, Imo State. 88 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2003a), Report on Geotechnical Investigation for the
MTN Cell Radio Tower Installation: STADIUM ROAD JUNCTION, Port Harcourt, Rivers State Technical
Reports
submitted to MTN Nigeria. Lagos 88 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2003f), Report on Geotechnical Investigation for the
MCM Nigeria Building Foundation at Olu- Obasanjo road, Port Harcourt, Rivers State Technical Reports
submitted to MCM Nigeria, Benjamin Okpara Street, Off Olu-Obasanjo Road, PHC. 66 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2003g), Report on Geotechnical Investigation for the
MTN Cell Radio Tower Installation: RUKPOKWU, RIVERS STATE Technical Reports submitted to MTN
Nigeria,
Lagos, Nigeria. 66 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2003h), Report on Geotechnical Investigation for the
MTN Cell Radio Tower Installation: PEOPLES CLUB, ONITSHA, ANAMBRA STATE Technical Reports
submitted
to MTN Nigeria, Lagos, Nigeria. 66 pages.
Teks Geotechnical Consultancy (Nigeria) Limited, (2003i), Report on Geotechnical Investigation for the
MTN Cell Radio Tower Installation: ALL SAINTS ANGLICAN CHURCH, AWKA, ANAMBRA STATE Technical
Reports submitted to MTN Nigeria, Lagos, Nigeria. 66 pages.
Teks Geotechnical Consultancy(Nig.) Limited, (2003j), Geotechnical Investigation for the MTN Cell Radio
Tower Installation: STADIUM ROAD JUNCTION, Port Harcourt, Rivers State. Technical Reports
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 314
submitted to MTN Nigeria, Lagos, Nigeria. 60 pages.
Teks Geotechnical Consultancy (Nig.) Limited, (2003k), Geotechnical Investigation for the MTN Cell
Radio Installation: BLESSED BAPTIST CHURCH, Port Harcourt, Rivers State Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 60 pages.
Teks Geotechnical Consultancy (Nig.) Limited, (2003l),Geotechnical Investigation for the CAT
CONSTRUCTION GROUP Building Foundation at Olu-Obasanjo Road, Port Harcourt, Rivers State.
Technical Reports Submitted to Cat Construction Group Limited, PHC, Rivera State. 60 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003m), Geotechnical Investigation for the Design of
Bridge Abutment Foundation for the Okogbe-Oyakama-Ogbhologbholo-Ochigba Road Alignment
Ahoada-East Local Government Area, Rivers State. Technical Reports submitted to Aserima Associates, 2
Tombia Street/ Opobo Crescent, GRA Phase I, Port Harcourt, Rivers State. 60 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003n), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: JIDEOFOR NZEGWU, ONITSHA Technical Reports submitted to MTN Nigeria,
Lagos, Nigeria. 60 pages.
Teks Geotechnical Consultancy (Nig.) Limited, (2003,o), Geotechnical Investigation for the MCM Nigeria
Building Foundation at Olu-Obasanjo Road, Port Harcourt, Rivers State. Technical Reports Submitted to
MCM Nigeria, Benjamin Okpara Street, Off Olu-Obasanjo Road, PHC, River State.
63 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003p), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: RUKPOKWU, RIVERS STATE. Technical Reports submitted to MTN Nigeria,
Lagos, Nigeria. 68 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003q), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: EMUOHA, RIVERS STATE. Technical Reports submitted to MTN Nigeria, Lagos,
Nigeria. 70 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003r), Geotechnical Investigation for the MTN Cell Radio
Tower Installation:, ALUU TOWN, RIVERS STATE. Technical Reports submitted to MTN Nigeria, Lagos,
Nigeria. 69 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003s), Geotechnical Investigation for the MTN Cell Radio
Tower Installation:, ALL SAINTS ANGLICAN CHURCH, AWKA, ANAMBRA STATE Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 64 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003t), Geotechnical Investigation for the MTN Cell Radio
Tower Installation:, PEOPLES CLUB, ONITSHA, ANAMBRA STATE Technical Reports submitted to MTN
Nigeria, Lagos, Nigeria. 70 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003u), Geotechnical Investigation for the MTN Cell
Radio Tower Installation:, METHODIST CHURCH, ORON, AKWA IBOM STATE Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 72 pages.
Teks Geotechnical Consultancy (Nig.) Limited,(2003v), Geotechnical Investigation for the MTN Cell
Radio Tower Installation:, METHODIST CHURCH, IKOT EKPENE, AKWA IBOM STATE. Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 70 pages.
Teks Geotechnical Consultancy (Nig.) Limited, (2003,w), Geotechnical Investigation for the Building
Foundation for a 7-Storey Luxury Apartments at Old GRA, Port Harcourt, RIVERS STATE. Technical
Reports Submitted to Bekin Caterers and Supermarkets (Nig.) Ltd. 63 pages
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 315
Teks Geotechnical Consultancy (Nig.) Limited,(2003x), Geotechnical Investigation for the MTN Cell
Radio Tower Installation:, WATERLINES JUNCTION, PORT HARCOURT, RIVERS STATE. Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 71 pages
.
Teks Geotechnical Consultancy (Nig.) Limited,(2003y), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: OHAUKWU LGA HQR, EBONYI STATE. Technical Reports submitted to MTN
Nigeria, Lagos, Nigeria. 68 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003z), Geotechnical Investigation for the MTN Cell Radio
Tower Installation: ABAKALIKI HIGH COURT, EBONYI STATE. Technical Reports submitted to MTN
Nigeria, Lagos, Nigeria. 66 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003aa), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: WILKINSON STREET, ONITSHA, ANAMBRA STATE. Technical Reports submitted
to MTN Nigeria, Lagos, Nigeria. 67 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2003ab), Geotechnical Investigation for the 50,000
Gallon
Overhead Water Tank, Odiemerenyi, Ahoada-East LGA RIVERS STATE. Technical Reports Submitted to 1.
Osia (Nig.) Ltd 8 Ohonda Street, Of Ikwerre Road, Mile II, Diobu, Port Harcourt. 74 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003ac), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: NTIGHA JUNCTION, ABIA STATE. Technical Reports submitted to MTN Nigeria,
Lagos, Nigeria. 67 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003ad), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: SOALA’S PLOT SITE (T/X 2068), RIVERS STATE. Technical Reports submitted to
MTN Nigeria, Lagos, Nigeria. 67 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2003ae), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: WILKINSON ROAD SITE (T/X 4065), RIVERS STATE. Technical Reports
submitted to MTN Nigeria, Lagos, Nigeria. 66 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2003af), Geotechnical Investigation for the building
Project at 172Ikwerre road, Mile II Diobu, Port Harcourt, RIVERS STATE. Technical Reports Submitted to
Dokitek Enterprise, 69 Abonnema Wharf Road, Port Harcourt, Rivers State.. 74 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2003ag), Geotechnical Investigation for the Building
Foundation for a building Project: Luxury Apartment for Bekin Caterers & Supermarket (Nigeria)
Limited, Port Harcourt, RIVERS STATE. Technical Reports Submitted to Bekin Caterers and Supermarkets
(Nig.) Ltd 19 Hospital Road, P.O. Box 572, PORT HARCOURT, RIVERS STATE.. 63 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2003ah),Geotechnical Investigation for the design of
slope
protection measures – Combined sheet-pile Cantilever Retaining Wall System: Shonekon Hill, Project
Site, Maitama, Abuja. Technical Reports Submitted to A.Group Properties Limited, A6 Plot 2378 Limpopo
Street, FHA Opposite NDIC Quarters, Maitama – Abuja, Nigeria.. 80 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004a),Geotechnical Investigation for the H.A.R.
Petroleum Services Limited Import / Export Terminal Calabar. Technical Reports Submitted to
H.A.R.Petroleum Services Loimited, Calabar Cross-River State. 78 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004b), Geotechnical Investigation for the Bridge
Abutment Foundation Design: Abua Central – Owerewere – Ochigba Road / Bridge.. Technical Reports
Submitted to Aserima Associates, 2 Tombia Street / Opobo Crescent, GRA Phase 1, P.O. Box 2665, Port
Harcourt. 72 pages
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 316
Teks Geotechnical Consultancy (Nig.) Limited, (2004c), Geotechnical Investigation for the Bridge
Abutment Foundation Design: Bridge Abutment Foundation Design: Okuni-Abijang-Nsofang-Okoroba-
Ekang Road-Bridge #1. Technical Reports Submitted to MotherCat JV, 5 Utang street, Uyo, Akwa Ibom
State, Nigeria.. 72 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004d), Geotechnical Investigation for the Bridge
Abutment Foundation Design: Bridge Abutment Foundation Design: Okuni-Abijang-Nsofang-Okoroba-
Ekang Road-Bridge #2. Technical Reports Submitted to MotherCat JV, 5 Utang street, Uyo, Akwa Ibom
State, Nigeria.. 72 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004e), Geotechnical Investigation for the Bridge
Abutment Foundation Design: Bridge Abutment Foundation Design: Okuni-Abijang-Nsofang-Okoroba-
Ekang Road-Bridge #3. Technical Reports Submitted to MotherCat JV, 5 Utang street, Uyo, Akwa Ibom
State, Nigeria.. 72 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004f), Geotechnical Investigation for the Sand search
along the Nun River at Opokuma, Bayelsa State, Nigeria. Technical Reports Submitted to Coastal
Dredging and Construction Limited, Port Harcourt. 78 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004g), Geotechnical Investigation for the designs for
Piling and Piling Caps for the for Transmission Towers at River Crossings: Polaku – Sabagreia –Opokuma
- Koroama . Technical Reports Submitted to HPI Africa Limited 42 Hospital Road, Ahoada Rivers State.
80 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2004h), Geotechnical Investigation for the MTN Cell
Radio Tower Installation: JOR’S PLOT SITE, MAKURDI: T4908, BENUE STATE, NIGERIA . Technical
Reports submitted to MTN Nigeria, Lagos, Nigeria. 68 pages
Teks Geotechnical Consultancy (Nig.) Limited,(2004i), Geotechnical Investigation for the MTN Cell Radio
Tower Installation: POLICE STATION, OTURKPO SITE: T4908, OTURKPO, BENUE STATE NIGERIA .
Technical Reports submitted to MTN Nigeria, Lagos, Nigeria. 68 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004j), Geotechnical Investigation for the foundation
design: NPA CONTROL TOWER, ORON, AKWA IBOM STATE, NIGERIA. Technical Reports Submitted to
Roundo Nigeria Limited, Km 17 Port Harcourt – Aba Expressway, Port Harcourt. Rivers State, Nigeria.
74 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004k), Geotechnical Investigation for the foundation
design: NPA CONTROL TOWER, BONNY, RIVERS STATE, NIGERIA.. Technical Reports Submitted to Roundo
Nigeria Limited, Km 17 Port Harcourt – Aba Expressway, Port Harcourt. Rivers State, Nigeria.
74 pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004l), Geotechnical Investigation for the foundation
design: ACCOUNTANT GENERAL’S OFFICE BUILDING, YENAGOA, BAYELSA STATE, NIGERIA. Technical
Reports Submitted to Bayelsa State Government, Governor’s Office, Yenagoa, Bayelsa State.
69 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004m), Geotechnical Investigation for the Site Visit to
the Esit Uruah Elevated Water Tank Site, Eket, Akwa Ibom State. Technical Reports Submitted to AIM
Consultants / MotherCat Group, 5 Utang Street, Uyo, Akwa Ibom State Nigeria. 65 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004n), Geotechnical Investigation for the Bridge
Abutment Foundation Design: Okuni-Abijang-Nsofang-Okoroba-Ekang Road-Bridge #4. Technical
Reports Submitted to MotherCat JV, 5 Utang street, Uyo, Akwa Ibom State, Nigeria.. 70 Pages
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 317
Teks Geotechnical Consultancy (Nig.) Limited, (2004,o), Geotechnical Investigation for the : Port
Harcourt East/West – Airport Link Road Flyover Bridge, Port Harcourt.. Technical Reports Submitted to
Bullletine Construction Company Limited, Plot 230 Trans-Amadi Industrial Layout, Port Harcourt, Rivers
State, Nigeria. 70 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004p), Geotechnical Investigation for the Bridge
Abutments foundations design,Creek Haven Bridge, Yenagoa, Bayelsa State.. Technical Reports
Submitted to A.Group Properties Ltd.,A6 Plot 2378 Limpopo Str.,FHA Opposite NDIC QuartersMaitama-
Abuja, Nigeria 72 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004q), Geotechnical Investigation for the : Port
Harcourt East/West Road (up to Mbiama) Bridge, Rivers State. Technical Reports Submitted to AIM
Consultants Limited, 267A Etim Inyang Crescent,Victoria Island Annex, Lagos, Nigeria. 69 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004r), Geotechnical Investigation for the: Prodos
Petroleum Product Depot, Nigerian Ports Authority, Onne Rivers State. Technical Reports Submitted to
Prodos Limited,11 Azikiwe Road, Port Harcourt, R/State. 67 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004s), Geotechnical Investigation for theProposed
Fabrication, Shop Onne Oil & Gas Free Zone, Eleme LGA, Rivers State. Technical Reports Submitted to
Vibro Flotation & Geotechnical (Nig.) Limited,6/8 Michael Adekola Street,Ilupeju Lagos Street, Lagos. 69
Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004t), Geotechnical Investigation for the Shore
Protection, Dredging and Reclamation of the Port Harcourt NPA Port Complex. Technical Reports
Submitted to AIM Consultants Limited, 267A Etim Inyang Crescent,Victoria Island Annex, Lagos, Nigeria.
69 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004u), Geotechnical Investigation for the Ogoja – Ikom
–
Mfum – Cameroun Border Road / Bridge site Investigation. Technical Reports Submitted to AIM
Consultants Limited, 267A Etim Inyang Crescent,Victoria Island Annex, Lagos, Nigeria. 72 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004v), Geotechnical Investigation for the Sub-Soil and
Geophysical Investigations for Dape District, FCT, Abuja. Technical Reports Submitted to Federal Capital
Development Authority (FCDA), Engineering Services Department, Abuja, Nigeria 150 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004w), Geotechnical Investigation for the Auto Disable
Syringe Factory, East-West Road, Port Harcourt. Technical Reports Submitted to AIM
Consultants Limited, 267A Etim Inyang Crescent,Victoria Island Annex, Lagos, Nigeria.
150 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2004y), Geotechnical Investigation for the Port Harcourt
– Mbiama Highway Dualisation Project. Technical Reports to beSubmitted to AIM Consultants Limited,
267A Etim Inyang Crescent, Victoria Island Annex, Lagos, Nigeria. In-progress
Teks Geotechnical Consultancy (Nig.) Limited, (2005a), Geotechnical Investigation for the Earth Dam at
Ngor –Okpala, Anambra- Imo River Basin Development Authority, Imo State. Technical Reports to be
Submitted to AIM Consultants Limited, 267A Etim Inyang Crescent, Victoria Island Annex, Lagos, Nigeria.
In-progress
Teks Geotechnical Consultancy (Nig.) Limited, (2005b), Geotechnical Investigation for Gbaran –Ubie
Flood and
Erosion Control Study, Bayelsa State. Technical Reports to be Submitted to Shell Petroleum Development
Company (SPDC),Rumuomasi, Port Harcourt Rivers State. In-progress
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 318
Teks Geotechnical Consultancy (Nig.) Limited, (2005c), Geotechnical Investigation for Pavement
Foundation Design:Oguta, IMO STATE, NIGERIA.. Technical Reports Submitted to Abibbet Consult, 9A
Station Road,Port Harcourt. 69 Pages.
Teks Geotechnical Consultancy (Nig.) Limited, (2005d), Geotechnical Investigation for the Integrity
survey of the Kolo Creek Bridge Abutments piles., Bayelsa State. Technical Reports Submitted to
Pentagon Consultants,Ibadan, Oyo State. 74 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005e), Geotechnical Investigation for the Earth Dam at
Awgu, Enugu State. Technical Reports Submitted to Anbeez Services Limited, Enugu, Enugu State.74
Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005f), Geotechnical Investigation for the Compaction
Monitoring Along the Earth axis at Awgu, Enugu State. Technical Reports Submitted to Anbeez Services
Limited, Enugu, Enugu State. 64 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005g), Geotechnical Investigation for the AIM East
Regional
Office Headquarters Auto Disable Syringe Factory, East-West Road, Port Harcourt. Technical Report
Submitted to AIM Consultants Limited, 267A Etim Inyang Crescent, Victoria Island Annex, Lagos, Nigeria.
66 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005h), Geotechnical Investigation for the CSCCL
Shopping
Complex Building Site along NTA Road, Mgbuoba, Port Harcourt . Technical Reports Submitted to Comag
Steel & Construction Co. Ltd, Km 16, PH/ABA RD, P.O.Box 3151, Port Harcourt, Rivers State.
62 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005i), Geotechnical Investigation for the Building of
Prof. Nimi Briggs at Trans-Amadi Flats Old GRA, Port Harcourt . Technical Reports Submitted to Prof.
Nimi BriggsAmadi Flats, Port Harcourt. 67 Pages
Teks Geotechnical Consultancy (Nig.) Limited, (2005j), Geotechnical Investigation for the 2-storey
building at Native Compensation Plot, Oromeruzingbu Community, GRA Phase IV, Port Harcourt .
Technical Reports Submitted to Mr. Oba OnyebuchiObalink Int.11 Trans-Amadi Industrial Estate, PHC. 65
Pages
Teme, S.C. and Edet, A.E. (1994) Settlement Problems at the Utility Plant, The National Fertilizer
Company of Nigeria, (NAFCON LTD), Technical Report to NAFCON LTD
Terzaghi, K and Peck, R.B. (1967), Soil Mechanics in Engineering Practice.
2nd Ed. John Wiley, New York. Pp 271 – 276.
Tomlinson, M.J. (1980), Foundation Design and Construction, Pitman Advanced Publishing Programme,
London 4th edition 793 pages.
HAALP Consult Limited & TEKS Geotechnical Consultancy (Nigeria) Limited | FUO |Geo Technical Survey |March-May 2013 319