CHAPTER V
5.1 Summary
The researchers collected the architectural plan such as the floor plans and site
development plan of the proposed MedixGlam Protean MedSpa Resort Complex in Bay,
Laguna from the preceding architecture research students of LPU-Cavite. The collected
files and data are in AutoCAD file format (.dwg) and it includes an entire site development
As to aiming the objectives of this research, the proponents were able to design an
electrical layout specified as power and lighting layout. Also, the panel details, single-line
diagram, grounding system and a grid-tied solar farm dedicated for the complex. All
values, codes and standards are guaranteed reliable based on the Philippine Electrical Code
(PEC) 2017, the Department of Energy Manual on Efficient Lighting, IEEE and National
Electrical Code. The computations and results made were also evaluated for the reliable
protection requirements and was validated from the ETAP software together with a
To be able to accomplish the entire system design, the Architectural Plan, Mechanical
Plan, Low Current System Design, complete dimensions, Legends, General Notes,
Electrical Layout, Schedule of Loads, Load Computation, One-line Diagram and the
5.2 Conclusion
The proponents gathered the data for the architectural, electrical, mechanical and low
current system requirement for each of the building included in the complex, each data was
used for the electrical computation needed to have an electrical system that is safe and
efficient.
Using a drawing software called AutoCAD, the designers have designed an electrical
layout which consists of the lighting layout and power layout for the buildings in the
complex. The researchers also designed a single line diagram of the whole electrical system
to represent each of the electrical components in the system that will also serve as the
guiding map for the electrical personnel in case of maintenance. Riser diagram were also
designed for each of the building, these diagrams are used to show major items of electrical
equipment in a building.
protection devices, sizes of conductor, conduit and other wiring device, voltage drop, short
circuit, arc flash, protection coordination, and grounding system. The illumination design
was calculated by the designers and simulated through DIALux desktop application that
are used by professional in terms of illumination design, the data used in the illumination
Department of Energy, Philippines. The proper size of conductor, conduit and over current
protection are following the provision stated in the latest PEC. Calculation for the voltage
drop of both the branch circuits and feeder circuits met the requirements of the allowable
voltage drop according to the Article 2.10.2.2(A) FPN No.4 of PEC 2017 for the branch
circuits and to Article 2.15.1.2(A) FPN no.2 of PEC 2017 for the feeder circuits. The short
circuit calculations are based on the provisions of the latest PEC and IEEE std. 551 – 2006,
these calculated values were verified by the results of the simulated value given by the
ETAP 16.0, an electrical power system desktop application used by the professionals for
the purpose of electrical design analysis, and met the ±5% acceptable tolerance of the
simulated values to the calculated values of the short circuit currents. The protection
coordination was represented by the TCC curve that was graphed to be able to represent
the coordination of the protection devices of the system, these curves are gathered using
Simaris App, an application that produces TCC curves for the Siemens’ circuit breaker
product, and was fully graphed in excel to have a complete output of a coordinated TCC
curve for the electrical system. IEEE std. 1584 and NFPA 70E were the basis on the
calculation for the arc flash analysis, the analysis identifies the proper personnel protective
equipment that will greatly reduce the possibility of injury or death are identified in this
analysis.
The electrical system’s simplified single-line diagram was represented in the design
power system in the ETAP 16.0. The application was used to simulate the short circuit test
on the electrical system and was also used to validate the computed values of the designers.
The researchers have designed a solar grid-tied electrical system for some of the
building in the complex, somehow, the researchers are not able to use the dedicated land
for solar use because of the power losses issue when designing a solar farm that will
distribute the power generated to a far location. The designers decided to use a roof-
mounted solar grid-tied system that will greatly minimize the power losses that may occur
The designed solar grid-tied electrical system for the proposed Protean MedSpa Resort
5. 3 Recommendation
The proponents were able to accomplish all necessary data and design analysis that is in
accordance to the general objectives of the research study. For the improvement of this
line that has less power losses in the system and can accommodate all the
Compute for the load flow analysis, harmonics of the system and insulation