Reference Drawings
Dwg. No. Description
1. Vessel classification................................................................................................... 3
2. Battery Size Calculation............................................................................................. 3
2.1. 24Vdc Emergency Services ............................................................................. 3
3. Battery technical data ............................................................................................... 7
4. Charging time ............................................................................................................ 9
1. Vessel classification
The vessel shall be built under the rules of the Lloyd's Register, who will approve the
plans and supervise the construction for the completion of the same deliver class
certificates.
Register Classification notation shall be the following:
+ 100A1 Tug, Fire Fighting Ship 1 (2400m3/h with water spray, * IWS
+LMC, UMS, CCS, Oil Recovery (F.P. >60ºC), ECO (NO-x3), CAC (3)
Descriptive Note: Escort operations for sheltered waters
Battery size is calculated according to Standard IEEE 485 and considering the following
premises:
In this regard and taking into consideration the technical specification of the vessel the
discharging time shall be split into three periods:
cycle Time Description
t1 0 to 0.5 hours Services non essentials for safety. In this period those non-essential
services shall be switched off by the crew.
t2 0 to 3 hours Emergency lighting at embarkation station
t3 0 to 18 hours Rest of emergency services according to SOLAS II-1, Part D, reg.43
DISCHARGE CURVE
600
500 y = 1713,5x-0,695
400
300
200
100
0
0 100 200 300 400 500 600 700
-100
.
1713
t in minutes
I in Amperes
Section Load Change Load Period Duration Time to end of Capacity Required
h section capacity
1 54,04 54,04 0,50 0,50 183,00 0,295
Final capacity of the battery: 2+2 batteries 200Ah each (total capacity 400Ah)
C= 400Ah
Manufacturer: Sonneschein
Battery Box
4. Charging time
TAG Battery Qty Ah Total I20 Batt. Charger Load Charging Charging Charging
A A Current A/I20 Time*
DC10 A512/200A 2+2 400Ah 20A 75A 26,7A 48,3A 2.52 7,9 hours
* up to 90%