Professional Documents
Culture Documents
Generator Relay
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Date: 2019-02-21
Preface
DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.
CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded.
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
WARNING!
Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.
WARNING!
Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Earthing
Operating environment
ONLY use the device within the range of ambient environment and in an
environment free of abnormal vibration.
Ratings
Date: 2019-02-21
Preface
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.
Do NOT attach or remove printed circuit board if the device is powered on.
External circuit
Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.
Connection cable
NOTICE!
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Date: 2019-02-21
Preface
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
5 Management
Introduce the management function (measurment and recording) of this relay.
6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module, typical wiring is provided.
7 Settings
List settings including system settings, communication settings and etc.
9 Configurable Function
Brief introduction of configurable functions and configuration software.
10 Communication
Introduce the communication port and protocol which this relay can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
11 Installation
Date: 2019-02-21
Preface
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
earthing recommendations.
12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
13 Maintenance
A general maintenance policy for this relay is outlined.
Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.
&
AND gate
≥1
OR gate
Comparator
Date: 2019-02-21
Preface
Timer
t
Time (optional definite-time or inverse-time characteristic)
t
10ms 2ms
Timer [delay pickup (10ms), delay dropoff (2ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay drop off, settable)
[XXX] [XXX]
Timer (delay pickup, delay drop off, settable)
Basic
A, B, C L1, L2, L3 R, Y, B
AN, BN, CN L1N, L2N, L3N RN,YN, BN
ABC L123 RYB
U (voltage) V U
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
Date: 2019-02-21
1 Introduction
1 Introduction
Table of Contents
List of Figures
List of Tables
Date: 2016-08-16
1 Introduction
Date: 2016-08-16
1 Introduction
1.1 Application
PCS-985GE is a kind of high performance numerical generator protection device, which integrates
main and backup protection into one device. It provides complete protection of a generator in
power plant, and it also provides basic protection of a generator and an excitation transformer.
PCS-985GE can be applied for turbo-dynamo generator, gas-turbine generator, hydro generator
and nuclear power generator with different connection modes.
PCS-985GE provides up to 28 analog input channels including current and voltage inputs. The
generator protections are configurable. Ancillary functions of fault diagnostic, disturbance records,
event records and communication function are integrated in the device.
NOTICE!
Current transformers (CT) used for differential protection may be DIFFERENT from
those for backup protection.
PCS-985GE
MR 51GS
Generator Busbar
GCB 81O
24 59P 27P
81U
ncba n l
VT
*
Exciting 32R
87G 50P,51P 21 49S 46G 59N 40G 78 50/27 50BF
Transformer 32F
+
Generator
_
Low Resistance
Date: 2016-08-16
1 Introduction
PCS-985GE
MR 51GS
Generator Busbar
GCB 81O
24 59P 27P
81U
ncba n l
VT
32R
87G 50P,51P 21 49S 46G 51G/67G 40G 78 50/27 50BF
* Exciting 32F
Transformer
+
Generator
_
*
64R StShut
Busbar 1
Busbar 2
Busbar VT
TCB
l n abcn
PCS-985GE
MR
Main
Transformer
GCB 81O
24 59P 59NIT 64S1
81U
ncba n l
*
VT1
ncba n l
VT2 Exciting 87ET 50P,51P 49E 87G 50P,51P 21 64S2 40G 78 49S 46G 32R 50/27 50BF
* Transformer
+
Generator *
_
64R
1.2 Functions
Protective Functions
Date: 2016-08-16
1 Introduction
The protective functions listed in following table are available for PCS-985GE, the functions can be
configured according to user’s requirement.
Miscellaneous functions
Date: 2016-08-16
1 Introduction
Miscellaneous functions are listed in the following table, such as measurement, self-supervision
and oscillography, communication functions, and etc.
Miscellaneous functions
Serial port
Ports type Electrical Ethernet port
Optical Ethernet port
Rear communication IEC 60870-5-103 (Ethernet port or serial port)
ports to host IEC 61850-8-1 (Ethernet port)
Protocol type Modbus (Serial port)
DNP 3.0 (Ethernet port)
(Specified when ordering)
Date: 2016-08-16
1 Introduction
Miscellaneous functions
2) SAS
SNTP (PTP): Unicast (point-to-point) SNTP mode via
Ethernet network
SNTP (BC): Broadcast SNTP mode via Ethernet network
Message (IEC103): Clock messages through IEC103
protocol
3) Advanced
IEEE1588: Clock message via IEEE1588
IRIG-B (Fiber): IRIG-B via optical-fibre interface
PPS (Fiber) PPS: Pulse per second (PPS) via
optical-fibre interface
4) NoTimeSyn
1.3 Features
Configurable Function
Modules of the device adopt intelligent design, amount of input and output modules and module
slot position are configurable. User can increase or decrease the amount of AC input module,
binary input module and binary output module, and terminals of those modules can be defined
according to actual requirement. Besides, configurability is also reflected in software design of
device, which means that user can hide the protective element not used or add new protective
module not in standard configuration.
The hardware of the device comprises a 32-bit microprocessor and two 32-bit digital signal
processors (DSP). Those processors can operate in parallel companied by fast A/D converter. The
32-bit microprocessor performs logic calculation and the DSP performs the protection calculation.
High performance hardware ensures real time calculation of all protection relays within a sampling
interval.
On the premise of 24 samples per cycle, all data measurement, calculation and logic
discrimination could be done within one sampling period. The event recording and protection logic
calculation are completed simultaneously.
Date: 2016-08-16
1 Introduction
Independent fault detectors in fault detector DSP module for connecting power supply of output
relays. The relay can drive a tripping output only when protection element on protection DSP
module operates with the fault detector in the fault detector DSP module operating simultaneously.
This kind of independent supervision of tripping outputs using fault detectors can avoid any
mal-operation possibly caused by any hardware component failure. This highly increases the
security. Please refer to Chapter 6 for details.
The tripping output contacts can be configured by tripping matrix and suitable to any mode of
tripping.
Event records include 1024 binary input events and 1024 alarm events. Disturbance records
including 64 fault reports, and 64 disturbance waveforms, and file format of waveform is
compatible with international COMTRADE91 and COMTRADE99 file. Analog inputs and binary
inputs can be recorded, and three oscillography triggering mode are supported, which are
protection pickup triggering, manual triggering on keypad of device, and remote triggering through
PCS-Explorer2 software.
Powerful PC tool software (PCS-Explorer2) can fulfill protection function configuration, modify
setting and waveform analysis.
Main and backup protection are integrated in one set of protection device. Protection information
is shared by all parts. The device can record all relevant waveforms of any fault.
DPFC (deviation of power frequency component) biased current differential protection element is
regardless of the load current and is sensitive to small internal fault current within the generator. Its
performance against current transformer saturation is also good.
Based on the operation sequence of DPFC restraint current element and DPFC differential current
element of differential protection, external fault with CT saturation or internal fault can be
distinguished correctly.
Date: 2016-08-16
2 Technical Data
2 Technical Data
Table of Contents
Date: 2016-08-16
2 Technical Data
2.10.6 Generator 3rd Harmonic Stator Ground Fault Protection .................................................. 2-9
2.10.7 Generator Ping-Pang Type Rotor Ground Fault Protection ............................................... 2-9
2.10.8 Generator Rotor Ground Fault Protection with Low-frequency Square-wave Voltage
Injection ......................................................................................................................................... 2-9
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
2. Signal contact
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
®
Printer type EPSON 300K printer
Safety level Isolation to ELV level
Date: 2016-08-16
2 Technical Data
2.6 Certifications
ISO9001: 2008
ISO14001:2004
OHSAS18001: 2007
ISO10012:2003
CMMI L5
2.7 Terminals
Connection Type Wire Size
Crimp terminals, 1.5mm ~4.0mm2 lead
2
AC current If using 4.0mm2 lead, only dedicated terminal cable lug provided by NR
can be adopted.
2 2
AC voltage Crimp terminals, 1.0mm ~2.5mm lead
Power supply Crimp terminals, 1.0mm ~2.5mm2 lead
2
Date: 2016-08-16
2 Technical Data
2 2
Contact I/O Crimp terminals, 1.0mm ~2.5mm lead
2
Grounding (Earthing) Connection BVR type, 2.5mm²~6.0mm lead
There are some symbols mentioned in the following sections and the meaning of them is given
here.
pu – per-unit value
Date: 2016-08-16
2 Technical Data
Tolerance of operating current ≤5% of operating current or 0.02 pu, whichever is greater
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Date: 2016-08-16
2 Technical Data
Tolerance of definite-time time delay ≤1% of setting +40ms (at 2 times current setting)
Operating time of inverse-time overcurrent ≤2.5% operating time or 40ms, whichever is greater(for current
element between 1.2 and 20 multiples of pickup)
Date: 2016-08-16
2 Technical Data
Operating time of inverse-time overvoltage ≤2.5% operating time or 40ms, whichever is greater (for voltage
element between 1.2 and 2 multiples of pickup)
Date: 2016-08-16
2 Technical Data
Tolerance of time delay ≤1% of setting +40ms (at 2 times current setting)
Tolerance of operating current ≤5% of operating current or 0.02 pu, whichever is greater
Date: 2016-08-16
3 Operation Theory
3 Operation Theory
Table of Contents
3.3 Generator Neutral Point Transverse Differential Protection (87NTG) ....... 3-18
3.3.1 Application .......................................................................................................................... 3-18
Date: 2016-08-16
3 Operation Theory
3.7 Generator 3rd Harmonic Stator Ground Fault Protection (64S2) ................ 3-49
3.7.1 Application .......................................................................................................................... 3-49
3.8 Generator Ping-Pang Type Rotor Ground Fault Protection (64R) ............. 3-58
3.8.1 Application .......................................................................................................................... 3-58
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.17.5 Settings............................................................................................................................3-111
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
List of Figures
Figure 3.2-1 Current calculation process of generator current differential protection ....... 3-4
Figure 3.2-3 Operation characteristic curve of DPFC differential element of generator..... 3-9
Figure 3.2-4 Logic diagram of startup of generator current differential protection .......... 3-12
Figure 3.2-5 Logic diagram of steady-state current differential element of generator...... 3-13
Figure 3.2-6 Logic diagram of DPFC current differential element of generator ................. 3-14
Figure 3.2-7 Function block diagram of generator current differential protection ............ 3-14
Figure 3.3-1 Current calculation process of neutral point transverse differential protection
..................................................................................................................................................... 3-19
Figure 3.3-2 Logic diagram of generator neutral point transverse differential protection 3-21
Figure 3.3-3 Function block diagram of generator neutral point transverse differential
protection ................................................................................................................................... 3-22
Figure 3.4-3 Function block diagram of generator inter-turn protection ............................ 3-29
Figure 3.5-1 Operation characteristic of inverse-time stator overload protection ............ 3-32
Figure 3.5-2 Logic diagram of generator stator overload protection .................................. 3-34
Figure 3.5-3 Function block diagram of generator stator overload protection .................. 3-34
Figure 3.6-2 Characteristic of the zero sequence directional element ................................ 3-40
Figure 3.6-3 Logic diagram of generator fundamental zero-sequence stator ground fault
protection ................................................................................................................................... 3-44
Figure 3.7-1 Calculation process of generator 3rd harmonic stator ground fault protection
..................................................................................................................................................... 3-50
Figure 3.7-2 Logic diagram of generator 3rd harmonic stator ground fault protection ..... 3-54
Figure 3.7-3 Function block diagram of generator 3rd harmonic stator ground fault
Date: 2016-08-16
3 Operation Theory
Figure 3.8-1 Schematic diagram of Ping-Pang type rotor ground fault protection ........... 3-59
Figure 3.8-2 Logic diagram of generator Ping-Pang type rotor ground fault protection .. 3-60
Figure 3.8-3 Function block diagram of generator Ping-Pang type rotor ground fault
protection ................................................................................................................................... 3-61
Figure 3.9-1 Schematic diagram of rotor ground fault protection with low-frequency
square-wave voltage injection ................................................................................................. 3-65
Figure 3.9-2 Logic diagram of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) ................................................................................................ 3-67
Figure 3.9-3 Function block diagram of generator rotor ground fault protection (with
low-frequency square-wave voltage injection) ...................................................................... 3-68
Figure 3.10-3 Function block diagram of rotor winding overload protection..................... 3-75
Figure 3.11-2 Function block diagram of inadvertent energization protection .................. 3-80
Figure 3.12-3 Function block diagram of generator out-of-step protection ....................... 3-86
Figure 3.13-1 Logic diagram of generator startup and shutdown protection .................... 3-90
Figure 3.13-2 Function block diagram of generator startup and shutdown protection .... 3-90
Figure 3.14-1 Logic diagram of generator shaft overcurrent protection ............................ 3-95
Figure 3.14-2 Function block diagram of generator shaft overcurrent protection ............ 3-95
Figure 3.15-2 Logic diagram of generator negative-sequence overload protection ....... 3-101
Figure 3.16-2 Function block diagram of generator reverse power protection ............... 3-106
Figure 3.17-1 Logic diagram of generator low forward power protection ........................ 3-110
Date: 2016-08-16
3 Operation Theory
Figure 3.17-2 Function block diagram of generator low forward power protection ........ 3-110
Figure 3.19-4 Function block diagram of loss of excitation protection ............................ 3-124
Figure 3.20-1 Function diagram of generator phase overcurrent protection ................... 3-130
Figure 3.20-3 Direction characteristic of generator phase overcurrent protection ......... 3-134
Figure 3.20-4 Logic diagram of generator phase overcurrent protection (n=1,2,3) ......... 3-135
Figure 3.20-7 Logic diagram of direction element of generator phase overcurrent protection
................................................................................................................................................... 3-136
Figure 3.20-8 Function block diagram of generator phase overcurrent protection ........ 3-137
Figure 3.21-2 Function block diagram of phase overvoltage protection .......................... 3-143
Figure 3.23-2 Logic diagram of stage 1 of overfrequency band accumulate protection 3-152
Figure 3.23-3 Logic diagram of stage 4 of overfrequency band accumulate protection 3-153
Figure 3.24-1 Logic diagram of stage x of underfrequency protection (x=1~4) ............... 3-160
Date: 2016-08-16
3 Operation Theory
................................................................................................................................................... 3-161
Figure 3.25-5 Logic diagram of stage 1 of phase-to-phase impedance protection ......... 3-172
Figure 3.26-2 Function block diagram of breaker failure protection ................................. 3-178
Figure 3.27-2 Function block diagram of mechanical protection (x=1, 2)......................... 3-181
Figure 3.28-1 Excitation transformer current compensation calculation process .......... 3-190
Figure 3.28-4 Logic diagram of excitation transformer current differential protection... 3-199
Figure 3.29-1 Logic diagram of excitation transformer phase overcurrent protection (n=1,2)
................................................................................................................................................... 3-205
Figure 3.30-1 Logic diagram of interconnection status element ([En_GCB]=1) .............. 3-208
Figure 3.30-2 Logic diagram of interconnection status element ([En_GCB]=0) .............. 3-208
Figure 3.30-3 Function block diagram of interconnection status element ....................... 3-208
Figure 3.31-2 Function block diagram of voltage balance protection ............................... 3-214
Figure 3.32-2 Function block diagram of three-phase current element ............................ 3-217
Date: 2016-08-16
3 Operation Theory
Figure 3.33-2 Function block diagram of three-phase voltage element ............................ 3-221
Figure 3.34-1 Function block diagram of single current element with filter ..................... 3-224
Figure 3.35-1 Function block diagram of residual voltage element .................................. 3-226
List of Tables
Table 3.2-1 Input signals of generator current differential protection ................................ 3-14
Table 3.2-2 Output signals of generator current differential protection ............................. 3-15
Table 3.2-3 Output signals of generator current differential protection (event recorder) 3-15
Table 3.2-4 Output signals of generator current differential protection (measurements) 3-15
Table 3.2-5 Settings list of generator current differential protection .................................. 3-17
Table 3.3-1 Input signals of generator neutral point transverse differential protection ... 3-22
Table 3.3-2 Output signals of generator neutral point transverse differential protection 3-22
Table 3.3-3 Output signals of generator neutral point transverse differential protection
(event recorder) ......................................................................................................................... 3-23
Table 3.3-4 Output signals of generator neutral point transverse differential protection
(measurements) ......................................................................................................................... 3-23
Table 3.3-5 Settings list of generator neutral point transverse differential protection ..... 3-23
Table 3.4-3 Output signals of generator inter-turn protection (event recorder)................. 3-29
Table 3.4-4 Output signals of generator inter-turn protection (measurements) ................ 3-30
Table 3.5-1 Input signals of generator stator overload protection ...................................... 3-34
Table 3.5-2 Output signals of generator stator overload protection ................................... 3-35
Table 3.5-3 Output signals of generator stator overload protection (event recorder) ...... 3-35
Table 3.5-4 Output signals of generator stator overload protection (measurements) ...... 3-35
Table 3.5-5 Settings list of generator stator overload protection ........................................ 3-36
Table 3.6-1 Input signals of generator fundamental zero-sequence stator ground fault
protection ................................................................................................................................... 3-45
Table 3.6-2 Output signals of generator fundamental zero-sequence voltage stator ground
Date: 2016-08-16
3 Operation Theory
Table 3.6-3 Output signals of generator fundamental zero-sequence voltage stator ground
fault protection (event recorder) .............................................................................................. 3-45
Table 3.6-4 Output signals of generator fundamental zero-sequence voltage stator ground
fault protection (measurements) ............................................................................................. 3-46
Table 3.6-5 Settings list of generator fundamental zero-sequence voltage stator ground
fault protection .......................................................................................................................... 3-47
Table 3.7-1 Input signals of generator 3rd harmonic stator ground fault protection.......... 3-55
Table 3.7-2 Output signals of generator 3rd harmonic stator ground fault protection....... 3-56
Table 3.7-3 Output signals of generator 3rd harmonic stator ground fault protection (event
recorder) ..................................................................................................................................... 3-56
Table 3.7-4 Output signals of generator 3rd harmonic stator ground fault protection
(measurements) ......................................................................................................................... 3-56
Table 3.7-5 Settings list of generator 3rd harmonic stator ground fault protection ........... 3-57
Table 3.8-1 Input signals of generator Ping-Pang type rotor ground fault protection ...... 3-61
Table 3.8-2 Output signals of generator Ping-Pang type rotor ground fault protection ... 3-61
Table 3.8-3 Output signals of generator Ping-Pang type rotor ground fault protection (event
recorder) ..................................................................................................................................... 3-62
Table 3.8-4 Output signals of generator Ping-Pang type rotor ground fault protection
(measurements) ......................................................................................................................... 3-62
Table 3.8-5 Settings list of generator Ping-Pang type rotor ground fault protection ........ 3-63
Table 3.9-1 Input signals of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) ................................................................................................ 3-68
Table 3.9-2 Output signals of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) ................................................................................................ 3-68
Table 3.9-3 Output signals of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) (event recorder) ................................................................... 3-69
Table 3.9-4 Output signals of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) (measurements) ................................................................... 3-69
Table 3.9-5 Settings list of generator rotor ground fault protection (with low-frequency
square-wave voltage injection) ................................................................................................ 3-70
Table 3.10-1 Input signals of rotor winding overload protection ......................................... 3-75
Table 3.10-2 Output signals of rotor winding overload protection ...................................... 3-75
Table 3.10-3 Output signals of rotor winding overload protection (event recorder) ......... 3-75
Date: 2016-08-16
3 Operation Theory
Table 3.10-4 Output signals of rotor winding overload protection (measurements)......... 3-76
Table 3.11-3 Output signals of inadvertent energization protection (event recorder) ...... 3-81
able 3.11-4 Output signals of inadvertent energization protection (measurements) ........ 3-81
Table 3.12-3 Output signals of generator out-of-step protection (event recorder)............ 3-86
Table 3.12-4 Output signals of generator out-of-step protection (measurements) ........... 3-87
Table 3.13-1 Input signals of generator startup and shutdown protection ........................ 3-91
Table 3.13-2 Output signals of generator startup and shutdown protection ..................... 3-91
Table 3.13-3 Output signals of generator startup and shutdown protection (event recorder)
..................................................................................................................................................... 3-91
Table 3.13-4 Output signals of generator startup and shutdown protection (measurements)
..................................................................................................................................................... 3-92
Table 3.13-5 Settings list of generator startup and shutdown protection .......................... 3-92
Table 3.14-1 Input signals of generator shaft overcurrent protection ................................ 3-95
Table 3.14-2 Output signals of generator shaft overcurrent protection ............................. 3-96
Table 3.14-3 Output signals of generator shaft overcurrent protection (event recorder) . 3-96
Table 3.14-4 Output signals of generator shaft overcurrent protection (measurements) 3-96
Table 3.14-5 Settings list of generator shaft overcurrent protection .................................. 3-97
Table 3.15-1 Input signals of generator negative-sequence overload protection ........... 3-101
Table 3.15-2 Output signals of generator stator overload protection ............................... 3-102
Table 3.15-5 Settings list of generator negative-sequence overload protection ............. 3-103
Date: 2016-08-16
3 Operation Theory
Table 3.16-1 Input signals of generator reverse power protection .................................... 3-106
Table 3.16-3 Output signals of generator reverse power protection (event recorder) .... 3-107
Table 3.16-4 Output signals of generator reverse power protection (measurements).... 3-107
Table 3.17-1 Input signals of generator low forward power protection ............................ 3-110
Table 3.17-2 Output signals of generator low forward power protection ......................... 3-110
Table 3.17-3 Output signals of generator low forward power protection (event recorder)
................................................................................................................................................... 3-111
Table 3.17-4 Settings list of generator low forward power protection .............................. 3-111
Table 3.18-3 Output signals of overexcitation protection (event recorder) ...................... 3-116
Table 3.19-3 Output signals of loss of excitation protection (event recorder)................. 3-125
Table 3.19-4 Output signals of loss of excitation protection (measurements) ................ 3-125
Table 3.20-4 Output signals of generator phase overcurrent protection (event recorder)
................................................................................................................................................... 3-137
Table 3.20-6 Settings list of generator phase overcurrent protection .............................. 3-138
Date: 2016-08-16
3 Operation Theory
Table 3.21-3 Output signals of phase overvoltage protection (event recorder) .............. 3-143
Table 3.21-4 Output signals of phase overvoltage protection (measurements) .............. 3-144
Table 3.22-3 Output signals of phase undervoltage protection (event recorder) ............ 3-148
Table 3.23-3 Output signals of overfrequency protection (event recorder) ..................... 3-154
Table 3.24-3 Output signals of underfrequency protection (event recorder) ................... 3-162
Table 3.25-3 Output signals of impedance protection (event recorder) ........................... 3-173
Table 3.26-3 Output signals of breaker failure protection (event recorder) ..................... 3-179
Table 3.26-4 Output signals of breaker failure protection (measurements) ..................... 3-179
Date: 2016-08-16
3 Operation Theory
Table 3.27-3 Output signals of mechanical protection (event recorder) (x=1, 2) ............. 3-182
Table 3.28-1 Phase shift matrix for phase compensation .................................................. 3-187
Table 3.28-2 Input signals of excitation transformer current differential protection....... 3-200
Table 3.28-3 Output signals of excitation transformer current differential protection.... 3-201
Table 3.28-4 Output signals of excitation transformer current differential protection (event
recorder) ................................................................................................................................... 3-201
Table 3.28-5 Output signals of excitation transformer current differential protection.... 3-201
Table 3.28-6 Settings list of excitation transformer current differential protection ........ 3-203
Table 3.29-1 Input signals of excitation transformer phase overcurrent protection ....... 3-205
Table 3.29-2 Output signals of excitation transformer phase overcurrent protection .... 3-206
Table 3.29-3 Output signals of excitation transformer phase overcurrent protection (event
recorder) ................................................................................................................................... 3-206
Table 3.29-4 Settings list of excitation transformer phase overcurrent protection ......... 3-206
Table 3.30-3 Output signals of interconnection status element (measurements) ........... 3-209
Table 3.31-3 Output signals of voltage balance protection (event recorder) ................... 3-214
Table 3.31-4 Output signals of voltage balance protection (measurements) ................... 3-215
Table 3.32-3 Output signals of three-phase current element (event recorder) ................ 3-217
Table 3.32-4 Output signals of three-phase current element (measurements) ................ 3-217
Date: 2016-08-16
3 Operation Theory
Table 3.33-3 Output signals of three-phase voltage element (event recorder) ................ 3-222
Table 3.33-4 Output signals of three-phase voltage element (measurements) ................ 3-222
Table 3.34-1 Input signals of single current element with filter ......................................... 3-224
Table 3.34-2 Output signals of single current element with filter ...................................... 3-224
Table 3.34-3 Output signals of single current element with filter (measurements) ......... 3-225
Table 3.34-4 Settings list of single current element with filter ........................................... 3-225
Table 3.35-3 Output signals of residual voltage element (measurements) ...................... 3-226
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.1 Overview
The device has 2 plug-in modules (protection DSP module and fault detector DSP module) for
protection calculation. Protection DSP module is responsible for calculation of protection elements,
and fault detector DSP module is responsible for calculation of general fault detector element to
determine fault appearance on the protected power system. General fault detector picks up to
provide positive supply to output relays. The output relays can only operate when both a protection
element and the corresponding general fault detector operate simultaneously. Otherwise, the
output relays would not operate. An alarm message will be issued with blocking output if a
protection element operates while the corresponding general fault detector does not operate.
The fault detector of fault detector DSP module consists of several independent fault detector
elements, which can monitor corresponding protection elements without influence to other
protection elements. For example, biased current differential protection will not release tripping
command until both protection element of protection DSP module and the corresponding fault
detector of fault detector DSP module operate simultaneously. Furthermore, if there is a hardware
fault on one DSP module or the differential current is at the trip boundary, the inconsistent pickup
of fault detectors of biased current differential protection on two DSP modules will occur.
3.2.1 Application
Generator current differential protection is the main protection for the internal short-circuit fault of
generator stator winding. Current differential protection can operate quickly to clear the internal
fault to avoid the generator from damages or reduce the maintenance cost as low as possible.
Biased current differential element with initial restraint slope is adopted, it consists of sensitive
and conventional biased differential elements as well as independent CT saturation criterion.
DPFC current differential element can fully reflect the change of differential current and
restraint current, and it is not affected by the load current and is sensitive to small internal fault
current within the generator. Its performance against CT saturation is also good.
For internal serious fault, once the differential current is larger than the current setting of
instantaneous differential element, the current differential element will operate to cut off the
fault quickly.
Date: 2016-08-16
3 Operation Theory
Voltage is also used to judge the abnormality of differential CT circuit, multi-phase CT circuit
failure, multi-side CT circuit failure and short-circuit condition can be detected.
Current differential protection includes three operation elements: biased differential element,
unrestrained differential element and DPFC differential element. When the differential current is
larger than the corresponding current threshold, current differential protection will operate, and it
will drop off if the fault current disappears.
Sensitive biased differential element is variable slope differential element with initial restraint slope.
Conventional biased differential element is differential element with two broken lines. Unrestrained
differential element is used to cut off the serious fault quickly and there is no any blocking element
for it. DPFC differential element adopts the current change to calculate, it is very sensitive to slight
fault under heavy loading condition. The three differential elements coordinate with each other, so
quick and high sensitive differential protection can be realized.
Generally, the CT ratio of the two sides of the generator is the same, as long as the polarity of CT
is correct, the secondary currents of two CTs will be balanced automatically. In some cases (such
as some hydropower units), the magnitudes of secondary current of two CTs are different due to
the difference of CT ratio. Then the secondary currents of two CTs should be balanced by
amplitude adjustment of software (i.e. CT ratio adjustment).
Pn / cos θ
I1b = Equation 3.2-1
3U1n
Where:
I1b I
I 2b _ Br1 = , I 2b _ Br 2 = 1b Equation 3.2-2
CT1 CT2
Date: 2016-08-16
3 Operation Theory
Where:
k _ Br1 = 1
I 2b _ Br1
k _ Br 2 =
I 2b _ Br 2 Equation 3.2-3
( I 2b _ Br1 / I 2 n _ Br1 )
≤ 16
( I 2b _ Br 2 / I 2 n _ Br 2 )
Where:
I 2b _ Br1 , I 2b _ Br 2 are rated secondary current of generator terminal side and generator neutral
point side.
I 2 n _ Br1 , I 2 n _ Br 2 are rated secondary current of CT of generator terminal side and generator
k _ Br1 , k _ Br 2 are adjust coefficient of generator terminal side and generator neutral point side.
Generator terminal side is the referenced side fixedly. If Equation 3.2-3 is not met, the setting error
alarm signals [87G.Fail_Settings] will be issued and displayed on LCD with the protective device
being blocked.
Date: 2016-08-16
3 Operation Theory
| I1cr + I2 cr |
I
r =
2
Where:
I1 , I2 are the secondary current of generator terminal side and generator neutral point side.
I 2 n _ Br1 , I 2 n _ Br 2 are rated secondary current of CT of generator terminal side and generator
I1cr , I2 cr are the corrected secondary current of generator terminal side and generator neutral
point side.
I d is differential current.
I r is restraint current.
Current adjustment process is shown in the flowing figure. The symbol “*” represents the polarity
of CT. If current flowing into the polarity side of CT, the current direction is defined as positive
direction. In an ideal situation, the differential current should be zero during the normal operation
of the generator or an external fault occurring.
PCS-985GE
I1cr I2 cr
Calculate differential current and restraint current
In above figure:
Date: 2016-08-16
3 Operation Theory
IP1 , IP2 are primary current vectors of generator terminal side and generator neutral point side
respectively.
I1 , I2 are the secondary current of generator terminal side and generator neutral point side.
I1cr , I2 cr are the corrected secondary current of generator terminal side and generator neutral
point side.
To clarify the principle, in an ideal situation, three important operation conditions are considered.
The current directions of two sides are the same with the defined direction. The corrected
secondary current amplitude of two sides are equal.
I1cr = I2 cr
| I1cr + I2 cr |
The differential current: I d =| I1cr − I2 cr |= 0 , the restraint current: I r = =| I 2 cr | .
2
No differential current, restraint current (Ir) is equal to the through-fault current, and current
differential protection will not operate.
2. Internal short-circuit fault, e.g. the fed currents of two sides are equal:
The current direction of generator terminal side is reverse with the defined direction.
I1cr = − I2 cr
| I1cr + I2 cr |
The differential current: I d =| I1cr − I2 cr |= 2 | I2 cr | , the restraint current: I r = = 0.
2
No restraint current, differential current is the total fault current, current differential protection
operates sensitively.
Assuming that the current of generator terminal side is zero. IP1 = 0 , so I1cr = 0
Differential current is two times of restraint current, current differential protection operates
sensitively.
Date: 2016-08-16
3 Operation Theory
I1 + I2
I r =
2
I = I − I
d 1 2
Where:
I 1 , I 2 are the corrected secondary currents of generator terminal side and generator neutral
point side respectively.
I Diff . Pckup is the pickup current setting of generator biased differential element [87G.I_Biased].
K bl1 is the initial slope setting of biased differential element [87G.Slope1], the setting range is
K bl 2 is the maximum slope setting [87G.Slope2] of biased differential element, the setting range
n is the restraint current multiple when the restraint coefficient reach to the maximum value. This
internal value is set as 4 fixedly.
Date: 2016-08-16
3 Operation Theory
Conventional biased differential element with higher pickup current and higher restraint coefficient
comparing with sensitive biased differential element is equipped. Its biased restraint characteristic
can make the differential element not operate due to CT transient and steady-state saturation
during external fault, and it can operate reliably even the CT is seriously saturated during internal
fault. Operation criterion of conventional biased differential element is:
I d > 1.2 × I e
I d > I r Equation 3.2-6
Where:
NOTICE!
The related parameters of conventional biased differential element are set FIXEDLY in
the device. Therefore, the slope and the knee point with constant values do not need to
be set by user.
Where:
If internal slight fault occurs in generator, sensitive and conventional biased differential element
may not response sensitively due to the influence of load current. DPFC (Deviation of Power
Frequency Component) biased differential element of generator is equipped with the device for
that and it can significantly improve the sensitivity of the protection during small current internal
fault of generator. It can be enabled or disabled conveniently by the corresponding logic setting.
Date: 2016-08-16
3 Operation Theory
∆I d = ∆I1 + ∆I2
Where:
∆I dt is the floating threshold varied with the change of differential current. Take its multiple as
1.25 can ensure the threshold value always a bit higher than the unbalance current. So that
unwanted operation of the device can be avoided during power swing or frequency deviation
condition.
∆I1 , ∆I 2 are the DPFC current of generator terminal side and generator neutral point side
respectively.
∆I r is the DPFC restraint current, the maximum value of three-phase DPFC current of two sides
are used as the restraint current.
NOTICE!
If the above criteria are met, CT saturation detection and CT circuit failure detection are also
adopted to control generator DPFC differential element.
For the restraint coefficient of generator DPFC differential element can take a higher value, so it
has high ability to eliminate the effect of transient and steady-state CT saturation during an
external fault. Generator DPFC differential element improves the sensitivity for detecting generator
internal slight fault.
Date: 2016-08-16
3 Operation Theory
Id
Tripping area of
instantaneous diff.
[87G.I_Inst]
Tripping area of
conventional biased diff.
.0
ed of
=1
ff.
K
di
as a
[87G.Slope2]
bi are
ve g
iti in
p
ns i p
se Tr
1.2Ie
[87G.I_Biased]
[87G.Slope1]
0 nIe
1.2Ie Ir
△ Id
m
K=
K=0.75
1.2Ie
K=0.6
[87G.I_Biased]
2Ie
△ Ir
Current differential protection carries out the fault discrimination according to the current of each
phase. If the current criteria are met and no related blocking element(s) operate, differential
protection will operate to trip.
1) Sensitive biased differential element will send tripping signal monitored by CT saturation and
Date: 2016-08-16
3 Operation Theory
CT circuit failure (optional). It can ensure the sensitivity of differential protection and avoid the
unwanted operation when CT is saturated during an external fault. Its operation area is the tint
shadow area in the figure above.
2) Conventional biased differential element will send tripping signal monitored by CT circuit
failure (optional). It eliminates the influence of transient and steady-state saturations of CT
during an external fault and ensures differential protection can operate reliably even if CT is
saturated during an internal fault by means of its biased characteristic. Its operation area is the
deeper shadow area in the figure above.
3) Unrestrained instantaneous differential element will send tripping signal without any blocking
element if differential current of any phase is larger than corresponding current setting.
Unrestrained instantaneous differential element is used to cut off the internal serious fault
quickly. Its operation area is the non-shaded area that located in the top of the figure.
When an generator external fault happens, great through-fault current will flowing through the CT,
if the saturation degree of generator terminal side CT is inconsistent with that of generator neutral
point side CT, great unbalance differential current will generate in the differential circuit, which will
lead to the mal-operation of differential protection. So the CT saturation detection function is
required for generator differential protection.
There is a certain time before the CT falling into saturated state, so the changing characteristic of
differential current and restraint current within the initial time of the fault can be used to judge
whether it is an external fault. For an external fault, the deviation of power frequency component
(DPFC) of restraint current appears before the appearance of DPFC of differential current; for an
internal fault, DPFC of restraint current and differential current appear almost simultaneously. If
external fault is detected, CT saturation blocking criterion is enabled.
Where:
If secondary harmonic of one phase differential current meets the above equation, it will be
considered that it is CT saturation to cause this phase differential current and sensitive biased
Date: 2016-08-16
3 Operation Theory
differential element will be blocked. The criterion is only enabled when the generator is in service.
If the generator differential current of any phase meets the following criteria and corresponding
differential element is enabled, the generator differential current abnormality alarm [87G.Alm_Diff]
with a time delay of 300ms, this alarm signal will not block the differential element. The signal will
reset if the differential current disappears with a time delay of 10s.
If any one of following four conditions is satisfied after the fault detector of biased differential
current picks up, it will be determined as fault and differential protection is released, otherwise it
will be determined that the fault detector of biased differential current picks up due to differential
CT circuit failure or short-circuit.
Any phase current of any side increases after the fault detector picks up.
The maximum phase current is larger than 1.2Ie after the fault detector picks up.
Among all the current channels, any three phases of the current decrease after fault
detector picks up.
If none of above four conditions is satisfied within 40ms after the fault detector of biased
differential current picks up, it will be determined as differential CT circuit failure and CT circuit
failure alarm will be issued. Then if the logic setting [87G.En_CTS_Blk] is set as “1”, sensitive and
conventional biased differential element will be blocked, if the logic setting [87G.En_CTS_Blk] is
set as “0”, sensitive and conventional biased differential element will not be blocked. Generator
unrestrained instantaneous differential element will not be blocked during CT circuit failure.
Generator CT circuit failure alarm and blocking function will quit automatically if the generator is
not connected to the power grid.
The above conditions contain the voltage criteria and current criteria, which realizes the high
accuracy and sensitivity of the CT circuit failure detection.
Date: 2016-08-16
3 Operation Theory
The CT circuit failure alarm is latched once issued, it can be reset only after the failure is cleared
and the device is reset (i.e. the binary input [BI_RstTarg] is energized).
No matter whether the abnormality alarm signal makes the differential protection picks up, there
must be some problems in the differential circuit. For example, when the differential circuit fails,
the differential protection will not pick up for light-loaded condition, but the differential current
abnormality alarm signal will be issued. If the abnormality is treated in time, the mal-operation of
differential protection due to increase of load or external fault can be avoided (if the logic setting
[87G.En_CTS_Blk] is set as “0”).
Once the differential CT circuit failure alarm is issued, the CT circuit should be check carefully, only
if the fault is cleared, the reset operation can be conducted.
3.2.4 Logic
For generator current differential protection, if following three conditions are met, the protection will
be enabled.
(2) The protection function enabling inputs [87G.En1], [87G.En2] are “1”
If generator differential protection is disabled, all the related output signals will be reset. If no
external input is configured to [87G.En1] ([87G.En2]), the default initial value of [87G.En1]
([87G.En2]) is “1”; if no external input is configured to [87G.Blk], the default initial value of [87G.Blk]
is “0”.
En 87G.En_Biased & ≥1
SIG Idmax>[87G.I_Biased]
En 87G.En_DPFC &
SIG ΔId>1.25ΔIdt+Idth
Where:
Date: 2016-08-16
3 Operation Theory
EN [87G.En_Inst]
SIG [87G.En1] &
&
SIG [87G.En2]
[87G.Op_Inst]
SIG [87G.Blk]
SIG Idmax>[87G.I_Inst]
0ms 500ms
SIG 87G.FD_Inst
EN [87G.En_Biased]
SIG [87G.En1] &
SIG Flg_ConvBiasDiff
SET [87G.En_CTS_Blk] ≥1
[87G.Op_Biased]
0ms 500ms
SIG 87G.FD_Biased
EN [87G.En_Biased]
SIG [87G.En1] &
SIG [87G.En2]
SIG [87G.Blk]
&
SIG Flg_SensBiasDiff
SET [87G.En_CTS_Blk]
Where:
Flg_ConvBiasDiff is the internal flag indicating that the operation criteria of conventional biased
differential element are satisfied.
Flg_SensBiasDiff is the internal flag indicating that operation criteria of sensitive biased differential
element are satisfied.
Flg_CTS is the internal flag indicating that differential CT circuit failure is detected.
87G.FD_Inst is the signal indicating that the fault detector of unrestrained instantaneous
differential element picks up (the fault detector of fault detector DSP module).
Date: 2016-08-16
3 Operation Theory
87G.FD_Biased is the signal indicating that the fault detector of steady-state biased differential
element picks up (the fault detector of fault detector DSP module).
EN [87G.En_DPFC]
SIG [87G.En1] &
SIG [87G.En2]
SIG [87G.Blk]
&
SIG Flg_DPFC_Diff [87G.Op_DPFC]
SET [87G.En_CTS_Blk]
Where:
Flg_DPFC_Diff is the internal flag indicating that the operation criteria of DPFC differential element
are satisfied.
Flg_CTS is the internal flag indicating that differential CT circuit failure is detected.
87G.FD_DPFC is the signal indicating that the fault detector of DPFC differential element picks up
(the fault detector of fault detector DSP module).
87G
87G.I3P1 87G.St
87G.I3P2 87G.Op_Biased
87G.En1 87G.Op_Inst
87G.En2 87G.Op_DPFC
87G.Blk 87G.Alm_Diff
87G.Alm_CTS
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.2-3 Output signals of generator current differential protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
87G.Ida
Three-phase differential current amplitude for generator
1 87G.Idb pu
current differential protection.
87G.Idc
Date: 2016-08-16
3 Operation Theory
87G.Ira
Three-phase restraint current amplitude for generator
2 87G.Irb pu
current differential protection.
87G.Irc
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Diff Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Diff Values
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Gen PhaseAngleValues
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Sec Rated Curr Values
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Diff Corr Coef Values
87G.Ida
Three-phase differential current amplitude for generator
8 87G.Idb pu
current differential protection.
87G.Idc
87G.Ida_HalfCycle
Three-phase differential current half-cycle integral amplitude
9 87G.Idb_HalfCycle pu
of generator current differential protection.
87G.Idc_HalfCycle
87G.Ira
Three-phase restraint current amplitude for generator
10 87G.Irb pu
current differential protection.
87G.Irc
87G.Ia_Cr_Br1
Three-phase corrected current of generator terminal side
11 87G.Ib_Cr_Br1 pu
that used for generator differential protection.
87G.Ic_Cr_Br1
87G.Ia_Cr_Br2
Three-phase corrected current of generator neutral point
12 87G.Ib_Cr_Br2 pu
side that used for generator differential protection.
87G.Ic_Cr_Br2
Date: 2016-08-16
3 Operation Theory
87G.Ia_Th_Biased_L
Three-phase current threshold for generator sensitive
13 87G.Ib_Th_Biased_L pu
biased current differential element.
87G.Ic_Th_Biased_L
87G.Ia_Th_Biased_H
Three-phase current threshold for generator conventional
14 87G.Ib_Th_Biased_H pu
biased current differential element.
87G.Ic_Th_Biased_H
87G.Ida_Hm2
Second harmonic amplitude of three-phase differential
15 87G.Idb_Hm2 pu
current for generator current differential protection.
87G.Idc_Hm2
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen Diff Prot Values
3.2.6 Settings
Table 3.2-5 Settings list of generator current differential protection
Date: 2016-08-16
3 Operation Theory
[87G.OutMap]
The tripping logic setting is used to specify which breaker(s) will be tripped when corresponding
protection element operates. This logic setting comprises 32 binary bits as follows and is
expressed by a hexadecimal number of 8 digits from 0H to 3FFFFFFFH. The tripping logic setting
of the device is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
TrpOutput15
TrpOutput14
TrpOutput13
TrpOutput12
TrpOutput11
TrpOutput10
TrpOutput09
TrpOutput08
TrpOutput07
TrpOutput05
TrpOutput04
TrpOutput03
TrpOutput02
TrpOutput01
TrpOutput06
Enable trip
Function
matrix
bit 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
TrpOutput016
TrpOutput29
TrpOutput28
TrpOutput27
TrpOutput26
TrpOutput25
TrpOutput24
TrpOutput23
TrpOutput22
TrpOutput20
TrpOutput19
TrpOutput18
TrpOutput17
TrpOutput21
Function
Spare
Spare
“TrpOutput01” just means to drive tripping output channel 1. Set bit0 as “1” means this protection
element can operate to trip breaker(s). The bit corresponding to the breaker to be tripped shall be
set as “1” and other bits shall be “0”. For example, if generator differential protection is defined to
trip breaker 3 (tripping output channel 3) and breaker 5 (tripping output channel 5), the bit0, bit3
and bit5 shall be set as “1” and other bits shall be set as “0”. Then a hexadecimal number
00000029H is formed as the tripping output logic setting of generator differential protection.
Please note that tripping output logic settings of the equipment have to be set on basis of
application-specific drawings.
All the tripping logic settings mentioned below should be defined with the same method.
(87NTG)
3.3.1 Application
When generator winding of one phase has several parallel branches, all the branches can be
divided into two or several groups (the parallel branch number of each group is the same), the
branch groups corresponds to three-phase winding will be connected to form one neutral point,
two or several neutral points can be connected to form the final neutral point. In theory, if no
internal fault happens at generator stator winding, the fundamental potential of two neutral points
are the same, the fundamental current of the connection line between the two neutral points is
zero. If an internal short-circuit fault happens or the welding between branches has open, there will
be a fundamental potential difference between the two neutral points, then a larger fundamental
current will be generated.
Date: 2016-08-16
3 Operation Theory
One CT can be equipped at the connection line between the two neutral points to constitute
neutral point transverse differential protection. The protection is the main protection for generator
stator winding internal (phase-to-phase, different branches of the same phase and inter-turn of the
same branch) short-circuit fault and branches welding open fault. Neutral point transverse
differential protection can operate quickly to clear the internal fault to avoid the generator from
damages or reduce the maintenance cost as low as possible.
One CT is equipped at the connection line between the two neutral points, the device measure the
fundamental component of the current, there will be a slight unbalance current during operation.
Generator
CT Ip
Neutral * Generator
point * CT1 terminal
Ipo
Io I1
PCS-985GE
Filtering
Figure 3.3-1 Current calculation process of neutral point transverse differential protection
Where:
IP is the primary value of generator terminal three-phase current and I1 is the corresponding
secondary value;
IPo is the primary value of the connection line current between the two neutral points and IO is
the corresponding secondary value;
Date: 2016-08-16
3 Operation Theory
The current setting of sensitive neutral point transverse differential element only should be larger
than the unbalance current during normal operation.
In order to prevent sensitive neutral point transverse differential element from mal-operation due to
generator rotor two-point ground fault, sensitive neutral point transverse differential element can
be switching to a settable time delay pick-up protection after the operation of generator rotor
one-point ground fault element.
When an internal slight fault happens to the generator stator winding, the phase current of
generator terminal does not change almost; but when an external short-circuit fault happens, the
phase current of generator terminal will increased significantly. So the phase current of generator
terminal is adopted as the restraint current, it can improve the sensitivity of sensitive neutral point
transverse differential element on the premise of making sure the reliability. Sensitive neutral point
transverse differential element mainly reflects the internal short-circuit fault for a small number of
turns or branches welding open fault.
The operation equation of sensitive neutral point transverse differential element is:
I d ≥ I Sens ( I max ≤ I e )
K hczd (I max − I e ) Equation 3.3-1
I d > 1 + I Sens ( I max > I e )
I e
Where:
I Sens is the current setting of sensitive neutral point transverse differential element;
Insensitive neutral point transverse differential element without any blocking element can reflect
generator internal serious fault, once the transverse differential current is larger than the current
setting of high setting neutral point transverse differential element, the protection will operate
immediately to cut off the fault.
The operation equation of sensitive neutral point transverse differential element is:
I d > I Insense
Equation 3.3-2
Where:
Date: 2016-08-16
3 Operation Theory
I Insens is the current setting of insensitive neutral point transverse differential element.
3.3.4 Logic
For generator neutral point transverse differential protection, if following three conditions are met,
the protection will be enabled.
If generator neutral point transverse differential protection is disabled, all the related output signals
will be reset. If no external input is configured to [87NTG.En1] ([87NTG.En2]), the default initial
value of [87NTG.En1] ([87NTG.En2]) is “1”; if no external input is configured to [87NTG.Blk], the
default initial value of [87NTG.Blk] is “0”.
&
En 87NTG.En_L ≥1
En 87NTG.En_H
EN [87NTG.En]
&
SIG [87NTG.En1]
SIG [87NTG.En2]
SIG [87NTG.Blk]
&
EN [87NTG.En_L] &
SIG Flg_I_L
>
& [87NTG.t_Op_L] 0s &
[87NTG.Op_L]
SIG [BI_1PEF_Rot]
0ms 500ms
SIG 87NTG.FD_L
EN [87NTG.En]
&
SIG [87NTG.En1]
SIG [87NTG.En2]
SIG [87NTG.Blk]
&
EN [87NTG.En_H] &
0ms 500ms
SIG 87NTG.FD_H
Figure 3.3-2 Logic diagram of generator neutral point transverse differential protection
Where:
Date: 2016-08-16
3 Operation Theory
Flg_I_L is the internal signal indicating that the operation equation of sensitive neutral point
transverse differential element is met;
87NTG.FD_L is the internal signal indicating that the sensitive neutral point transverse differential
element picks up (the fault detector of fault detector DSP module);
Flg_I_H is the internal signal indicating that the operation equation of insensitive neutral point
transverse differential element is met;
87NTG.FD_H is the internal signal indicating that the insensitive neutral point transverse
differential element picks up (the fault detector of fault detector DSP module).
87NTG
87NTG.I1P_Hm 87NTG.St
87NTG.U3P 87NTG.Op_L
87NTG.I3P 87NTG.Op_H
87NTG.En1
87NTG.En2
87NTG.Blk
BI_1PEF_Rot
Figure 3.3-3 Function block diagram of generator neutral point transverse differential protection
Table 3.3-1 Input signals of generator neutral point transverse differential protection
Table 3.3-2 Output signals of generator neutral point transverse differential protection
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Date: 2016-08-16
3 Operation Theory
Table 3.3-3 Output signals of generator neutral point transverse differential protection (event recorder)
Tripping reports
1 87NTG.Op_L The sensitive neutral point transverse differential element operates to trip.
2 87NTG.Op_H The insensitive neutral point transverse differential element operates to trip.
Start signals
Waveform recording
Table 3.3-4 Output signals of generator neutral point transverse differential protection (measurements)
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Diff Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Diff Values
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen IntTurn Prot Values
3.3.6 Settings
Table 3.3-5 Settings list of generator neutral point transverse differential protection
Date: 2016-08-16
3 Operation Theory
3.4.1 Application
Generator inter-turn protection is used to detect the inter-turn fault of generator stator winding. If
an inter-turn fault happens at generator stator winding, relatively large circulating current flows
among the short-circuit turns, so the generator stator winding and iron core will be damaged.
Conventional generator differential protection can not detect the inter-turn fault of generator stator
winding, so a dedicated inter-turn protection should be configured.
After filtering, if the broken-delta zero-sequence voltage of the dedicated VT is larger than the
voltage setting of longitudinal zero-sequence voltage inter-turn element, longitudinal
zero-sequence voltage inter-turn element will operate. Negative-sequence DPFC direction
inter-turn element adopts generator terminal voltage and current directly, so dedicated VT is not
needed for it. If the negative-sequence voltage variation, the negative-sequence current variation
and the negative-sequence power direction conditions are all met, Negative-sequence DPFC
direction inter-turn element will operate.
During normal operation, there will be a relatively large third harmonic zero- sequence voltage on
the broken-delta of the dedicated VT, it will affect the sensitivity of the protection. PCS-985 adopts
frequency tracking, digital filtering and full cycle Fourier algorithm, so the filtered ratio of the
zero-sequence voltage relative to the 3rd harmonic is larger than 100, and the protection only
reflects the fundamental component.
Date: 2016-08-16
3 Operation Theory
The voltage setting of longitudinal zero-sequence voltage inter-turn element only should be larger
than the maximum unbalance voltage during normal operation, so it can improve the sensitivity of
the element.
For the increase of longitudinal unbalance zero-sequence voltage for other normal operation
conditions, a floating threshold is adopted for longitudinal zero-sequence voltage inter-turn
element.
Generator longitudinal zero-sequence voltage inter-turn element will operate with a short time
delay (0.10s~0.20s).
Longitudinal zero-sequence voltage inter-turn element should be blocked when VT2 (i.e.
generator terminal dedicated VT) primary circuit failure happens.
(1) If there have two groups of three-phase voltage transformers, the voltage balance function is
in service. The operation criterion is as below.
Criterion 1:
Criterion 2:
Date: 2016-08-16
3 Operation Theory
Where:
When any of criterion 1 and criterion 2 operates, VT2 primary circuit failure alarm will be issued
with a time delay of 40ms and longitudinal zero-sequence voltage inter-turn element will be
blocked.
(2) If there only has one group of three-phase voltage transformer, the voltage balance function is
not in service. The operation criterion is as below.
Criterion:
When the criterion operates, VT2 primary circuit failure alarm will be issued with a time delay of
40ms and longitudinal zero-sequence voltage inter-turn element will be blocked.
After VT2 circuit restores to normal condition, the blocking for zero-sequence voltage inter-turn
element can be released by pressing the reset button.
∧
ΔF= Re ΔU 2 × Δ I 2 × e jΦ > ε + 1.25 × dF
Equation 3.4-1
∆U 2 > 0.5V + 1.25du
If the above three criterions are met simultaneity, the direction condition is met. Be broadened by
negative-sequence voltage and negative-sequence current, the negative-sequence DPFC
direction inter-turn element operates with a time delay of 0.2~0.5s.
Negative-sequence DPFC direction inter-turn element adopts generator terminal voltage and
current directly, so dedicated VT is not needed for it. If generator terminal VT1 circuit failure
happens, negative-sequence DPFC direction inter-turn element will be blocked. All the settings for
negative-sequence DPFC direction inter-turn element have been set in the device, users need not
to set them.
Date: 2016-08-16
3 Operation Theory
Negative-sequence DPFC direction inter-turn element can not reflect the inter-turn fault before the
generator is connected into the power system.
3.4.4 Logic
For generator inter-turn protection, if following three conditions are met, the protection will be
enabled.
If generator inter-turn protection is disabled, all the related output signals will be reset. If no
external input is configured to [59NIT.En1] ([59NIT.En2]), the default initial value of [59NIT.En1]
([59NIT.En2]) is “1”; if no external input is configured to [59NIT.Blk], the default initial value of
[59NIT.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
En [59NIT.En_P2_DPFC] ≥1
&
SIG 59NIT.Dir_P2_DPFC
EN [59NIT.OutMap].bit0
EN [59NIT.En]
SIG [59NIT.En1] &
EN [59NIT.En_ROV_Longl]
SIG 59NIT.Dir_P2_DPFC
SIG G_Term.VT2.VTS_Pri.Blk]
0ms 500ms
SIG 59NIT.FD_ROV_Longl
EN [59NIT.OutMap].bit0
EN [59NIT.En]
SIG [59NIT.En1] &
SIG [59NIT.En2] &
[59NIT.t_Op] 0ms [59NIT.Op_P2_DPFC]
SIG [59NIT.Blk]
EN [59NIT.En_P2_DPFC]
SIG G_Term.VT1.Alm_VTS]
0ms 500ms
SIG 59NIT.FD_P2_DPFC
EN [59NIT.OutMap].bit0 &
EN [59NIT.En] &
[59NIT.t_Op] 0ms
SIG [59NIT.Blk] [59NIT.Alm_P2_DPFC]
EN [59NIT.En_P2_DPFC]
SIG G_Term.VT1.Alm_VTS]
Where:
Flg_ROV_Longl is the internal signal indicating that the zero-sequence voltage condition for
longitudinal zero-sequence voltage inter-turn element is met.
59NIT.Dir_P2_DPFC is the internal signal indicating that the negative-sequence power direction
condition is met.
59NIT.FD_ROV_Longl is the internal signal indicating that the longitudinal zero-sequence voltage
inter-turn element picks up (the fault detector of fault detector DSP module).
59NIT.FD_P2_DPFC is the internal signal indicating that the negative-sequence DPFC direction
Date: 2016-08-16
3 Operation Theory
inter-turn element picks up (the fault detector of fault detector DSP module).
59NIT
59NIT.U1P_Hm 59NIT.St
59NIT.U3P 59NIT.Op_ROV_Longl
59NIT.I3P 59NIT.Op_P2_DPFC
59NIT.En1 59NIT.Alm_P2_DPFC
59NIT.En2
59NIT.Blk
G_Term.VT2.VTS_Pri.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Date: 2016-08-16
3 Operation Theory
Alarm signals
Waveform recording
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen IntTurn Prot Values
3.4.6 Settings
Table 3.4-5 Settings list of generator inter-turn protection
Date: 2016-08-16
3 Operation Theory
3.5.1 Application
Generator stator overload protection is equipped to reflect the average heating condition of
generator stator winding.
The temperature change of generator stator winding is mainly caused by copper loss. The copper
loss is proportional to the square of current, so there is a certain proportional relationship between
the temperature change of generator stator winding and the square of current. Via checking the
change of generator stator current can reflect the temperature change of stator winding indirectly.
For a given temperature increase (Δθ), the corresponding expression between permissive time (t)
and current can be got:
A
t=
(I )
∗ 2
−1
Equation 3.5-1
Where:
I ∗ is the per-unit value of stator current (the rated stator current is taken as the referenced value).
Generally the overload multiple and the corresponding duration of the generator is provided. For
example, a directly cooled turbo-generator, the permissive duration is 60s corresponds to 1.3
times of rated current, the heat capacity of the generator stator winding A can be calculated
according to Equation 3.5-1, then the permissive duration corresponds to a given current can be
calculated.
Date: 2016-08-16
3 Operation Theory
There are two stages of stator definite-time overload protection. The low-setting stage of
definite-time overload protection is used for alarm, and the settings should be set to make the
protection can drop off reliably for long-term permissive load current. The high-setting stage of
definite-time overload protection is used for tripping, and the settings should be set according to
the permissive time for more serious overload condition.
Inverse-time stator overload protection consists of three parts: lower-limit initiation part,
inverse-time part and upper limit definite-time part. Minimum operation time delay setting
[49S.IDMT.tmin] is provided for upper limit definite-time part.
When the stator current is over the low setting [49S.IDMT.I_Set], the heat accumulation starts.
When the heat accumulation reaches its setting [49S.IDMT.A_Therm], inverse-time stator
overload protection can operate to trip. The inverse time protection can simulate the heat
accumulation and dissipation process of the generator. If the stator current is larger than the low
setting [49S.IDMT.I_Set], the heat accumulation starts; if the stator current is lower than the low
setting [49S.IDMT.I_Set], the heat dissipation starts.
I
IU pper−limit
I P ickup
t min tmax t
Figure 3.5-1 Operation characteristic of inverse-time stator overload protection
Where:
t min is the minimum time delay for upper limit definite-time part, i.e. the setting [49S.IDMT.tmin].
I Pickup is the pickup current setting of inverse-time stator overload protection, i.e. the setting
[49S.IDMT.I_Set]
Date: 2016-08-16
3 Operation Theory
I Upper −lim it is the current that corresponds to the minimum time delay for upper limit definite-time
part.
[( I I b) − (k Disspt ) ] × t ≥ ATherm
2 2
Equation 3.5-2
Where:
k Disspt is the heat dissipation coefficient of the generator, i.e. the setting [49S.IDMT.K_Disspt]. In
order to make sure that the heat accumulation can be dissipated after an external fault, the heat
dissipation coefficient of the generator is recommended to be set as “1.02~1.05”.
ATherm is the heat capacity of generator stator winding, i.e. the setting [49S.IDMT.A_Therm].
3.5.4 Logic
For each stage of generator stator overload protection, if following three conditions are met, the
protection will be enabled.
If generator stator overload protection is disabled, all the related output signals will be reset. If no
external input is configured to [49S.En1] ([49S.En2]), the default initial value of [49S.En1]
([49S.En2]) is “1”; if no external input is configured to [49S.Blk], the default initial value of [49S.Blk]
is “0”.
Date: 2016-08-16
3 Operation Theory
En [49S.IDMT.OutMap].bit0 ≥1
&
SIG I>[49S.IDMT.I_Set]
EN [49S.En]
SIG [49S.En1] &
& [49S.DT.t_Op] 0ms
SIG [49S.En2] [49S.DT.Op]
SIG [49S.Blk]
SIG I>[49S.DT.I_Set]
0ms 500ms
SIG 49S.DT.FD
EN [49S.En]
SIG [49S.En1] &
SIG [49S.En2] &
IDMT
[49S.IDMT.Op]
SIG [49S.Blk]
SIG I>[49S.IDMT.I_Set]
0ms 500ms
SIG 49S.IDMT.FD
Where:
49S.DT.FD is the internal signal indicating that the stator definite-time overload protection picks up
(the fault detector of fault detector DSP module).
49S.IDMT.FD is the internal signal indicating that the stator inverse-time overload protection picks
up (the fault detector of fault detector DSP module).
49S
49S.I3P1 49S.St
49S.I3P2 49S.DT.Op
49S.En1 49S.IDMT.Op
49S.En2 49S.Alm
49S.Blk
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.5-3 Output signals of generator stator overload protection (event recorder)
Tripping reports
Start signals
Alarm signals
4 49S.Alm The alarm stage of stator overload protection operates to issue alarm signal
Waveform recording
5 49S.TrigDFR Tripping stage of stator overload protection operates to trigger waveform recording.
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
Date: 2016-08-16
3 Operation Theory
3.5.6 Settings
Table 3.5-5 Settings list of generator stator overload protection
Protection (64S1)
3.6.1 Application
Generator stator ground fault protection is used to detect the ground fault of generator stator
winding, it can be realized by detecting the displacement voltage of secondary side of neutral point
Date: 2016-08-16
3 Operation Theory
Fundamental zero-sequence voltage stator ground fault protection can detect the ground fault of
85%~95% of stator winding of generator terminal side.
Fundamental zero-sequence current stator ground fault protection can detect the ground fault of
85%~95% of stator winding of generator terminal side.
Generator fundamental zero-sequence voltage stator ground fault protection includes two
operation elements: sensitive fundamental zero-sequence voltage stator ground fault element and
conventional fundamental zero-sequence voltage stator ground fault element.
Generator fundamental zero-sequence current stator ground fault protection includes one
operation element: fundamental zero-sequence current stator ground fault element.
The calculation process of fundamental zero-sequence voltage stator ground fault protection is
shown in following figure. The generator neutral point is grounded via grounding transformer, it
can also be grounded via grounding VT. For the secondary side rated voltage of neutral point
grounding transformer is usually higher, so the tap voltage (generally it is 100V or 173V) of the
secondary winding load resistance is connected to the device. The generator system parameter
[G_NP.U1n] should be set according to the primary side voltage of the grounding transformer, and
[G_NP.U2n_Delt] should be set according to the actual tap voltage.
Date: 2016-08-16
3 Operation Theory
Generator CM
CT2
*
CT1
RB Main
CG Cl CTr transformer
Filtering
PCS-985
Figure 3.6-1 Calculation process of fundamental zero-sequence stator ground fault protection
Where:
UN0 is the tap voltage (it is 100V or 173V generally) of secondary load resistance of neutral point
grounding transformer;
CT1 is the current transformer of neutral point of generator and for zero sequence current ground
fault protection;
CT2 is the current transformer of generator terminal for zero sequence directional element;
CM is the coupling capacitance between the HV winding and LV winding of main transformer.
When a stator ground fault happens, the displacement voltage of neutral point and generator
terminal contains a relatively large 3rd harmonic voltage, which will affect the sensitivity of the
protection. The device adopts frequency tracking, digital filtering and full cycle Fourier algorithm,
so the filtered ratio of the zero-sequence voltage relative to the 3rd harmonic is larger than 100, and
the protection only reflects the fundamental component.
The zero sequence voltage can be selected from the generator terminal or one side of the neutral
point through the setting [64S1.Opt_Source_3U0]. If the setting [64S1.Opt_Source_3U0] is set as
Date: 2016-08-16
3 Operation Theory
“Source1”, the No.1 zero sequence voltage input is from the generator terminal or the neutral point,
and the No.2 zero sequence voltage input is not used. If the setting [64S1.Opt_Source_3U0] is set
as “BothSources”, the No.1 zero sequence voltage input is from the neutral point, and the No.2
zero sequence voltage input is from the generator terminal. It can be configured through
PCS-Explorer2.
If sensitive stage of fundamental zero-sequence voltage stator ground fault protection operates to
issue alarm signal, the operation criterion is:
Where:
U 0Set_Sen is voltage setting of sensitive stage of fundamental zero-sequence voltage stator ground
fault protection.
If the sensitive stage operates to trip, in order to prevent the sensitive stage of fundamental
zero-sequence voltage stator ground fault protection from undesired tripping due to external fault,
it can be blocked by main transformer HV side zero-sequence voltage, and the zero-sequence
voltage blocking setting [64S1.3U0_Tr_Blk] is settable. If the No.2 zero sequence voltage input is
not used and the setting [64S1.3U0_Tr_Blk] is set as non-zero value, this function is in service
automatically.
If the setting [64S1.Opt_Source_3U0] is set as “BothSources” and the sensitive stage operates to
trip, it will be blocked by broken-delta zero-sequence voltage of generator terminal, the
zero-sequence voltage blocking setting need not to be set, it can be converted automatically by
the device according to the VT ratio of generator terminal and neutral point. The calculation result
of the ratio of VT of generator terminal and neutral point is described as generator zero-sequence
voltage correlation coefficient [K_Delt&NP_VT_Gen].
Generator terminal zero-sequence voltage can adopts broken-delta zero-sequence voltage of VT1
or calculated zero-sequence voltage of VT1.
Insensitive stage of fundamental zero-sequence voltage stator ground fault protection only take
the zero sequence voltage of No.1 zero sequence voltage input as the operation quantity, the
operation criterion is:
Where:
Date: 2016-08-16
3 Operation Theory
If a single-phase ground fault of the stator of generator is occurred, and the zero sequence current
of ground fault can be detected, the zero sequence voltage stator ground fault protection can be
blocked by the zero sequence.
The zero sequence directional element is calculated through the zero sequence current and the
zero sequence voltage of generator terminal.
The 3U0 should be greater than 2V and the 3I0 should be greater than the setting
[64S1.3I0_Th_Dir].
3I0
phi_Reach
3U0
Fundamental zero-sequence current stator ground fault protection can detect the ground fault of
85%~95% of stator winding of generator terminal side.
Date: 2016-08-16
3 Operation Theory
Where:
3I0_Set is current setting of fundamental zero-sequence current stator ground fault protection.
For fundamental zero-sequence voltage stator ground fault protection adopts the generator neutral
point zero-sequence voltage and generator terminal broken-delta zero-sequence voltage, VT
circuit failure of corresponding VT will lead to miss-operation of the protection. So alarm signal
should be issued if generator neutral point VT or generator terminal broken-delta VT circuit fails.
The operation criteria for generator neutral point VT circuit failure are:
2) 3rd harmonic zero-sequence voltage of generator neutral point VT is less than 0.1V
The operation criteria for generator terminal broken-delta VT circuit failure are:
2) 3rd harmonic zero-sequence voltage of generator terminal broken-delta VT is less than 0.1V
If the operation criteria are met, the corresponding VT circuit failure alarm signal will be issued with
a time delay of 10s, and the signal can be reset automatically with a time delay of 10s if the
abnormality disappears.
If generator terminal zero-sequence voltage is derived from the calculated zero-sequence voltage,
the device will not detect generator terminal VT1 broken-delta circuit failure.
Generator neutral point VT or generator terminal broken-delta VT circuit failure alarm function can
be enabled or disabled by respective logic setting.
3.6.3.6 VT Circuit Failure at Generator Terminal Blocking Zero Sequence Voltage Protection
of Stator
If the setting [64S1.Opt_Source_3U0] is set as “Source1” and the zero sequence voltage is from
the zero sequence voltage of the generator terminal, the VT circuit failure of the generator terminal
maybe cause the mal-operation of the zero sequence voltage protection of stator. So, it is
necessary to block the zero sequence voltage protection of stator when the VT circuit failure of
generator terminal is occurred.
Criterion:
If above two conditions are satisfied, the VT1 circuit failure alarm signal is issued with a short time
delay, and the sensitive and insensitive stages of fundamental zero sequence voltage protection
will be blocked.
Date: 2016-08-16
3 Operation Theory
3.6.4 Logic
For fundamental zero-sequence voltage stator ground fault protection, if following three conditions
are met, the protection will be enabled.
If fundamental zero-sequence voltage stator ground fault protection is disabled, all the related
output signals will be reset. If no external input is configured to [64S1.En1] ([64S1.En2]), the
default initial value of [64S1.En1] ([64S1.En2]) is “1”; if no external input is configured to [64S1.Blk],
the default initial value of [64S1.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
En &
[64S1.En_Trp_ROV_L] ≥1
≥1
En [64S1.En_Trp_ROV_H]
En [64S1.En_Trp_ROC]
Flg_ROV
EN [64S1.En] &
SIG 3U0>[64S1.3U0_L]
&
SIG [64S1.Blk] [64S1.t_ROV_L] 0ms [64S1.Alm_ROV_L]
EN [64S1.En_Alm_ROV_L]
EN [64S1.En
SIG [64S1.En1] &
SIG [64S1.En2]
SIG [64S1.Blk]
EN [64S1.Opt_Source_3U0]
SIG Flg_Dir ≥1
EN [64S1.Dir_Ctrl_ROV_L]
SIG 3I0>[64S1.3I0_Set] ≥1
EN [64S1.ROC_Ctrl_ROV_L]
SIG 3Uh0>[64S1.3U0_Tr_Blk]
EN [64S1.En
SIG [64S1.En1] &
SIG [64S1.En2]
SIG [64S1.Blk]
EN [64S1.Dir_Ctrl_ROV_H]
SIG 3I0>[64S1.3I0_Set] ≥1
EN [64S1.ROC_Ctrl_ROV_H]
0ms 500ms
SIG 64S1.FD
Date: 2016-08-16
3 Operation Theory
Flg_ROC
EN [64S1.En] &
SIG 3I0>[64S1.3I0_Set]
&
SIG [64S1.Blk] [64S1.t_ROC] 0ms [64S1.Alm_ROC]
EN [64S1.En_Alm_ROC]
EN [64S1.En
SIG [64S1.En1] &
SIG [64S1.En2]
SIG [64S1.Blk]
0ms 500ms
SIG 64S1.FD
Figure 3.6-3 Logic diagram of generator fundamental zero-sequence stator ground fault protection
Where:
Flg_ROV is the internal signal indicating that the operation criterion of sensitive stage of
fundamental zero-sequence voltage stator ground fault protection is met, i.e. Equation 3.6-1 is
met.
Flg_ROV_Term is the internal signal indicating that the generator terminal broken-delta residual
voltage criterion is met.
Flg_Dir is the internal signal indicating that the zero sequence directional element is met.
Flg_ROC is the internal signal indicating that the zero sequence current stator ground fault
protection is met.
64S1.FD is the internal signal indicating that the fundamental zero-sequence voltage stator ground
fault protection picks up (the fault detector of fault detector DSP module).
3U0 is the residual voltage of the neutral point of the No.1 zero sequence voltage input.
64S1
64S1.U1P1_Hm 64S1.St
64S1.U1P2_Hm 64S1.Op_ROV_L
64S1.U1P3_Hm 64S1.Op_ROV_H
64S1.Alm_ROV_L
I1P_Hm
64S1.Alm_ROC
64S1.En1
64S1.Op_ROC
64S1.En2
64S1.Blk
G_Term.VT1.VTS_Pri.Blk
Figure 3.6-4 Function block diagram of generator fundamental zero-sequence stator ground fault
Date: 2016-08-16
3 Operation Theory
protection
Table 3.6-1 Input signals of generator fundamental zero-sequence stator ground fault protection
Table 3.6-2 Output signals of generator fundamental zero-sequence voltage stator ground fault protection
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.6-3 Output signals of generator fundamental zero-sequence voltage stator ground fault protection
(event recorder)
Tripping reports
Date: 2016-08-16
3 Operation Theory
Start signals
Alarm signals
Waveform recording
Table 3.6-4 Output signals of generator fundamental zero-sequence voltage stator ground fault protection
(measurements)
The phase angle between the zero sequence current and the
6 Ang(3I0-3U0_Hm1) deg
zero sequence voltage of generator
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen StaEF Prot Values
Date: 2016-08-16
3 Operation Theory
3.6.6 Settings
Table 3.6-5 Settings list of generator fundamental zero-sequence voltage stator ground fault protection
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.7.1 Application
Fundamental zero-sequence voltage stator ground fault protection can only detect the ground fault
of 85%~95% of stator winding of generator terminal side, for the ground fault that near the
generator neutral point, it can be detected by 3rd harmonic stator ground fault protection.
3rd harmonic differential stator ground fault element: theoretically it can detect the ground fault
of the whole stator winding.
Generator 3rd harmonic stator ground fault protection includes two operation elements: 3rd
harmonic ratio stator ground fault element and 3rd harmonic differential stator ground fault element.
Fundamental zero sequence voltage stator ground fault protection coordinate with 3rd harmonic
ratio stator ground fault element can constitute 100% stator ground fault protection. 3rd harmonic
differential stator ground fault element can reflect the ground fault of the whole stator winding, but
it is very sensitive, so generally it is only for alarm.
The calculation process of 3rd harmonic stator ground fault protection is shown in following figure.
The generator neutral point is grounded via grounding transformer, it can also be grounded via
grounding VT. When a ground fault happens at generator stator winding, the distribution of the
circuit ground capacitance will change, by detecting the 3rd harmonic zero sequence voltage of
generator terminal and neutral point, the device can judge whether a stator ground fault happens.
Date: 2016-08-16
3 Operation Theory
Generator CM
RB
Main transformer
CG Cl CTr
UN0 UT0
Filtering
PCS-985
Figure 3.7-1 Calculation process of generator 3rd harmonic stator ground fault protection
Where:
UN0 is the tap voltage (it is 100V or 173V generally) of secondary load resistance of neutral point
grounding transformer;
CM is the coupling capacitance between the HV winding and LV winding of main transformer.
3rd harmonic ratio stator ground fault element can only detect the ground fault of approximately
25% of stator winding of generator neutral point side, generator terminal 3rd harmonic voltage is
derived from generator terminal broken-delta zero-sequence voltage or calculated zero-sequence
voltage of VT1, generator neutral point side 3rd harmonic voltage is derived from generator neutral
point VT or the tap voltage of load resistance of grounding transformer.
The operation criterion of 3rd harmonic ratio stator ground fault element is:
U 3T
> K 3 wzd Equation 3.7-1
U 3N
Where:
Date: 2016-08-16
3 Operation Theory
U 3T and U 3 N are 3rd harmonic voltage value of generator terminal and neutral point
respectively;
K 3 wzd is the ratio setting of 3rd harmonic ratio stator ground fault element.
Generator terminal equivalent capacitance has a greater change before and after the unit is
connected with the power grid, so the 3rd harmonic voltage ratio will change with it. So two different
ratio settings are configured for the 3rd harmonic ratio stator ground fault element respectively for
the conditions before and after the unit is connected with the power grid, the two settings are
switched over automatically with the position contact change of generator terminal circuit breaker.
For 3rd harmonic voltage has a close relationship with the generator operating conditions, so 3rd
harmonic ratio stator ground fault element is only enabled when the generator positive-sequence
voltages are respectively larger than a certain threshold value. If the generator frequency shifts
near the power frequency, the ratio setting will add a frequency additional restraint threshold. If the
generator frequency seriously deviates from the power frequency, 3rd harmonic ratio stator ground
fault element will quit automatically.
3rd harmonic ratio stator ground fault element can operate to trip or alarm.
The operation criterion of 3rd harmonic differential stator ground fault element is:
Where:
U 3T and U 3 N are 3rd harmonic voltage vector of generator terminal and neutral point
respectively;
kt is the automatic tracking adjustment coefficient vector, it equals to the ratio between U 3T and
U 3 N during normal operation. If the automatic tracking adjustment coefficient is larger than the
maximum permissive adjustment multiple (i.e. the configuration setting
[64S2.Kmax_U_Hm3_Diff]), 3rd harmonic differential stator ground fault element will quit.
K re is the differential ratio setting of 3rd harmonic differential stator ground fault element.
The criterion is only enabled after the generator unit is connected with the power grid and the load
current is larger than 0.2Ie (Ie is the rated current of generator).
Date: 2016-08-16
3 Operation Theory
For 3rd harmonic voltage has a close relationship with the generator operating conditions, so 3rd
harmonic differential stator ground fault element is only enabled when the generator
positive-sequence voltages are respectively larger than a certain threshold value. If the generator
frequency seriously deviates from the power frequency, 3rd harmonic differential stator ground fault
element will quit automatically.
3rd harmonic differential stator ground fault element can operate to alarm.
Generator terminal VT1 secondary circuit failure will not affect stator ground fault protection, if
generator terminal VT1 primary circuit failure happens, the fundamental component of generator
terminal zero-sequence voltage will increase, but the neutral point zero-sequence voltage will not
change, it will not lead to mal-operation of fundamental zero-sequence voltage protection, but it
maybe lead to mal-operation of 3rd harmonic ratio stator ground fault element and 3rd harmonic
differential stator ground fault element, so 3rd harmonic ratio stator ground fault element and 3rd
harmonic differential stator ground fault element should be blocked if generator terminal VT1
primary circuit failure happens.
(1) If there have two groups of three-phase voltage transformers, the voltage balance function is
in service. The operation criterion is as below.
If above four conditions are met, generator terminal VT1 primary circuit failure alarm signal will be
issued with a short time delay, the 3rd harmonic ratio stator ground fault element and 3rd harmonic
differential stator ground fault element are blocked.
(2) If there only has one group of three-phase voltage transformer, the voltage balance function is
not in service. The operation criterion is as below.
If above four conditions are met, generator terminal VT1 primary circuit failure alarm signal will be
issued with a short time delay, the 3rd harmonic ratio stator ground fault element and 3rd harmonic
differential stator ground fault element are blocked.
If generator terminal zero-sequence voltage is derived from the calculated zero-sequence voltage,
the device will not detect generator terminal VT1 primary circuit failure.
Date: 2016-08-16
3 Operation Theory
3.7.4 Logic
For generator 3rd harmonic stator ground fault protection, if following three conditions are met, the
protection will be enabled.
If generator 3rd harmonic stator ground fault protection is disabled, all the related output signals will
be reset. If no external input is configured to [64S2.En1] ([64S2.En2]), the default initial value of
[64S2.En1] ([64S2.En2]) is “1”; if no external input is configured to [64S2.Blk], the default initial
value of [64S2.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
SIG Flg_V3rdHRatio
Flg_U_Hm3_Ratio
EN [64S2.En] &
SIG Flg_Blk_U1
SIG Flg_Blk_f
&
SIG U3T/U3N>[64S2.K_Pre_U_Hm3_Ratio] & SIG Flg_V3rdHRatio
SIG Flg_52a
SIG ≥1
G_Term.VT1.VTS_Pri.Blk
&
SIG U3T/U3N>[64S2.K_Post_U_Hm3_Ratio]
EN [64S2.En_Alm_U_Hm3_Ratio] &
& [64S2.t_Op] 0ms [64S2.Alm_U_Hm3_Ratio]
SIG Flg_V3rdHRatio
SIG [64S2.Blk]
SIG Flg_V3rdHRatio
0ms 500ms
SIG 64S2.FD_U_Hm3_Ratio
EN [64S2.En]
SIG [64S2.En1] & &
SIG [64S2.En2] SIG Flg_V3rdHDiff
SIG [64S2.Blk]
SIG Abs(U3N-Kt*U3T)/U3N>[64S2.K_U_Hm3_Diff]
EN [64S2.En_Alm_U_Hm3_Diff] &
[64S2.t_Op] 0ms
[64S2.Alm_U_Hm3_Diff]
SIG Flg_V3rdHDiff
rd
Figure 3.7-2 Logic diagram of generator 3 harmonic stator ground fault protection
Where:
Flg_Blk_U1 is the internal signal indicating that the generator positive-sequence voltage is lower
than a certain threshold value.
Flg_Blk_f is the internal signal indicating that the generator frequency seriously deviates from the
power frequency.
Flg_Blk_U1&F is the internal signal indicating that the generator positive-sequence voltage is
lower than a certain threshold value and the generator frequency seriously deviates from the
power frequency.
Date: 2016-08-16
3 Operation Theory
Flg_52a&Flg_Curr is the internal signal indicating that the generator unit is connected with the
power grid and the load current is larger than 0.2Ie (Ie is the generator rated current).
Flg_U_Hm3_Ratio is the internal signal indicating that 3rd harmonic ratio stator ground fault
element is released.
Flg_V3rdHRatio is the internal signal indicating that the operation criterion of 3rd harmonic ratio
stator ground fault element is met, i.e. Equation 3.7-1 is met.
Flg_U_Hm3_Diff is the internal signal indicating that 3rd harmonic differential stator ground fault
element is released.
Flg_V3rdHDiff is the internal signal indicating that the operation criterion of 3rd harmonic differential
stator ground fault element is met, i.e. Equation 3.7-2 is met.
64S2.FD_U_Hm3_Ratio is the internal signal indicating that the 3rd harmonic ratio stator ground
fault element picks up (the fault detector of fault detector DSP module).
64S2.FD_U_Hm3_Diff is the internal signal indicating that the 3rd harmonic differential stator
ground fault element picks up (the fault detector of fault detector DSP module).
64S2
64S2.U1P1_Hm 64S2.St
64S2.U1P2_Hm 64S2.Alm_U_Hm3_Ratio
Flg_52a 64S2.Op_U_Hm3_Ratio
64S2.En1 64S2.Alm_U_Hm3_Diff
64S2.En2
64S2.Blk
f
G_Term.VT1.VTS_Pri.Blk
Figure 3.7-3 Function block diagram of generator 3rd harmonic stator ground fault protection
rd
Table 3.7-1 Input signals of generator 3 harmonic stator ground fault protection
Date: 2016-08-16
3 Operation Theory
rd
Table 3.7-2 Output signals of generator 3 harmonic stator ground fault protection
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.7-3 Output signals of generator 3rd harmonic stator ground fault protection (event recorder)
Tripping reports
1 64S2.Op_U_Hm3_Ratio 3rd harmonic ratio stator ground fault element operates to trip.
Start signals
Alarm signals
rd
3 harmonic ratio stator ground fault element operates to issue alarm
3 64S2.Alm_U_Hm3_Ratio
signal.
3rd harmonic differential stator ground fault element operates to issue alarm
4 64S2.Alm_U_Hm3_Diff
signal.
Waveform recording
Table 3.7-4 Output signals of generator 3rd harmonic stator ground fault protection (measurements)
rd
2 64S2.Ud_Hm3_Diff 3 harmonic differential voltage V
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Volt Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Volt Values
rd
The enabled status of 3 harmonic differential stator ground
3 Flg_On_U_Hm3_Diff
fault element of 3rd harmonic stator ground fault protection
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Misc Prot Values
Date: 2016-08-16
3 Operation Theory
rd
10 64S2.Ud_Hm3_Diff 3 harmonic differential voltage V
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen StaEF Prot Values
3.7.6 Settings
Table 3.7-5 Settings list of generator 3rd harmonic stator ground fault protection
Date: 2016-08-16
3 Operation Theory
rd
1: enable 3 harmonic ratio stator ground fault
element operates to alarm.
Logic setting of enabling/disabling
0: disable 3
rd
harmonic differential stator
8 64S2.En_Alm_U_Hm3_Diff 1
1: enable ground fault element operates to
alarm.
3.8.1 Application
Rotor ground fault protection is used to detect the ground fault of generator excitation circuit. If
generator rotor winding one-point ground fault happens, the rotor will not be damaged immediately,
the generator can continue to run. Then if another-point ground fault happens, a closed electrical
circuit will be generated between the two grounded points, which will lead to winding overheating
and unit vibration, it will be a serious threat to the security of the generator.
Generator Ping-Pang type rotor ground fault protection includes three operation elements:
sensitive stage of rotor one-point ground fault element for alarm, insensitive stage of rotor
one-point ground fault element for tripping or alarm, and rotor two-point ground fault element for
tripping.
Rotor one-point ground fault element reflects the decline of the insulation resistance between rotor
winding and the shaft, two stages are equipped, the sensitive stage for alarm and the insensitive
stage for alarm or trip. Rotor two-point ground fault element reflects the change of rotor ground
position, it can operate to trip.
Generator Ping-Pang type rotor ground fault protection adopts switch-over sampling principle
(ping-pang type), the working circuit is shown as below.
Date: 2016-08-16
3 Operation Theory
Generator rotor
U
+ αU -
rotor
R Rg R
R S1 S2 R
Figure 3.8-1 Schematic diagram of Ping-Pang type rotor ground fault protection
Where:
U is rotor voltage;
Corresponding equations can be got by switching over the two electronic switches S1 and S2
alternately, then the rotor grounded resistance Rg and the grounded position percentage “α” (it is
0% for negative terminal and 100% for positive terminal) can be calculated.
Two stages are equipped for rotor one-point ground fault element, the sensitive stage for alarm
and the insensitive stage for alarm or trip. The time delay setting for the two stages can be set
respectively. When the measured generator rotor grounded resistance value is lower than the
resistance setting of sensitive stage, the sensitive stage will operate to alarm with a settable time
delay. When the measured generator rotor grounded resistance value is lower than the resistance
setting of insensitive stage, the insensitive stage will operate to alarm or trip with a settable time
delay.
If rotor one-point ground fault element is used for alarm only, when rotor grounded resistance Rg is
lower than the resistance setting of insensitive stage of rotor one-point ground fault element, rotor
two-point ground fault element will be enabled with a time delay automatically after the operation
of rotor one-point ground fault element. If the grounded position percentage α varies and the
variation reaches its setting value, two-point ground fault element will operate to trip.
3.8.4 Logic
For generator Ping-Pang type rotor ground fault protection, if following three conditions are met,
the protection will be enabled.
Date: 2016-08-16
3 Operation Theory
If generator Ping-Pang type rotor ground fault protection is disabled, all the related output signals
will be reset. If no external input is configured to [64R.En1] ([64R.En2]), the default initial value of
[64R.En1] ([64R.En2]) is “1”; if no external input is configured to [64R.Blk], the default initial value
of [64R.Blk] is “0”.
SIG Rg<[64R.1PEF.Rg_Insens] ≥1
EN [64R.2PEF.En]
&
SIG 64R.2PEF.On
SIG Δα>3%
En [64R.1PEF.En_Alm_Sens] &
[64R.1PEF.t_Alm] 0
SIG Rg<[64R.1PEF.Rg_Sens] [64R.1PEF.Alm_Sens]
EN [64R.En] &
SIG [64R.Blk]
&
En [64R.1PEF.En_Alm_Insens] [64R.1PEF.t_Alm] 0 [64R.1PEF.Alm_Insens]
SIG Rg<[64R.1PEF.Rg_Insens]
EN [64R.En]
SIG [64R.En1] &
SIG [64R.En2] &
[64R.1PEF.t_Op_Insens] 0 [64R.1PEF.Op_Insens]
SIG [64R.Blk]
EN [64R.1PEF.En_Trp_Insens]
SIG Rg<[64R.1PEF.Rg_Insens]
0ms 500ms
SIG 64R.1PEF.FD
EN [64R.En]
&
SIG [64R.En1]
SIG [64R.En2] & [64R.2PEF.t_Op] 0
[64R.2PEF.Op]
SIG [64R.Blk]
EN [64R.2PEF.En]
SIG 64R.2PEF.On
SIG Δα>3%
0ms 500ms
SIG 64R.2PEF.FD
Figure 3.8-2 Logic diagram of generator Ping-Pang type rotor ground fault protection
Where:
64R.1PEF.FD is the internal signal indicating that rotor one-point ground fault element picks up
(the fault detector of fault detector DSP module).
64R.2PEF.FD is the internal signal indicating that rotor two-point ground fault element picks up
Date: 2016-08-16
3 Operation Theory
64R.2PEF.On is the internal signal indicating that the enabled status of Ping-Pang type rotor
two-point ground fault element.
64R
64R.ur+ 64R.St
64R.ur- 64R.1PEF.Alm_Sens
64R.En1 64R.1PEF.Alm_Insens
64R.En2 64R.1PEF.Op_Insens
64R.2PEF.Op
64R.Blk
Figure 3.8-3 Function block diagram of generator Ping-Pang type rotor ground fault protection
Table 3.8-1 Input signals of generator Ping-Pang type rotor ground fault protection
Table 3.8-2 Output signals of generator Ping-Pang type rotor ground fault protection
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Date: 2016-08-16
3 Operation Theory
Table 3.8-3 Output signals of generator Ping-Pang type rotor ground fault protection (event recorder)
Tripping reports
1 64R.1PEF.Op_Insens Generator Ping-Pang type rotor one-point ground fault element operates to trip.
2 64R.2PEF.Op Generator Ping-Pang type rotor two-point ground fault element operates to trip.
Start signals
Alarm signals
The sensitive stage of Ping-Pang type rotor one-point ground fault element
4 64R.1PEF.Alm_Sens
operates to issue alarm signal
The insensitive stage of Ping-Pang type rotor one-point ground fault element
5 64R.1PEF.Alm_Insens
operates to issue alarm signal
Waveform recording
7 64R.1PEF.St Generator Ping-Pang type rotor one-point ground fault element starts.
8 64R.2PEF.St Generator Ping-Pang type rotor two-point ground fault element starts.
Table 3.8-4 Output signals of generator Ping-Pang type rotor ground fault protection (measurements)
The voltage between rotor positive pole and ground that used for
1 64R.U+_Rot V
generator Ping-Pang type rotor ground fault protection.
The voltage between rotor negative pole and ground that used for
2 64R.U-_Rot V
generator Ping-Pang type rotor ground fault protection.
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
The voltage between rotor positive pole and ground that used for
6 64R.U+_Rot V
generator Ping-Pang type rotor ground fault protection.
The voltage between rotor negative pole and ground that used for
7 64R.U-_Rot V
generator Ping-Pang type rotor ground fault protection.
Date: 2016-08-16
3 Operation Theory
The grounded position percentage of the rotor (it is “0” for rotor
9 64R.Location_EF winding negative pole ground fault and “100%” for rotor winding %
positive pole ground fault).
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen SwitchRotEF Prot Values
3.8.6 Settings
Table 3.8-5 Settings list of generator Ping-Pang type rotor ground fault protection
Date: 2016-08-16
3 Operation Theory
element.
Access path: Settings-> Prot Settings -> Gen SwitchRotEF Settings
3.9.1 Application
The low-frequency square-wave voltage is injected between the generator rotor winding
positive/negative pole leading-out terminal and the shaft, via measuring the leakage current, the
rotor one-point ground resistance is calculated, it can reflect the decline of insulation resistance
that between the rotor winding (includes the directly connected excitation circuit) and the rotor
shaft.
If double-ends injecting wiring is adopted, it can detect the location of rotor winding ground fault.
When the calculated rotor ground fault location changes, it will be considered that a two-point
ground fault happens.
The external low-frequency square-wave voltage is injected to generator rotor winding circuit, if no
rotor one-point ground fault happens, the leakage current generated by the injected signal is small,
capacitive current exists only when the square-wave is switching, the leakage current is zero
during the steady-state of the square-wave. If rotor one-point ground fault happens, the leakage
current will increase and the calculated ground transition resistance value will decrease, the
protection will operate with a time delay. Two stages of rotor one-point ground fault protection are
equipped, the sensitive stage is for alarm and the insensitive stage is for alarm or trip.
If double-end injecting wiring is adopted, the device can calculate the location of rotor ground fault.
After the rotor one-point ground fault happens and the device is steady again, two-point ground
fault element can be enabled according to user’s requirement. When the calculated rotor ground
fault location changes, it will be considered that a two-point ground fault happens, the protection
will operate to trip with a time delay.
The calculation process of generator rotor ground fault protection with low-frequency square-wave
voltage injection is shown as below. In the figure generator rotor winding positive/negative pole
and the rotor shaft is leading out via slip-ring carbon brush. The device detects the injected voltage
and leakage current and other signals, calculates the ground transition resistance value and the
ground fault location.
Date: 2016-08-16
3 Operation Theory
Ry +
Generator
Ry Field
Generator
_ Rotor
Us Ur
Generator
Ry Field
Generator
_ Rotor
Us Ur
Figure 3.9-1 Schematic diagram of rotor ground fault protection with low-frequency square-wave voltage
injection
Where:
3.9.3.3 Rotor One-point Ground Fault Element with Low-frequency Square-wave Voltage
Injection
Rotor one-point ground fault element with low-frequency square-wave voltage injection adopts the
ground transition resistance to judge. Two stages are equipped, the sensitive stage is for alarm
and the insensitive stage is for alarm or trip. The criterion is:
Date: 2016-08-16
3 Operation Theory
Where:
3.9.3.4 Rotor two-point Ground Fault Element with Low-frequency Square-wave Voltage
Injection
For the unit that users can simultaneously lead-out the positive and negative pole of rotor winding,
double-ends injecting wiring can be adopted. The device can calculate the location of rotor
one-point ground fault, so it can realize the two-point ground fault protection via the change of the
rotor ground fault location. If above Equation 3.9-2 is met, and rotor one-point ground fault element
operates for alarm, two-point ground fault element is enabled automatically with a time delay.
3.9.4 Logic
For generator rotor ground fault protection (with low-frequency square-wave voltage injection), if
following three conditions are met, the protection will be enabled.
If generator rotor ground fault protection (with low-frequency square-wave voltage injection) is
disabled, all the related output signals will be reset. If no external input is configured to
[64RInj.En1] ([64RInj.En2]), the default initial value of [64RInj.En1] ([64RInj.En2]) is “1”; if no
external input is configured to [64RInj.Blk], the default initial value of [64RInj.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
SIG Rg<[64RInj.1PEF.Rg_Insens] ≥1
EN [64RInj.2PEF.En]
&
SIG 64RInj.2PEF.On
EN [64RInj.1PEF.En_Alm_Sens] &
[64RInj.1PEF.t_Alm] 0s
SIG Rg < [64RInj.1PEF.Rg_Sens] [64RInj.1PEF.Alm_Sens]
EN [64RInj.En] &
SIG [64RInj.Blk]
&
EN [64RInj.1PEF.En_Alm_Insens] [64RInj.1PEF.t_Alm] 0s
[64RInj.1PEF.Alm_Insens]
SIG Rg < [64RInj.1PEF.Rg_Insens]
EN [64RInj.1PEF.En_Trp_Insens]
&
SIG Rg < [64RInj.1PEF.Rg_Insens] [64RInj.1PEF.t_Op_Insens] 0s
[64RInj.1PEF.Op_Insens]
SIG 64RInj.1PEF.FD 0ms 500ms
EN [64RInj.En]
&
SIG [64RInj.En1]
SIG [64RInj.En2]
SIG [64RInj.Blk]
Figure 3.9-2 Logic diagram of generator rotor ground fault protection (with low-frequency square-wave
voltage injection)
Where:
64RInj.1PEF.FD is the internal signal indicating that the generator rotor one-point ground fault
protection (with low-frequency square-wave voltage injection) picks up (the fault detector of fault
detector DSP module).
64RInj.2PEF.On is the internal signal indicating that generator rotor two-point ground fault
protection (with low-frequency square-wave voltage injection) is enabled.
64RInj.2PEF.FD is the internal signal indicating that the generator rotor two-point ground fault
protection (with low-frequency square-wave voltage injection) picks up (the fault detector of fault
detector DSP module).
Date: 2016-08-16
3 Operation Theory
64RInj
64RInj.us 64RInj.St
64RInj.ix 64RInj.1PEF.Op_Insens
64RInj.ur 64RInj.2PEF.Op
64RInj.iDC 64RInj.1PEF.Alm_Sens
64RInj.En1 64RInj.1PEF.Alm_Insens
64RInj.En2
64RInj.Blk
Figure 3.9-3 Function block diagram of generator rotor ground fault protection (with low-frequency
square-wave voltage injection)
Table 3.9-1 Input signals of generator rotor ground fault protection (with low-frequency square-wave
voltage injection)
Table 3.9-2 Output signals of generator rotor ground fault protection (with low-frequency square-wave
voltage injection)
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Date: 2016-08-16
3 Operation Theory
Table 3.9-3 Output signals of generator rotor ground fault protection (with low-frequency square-wave
voltage injection) (event recorder)
Tripping reports
Start signals
Alarm signals
The external injected power supply of generator rotor ground fault protection
4 64RInj.Alm_Pwr_Inj
(with low-frequency square-wave voltage injection) is abnormal.
Waveform recording
Table 3.9-4 Output signals of generator rotor ground fault protection (with low-frequency square-wave
voltage injection) (measurements)
Rotor ground fault location (it is “0” for rotor winding negative pole
5 64RInj.Location_EF %
ground fault and “100%” for rotor winding positive pole ground fault).
Date: 2016-08-16
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
Rotor ground fault location (it is “0” for rotor winding negative pole
13 64RInj.Location_EF %
ground fault and “100%” for rotor winding positive pole ground fault).
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen InjRotEF Prot Values
3.9.6 Settings
Table 3.9-5 Settings list of generator rotor ground fault protection (with low-frequency square-wave
voltage injection)
Date: 2016-08-16
3 Operation Theory
trip.
Time delay setting of rotor two-point
6 64RInj.2PEF.t_Op 0.00~30.00 0.01 s ground fault element (with low-frequency
square-wave voltage injection).
The switching cycle of the injected
7 64RInj.t_Switch 0.50~10.00 0.01 s
square-wave voltage.
The resistance value of the big-power
8 64RInj.R_Injected 0.10~100.00 0.01 kΩ
resistor of the injected circuit.
Tripping logic setting of generator rotor
9 64RInj.OutMap 0~3FFFFFFF ground fault protection (with low-frequency
square-wave voltage injection).
Logic setting of enabling/disabling sensitive
0: disable stage of rotor one-point ground fault
10 64RInj.1PEF.En_Alm_Sens 1
1: enable element (with low-frequency square-wave
voltage injection) operates to alarm.
Logic setting of enabling/disabling
insensitive stage of rotor one-point ground
0: disable
11 64RInj.1PEF.En_Alm_Insens 1 fault element (with low-frequency
1: enable
square-wave voltage injection) operates to
alarm.
Logic setting of enabling/disabling
insensitive stage of rotor one-point ground
0: disable
12 64RInj.1PEF.En_Trp_Insens 1 fault element (with low-frequency
1: enable
square-wave voltage injection) operates to
trip.
Logic setting of enabling/disabling rotor
0: disable two-point ground fault element (with
13 64RInj.2PEF.En 1
1: enable low-frequency square-wave voltage
injection).
Rotor voltage input mode.
14 64RInj.Opt_U_Rot 0, 1 1 0: the measured result of rotor voltage
1: the measured result of 20mA transmitter
0: The injected mode selection.
15 64RInj.Opt_Mode_Inj Double-ends 0: Double-ends injecting type
1: Single-end 1: Single-end injecting type
Access path: Settings-> Prot Settings -> Gen InjRotEF Settings
3.10.1 Application
Generator rotor winding overload protection is equipped to reflect the average heating condition of
rotor winding.
Date: 2016-08-16
3 Operation Theory
Generator rotor winding overload protection comprises definite-time overload protection and
inverse-time overload protection. The low-setting stage of definite-time overload protection is used
for alarm and the high-setting stage of definite-time overload protection is used for tripping.
Inverse-time overload protection can simulate the heat accumulation process of the rotor winding.
Only considering the temperature change that caused by copper loss of rotor winding. The copper
loss is proportional to the square of current, so there is a certain proportional relationship between
the temperature change of rotor winding and the square of excitation circuit current. Via checking
the change of excitation circuit current can reflect the temperature change of rotor winding
indirectly. For a given temperature increase (Δθ), the corresponding expression between
permissive time (t) and current can be got:
A
t=
(I )
∗ 2
−1
Equation 3.10-1
Where:
I ∗ is the per-unit value of excitation circuit current (when the excitation current is the rated
current, the checked rotor circuit current is taken as the referenced value).
There are two stages of rotor winding definite-time overload protection. The low-setting stage of
definite-time overload protection is used for alarm, and the settings should be set to make the
protection can drop off reliably for long-term permissive load current. The high-setting stage of
definite-time overload protection is used for tripping, and the settings should be set according to
the permissive time for more serious overload condition.
Inverse-time rotor winding overload protection consists of three parts: lower-limit initiation part,
inverse-time part and upper limit definite-time part. Minimum operation time delay setting
[49E.IDMT.tmin] is provided for upper limit definite-time part.
When the current in excitation circuit is over the low setting [49E.IDMT.I_Set], the heat
accumulation starts. When the heat accumulation reaches its setting [49E.IDMT.A_Therm],
inverse-time rotor winding overload protection can operate to trip. The inverse time protection can
simulate the heat accumulation and dissipation process of the excitation circuit. If the current in
excitation circuit is over the low setting [49E.IDMT.I_Set], the heat accumulation starts; if the
Date: 2016-08-16
3 Operation Theory
current in excitation circuit is lower than the low setting [49E.IDMT.I_Set], the heat dissipation
starts.
IE
IUpper −lim it
I Pickup
t min tmax t
Figure 3.10-1 Operation characteristic of inverse-time rotor winding overload protection
Where:
t min is the minimum time delay for upper limit definite-time part, i.e. the setting [49E.IDMT.tmin].
I Pickup is the pickup current setting of inverse-time rotor winding overload protection, i.e. the
setting [49E.IDMT.I_Set].
I Upper −lim it is the current that corresponds to the minimum time delay for upper limit definite-time
part.
[( I E I b) − 1] × t ≥ ATherm
2
Equation 3.10-2
Where:
Date: 2016-08-16
3 Operation Theory
ATherm is the heat capacity of rotor winding, i.e. the setting [49E.IDMT.A_Therm].
3.10.4 Logic
For rotor winding overload protection, if following three conditions are met, the protection will be
enabled.
If rotor winding overload protection is disabled, all the related output signals will be reset. If no
external input is configured to [49E.En1] ([49E.En2]), the default initial value of [49E.En1]
([49E.En2]) is “1”; if no external input is configured to [49E.Blk], the default initial value of [49E.Blk]
is “0”.
En [49E.IDMT.OutMap].bit0 ≥1
&
SIG I>[49E.IDMT.I_Set]
SIG [49E.Blk]
EN [49E.En]
SIG [49E.En1] &
& [49E.DT.t_Op] 0
SIG [49E.En2] [49E.DT.Op]
SIG [49E.Blk]
SIG I>[49E.DT.I_Set]
0ms 500ms
SIG 49E.DT.FD
EN [49E.En]
SIG [49E.En1] &
SIG I>[49E.IDMT.I_Set]
0ms 500ms
SIG 49E.IDMT.FD
Where:
49E.DT.FD is the internal signal indicating that the rotor winding definite-time overload protection
picks up (the fault detector of fault detector DSP module).
49E.IDMT.FD is the internal signal indicating that the rotor winding inverse-time overload
Date: 2016-08-16
3 Operation Theory
49E
49E.I3P 49E.St
49E.En1 49E.IDMT.Op
49E.En2 49E.DT.Op
49E.Blk 49E.Alm
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.10-3 Output signals of rotor winding overload protection (event recorder)
Tripping reports
Start signals
Alarm signals
The alarm stage of rotor winding overload protection operates to issue alarm
4 49E.Alm
signal
Waveform recording
Date: 2016-08-16
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
3.10.6 Settings
Table 3.10-5 Settings list of rotor winding overload protection
Date: 2016-08-16
3 Operation Theory
3.11.1 Application
For a generator have not been connected to the power grid, if the circuit breaker is closed wrongly,
voltage will be injected to the generator stator winding suddenly, which may lead to severe current
impact. Generator inadvertent energization protection is used to detect the fault, once the
protection operates, circuit breaker can be tripped quickly.
During resting, hand turning and startup-and-shutdown process, the generator has not been
excited or the excitation current is small, generator terminal voltage and the frequency is low, then
if the generator is closed inadvertently, the generator voltage will be pulled high, the frequency will
be pulled into synchronism, and significant impulse current will be generated. If generator voltage
is larger enough and the frequency is close to the rated value, then if the generator is closed
inadvertently, larger impulse current due to asynchronous closing may be generated.
The protection device according to the characteristics of voltage, frequency, circuit breaker state
and current before and after the generator is closed inadvertently to detect inadvertent
energization condition.
1) Detect the three-phase voltage of generator terminal, calculate the value of voltage to judge
the low-voltage condition;
3) Detect the three-phase current of generator terminal and generator neutral point, calculate
the value of current to judge the overcurrent condition;
4) Detect the auxiliary contact of the circuit breaker to judge the circuit breaker state before and
after the generator is closed inadvertently.
Following three types of inadvertent energization conditions are taken into account:
1. In the course of generator’s hand turning (low frequency condition), if it has not been excited,
inadvertent closure of the circuit breaker may lead to asynchronous starting of the generator.
Under this condition, before the generator is closed inadvertently, generator voltage is low,
low-voltage element will be enabled with a time delay of t1; after the generator is closed
inadvertently, generator voltage will rise, low-voltage element will quit with a time delay of t2
Date: 2016-08-16
3 Operation Theory
2. In the case that generator circuit breaker is closed inadvertently in excited condition but the
frequency is lower than the setting which occurs during startup-and-shutdown process. Under
this condition, before the generator is closed inadvertently, generator frequency is low,
low-frequency element will be enabled with a time delay of t3; after the generator is closed
inadvertently, generator frequency will be pulled into synchronism, low- frequency element will
quit with a time delay of t4 (the time delay should make sure the completion of the tripping
course of inadvertent energization protection).
3. In the case that generator circuit breaker is closed inadvertently or asynchronously in excited
condition but the frequency is larger than the setting which occurs during
startup-and-shutdown process. Under this condition, circuit breaker position is adopted to
judge, circuit breaker position element is enabled with a time delay of t5 (the opening time of
the circuit breaker is taken into account) and quit with a time delay of t6.
After the generator is closed inadvertently, the current will increase suddenly, take the overcurrent
element of generator terminal current and generator neutral point current to reflect the fault
characteristic of current increase.
f < f UF
Where:
Where:
I max > I OC
Date: 2016-08-16
3 Operation Theory
Where:
If the current source selection setting for inadvertent energization protection [50/27.Opt_Source_I]
is set as “0”, I max takes the maximum phase current value of three-phase current input 1
(three-phase current input 1 can be configured as generator terminal current or neutral point side
current). If the current source selection setting for inadvertent energization protection
[50/27.Opt_Source_I] is set as “1”, I max takes the smaller value of three-phase current input 1
maximum phase current and three-phase current input 2 maximum phase current (three-phase
current input 1 and three-phase current input 2 can be configured as generator terminal current
and neutral point side current).
If the logic selection setting for inadvertent energization protection [50/27.Opt_Mode] is set as “0”,
the internal logic between low-frequency/voltage element and circuit breaker position element is
“Or”; if the logic selection setting for inadvertent energization protection [50/27.Opt_Mode] is set
as “1”, the internal logic between low-frequency/voltage element and circuit breaker position
element is “And”.
3.11.4 Logic
For inadvertent energization protection, if following three conditions are met, the protection will be
enabled.
If inadvertent energization protection is disabled, all the related output signals will be reset. If no
external input is configured to [50/27.En1] ([50/27.En2]), the default initial value of [50/27.En1]
([50/27.En2]) is “1”; if no external input is configured to [50/27.Blk], the default initial value of
[50/27.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
t1 0s t2
EN [50/27.Opt_Mode]
EN [50/27.Opt_Source_I] & ≥1
SIG Imax1 > [50/27.I_Set] &
&
&
[50/27.St]
SIG Imax2 > [50/27.I_Set]
0 500ms
SIG 50/27.FD
Where:
50/27.FD is the internal signal indicating that the inadvertent energization protection picks up (the
fault detector of fault detector DSP module).
50/27
50/27.I3P1 50/27.St
50/27.I3P2 50/27.Op
50/27.U3P
50/27.En1
50/27.En2
50/27.Blk
Flg_52a
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen AccEnerg Prot Values
3.11.6 Settings
Table 3.11-5 Settings list of inadvertent energization protection
Date: 2016-08-16
3 Operation Theory
3.12.1 Application
Generator out-of-step protection is used to detect the asynchronous operation due to generator
out-of-step.
U 1
Z1 = Equation 3.12-1
I
1
Where:
Date: 2016-08-16
3 Operation Theory
Following figure shows operation characteristic of out-of-step protection that comprises three parts:
①lens, ②boundary and ③reactance line.
jX
Left Right
2
Za
Up Out
In
Down
Zc
3
α
OL
IL
1 IR
OR
ϕ
O R
Zb
1. ①lens divides the impedance plane into lens inside part (In) and lens outside part (Out).
2. ②boundary divides the impedance plane into left half part (Left) and right half part (Right).
3. ③reactance line divides the impedance plane into upper half part (Up) and lower half part
(Down).
α is the interior angle of ①lens, it takes 120deg by default. φ is the sensitive angle of ②boundary,
it takes 85deg by default.
The impedance plane is divided into four areas by ①lens and ②boundary: OL, IL, IR and OR. If
the impedance locus passes through these four areas in sequence from right to left or vice versa
(OLILIROR or ORIRILOL), and staying in each area for a duration longer than a
certain time delay, this case is considered as out-of-step swing. The times of the impedance locus
passing through the four areas in sequence is considered as the pole sliding times. Per time the
impedance locus passes through the four areas in sequence, the pole sliding times will plus 1. If
the sequence for impedance locus passing through these four areas is OLILIROR, it is
called decelerate out-of-step; if the sequence for impedance locus passing through these four
areas is ORIRILOL, it is called accelerate out-of-step. Once the pole sliding times is over
the corresponding setting, out-of-step protection can operate to alarm or trip.
As to ③reactance line, if the impedance locus falls into the lower half part (Down), the swing
center is considered within the generator. If the impedance locus falls into the upper half part (Up),
the swing center is considered outside the generator. Pole sliding times setting for these two cases
Date: 2016-08-16
3 Operation Theory
The minimum swing period that can be identified by out-of-step protection is 120ms.
The tripping permissive current setting is an auxiliary criterion for out-of-step protection, it should
be set according to the circuit breaker permissive breaking capacity. The device can automatically
select to trip when the current is small, so that the damage to the circuit breaker due to too larger
tripping current can be prevented.
3.12.4 Logic
For generator out-of-step protection, if following three conditions are met, the protection will be
enabled.
(4) The input signal for loss-of-excitation protection operation to block out-of-step protection
[78.ExcLoss_Blk] is “0”
If generator out-of-step protection is disabled, all the related output signals will be reset. If no
external input is configured to [78.En1] ([78.En2]), the default initial value of [78.En1] ([78.En2]) is
“1”; if no external input is configured to [78.Blk] and [78.ExcLoss_Blk], the default initial value of
[78.Blk] and [78.ExcLoss_Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
EN [78.En_Alm_Ext] &
SIG 78.N_Slip_Ext≥[78.Num_Slip_Ext] [78.Alm_Ext]
EN [78.En] &
SIG [78.Blk]
&
EN [78.En_Alm_Int] [78.Alm_Int]
SIG 78.N_Slip_Int≥[78.Num_Slip_Int]
EN [78.En]
SIG [78.En1] &
SIG [78.En2]
[78.St]
SIG [78.Blk] &
&
SIG 78.N_Slip_Ext≥[78.Num_Slip_Ext]
SIG [78.ExcLoss_Blk]
0 500ms
SIG 78.FD
EN [78.En]
SIG [78.En1] &
SIG [78.En2]
[78.St]
SIG [78.Blk] &
&
SIG 78.N_Slip_Int≥[78.Num_Slip_Int]
SIG [78.ExcLoss_Blk]
0 500ms
SIG 78.FD
Where:
78.FD is the internal signal indicating that the out-of-step protection picks up (the fault detector of
fault detector DSP module).
Ibrk_max is the maximum value of the three phase currents that flows through the circuit breaker.
78.ExcLoss_Blk is the input signal for loss-of-excitation protection operation to block out-of-step
protection.
Date: 2016-08-16
3 Operation Theory
78
78.U3P 78.St
78.I3P1 78.Op_Ext
78.I3P2 78.Op_Int
78.En1 78.Alm_Ext
78.En2 78.Alm_Int
78.Blk 78.Alm_Accel
78.ExcLoss_Blk 78.Alm_Decel
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Date: 2016-08-16
3 Operation Theory
Start signals
Alarm signals
Waveform recording
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen OOS Prot Values
3.12.6 Settings
Table 3.12-5 Settings list of generator out-of-step protection
Date: 2016-08-16
3 Operation Theory
swing.
Pole sliding times setting for internal power
8 78.Num_Slip_Int 1~1000 1
swing.
Tripping permissive current setting for
9 78.Ibrk_Perm_CB 0.10~20In 0.01 A
out-of-step protection.
Tripping logic setting of definite-time out-of-step
10 78.OutMap 0~3FFFFFFF
protection
Logic setting of enabling/disabling out-of-step
0: disable
11 78.En_Alm_Ext 1 protection for external power swing operates to
1: enable
alarm.
Logic setting of enabling/disabling out-of-step
0: disable
12 78.En_Trp_Ext 1 protection for external power swing operates to
1: enable
trip.
Logic setting of enabling/disabling out-of-step
0: disable
13 78.En_Alm_Int 1 protection for internal power swing operates to
1: enable
alarm.
Logic setting of enabling/disabling out-of-step
0: disable
14 78.En_Trp_Int 1 protection for internal power swing operates to
1: enable
trip.
Access path: Settings-> Prot Settings -> Gen OOS Settings
3.13.1 Application
Generator startup and shutdown protection can reflect single-phase ground fault or
phase-to-phase short-circuit fault during startup and shutdown process of generator.
During startup and shutdown process of generator, frequency is usually very low, if single-phase
ground fault happens, the residual voltage will increase; if phase-to-phase short-circuit fault
happens, the current of generator neutral point side will increase. According to these two fault
features, the device adopts a frequency-independent calculation method to calculate the
Date: 2016-08-16
3 Operation Theory
generator neutral point-to-earth residual voltage and generator neutral point side current.
Detect the generator neutral point-to-earth residual voltage, detect generator neutral point side
current and takes the maximum value.
f < fUF
Equation 3.13-1
3U 0 > 3U0 Set
Where:
fUF is the frequency setting for generator startup and shutdown protection;
3U0Set is the residual voltage setting for generator startup and shutdown protection.
If the two equations are met simultaneously, low-frequency zero-sequence overvoltage element
will operate with a time delay.
f < fUF
Equation 3.13-2
I max > I OC
Where:
Imax is the maximum value of generator neutral point side three-phase current;
IOC is the current setting for generator startup and shutdown protection.
If the two equations are met simultaneously, low-frequency overcurrent element will operate with a
time delay.
3.13.4 Logic
For generator startup and shutdown protection, if following three conditions are met, the protection
will be enabled.
If generator startup and shutdown protection is disabled, all the related output signals will be reset.
If no external input is configured to [StShut.En1] ([StShut.En2]), the default initial value of
[StShut.En1] ([StShut.En2]) is “1”; if no external input is configured to [StShut.Blk], the default
Date: 2016-08-16
3 Operation Theory
EN [StShut.En]
&
SIG [StShut.En1]
SIG [StShut.En2]
SIG [StShut.Blk]
[StShut.St]
&
EN [StShut.En_StaROV] &
& [StShut.t_StaROV] 0s
SIG U0P > [StShut.3U0_StaROV] [StShut.Op_StaROV]
0 500ms
SIG StShut.FD_StaROV
EN [StShut.En]
&
SIG [StShut.En1]
SIG [StShut.En2]
SIG [StShut.Blk]
[StShut.St]
&
EN [StShut.En_OC] &
& [StShut.t_OC] 0s
SIG Imax > [StShut.I_OC] [StShut.Op_OC]
0 500ms
SIG StShut.FD_OC
Where:
StShut.FD_OC is the internal signal indicating that the low-frequency overcurrent element of
generator startup and shutdown protection picks up (the fault detector of fault detector DSP
module).
StShut
StShut.U1P_Hm StShut.St
StShut.I3P StShut.Op_StaROV
f StShut.Op_OC
StShut.En1
StShut.En2
StShut.Blk
Flg_52a
Figure 3.13-2 Function block diagram of generator startup and shutdown protection
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.13-3 Output signals of generator startup and shutdown protection (event recorder)
Tripping reports
Start signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
Table 3.13-4 Output signals of generator startup and shutdown protection (measurements)
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen StShut Prot Values
3.13.6 Settings
Table 3.13-5 Settings list of generator startup and shutdown protection
Date: 2016-08-16
3 Operation Theory
3.14.1 Application
Generator shaft overcurrent protection detects the shaft current of generator rotor shaft, it can
prevent the bearing from damage. The function is mainly used for hydropower unit.
If generator shaft current density exceeds the allowed value, the journal sliding surface and the
axle bush of generator shaft will be damaged. Generally the shaft overcurrent protection that
reflect the fundamental component is selected, users can also select the shaft overcurrent
protection that reflect the 3rd harmonic component by corresponding logic setting. Shaft
overcurrent protection includes two operation stages: sensitive stage and insensitive stage.
Sensitive stage of shaft overcurrent protection can operate to alarm or trip, and insensitive stage of
shaft overcurrent protection can operate to trip.
The device detects the generator shaft current (via shaft current CT or transmitter), than the
fundamental and 3rd harmonic component of the shaft current is calculated, then the device can
select the fundamental component or 3rd harmonic component (according to corresponding logic
setting) to conduct the logic judgment.
Where:
I is the fundamental component or 3rd harmonic component (controlled by the two logic settings
[51GS.En_Hm1] and [51GS.En_Hm3]) of the shaft current;
Date: 2016-08-16
3 Operation Theory
Where:
I is the fundamental component or 3rd harmonic component (controlled by the two logic settings
[51GS.En_Hm1] and [51GS.En_Hm3]) of the shaft current;
3.14.4 Logic
For generator shaft overcurrent protection, if following three conditions are met, the protection will
be enabled.
If generator shaft overcurrent protection is disabled, all the related output signals will be reset. If no
external input is configured to [51GS.En1] ([51GS.En2]), the default initial value of [51GS.En1]
([51GS.En2]) is “1”; if no external input is configured to [51GS.Blk], the default initial value of
[51GS.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
EN [51GS.En_Alm_L]
EN [51GS.En] &
SIG [51GS.Blk]
EN [51GS.En] &
SIG [51GS.En1]
SIG [51GS.En2]
SIG [51GS.Blk]
&
EN [51GS.En_Trp_L] [51GS.t_L] 0s
[51GS.Op_L]
EN [51GS.OutMap_L].bit0
0 500ms
SIG 51GS.FD
≥1
[51GS.St]
EN [51GS.En_Trp_H]
EN [51GS.OutMap_H].bit0
Where:
51GS.FD is the internal signal indicating that the generator shaft overcurrent protection picks up
(the fault detector of fault detector DSP module).
51GS
51GS.I1P_Hm 51GS.St
51GS.En1 51GS.Op_L
51GS.En2 51GS.Op_H
51GS.Blk 51GS.Alm
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.14-3 Output signals of generator shaft overcurrent protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
Date: 2016-08-16
3 Operation Theory
3.14.6 Settings
Table 3.14-5 Settings list of generator shaft overcurrent protection
3.15.1 Application
Negative-sequence current protection detects the unbalanced load of three-phase induction motor,
negative-sequence current will generate a magnetic field rotating in reverse direction, the
frequency of the magnetic field is twice relative to the frequency of the rotor. The double-frequency
magnetic field will generate eddy current on the surface of the rotor, which will lead to the
over-heating of the surface of the rotor. Generator negative-sequence overload protection can
Date: 2016-08-16
3 Operation Theory
reflect the over-heating condition of generator rotor surface, it can also reflect the other
abnormalities that caused by negative-sequence current.
Negative-sequence current can be calculated after filtering the three-phase current, if the negative
sequence current is larger than the threshold value, the protection starts, once the starting time is
longer than the time delay setting, the protection will operate to issue alarm signal or trip.
Generally the generator manufacturer will provide the long-term permissive negative-sequence
current I2∞ (per-unit value) and the rotor negative-sequence heating time constant A. for example,
a rotor-directly-cooled turbo-generator, the long-term permissive negative-sequence current is 8%
(per-unit value), the rotor negative-sequence heating time constant is 8, then the permissive
operation duration corresponds to a given negative-sequence current can be calculated according
to following equation.
A
t=
(I )
2
∗ 2
Equation 3.15-1
Where:
∗
I 2 is the per-unit value of rotor negative-sequence current.
There are two stages of definite-time negative-sequence overload protection. The low-setting
stage of definite-time negative-sequence overload protection is used for alarm, and the settings
should be set to make the protection can drop off reliably for long-term permissive
negative-sequence current. The high-setting stage of definite-time negative-sequence overload
protection is used for tripping, and the settings should be set larger than the maximum
negative-sequence current that flowing through the generator for an external asymmetric
Date: 2016-08-16
3 Operation Theory
short-circuit fault.
When the negative-sequence current is over the pickup current setting for negative-sequence
overload protection [46G.IDMT.I_Set], the heat accumulation starts. When the heat accumulation
reaches its setting [46G.IDMT.A_Therm], inverse-time negative-sequence overload protection can
operate to trip. The inverse-time negative-sequence overload protection can simulate the heat
accumulation and dissipation process of the rotor. Since the heat accumulation starts, if the
negative-sequence current is lower than the pickup current setting [46G.IDMT.I_Set], the heat
dissipation starts; then if the negative-sequence current increases to over the pickup current
setting [46G.IDMT.I_Set], the heat accumulation will starts again from the current heat
accumulation value.
I2
IU pper−limit
I P ickup
t min tmax t
Figure 3.15-1 Operation characteristic of inverse-time negative-sequence overload protection
Where:
t min is the minimum time delay for upper limit definite-time part, i.e. the setting [46G.IDMT.tmin].
I Pickup is the pickup current setting of inverse-time negative-sequence overload protection, i.e. the
setting [46G.IDMT.I_Set]
I Upper −lim it is the current that corresponds to the minimum time delay for upper limit definite-time
Date: 2016-08-16
3 Operation Theory
part.
[(I 2 I b) − (I 2 ∞ I b) ] × t ≥ A
2 2
Equation 3.15-2
Where:
The maximum time delay for lower-limit initiation part should be smaller than the calculated
operating time corresponds to the lower-limit pickup current setting according to Equation 3.15-2.
3.15.4 Logic
For generator negative-sequence overload protection, if following three conditions are met, the
protection will be enabled.
If generator negative-sequence overload protection is disabled, all the related output signals will
be reset. If no external input is configured to [46G.En1] ([46G.En2]), the default initial value of
[46G.En1] ([46G.En2]) is “1”; if no external input is configured to [46G.Blk], the default initial value
of [46G.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
En [46G.IDMT.OutMap].bit0 ≥1
&
SIG I2>[46G.IDMT.I_Set]
EN [46G.En]
SIG [46G.En1] &
& [46G.DT.t_Op] 0ms
SIG [46G.En2] [46G.DT.Op]
SIG [46G.Blk]
SIG I2>[46G.DT.I_Set]
0ms 500ms
SIG 46G.DT.FD
EN [46G.En]
SIG [46G.En1] &
& IDMT ≥1
SIG [46G.En2]
SIG [46G.Blk] t ≥ t max &
[46G.IDMT.Op]
SIG I2>[IDMT.I_Set]
0ms 500ms
SIG 46G.IDMT.FD
Where:
46G.DT.FD is the internal signal indicating that the definite-time generator negative-sequence
overload protection picks up (the fault detector of fault detector DSP module).
46G.IDMT.FD is the internal signal indicating that the inverse-time generator negative-sequence
overload protection picks up (the fault detector of fault detector DSP module).
46G
46G.I3P1 46G.St
46G.I3P2 46G.DT.Op
46G.En1 46G.IDMT.Op
46G.En2 46G.Alm
46G.Blk
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.15-3 Output signals of generator negative-sequence overload protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
3.15.6 Settings
Table 3.15-5 Settings list of generator negative-sequence overload protection
Date: 2016-08-16
3 Operation Theory
3.16.1 Application
For some reasons the generator will change into motor operating mode due to loss of its motive
power, then the generator will absorb energy from the power grid to driven the turbine (gas turbine)
to run. In order to prevent the turbine blades or gas turbine gears from damage, generator reverse
power protection should be configured.
Generator reverse power protection includes two operation elements: conventional reverse power
element and sequence tripping reverse power element.
If conventional reverse power element is enabled, when the detected reverse power value
exceeds the conventional reverse power setting, conventional reverse power element can operate
to alarm or trip with a time delay.
After the operation of some abnormal protections (such as overload protection, overexcitation
protection, loss-of-excitation protection and etc.) and sequence tripping is needed, the device will
turn off the main valve first, then sequence tripping reverse power element (controlled by main
valve contact and interconnection status between the generator and the power grid) operates to
trip with a short time delay.
The active power absorption level of a generator depends on the friction loss that needs to
overcome, the reverse power setting will be different for different type of units. When testing on the
primary side of the unit, the absorbed active power of the generator can be measured by the
Date: 2016-08-16
3 Operation Theory
device. Users should set the reverse power setting as 50% of the measured reverse power value.
Two time delays are configured for conventional reverse power element, time delay 1 is for alarm
and time delay 2 is for shutdown.
Where:
The setting range of conventional reverse power setting is (0.5%~50%)Pn, Pn is the rated active
power of the generator.
One time delay is configured for sequence tripping reverse power element, if the main valve is
closed and the reverse power value exceeds the sequence tripping reverse power setting, the
sequence tripping reverse power will operate to trip with a short time delay.
Where:
The setting range of sequence tripping reverse power setting is (0.5%~10%)Pn, Pn is the rated
active power of the generator.
3.16.4 Logic
For generator reverse power protection, if following three conditions are met, the protection will be
enabled.
If generator reverse power protection is disabled, all the related output signals will be reset. If no
external input is configured to [32R.En1] ([32R.En2]), the default initial value of [32R.En1]
([32R.En2]) is “1”; if no external input is configured to [32R.Blk], the default initial value of [32R.Blk]
is “0”.
Date: 2016-08-16
3 Operation Theory
EN P<-[32R.CONV.P_Set] &
[32R.CONV.t_Alm] 0ms
SIG [32R.En] [32R.CONV.Alm]
SIG [32R.Blk]
SIG [32R.En]
& [32R.CONV.St]
SIG [32R.En1]
& [32R.CONV.t_Op] 0ms
SIG [32R.En2] [32R.CONV.Op]
SIG [32R.Blk]
SIG P<-[32R.CONV.P_Set]
0ms 500ms
SIG 32R.CONV.FD
SIG [32R.En]
&
SIG [32R.En1] [32R.SEQ.St]
SIG [32R.En2] &
[32R.SEQ.t_Op] 0ms
[32R.SEQ.Op]
SIG [32R.Blk]
SIG P<-[32R.SEQ.P_Set]
SIG [BI_Valve]
0ms 500ms
SIG 32R.SEQ.FD
Where:
32R.CONV.FD is the internal signal indicating that the conventional reverse power element picks
up (the fault detector of fault detector DSP module).
32R.SEQ.FD is the internal signal indicating that the sequence tripping reverse power element
picks up (the fault detector of fault detector DSP module).
32R
32R.POWER 32R.St
32R.En1 32R.CONV.Op
32R.En2 32R.SEQ.Op
32R.Blk 32R.CONV.Alm
BI_Valve
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.16-3 Output signals of generator reverse power protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Curr Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Curr Values
Date: 2016-08-16
3 Operation Theory
12 Flg_52a The signal indicating that the generator is connected with the system.
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen Power Prot Values
3.16.6 Settings
Table 3.16-5 Settings list of generator reverse power protection
3.17.1 Application
For some reasons the generator will change into motor operating mode due to loss of its motive
power, the generator power is gradually reduced to zero and then is reversed. When the generator
power is lower than a set low forward power threshold, generator low forward power protection will
operate to alarm and output a contact or shutdown.
In case generator low forward power protection is enabled, if the detected forward active power
Date: 2016-08-16
3 Operation Theory
reduces and when it is lower than the low forward power setting, low forward power protection can
operate to alarm and output a contact or shutdown with a time delay. Usually generator low
forward power protection can be blocked by emergency shutdown binary input or main valve open
contact.
One time delay is configured for generator low forward power protection, it can operate to alarm
and output a contact or trip. The criterion of generator low forward power protection is:
Where:
The setting range of low forward power setting is (0.5%~100%)Pn, Pn is the rated active power of
the generator.
3.17.3 Logic
For generator low forward power protection, if following three conditions are met, the protection
will be enabled.
If generator low forward power protection is disabled, all the related output signals will be reset. If
no external input is configured to [32F.En1] ([32F.En2]), the default initial value of [32F.En1]
([32F.En2]) is “1”; if no external input is configured to [32F.Blk], the default initial value of [32F.Blk]
is “0”.
Date: 2016-08-16
3 Operation Theory
SIG P<[32F.P_Set]
&
EN [32.En_Alm] [32F.t_Op] 0ms [32F.Alm]
SIG [BI_UnderPower_Blk]
SIG [32F.En] &
SIG [32F.Blk]
SIG [32F.En]
&
SIG [32F.En1] [32F.St]
SIG [32F.En2] &
[32F.t_Op] 0ms
SIG [32F.Op]
[32F.Blk]
SIG P<[32F.P_Set]
SIG [BI_UnderPower_Blk]
0ms 500ms
SIG 32F.FD
Where:
32F.FD is the internal signal indicating that generator low forward power protection picks up (the
fault detector of fault detector DSP module).
32F
32F.POWER 32F.St
32F.En1 32F.Op
32F.En2 32F.Alm
32F.Blk
BI_UnderPower_Blk
Figure 3.17-2 Function block diagram of generator low forward power protection
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Date: 2016-08-16
3 Operation Theory
Table 3.17-3 Output signals of generator low forward power protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
3.17.5 Settings
Table 3.17-4 Settings list of generator low forward power protection
3.18.1 Application
Overexcitation protection is used to check the over-flux phenomenon during operation of the
generator and transformer. Abnormal voltage increase and abnormal frequency decline will lead to
the increase of flux density. When the flux density increase quickly over the rated flux density, it will
cause core saturation and resulting in great vortex, then it will lead to severe heating, the
insulation of the equipment will be damaged.
Date: 2016-08-16
3 Operation Theory
The ratio of voltage and frequency is adopted to check overexcitation, for the ratio is
proportional to the flux density (B) of the protected object
RMS of three phase-to-phase voltages is used to calculate the overexcitation multiple, which
is not affected by frequency fluctuation.
One stage definite-time overexcitation protection for tripping and one stage definite-time
overexcitation protection for alarm are equipped (with respective overexcitation multiple
setting and time delay).
n = U* / f* Equation 3.18-1
Where:
The reference value for calculating per unit value of voltage is generator secondary voltage, and
the reference value for calculating per unit value of frequency is rated frequency. During normal
operation, n = 1.
For example, if generator primary voltage is 20kV (i.e. [Gen.U1n_Plate]=20kV) and voltage
transformer ratio is 20kV/100V (i.e. [G_Term.VT1.U1n] =20kV, [G_Term.VT1.U2n]=100V). The
reference value for calculating per unit value of voltage is:
The device will calculate the voltage reference value automatically according to the above settings,
so the primary voltage of the protected equipment, the primary and secondary voltage of the
voltage transformer should be set correctly.
Tripping stage
Date: 2016-08-16
3 Operation Theory
For Definite-time overexcitation protection tripping stage, the operation equation is:
Where:
Alarm stage
For Definite-time overexcitation protection alarm stage, the operation equation is:
Where:
Users can set eight groups of overexcitation multiple and tripping time to simulate the inverse-time
operation characteristics curve and it can satisfy the overexcitation requirement of various
generator. For the overexcitation multiple between two overexcitation multiple settings, the
corresponding tripping time can be calculated via the internal piece-wise linear interpolation
method.
Date: 2016-08-16
3 Operation Theory
U*/f*
K0
K1
K2
K3
K4
K5
K6
K7
t0 t1 t2 t3 t4 t5 t6 t7 t(s)
The main harm of generator overexcitation is overheat, inverse-time characteristic curve can
roughly simulate the heat accumulation and dissipation process for generator overexcitation. Once
the generator overexcitation multiple over the lower limit of inverse-time overexcitation multiple
[Gen.24.IDMT.K7], the time will be accumulated. When accumulated time delay is larger than the
tripping time of overexcitation protection, a tripping command will be issued by the device. Once
the generator overexcitation multiple is less than the lower limit of inverse-time overexcitation
multiple [Gen.24.IDMT.K7], the inverse-time dissipation process starts. If the generator
overexcitation multiple is always less than the lower limit of inverse-time overexcitation multiple,,
the accumulated value will decrease to “0” gradually.
The eight groups of settings of inverse-time characteristic curve must meet following conditions:
K0≥K1 ≥ K2 ≥ K3 ≥ K4 ≥ K5 ≥ K6 ≥ K7
t0 ≤t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7
3.18.4 Logic
For overexcitation protection, if following three conditions are met, the protection will be enabled.
If overexcitation protection is disabled, all the related output signals will be reset. If no external
input is configured to [Gen.24.En1] ([Gen.24.En2]), the default initial value of [Gen.24.En1]
([Gen.24.En2]) is “1”; if no external input is configured to [Gen.24.Blk], the default initial value of
[Gen.24.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
EN [Gen.24.En]
SIG [Gen.24.En1] &
SIG U*/f*>[Gen.24.DT.K]
>=1
≥1
0ms 500ms
SIG Gen.24.DT.FD
[Gen.24.St]
EN [Gen.24.En]
SIG [Gen.24.En1] &
SIG U*/f*>[Gen.24.IDMT.K7]
0ms 500ms
SIG Gen.24.IDMT.FD
Where:
Gen.24.DT.FD is the internal signal indicating that the definite-time overexcitation protection picks
up (the fault detector of fault detector DSP module).
Gen.24.IDMT.FD is the internal signal indicating that the inverse-time overexcitation protection
picks up (the fault detector of fault detector DSP module).
24
Gen.24.U3P Gen.24.St
f Gen.24.DT.Op
Gen.24.En1 Gen.24.IDMT.Op
Gen.24.En2 Gen.24.Alm
Gen.24.Blk
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
4 Gen.24.Alm The alarm stage of overexcitation protection operates to issue alarm signal
Waveform recording
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
Date: 2016-08-16
3 Operation Theory
3.18.6 Settings
Table 3.18-5 Settings list of overexcitation protection
Date: 2016-08-16
3 Operation Theory
3.19.1 Application
Loss of excitation protection can reflects the generator abnormal operation condition due to failure
of generator excitation circuit. If a fault happens in excitation system or the excitation adjusting
device is abnormal, loss of excitation protection can prevent the generator running in
asynchronous state, and it can also prevent the stator and rotor from overheating. In addition, loss
of excitation protection can ensure the stability of the power grid is not endangered due to
underexcitation of large synchronous generators.
3.19.2 Function
Three stages of loss of excitation protection with respective impedance setting and time delay
are available.
The offset characteristics of impedance circle of each stage of loss of excitation protection
can be configured as forward offset or reverse offset.
Each stage of loss of excitation protection can be controlled by reverse reactive power
element (reverse reactive power element can be enabled or disabled by corresponding logic
setting).
Each stage of loss of excitation protection can be controlled by stator side busbar low voltage
element (stator side busbar low voltage element can be enabled or disabled by corresponding
logic setting).
Each stage of loss of excitation protection can be controlled by rotor low voltage element
(rotor low voltage element can be enabled or disabled by corresponding logic setting).
Date: 2016-08-16
3 Operation Theory
Reverse reactive power element, it provides reverse reactive power auxiliary releasing
function.
Stator side busbar low voltage element, it provides stator side busbar low voltage controlling
function.
Rotor low voltage element, it provides rotor low voltage controlling function.
Reverse Flag_RevQ
Power Stage1
reactive power 40G.St
element
Impedance 40G.Op
element
The voltage and current used in loss of excitation protection is the positive-sequence voltage and
voltage of generator terminal. The operation equation is
Z + jX B
270° ≥ Arg ≥ 90° Equation 3.19-1
Z − jX A
Where:
XA: it is the upper boundary setting of the impedance circle, it corresponds to the setting [40Gn.Za],
i.e. the impedance setting ZA of stage n of loss of excitation protection (n=1, 2 or 3).
XB: it is the lower boundary setting of the impedance circle, it corresponds to the setting [40Gn.Zb],
i.e. the impedance setting ZB of stage n of loss of excitation protection (n=1, 2 or 3).
Via the setting [40Gx.Opt_Offset_Z], users can select the offset characteristic (forward offset or
reverse offset) of the upper boundary of the impedance circle. If forward offset characteristic is
selected, the impedance circle is a static stabilization boundary impedance circle. If reverse offset
characteristic is selected, the impedance circle is an asynchronous impedance circle or a standard
impedance circle.
Date: 2016-08-16
3 Operation Theory
2
U gn × na
X= Xs × Equation 3.19-2
S gn × nv
A
2
U gn × na
XB =
−( X d ) × non-salient pole generator
S gn × nv
X d +X q U gn2
× na
XB =
−( )× salient pole generator
2 S gn × nv
Where:
X s is per unit value (takes generator apparent power as the referenced capacity) of the maximum
tie reactance between the generator and system (including the impedance of step-up transformer).
X d ' and X d are per unit value of transient reactance and direct-axis synchronous reactance of
generator respectively.
U gn and S gn are rated voltage and rated apparent power of generator respectively.
X d' U gn × na
2
XA =
− × Equation 3.19-3
2 S gn × nv
2
U gn × na
XB =
−( X d ) × non-salient pole generator
S gn × nv
X d +X q U gn2
× na
XB =
−( )× salient pole generator
2 S gn × nv
Date: 2016-08-16
3 Operation Theory
X ' U gn × na
2
XA =
− d ×
2 S gn × nv
Equation 3.19-4
X U × na
' 2
X B =−(1 + d gn
)
2 S gn × nv
Where:
The diameter of the standard impedance circle is 1.0p.u (per unit value is 1, takes generator
apparent power as the referenced capacity).
jx
R
Static stabilization boundary
impedance circle
Following auxiliary criteria are used for the impedance element loss of excitation protection.
The negative-sequence voltage U2<0.1Un (Un is the rated voltage of the generator)
The generator current Ig≥0.1In (In is the rated current of CT of the generator)
Where:
Date: 2016-08-16
3 Operation Theory
This criterion is mainly used to prevent the system voltage collapse and widespread power cut due
to inadequate reactive power reserve which caused by generator loss of excitation or
underexcitation fault. The voltage used for system low voltage criterion is derived from the HV side
VT of the main transformer, if main transformer HV side VT circuit failure happens, system low
voltage criterion will be blocked.
Where:
U L _ Set1 is the system low voltage setting [Tr_HVS.Upp_VCE], generally it takes 90%~95% of the
The voltage setting of generator terminal low voltage criterion should be set to not destroy the
safety of auxiliary power and it should be lower than the forced excitation pick up voltage. The
voltage used for generator terminal low voltage criterion is derived from the generator terminal VT,
if generator terminal VT circuit failure happens, generator terminal low voltage criterion will be
blocked.
Where:
U L _ Set 2 is the generator terminal low voltage setting [G_Term.Upp_VCE], generally it takes
Generally, stage 1 of loss of excitation protection adopts system low voltage criterion and stage 2
of loss of excitation protection adopts generator terminal low voltage criterion.
If the rotor voltage input mode setting [40G.Opt_U_Rot] is set as “0”, means rotor voltage directly
input mode is adopted. If the rotor voltage input mode setting [40G.Opt_U_Rot] is set as “1”,
means 4~20mA transducer input mode is adopted, i.e. the rotor voltage is converted as 4~20mA
signal via the transducer, then the 4~20mA signal is input to the device. The setting transducer
input voltage upper limit value [Umax_Rot_Transducer] should be set according to the rotor
voltage that corresponds to 20mA signal. The 4~20mA signal will be converted into rotor voltage
according to the setting [Umax_Rot_Transducer], then the converted rotor voltage will be
displayed.
Date: 2016-08-16
3 Operation Theory
The rotor voltage described below is the directly input rotor voltage or the rotor voltage converted
from 4~20mA signal.
Where:
Ur1set is the rotor low voltage setting [40G.U_UV_Rot], generally it takes 60%~80% of the
generator no-load rated excitation voltage.
Ur < Kxs*(P-Pt)*Uf0
Equation 3.19-9
Kxs =Krel*(Xd+Xs)
Where:
Pt is the per unit value of generator salient pole power, for hydro-generator, Pt= 0.5* (1/Xq∑-
1/Xd∑); for turbo-generator, Pt=0;
Xd is the per unit value of generator direct-axis synchronous reactance, and Xs is the per unit
value of system tie reactance.
If the rotor voltage Ur drops to zero or minus value suddenly during loss of excitation, the rotor low
voltage criterion will be met quickly (before the static stability limit of the generator reaches). If Ur
drops to zero or reduces to a value gradually during underexcitation or loss of excitation fault, the
variable excitation voltage criterion will be met. Underexcitation or loss of excitation fault will cause
out-of-step, and then the rotor voltage Ur and the output power of the generator will swing
seriously. In this case, the rotor low voltage criterion and the variable excitation voltage criterion
will be met and reset periodically in general. So the rotor voltage element will reset with a time
delay after out-of-step happens (the measured impedance fall into the static stabilization boundary
impedance circle).
3.19.4 Logic
For each stage of loss of excitation protection, if following three conditions are met, the protection
will be enabled.
Date: 2016-08-16
3 Operation Theory
If loss of excitation protection is disabled, all the related output signals will be reset. If no external
input is configured to [40Gn.En1] ([40Gn.En2]), the default initial value of [40Gn.En1] ([40Gn.En2])
is “1”; if no external input is configured to [40Gn.Blk], the default initial value of [40Gn.Blk] is “0”
(n=1, 2 or 3).
SET [40Gn.En_Alm]
&
EN [40Gn.En] [40Gn.t_Op] 0ms
[40Gn.Alm]
SIG [40Gn.Blk]
[40Gn.t_Op] 0ms
[40Gn.Op]
SET [40Gn.En_BusUV]
SET [40Gn.En_RotUV]
EN [40Gn.En]
SIG [40Gn.En1] &
SIG [40Gn.En2]
SIG [40Gn.Blk]
0ms 500ms
SIG 40Gn.FD
Where:
Op_StaUV is the internal signal indicating that Equation 3.19-6 or Equation 3.19-7 is met;
Op_RotUV is the internal signal indicating that Equation 3.19-8 or Equation 3.19-9 is met;
40Gn.FD is the internal signal indicating that stage n of loss of excitation protection picks up (the
fault detector of fault detector DSP module).
40G
40Gn.U3P 40Gn.St
40Gn.I3P 40Gn.Op
40Gn.POWER 40Gn.Alm
40Gn.En1
40Gn.En2
40Gn.Blk
40Gn.RotVolt_Ctrl
40Gn.StaVolt_Ctrl
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Alarm signals
4 40Gn.Alm_RotVoltCircuit Rotor voltage circuit failure alarm for stage n of loss of excitation protection.
Waveform recording
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
Date: 2016-08-16
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Misc Prot Values
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen ExcLoss Prot Values
3.19.6 Settings
Table 3.19-5 Settings list of loss of excitation protection
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.20.1 Application
When a fault occurs in power system, the current increases and generator phase overcurrent
protection operates to avoid damages to protected equipment. Voltage controlled element can be
selected to improve the sensitivity of generator phase overcurrent protection and direction element
can be selected to improve the selectivity of the protection. For self and parallel-excited generator,
current will decrease so quick during fault that it may be lower than overcurrent setting before
tripping. So memorizing function for fault current can be enabled for this phase overcurrent
protection.
An external fault will result in generator overload, it will lead to damage of generator if the fault can
not be cut off quickly, in this case generator phase overcurrent protection can operate to trip
generator circuit breaker to avoid physical damage. For small-scale generator, generator phase
overcurrent protection can protect generator from internal fault, for large-scale generator,
generator phase overcurrent protection is applied as the backup protection of generator differential
protection.
Three-stage generator phase overcurrent protection with independent logic, current and time
delay settings.
Stage 1 and stage 2 are definite-time characteristic, stage 3 can be selected as definite-time
or inverse-time characteristic. The inverse-time characteristic is selectable among IEC and
ANSI/IEEE standard inverse-time characteristics and a user-defined inverse-time curve.
Voltage controlled element can be selected to control each stage of generator phase
overcurrent protection.
Direction element can be selected to control each stage of generator phase overcurrent
protection with three options: no direction, forward direction and reverse direction.
Memorizing function for fault current can be enabled or disabled for each stage of generator
phase overcurrent protection.
Phase overcurrent element: each stage is equipped with one independent overcurrent
element.
Voltage controlled element: one voltage controlled element shared by all phase overcurrent
elements.
Date: 2016-08-16
3 Operation Theory
Direction element: one direction element shared by all phase overcurrent elements.
U3P
Stage 1
[Alm_VTS] Direction Direction signal St
Element
Overcurrent Op
Element
voltage signal
Voltage Stage 2
Control St
Element Overcurrent Op
Element
I3P
Stage 3
St
Overcurrent Op
Element
The operation criterion of each stage of generator phase overcurrent protection is:
Where:
If any phase current is larger than the current setting of any enabled stage of generator phase
overcurrent protection, voltage controlled element operates (or voltage controlled element is
disabled), and direction element operates (or direction element is disabled), the stage of generator
phase overcurrent protection will operate after a settable time delay. The stage generator phase
overcurrent protection will drop off instantaneously or with a memorizing time delay (if the fault
current memorizing function is enabled) after fault current disappears.
Generator phase overcurrent protection stage 1 and stage 2 are definite-time characteristic and
each stage can perform instantaneous operation if the corresponding time delay setting is set as
“0”. Stage 3 can be selected as definite-time or inverse-time characteristic, and inverse-time
operating time curve is as follows.
Date: 2016-08-16
3 Operation Theory
t(I) =
K
+ C × TP Equation 3.20-2
I α
( ) −1
I set
Where:
I set is the base current setting, corresponds to the setting [Gen.50/51P3.Ib_Set]. The maximum
operating current of the circuit should be taken into account, it should not pick up for overload.
The user can select the operating characteristic from various inverse-time characteristic curves by
the setting [Gen.50/51P3.Opt_Curve], and parameters of available characteristics for selection are
shown in the following table.
Table 3.20-1 Inverse-time curve parameters of stage 3 of generator phase overcurrent protection
0 Definite time
13 Programmable user-defined
If all available curves do not comply with user application, user can configure
[Gen.50/51P3.Opt_Curve] as “13” to customize the inverse-time curve characteristic (by
Date: 2016-08-16
3 Operation Theory
Generator phase overcurrent protection is equipped as the backup protection of generator and
adjacent power equipment, and voltage element is usually used to control generator phase
overcurrent protection to improve sensitivity of the protection. Unsymmetrical fault will result in
unsymmetrical sequence voltages and symmetrical fault will lead to low three phase voltages at
relay location. If voltage element is enabled, generator phase overcurrent protection can operate if
the sequence voltage is larger than a setting or phase-to-phase voltage is lower than a setting, so
current settings of generator phase overcurrent protection can be set lower with high sensitivity.
The voltage controlled element picks up if phase-to-phase voltage is lower than its setting or
negative-sequence voltage is larger than its setting.
Criteria:
Where:
Voltage of any side can be used as the input of voltage controlled element through PCS-Explorer2.
Effect of VT Circuit
The logic setting [Gen.50/51P.En_VTS_Blk] is used to control the voltage controlled element of
generator phase overcurrent protection during VT circuit failure. When VT circuit fails, if setting
[Gen.50/51P.En_VTS_Blk] is set as “1”, the voltage controlled element will not pick up when VT
circuit fails; if the setting is set as “0”, and voltage controlled element meet the criterion, voltage
controlled element will pick up.
For self and parallel-excited generator, current will decrease so quick during fault that it may be
lower than overcurrent setting before tripping. So memorizing function for fault current is equipped
with this protection. Once the generator phase overcurrent protection picks up and the voltage
Date: 2016-08-16
3 Operation Theory
controlled element operates, memorizing function is equipped to make the protection operates to
trip reliably. The logic setting [Gen.50/51Pn.En_CurrMem] should be set as “1” for self and
parallel-excited generator. Meanwhile, the voltage controlled element for generator phase
overcurrent protection should be enabled. If voltage controlled element is disabled, fault current
memorizing function will quit automatically. If fault current is smaller than 10% of the setting
[Gen.50/51Pn.I_Set], the fault will be thought as cut off, then fault current memorizing function will
quit automatically.
Direction element can be selected to control generator phase overcurrent protection to coordinate
with other protections of power grid. If the element is selected for generator phase overcurrent
protection, then the protection becomes directional overcurrent protection.
When a fault occurs at forward direction, the angle between polarizing voltage U ref and fault
U
ϕ k = arg ref Equation 3.20-3
I dir
U
ϕ ′k = arg ref = 180° + ϕ k Equation 3.20-4
I dir
Assuming that relay characteristic angle is ϕ sen (corresponds to the setting [Gen.50/51P.RCA]),
i.e. the angle polarizing voltage leading fault current, in order to ensure the direction element can
operate reliably, the angle range of the forward direction is:
U ref <
ϕ sen − 90° < arg ϕ sen + 90° Equation 3.20-5
I dir
If VT and CT are connected as following figure, i.e. positive polarity of CT is at busbar side, points
to the protected object, then the operation zone of forward and reverse direction element are
shown in Figure 3.20-3 (Wherein the hatched portion is the operation zone of forward direction
Date: 2016-08-16
3 Operation Theory
Reverse Forward
CT
Protected
Object
VT
Direction
Element
Reverse
Uref(U1)
Φsen
Φsen+180°
Idir(Ip)
Forward
Effect of VT Circuit
The logic setting [Gen.50/51P.En_VTS_Blk] is used to control the direction element of generator
phase overcurrent protection during VT circuit failure. When VT circuit fails, if setting
[Gen.50/51P.En_VTS_Blk] is set as “1”, the direction element will not pick up when VT circuit fails;
if the setting is set as “0”, and direction element meet the criterion, direction element will pick up.
3.20.4 Logic
Logic diagram of generator phase overcurrent is shown in the following figure, including phase
overcurrent element, voltage controlled element and direction element, fault current memorizing
function and enabling and blocking logic of the protection.
Function Enable/Disable
For stage n of generator phase overcurrent protection, if following three conditions are met, stage
n of generator phase overcurrent protection is enabled.
(2) The protection function enabling inputs [Gen.50/51Pn.En1], [Gen.50/51Pn.En2] are “1”
Date: 2016-08-16
3 Operation Theory
If generator phase overcurrent protection is disabled, all the related output signals will be reset. If
no external input is configured to [Gen.50/51Pn.En1] ([Gen.50/51Pn.En2]), the default initial value
of [Gen.50/51Pn.En1] ([Gen.50/51Pn.En2]) is “1”; if no external input is configured to
[Gen.50/51Pn.Blk], the default initial value of [Gen.50/51Pn.Blk] is “0”.
EN [Gen.50/51Pn.En]
SIG [Gen.50/51Pn.En1] &
SIG [Gen.50/51Pn.En2]
SIG [Gen.50/51Pn.Blk]
SIG [Gen.50/51P.I3P]
& &
[Gen.50/51Pn.St]
SET [Gen.50/51Pn.I_Set]
0ms 500ms
SIG Gen.50/51Pn.FD
Where:
[Gen.50/51Pn.VCE.Op] is the signal indicating that the voltage controlled element operates.
50/51Pn.FD is the internal signal indicating that stage n of generator phase overcurrent protection
picks up (the fault detector of fault detector DSP module).
EN [Gen.50/51P.En_VTS_Blk]
Figure 3.20-5 Logic diagram of phase-to-phase VCE of generator phase overcurrent protection
Date: 2016-08-16
3 Operation Theory
EN [Gen.50/51P.En_VTS_Blk]
Figure 3.20-6 Logic diagram of negative-sequence VCE of generator phase overcurrent protection
Where:
U ΦΦ
is the phase-to-phase voltage.
EN [Gen.50/51P.En] &
Fwd/Rev
SET [Gen.50/51P.Opt_Dir]
EN [Gen.50/51P.En_VTS_Blk]
Figure 3.20-7 Logic diagram of direction element of generator phase overcurrent protection
Where:
[Gen.50/51P.DIR.Op] is the internal signal indicating that the direction element operates.
Date: 2016-08-16
3 Operation Theory
50/51P
Gen.50/51Pn.I3P Gen.50/51Pn.St
Gen.50/51Pn.U3P Gen.50/51Pn.Op
Gen.50/51Pn.En1
Gen.50/51Pn.En2
Gen.50/51Pn.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.20-4 Output signals of generator phase overcurrent protection (event recorder)
Tripping reports
Start signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values->Gen PPF Prot Values
3.20.6 Settings
Table 3.20-6 Settings list of generator phase overcurrent protection
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.21.1 Application
In the power system, there many causes will lead to overvoltage, such as mal-operation of the
excitation system, fault of voltage automatic adjustment device, load shedding due to full load of
generator, disconnection between generator and the system or isolated operation of the generator.
Overvoltage protection is provided to protect the operating equipment against the risk due to
abnormal rise of voltage.
Date: 2016-08-16
3 Operation Theory
Two-stage phase overvoltage protection for tripping and one-stage phase overvoltage
protection for alarm are available (with respective voltage setting, time delay and logic
setting).
Stage 1 of phase overvoltage protection for tripping and the phase overvoltage protection for
alarm are definite-time overvoltage protection fixedly, stage 2 of phase overvoltage
protection for tripping can be configured as inverse-time overvoltage protection (IDMT) or
definite-time overvoltage protection by the setting [Gen.59P2.Opt_Curve] (0: definite-time
characteristic, 1: inverse-time characteristic).
When phase-to-phase voltage is larger than corresponding voltage setting, corresponding stage of
overvoltage protection will pick up and operate with a settable time delay.
Where:
Stage 1 of phase overvoltage protection for tripping and the phase overvoltage protection for alarm
are definite-time overvoltage protection fixedly.
Stage 2 of phase overvoltage protection for tripping can be configured as inverse-time overvoltage
protection (IDMT) or definite-time overvoltage protection by the setting [Gen.59P2.Opt_Curve] (0:
definite-time characteristic, 1: inverse-time characteristic), the equation of inverse-time
characteristic is:
Date: 2016-08-16
3 Operation Theory
TP
t=
U Equation 3.21-2
−1
U set
Where:
3.21.4 Logic
For each stage of phase overvoltage protection, if following three conditions are met,
corresponding stage of phase overvoltage protection will be enabled.
(2) The protection function enabling inputs [Gen.59Pn.En1], [Gen.59Pn.En2] are “1”
If overvoltage protection is disabled, all the related output signals will be reset. If no external input
is configured to [Gen.59Pn.En1] ([Gen.59Pn.En2]), the default initial value of [Gen.59Pn.En1]
([Gen.59Pn.En2]) is “1”; if no external input is configured to [Gen.59Pn.Blk], the default initial value
of [Gen.59Pn.Blk] is “0”.
SIG [Gen.59PAlm.U3P]
&
SET [Gen.59PAlm.Upp_Set] [Gen.59PAlm.St]
EN [Gen.59Pn.En] &
SIG [Gen.59Pn.Blk]
Timer
Gen.59PAlm.t_Op
[Gen.59PAlm.Alm]
EN [Gen.59Pn.En]
SIG [Gen.59Pn.En1] &
SIG [Gen.59Pn.En2]
SIG [Gen.59Pn.Blk]
Where:
[Gen.59Pn.U3P] is the three-phase voltage input for alarm or tripping stage of phase overvoltage
protection.
59Pn.FD is the signal to indicate that the fault detector of overvoltage protection picks up (the fault
detector of fault detector DSP module).
Date: 2016-08-16
3 Operation Theory
Gen.59Pn.En2 Gen.59PAlm.En2
Gen.59Pn.Blk Gen.59PAlm.Blk
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
3 Gen.59PAlm.Alm Phase overvoltage protection alarm stage operates to issue alarm signal.
Start signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen Volt Prot Values
3.21.6 Settings
Table 3.21-5 Settings list of phase overvoltage protection
Date: 2016-08-16
3 Operation Theory
3.22.1 Application
Undervoltage protection is used to detect the voltage decline of the operating motor, so to avoid
the impermissible operating conditions and the possible loss of stability. When the system voltage
decline to a certain degree so that the system stability will be affected, undervoltage protection can
be used as the operation criterion of load shedding.
Two-stage phase undervoltage protection for tripping and one-stage phase undervoltage
protection for alarm are available (with respective voltage setting, time delay and logic
setting).
Stage 1 of phase undervoltage protection for tripping and the phase undervoltage protection
for alarm are definite-time undervoltage protection fixedly, stage 2 of phase undervoltage
protection for tripping can be configured as inverse-time undervoltage protection (IDMT) or
definite-time undervoltage protection by the setting [Gen.27P2.Opt_Curve] (0: definite-time
characteristic, 1: inverse-time characteristic).
When phase-to-phase voltage is lower than corresponding voltage setting and the auxiliary
criterion is also met, corresponding stage of undervoltage protection will pick up and operate with
Date: 2016-08-16
3 Operation Theory
Where:
Stage 1 of phase undervoltage protection for tripping and the phase undervoltage protection for
alarm are definite-time undervoltage protection fixedly.
TP
t=
U Equation 3.22-2
1−
U set
Where:
Undervoltage protection can be blocked by the normally open auxiliary contact of the circuit
breaker [Flg_52a]. If [Flg_52a] is “0”, undervoltage protection is blocked. Besides, the normally
open auxiliary contact of the circuit breaker can be replaced by the internal signal that indicating
the generator is connected with the system.
The undervoltage protection is also controlled by the load current, only if any phase current is
larger than 0.04In (the signal [Gen.27Px.Flg_OnLoad]=1), the undervoltage protection can be
enabled.
When a fault happens at the secondary circuit of VT, the undervoltage protection tripping stage
can be blocked by a binary input signal (such as VT MCB auxiliary contact and etc.). The output
Date: 2016-08-16
3 Operation Theory
signal of VT circuit supervision function can also be adopted to block the undervoltage protection.
[Flg_52a], [Gen.27Px.Flg_OnLoad] and the VT abnormal binary input (or signal) can be configured
by the software PCS-Explorer2.
3.22.4 Logic
For each stage of phase undervoltage protection, if following three conditions are met,
corresponding stage of phase undervoltage protection will be enabled.
(2) The protection function enabling inputs [Gen.27Pn.En1], [Gen.27Pn.En2] are “1”
If undervoltage protection is disabled, all the related output signals will be reset. If no external input
is configured to [Gen.27Pn.En1] ([Gen.27Pn.En2]), the default initial value of [Gen.27Pn.En1]
([Gen.27Pn.En2]) is “1”; if no external input is configured to [Gen.27Pn.Blk], the default initial value
of [Gen.27Pn.Blk] is “0”.
0ms 500ms
SIG Gen.27Pn.FD
Timer
t
[Gen.27Pn.Op]
t
Where:
n=1 or 2 or Alm;
Gen.27Pn.FD is the internal signal to indicate that stage n of undervoltage protection picks up (the
fault detector of fault detector DSP module).
Date: 2016-08-16
3 Operation Theory
Gen.27Pn.En2 Gen.27PAlm.En2
Gen.27Pn.Blk Gen.27PAlm.Blk
Flg_52a Flg_52a
Gen.27Pn.Flg_Onload Gen.27PAlm.Flg_Onload
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
3 Gen.27PAlm.Alm Phase undervoltage protection alarm stage operates to issue alarm signal.
Start signals
Date: 2016-08-16
3 Operation Theory
Waveform recording
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Gen Volt Prot Values
3.22.6 Settings
Table 3.22-5 Settings list of undervoltage protection
Date: 2016-08-16
3 Operation Theory
3.23.1 Application
When active power surplus happens to the power system or the speed regulating system of
generator is in abnormal operation, the frequency of the power system will rise, so overfrequency
protection can be used to detect the above abnormal over-frequency conditions. If the frequency is
larger than the overfrequency protection setting, overfrequency protection will operate to issue
alarm signal or trip with a time delay.
Steam-turbine generator is able to withstand the frequency shifting, but this will leads to the
vibration of the turbine blade which will eventually cause the metal fatigue damage of the blade.
This kind of damage is a process of accumulation and it is irreversible, therefore, when the
frequency protection is applied for steam-turbine generator, a feature of frequency accumulation is
required.
Four stages of overfrequency protection (with respective frequency setting, time delay and
logic setting) are available. Each stage can be configured to issue alarm signal or trip.
Four stages of overfrequency band accumulate protection are available and each stage has
respective frequency upper limit setting, lower limit frequency setting, accumulated time
setting and logic setting. Each stage can be configured to issue alarm signal or trip.
When the system frequency is larger than the overfrequency setting, the protection picks up, after
Date: 2016-08-16
3 Operation Theory
a time delay determined by the time delay setting, the overfrequency protection will operate to
issue alarm signal or trip. If the frequency accumulation function is enabled, i.e. the logic setting
[81O.OFx.En_Alm_Accu] or [81O.OFx.En_Trp_Accu] (x=1~4) is set as “1”, the relay will
accumulate the time that the system frequency falling into the corresponding overfrequency band,
if the accumulated time is larger than the corresponding time delay setting, the overfrequency
band accumulate protection will operate to issue alarm signal or trip.
The positive voltage is used to calculate the system frequency, after a filtering process, the
measurement of system frequency will not be affected by the harmonic component.
Where:
f is system frequency.
Where:
f is system frequency.
[81O.OFx.f_Set] is the lower limit frequency setting of stage x (x=1~4) of overfrequency band
accumulate protection.
[81U.UFx’.f_Set] is the upper limit frequency setting of stage x (x=1~4) of overfrequency band
accumulate protection.
If x=1~3, x’=x+1.
If the setting [81O.En_NVM_Accu] is set as “0”, the accumulation value will be cleared
automatically when this protection is reverted. If the setting [81O.En_NVM_Accu] is set as “1”, the
accumulation value will be kept even this protection is reverted or this device is re-energized,
when this protection is picked up again, the accumulation value will be accumulated continuously
on the base of present accumulation value. The accumulation value can be cleared by energizing
the binary input [81O.Clear].
Date: 2016-08-16
3 Operation Theory
3.23.4 Logic
For overfrequency protection, when following three conditions are met, the protection is enabled.
(2) The protection function enabling binary inputs [81O.En1] and [81O.En2] are “1”
If overfrequency protection is disabled, all the related output signals will be reset. If no external
input is configured to [81O.En1] ([81O.En2]), the default initial value of [81O.En1] ([81O.En2]) is
“1”; if no external input is configured to [81O.Blk], the default initial value of [81O.Blk] is “0”.
EN [81O.En] &
SIG [81O.Blk] &
[81O.OFx.t_Op] 0s
[81O.OFx.Alm]
EN [81O.OFx.En_Alm] &
& [81O.St]
EN [81O.En]
& [81O.OFx.t_Op] 0s
EN [81O.OFx.En_Trp] &
[81O.OFx.Op]
SIG f > [81O.OFx.f_Set]
0 500ms
SIG 81O.FD
EN [81O.En] &
SIG [81O.Blk]
SIG [81O.Flg_OnLoad]
&
[81O.OF1.t_Accu] 0s
[81O.OF1.Alm_Accu]
EN [81O.OF1.En_Alm_Accu] &
SIG [81O.OF2.f_Set]>f>[81O.OF1.f_Set]
& [81O.St]
EN [81O.En]
& [81O.OF1.t_Accu] 0s
EN [81O.OF1.En_Trp_Accu] &
[81O.OF1.Op_Accu]
SIG [81O.OF2.f_Set]>f>[81O.OF1.f_Set]
0 500ms
SIG 81O.FD
The stage 2 and stage 3 of overfrequency band accumulate protection are similar to stage 1 of
overfrequency band accumulate protection.
Date: 2016-08-16
3 Operation Theory
EN [81O.En] &
SIG [81O.Blk]
SIG [81O.Flg_OnLoad]
&
[81O.OF4.t_Accu] 0s
[81O.OF4.Alm_Accu]
EN [81O.OF4.En_Alm_Accu] &
SIG f>[81O.OF4.f_Set]
& [81O.St]
EN [81O.En]
& [81O.OF4.t_Accu] 0s
EN [81O.OF4.En_Trp_Accu] &
[81O.OF4.Op_Accu]
SIG f>[81O.OF4.f_Set]
0 500ms
SIG 81O.FD
Where:
f is system frequency.
81O.FD is the internal signal to indicate that overfrequency protection picks up (the fault detector
of fault detector DSP module).
81O
f 81O.St
81O.En1 81O.OF1.Op
81O.En2 81O.OF2.Op
81O.Blk 81O.OF3.Op
81O.Flg_OnLoad 81O.OF4.Op
Flg_52a 81O.OF1.Op_Accu
Clear 81O.OF2.Op_Accu
81O.OF3.Op_Accu
81O.OF4.Op_Accu
81O.OF1.Alm
81O.OF2.Alm
81O.OF3.Alm
81O.OF4.Alm
81O.OF1.Alm_Accu
81O.OF2.Alm_Accu
81O.OF3.Alm_Accu
81O.OF4.Alm_Accu
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Date: 2016-08-16
3 Operation Theory
Start signals
Alarm signals
Waveform recording
IO events
Date: 2016-08-16
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Freq Prot Values
3.23.6 Settings
Table 3.23-5 Settings list of overfrequency protection
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.24.1 Application
When the power system requires more active power or the speed regulating system of generator
is in abnormal operation, the frequency of the power system will decline, so underfrequency
protection can be used to detect the above abnormal low-frequency conditions. If the frequency is
lower than the underfrequency protection setting, underfrequency protection will operate to issue
alarm signal or trip with a time delay.
Steam-turbine generator is able to withstand the frequency shifting, but this will leads to the
vibration of the turbine blade which will eventually cause the metal fatigue damage of the blade.
This kind of damage is a process of accumulation and it is irreversible, therefore, when the
frequency protection is applied for steam-turbine generator, a feature of frequency accumulation is
required.
Four stages of underfrequency protection (with respective frequency setting, time delay and
logic setting) are available. Each stage can be configured to issue alarm signal or trip.
Four stages of underfrequency band accumulate protection are available and each stage has
respective frequency upper limit setting, lower limit frequency setting, accumulated time
setting and logic setting. Each stage can be configured to issue alarm signal or trip.
When the system frequency is smaller than the underfrequency setting, the protection picks up,
Date: 2016-08-16
3 Operation Theory
after a time delay determined by the time delay setting, the underfrequency protection will operate
to issue alarm signal or trip. If the frequency accumulation function is enabled, i.e. the logic setting
[81U.UFx.En_Alm_Accu] or [81U.UFx.En_Trp_Accu] (x=1~4) is set as “1”, the relay will
accumulate the time that the system frequency falling into the corresponding underfrequency band,
if the accumulated time is larger than the corresponding time delay setting, the underfrequency
band accumulate protection will operate to issue alarm signal or trip.
The positive voltage is used to calculate the system frequency, after a filtering process, the
measurement of system frequency will not be affected by the harmonic component.
Where:
f is system frequency.
Where:
f is system frequency.
[81U.UFx.f_Set] is the upper limit frequency setting of stage x (x=1~4) of underfrequency band
accumulate protection.
[81U.UFx’.f_Set] is the lower limit frequency setting of stage x (x=1~4) of underfrequency band
accumulate protection.
If the setting [81U.En_NVM_Accu] is set as “0”, the accumulation value will be cleared
automatically when this protection is reverted. If the setting [81U.En_NVM_Accu] is set as “1”, the
accumulation value will be kept even this protection is reverted or this device is re-energized,
when this protection is picked up again, the accumulation value will be accumulated continuously
on the base of present accumulation value. The accumulation value can be cleared by energizing
the binary input [81U.Clear].
3.24.4 Logic
For underfrequency protection, when following three conditions are met, the protection is enabled.
Date: 2016-08-16
3 Operation Theory
(2) The protection function enabling binary inputs [81U.En1] and [81U.En2] are “1”
If underfrequency protection is disabled, all the related output signals will be reset. If no external
input is configured to [81U.En1] ([81U.En2]), the default initial value of [81U.En1] ([81U.En2]) is “1”;
if no external input is configured to [81U.Blk], the default initial value of [81U.Blk] is “0”.
EN [81U.En] &
SIG [81U.Blk]
SIG [81U.Flg_OnLoad]
&
[81U.UFx.t_Op] 0s
[81U.UFx.Alm]
EN [81U.UFx.En_Alm] &
& [81U.St]
EN [81U.En]
& [81U.UFx.t_Op] 0s
EN [81U.UFx.En_Trp] &
[81U.UFx.Op]
SIG f < [81U.UFx.f_Set]
0 500ms
SIG 81U.FD
EN [81U.En] &
SIG [81U.Blk]
SIG [81U.Flg_OnLoad]
&
[81U.UF1.t_Accu] 0s
[81U.UF1.Alm_Accu]
EN [81U.UF1.En_Alm_Accu] &
& [81U.St]
EN [81U.En]
& [81U.UF1.t_Accu] 0s
EN [81U.UF1.En_Trp_Accu] &
[81U.UF1.Op_Accu]
SIG [81U.UF2.f_Set]<f< [81U.UF1.f_Set]
0 500ms
SIG 81U.FD
The stage 2 and stage 3 of underfrequency band accumulate protection are similar to stage 1 of
underfrequency band accumulate protection.
Date: 2016-08-16
3 Operation Theory
EN [81U.En] &
SIG [81U.Blk]
SIG [81U.Flg_OnLoad]
&
[81U.UF4.t_Accu] 0s
[81U.UF4.Alm_Accu]
EN [81U.UF4.En_Alm_Accu] &
& [81U.St]
EN [81U.En]
& [81U.UF4.t_Accu] 0s
EN [81U.UF4.En_Trp_Accu] &
[81U.UF4.Op_Accu]
SIG 0<f< [81U.UF4.f_Set]
0 500ms
SIG 81U.FD
Where:
f is system frequency.
81U.FD is the internal signal to indicate that underfrequency protection picks up (the fault detector
of fault detector DSP module).
81U
f 81U.St
81U.En1 81U.UF1.Op
81U.En2 81U.UF2.Op
81U.Blk 81U.UF3.Op
81U.Flg_OnLoad 81U.UF4.Op
Flg_52a 81U.UF1.Op_Accu
Clear 81U.UF2.Op_Accu
81U.UF3.Op_Accu
81U.UF4.Op_Accu
81U.UF1.Alm
81U.UF2.Alm
81U.UF3.Alm
81U.UF4.Alm
81U.UF1.Alm_Accu
81U.UF2.Alm_Accu
81U.UF3.Alm_Accu
81U.UF4.Alm_Accu
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Date: 2016-08-16
3 Operation Theory
Start signals
Alarm signals
Waveform recording
IO events
Date: 2016-08-16
3 Operation Theory
Access Path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Freq Prot Values
3.24.6 Settings
Table 3.24-5 Settings list of underfrequency protection
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
3 Operation Theory
3.25.1 Application
When generator phase overcurrent protection cannot meet the sensitivity requirement of
generator and transformer backup protection, generator impedance protection can be configured.
The operation mode of power system has little effect on impedance protection, so impedance
protection can coordinate with protections of adjacent equipment easily.
Two stage phase-to-phase impedance protection elements with respective impedance setting,
time delay setting and logic setting.
Two stage phase-to-earth impedance protection elements with respective impedance setting,
time delay setting and logic setting.
Date: 2016-08-16
3 Operation Theory
The fault detector of impedance protection includes the DPFC phase-to-phase current fault
detector and the negative-sequence current fault detector. The fault detector output signal will last
for 500ms after the corresponding fault detector picks up, if phase-to-phase or phase-to-earth
impedance relay operates within 500ms, the fault detector output signal will be kept.
Where:
∆I t is the floating threshold value which will arise automatically and gradually according to
increasing of the current changing. The coefficient takes 1.25 in order to ensure the threshold
current is always slightly larger than the unbalance output, so the protection will not mal-operate
under power swing and frequency shifting condition.
Where:
If VT and CT are connected as following figure, i.e. the positive polarity of CT is at busbar side,
points to the protected object, then the setting [Y.21Mx.ZP.Opt_Dir] and [Y.21Mx.ZG.Opt_Dir]
should be set as “1”. Otherwise [Y.21Mx.ZP.Opt_Dir] and [Y.21Mx.ZG.Opt_Dir] should be set as “0”.
Date: 2016-08-16
3 Operation Theory
Reverse Forward
CT
Protected
Object
VT
Direction
Element
Following figure shows operating characteristic of phase-to-phase impedance relay, the setting
[Y.21Mx.RCA] (x=1 or 2) is impedance characteristic angle (i.e. ϕ m shown in the following figure,
it is also called reach angle). In the figure, if the setting [Y.21Mx.ZP.Opt_Dir] is “1”, Zn is the
reverse impedance setting [Y.21Mx.ZP.Z_Rev] and Zp is the forward impedance setting
[Y.21Mx.ZP.Z_Fwd]. If the setting [Y.21Mx.ZP.Opt_Dir] is “0”, Zn is the forward impedance setting
[Y.21Mx.ZP.Z_Fwd] and Zp is the reverse impedance setting [Y.21Mx.ZP.Z_Rev].
jx
IZ p
U − IZ
p
U
ϕm
R
U + IZ
− IZ n
n
Date: 2016-08-16
3 Operation Theory
Where:
NOTICE!
Following figure shows operating characteristic of phase-to-earth impedance relay, the setting
[Y.21Mx.RCA] (x=1 or 2) is impedance characteristic angle (i.e. ϕ m shown in the following figure,
it is also called reach angle). In the figure, If the setting [Y.21Mx.ZG.Opt_Dir] is “1”, Zn is the
reverse impedance setting [Y.21Mx.ZG.Z_Rev] and ZG is the forward impedance setting
[Y.21Mx.ZG.Z_Fwd]. If the setting [Y.21Mx.ZG.Opt_Dir] is “0”, Zn is the forward impedance setting
[Y.21Mx.ZG.Z_Fwd] and ZG is the reverse impedance setting [Y.21Mx.ZG.Z_Rev].
jx •
I ϕ ZG
• •
Uϕ − I ϕ ZG
U φ
ϕm
R
• •
•
Uϕ + I ϕ Z n
- I ϕ Zn
• •
Uϕ − I ϕ ZG
90 < Arg • •
< 270 Equation 3.25-4
Uϕ + I ϕ Z n
Where:
Date: 2016-08-16
3 Operation Theory
NOTICE!
The device adopts power swing blocking releasing to avoid mal-operation of impedance protection
due to power swing. The protection is blocked all along under the normal condition and power
swing. Only if fault (internal fault or power swing with internal fault) is detected, power swing
blocking for impedance protection is released by PSBR element.
The logic setting [Gen.21Mx.En_PSBR] is used to enable or disable PSBR function. If it is set as
“1”, the PSBR function is enabled. Otherwise, it is disabled.
If the time delay of impedance protection is more than 1.5s, PSBR function is not needed for the
impedance protection.
Power swing blocking for impedance relay will be released if any of the following PSBR elements
operate.
At the moment that any impedance protection fault detector picks up, if positive-sequence
overcurrent element does not operate or the operating duration is less then 10ms, FD PSBR will
operate for 160ms.
I1 is positive-sequence current.
[Gen.21Mx.I_PSBR] (x=1 or 2) is the current setting of FD PSBR, which is set larger than the
maximum load current of generator.
10ms 0
SIG I1>[Gen.21Mx.I_PSBR] >=1
&
0 160ms
SIG I1≤[Gen.21Mx.I_PSBR] Flg_Pkp_FDPSBR
SIG FD_Gen.21M
Date: 2016-08-16
3 Operation Theory
When an internal unsymmetrical fault happens, power swing blocking for impedance relay can be
released by following element:
Where:
“m” is an internal fixed coefficient with a certain margin which can ensure UF PSBR operate during
power swing with internal unsymmetrical fault, while not operate during power swing or power
swing with external fault.
I1,I 2,I 0 are positive-sequence current, negative-sequence current and zero-sequence current
respectively.
When fault detector operates and after 160ms, or during the power swing, if a three-phase fault
occurs, both of FD PSBR and UF PSBR can not operate to release the impedance protection.
Thus, SF PSBR is provided for this case specially. This detection is based on measuring the
voltage of power swing center:
Where:
1) When − 0.03U N < U OS < 0.08U N , the SF PSBR element will operate with a time delay
150ms.
2) When − 0.1U N < U OS < 0.25U N , the SF PSBR element will operate with a time delay
500ms.
3.25.4 Logic
The logic of phase-to-earth impedance protection is same to that of phase-to phase impedance
protection, and stage 1 of phase-to-phase impendence protection is taken as an example as
shown below.
For each stage of impedance protection, if following three conditions are met, the corresponding
stage of impedance protection is enabled.
Date: 2016-08-16
3 Operation Theory
(2) The protection function enabling inputs [Gen.21Mx.En1], [Gen.21Mx.En2] are “1”.
If impedance protection is disabled, all the related output signals will be reset. If no external input
is configured to [Gen.21Mx.En1] ([Gen.21Mx.En2]), the default initial value of [Gen.21Mx.En1]
([Gen.21Mx.En2]) is “1”; if no external input is configured to [Gen.21Mx.Blk], the default initial
value of [Gen.21Mx.Blk] is “0”.
EN Flg_Pkp_UFPSBR
≥1
EN Flg_Pkp_SFPSBR Flg_Pkp_PSBR
SIG Flg_Pkp_FDPSBR
SIG Flg_Pkp_PSBR ≥1
SIG [Gen.21M1.En_PSBR]
SIG Flg_Op_ZP1
&
SET [Gen.21M1.En]
&
SIG [Gen.21M1.En1] &
[Gen.21M1.ZP.St]
SIG [Gen.21M1.En2]
[Gen.21M1.ZP.t_Op] 0s
SIG [Gen.21M1.Blk] [Gen.21M1.ZP.Op]
SIG [Gen.21M1.En_VTS_Blk]
0ms 500ms
SIG 21M1.FD
Where:
Flg_Pkp_UFPSBR is the internal flag indicating that unsymmetrical fault PSBR element picks up.
Flg_Pkp_SFPSBR is the internal flag indicating that symmetrical fault PSBR element picks up.
Flg_Pkp_FDPSBR is the internal flag indicating that fault detector PSBR element picks up.
21M1.FD is the operation flag of the fault detector of DPFC phase-to-phase current or that of
negative-sequence current (the fault detector of fault detector DSP module).
Flg_Pkp_PSBR is the internal flag indicating that power swing blocking releasing element picks
up.
Flg_Op_ZP1 is the internal flag indicating that the operation criterion of stage 1 of phase-to-phase
impedance relay (i.e. Equation 3.25-3) is met.
Date: 2016-08-16
3 Operation Theory
21
Gen.21Mx.U3P Gen.21Mx.St
Gen.21Mx.I3P Gen.21Mx.ZP.Op
Gen.21Mx.En1 Gen.21Mx.ZG.Op
Gen.21Mx.En2
Gen.21Mx.Blk
x=1 and 2.
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
19 Gen.21Mx.Ang(Uab-Iab) Phase angle between phase-AB voltage and phase-AB current deg
20 Gen.21Mx.Ang(Ubc-Ibc) Phase angle between phase-BC voltage and phase-BC current deg
21 Gen.21Mx.Ang(Uca-Ica) Phase angle between phase-CA voltage and phase-CA current deg
22 Gen.21Mx.Ang(Ua-Ia) Phase angle between phase-A voltage and phase-A current deg
23 Gen.21Mx.Ang(Ub-Ib) Phase angle between phase-B voltage and phase-B current deg
24 Gen.21Mx.Ang(Uc-Ic) Phase angle between phase-C voltage and phase-C current deg
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values->Gen PPF Prot Values
Date: 2016-08-16
3 Operation Theory
3.25.6 Settings
Table 3.25-5 Settings list of impedance protection
x=1 or 2
Date: 2016-08-16
3 Operation Theory
3.26.1 Application
Breaker failure protection is applied to monitor the circuit breaker state to ensure that the circuit
breaker is correctly opened. When a tripping command is issued from the protection device, but
the circuit breaker have not been tripped within a certain time delay, so that the fault can not be cut
off, then the circuit breaker of upper stream will be initiated to trip.
After the tripping command been issued, the device will check whether the phase current and
negative-sequence current are larger than corresponding setting.
The protection will use the auxiliary contact of the circuit breaker to judge whether the circuit
breaker is correctly tripped. As under certain circumstances, the criteria of current are not
applicable, like frequency protection, voltage protection and overexcitation protection etc.
The internal logic between above two criteria can be “And” or “Or”. If the setting
[Gen.50BF.Opt_Mode] is set as “0”, the internal logic between current criterion and circuit breaker
auxiliary contact criterion is “Or”; if the setting [Gen.50BF.Opt_Mode] is set as “1”, the internal logic
between current criterion and circuit breaker auxiliary contact criterion is “And”. Current criterion
and circuit breaker auxiliary contact criterion can be enabled or disabled separately, so that there
are four possible combinational logics for breaker failure protection:
The breaker failure protection has two independent tripping stages and is controlled by the input
signal [Gen.50BF.Init], which can be an internal protection tripping signal or an external protection
operating binary input.
Date: 2016-08-16
3 Operation Theory
Current criteria include phase current criterion and negative-sequence current criterion. If any
current criterion is satisfied, current element of breaker failure protection picks up.
Where:
Where:
3.26.4 Logic
For breaker failure protection, when following three conditions are met, the breaker failure
protection is enabled.
(2) The protection function enabling inputs [Gen.50BF.En1], [Gen.50BF.En2] are “1”.
If breaker failure protection is disabled, all the related output signals will be reset. If no external
input is configured to [Gen.50BF.En1] ([Gen.50BF.En2]), the default initial value of [Gen.50BF.En1]
([Gen.50BF.En2]) is “1”; if no external input is configured to [Gen.50BF.Blk], the default initial value
of [Gen.50BF.Blk] is “0”.
Logics of breaker failure protection (with two time delays) is shown in following figure.
Date: 2016-08-16
3 Operation Theory
Sig [BI_52b]
OR/AND
&
Set [Gen.50BF.Opt_Mode] [Gen.50BF.St]
[Gen.50BF.t1_Op] 0ms
En [Gen.50BF.En] [Gen.50BF.Op_t1]
&
SIG [Gen.50BF.En1] [Gen.50BF.t2_Op] 0ms
[Gen.50BF.Op_t2]
SIG [Gen.50BF.En2]
SIG [Gen.50BF.Blk]
Sig [50BF.Init]
0ms 500ms
Sig 50BF.FD
Where:
50BF.FD is the operation flag of the fault detector of breaker failure protection (the fault detector of
fault detector DSP module).
50BF
Gen.50BF.I3P Gen.50BF.St
Gen.50BF.Init Gen.50BF.Op_t1
Gen.50BF.En1 Gen.50BF.Op_t2
Gen.50BF.En2
Gen.50BF.Blk
BI_52b
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Access path:
Main menu -> Measurements -> Measurements1-> Prot Values->Gen Curr Values
Main menu -> Measurements -> Measurements2-> Prot Values->Gen Curr Values
3.26.6 Settings
Table 3.26-5 Settings list of breaker failure protection
Date: 2016-08-16
3 Operation Theory
3.27.1 Application
Any operation signal from the generator body protection or other external device can be coupled to
the microprocessor-based protection device via the binary input signal. Generator mechanical
protection can repeat these binary input signals to send alarm signals, tripping directly or tripping
with a time delay. By this way the output signal of some mechanical protection (such as gas
protection and etc.) can be coupled to the microprocessor-based protection device, then these
signals can be repeated through high-power relays to improve the anti-inference ability of the
protection.
Each module provides 4 mechanical signal input channels for trip or alarm.
Date: 2016-08-16
3 Operation Theory
drop off time of mechanical input signals is usually too long, an internal time delay setting
[MR1(2).t_PW_n] (n=1, 2, 3, and 4) is used to control the drop off time (the default value is 9s), it
can prevent the relay from sending long-time tripping command.
3.27.4 Logic
For mechanical protection, if following three conditions are met, the protection will be enabled.
(2) The protection function enabling inputs [MRx.En1], [MRx.En2] are “1”
If mechanical protection is disabled, all the related output signals will be reset. If no external input
is configured to [MRx.En1] ([MRx.En2]), the default initial value of [MRx.En1] ([MRx.En2]) is “1”; if
no external input is configured to [MRx.Blk], the default initial value of [MRx.Blk] is “0”.
Here takes channel 1 of mechanical protection 1 as an example. The logics of channel 2, 3 and 4
are similar with that of channel 1.
EN [MR1.En] &
EN [MR1.En_1] [MR1.Sig1]
SIG [MR1.Input1]
EN [MR1.En_1] &
SIG [MR1.Input1]
SET [MR1.OutMap_1] (bit0=1)
MRx
MRx.Input1 MRx.St
MRx.Input2 MRx.Op1
MRx.Input3 MRx.Op2
MRx.Input4 MRx.Op3
MRx.En1 MRx.Op4
MRx.En2 MRx.Sig1
MRx.Blk MRx.Sig2
MRx.Sig3
MRx.Sig4
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Tripping reports
Start signals
Waveform recording
Date: 2016-08-16
3 Operation Theory
IO events
3.27.6 Settings
Table 3.27-4 Settings list of mechanical protection
Date: 2016-08-16
3 Operation Theory
3.28.1 Application
Excitation transformer current differential protection is the main protection for the internal
short-circuit fault of excitation transformer winding. Current differential protection can operate
quickly to clear the internal fault to avoid the excitation transformer from damages or reduce the
maintenance cost as low as possible.
For Y-Y, △→△, △→Y and Y→△ connection, all possible vector combinations have been taken
into account, so it is very flexible.
Optional inrush current distinguished principles and inrush current blocking method, which
can avoid the inrush current reliably, and it can also ensure the operation speed when a fault
happens during normal operation.
Date: 2016-08-16
3 Operation Theory
Biased current differential element with initial restraint slope is adopted, it consists of sensitive and
conventional biased differential elements as well as independent CT saturation criterion.
For internal serious fault, once the differential current is larger than the current setting of
instantaneous differential element, the current differential protection will operate to cut off the fault
quickly.
Voltage is also used to judge the abnormality of differential CT circuit, multi-phase CT circuit failure,
multi-side CT circuit failure and short-circuit condition can be detected.
Current differential protection includes two operation elements: biased differential element, and
unrestrained differential element. When the differential current is larger than the corresponding
current threshold and no larger harmonic is detected, current differential protection will operate,
and it will drop off if the fault current disappears.
Sensitive biased differential element is variable slope differential element with initial restraint slope.
Conventional biased differential element is differential element with two broken lines. Unrestrained
differential element is used to cut off the serious fault quickly and there is no any blocking element
for it.
Generally, the magnitudes of secondary current of each side of excitation transformer are different
due to the difference of voltage level and CT ratio. The current value difference between each side
shall be eliminated before calculation for current differential protection by amplitude
compensation.
The nameplate parameters of the excitation transformer (includes the rated apparent power and
the rated voltage of each side) and the primary and secondary data of CT of each side of the
excitation transformer should be input to the device. The device will calculate the rated current of
each side and the differential adjust coefficient automatically according to the parameters.
Sn
I1bBrm = Equation 3.28-1
3U1nBrm
Where:
Date: 2016-08-16
3 Operation Theory
I
I 2bBrm = 1bBrm Equation 3.28-2
CTBrm
Where:
k Base = 1
I 2bBase
k Brm =
I 2bBrm Equation 3.28-3
( I 2bBase / I 2 nBase )
≤ 32
( I 2bBrm / I 2 nBrm )
Where:
I 2bBrm , I 2bBase are rated secondary current of calculated side and referenced side of excitation
transformer.
I 2nBrm , I 2nBase are rated secondary current of CT of calculated side and referenced side of
Excitation transformer HV side is the referenced side. If Equation 3.28-3 is not met, the setting
error alarm signals [87ET.Fail_Settings] will be issued and displayed on LCD and the protective
device will be blocked.
Date: 2016-08-16
3 Operation Theory
For the connection mode of excitation transformer each side winding is different, different vector
group will be generated, the vector group will lead the phase shift of secondary currents of each
side, which should be adjusted via the phase compensation of the software.
2) The secondary current channel of CT will be connected to the protection device directly.
Phase compensation is carried out from LV side to HV side. The HV side (the referenced side) is 0
or 12 o’clock. LV side is n o’clock (n=0~11) relative to HV side. If the HV side is △ connection, then
it does not need to be compensated, LV side needs to shift for n o’clock. If the HV side is Y
connection, then HV side is 1 o’clock to eliminate the effects of zero-sequence current, LV side
needs to shift for n+1 o’clock.
For example:
The vector group of a excitation transformer is Y0/Δ11, the setting [ET_S1.WdgConn] should be
set as “Wye”, the setting [ET_S2.WdgConn] should be set as “Delta”, and the setting
[ET_S2.Clk_WRT_S1] should be set as “11”. The HV side is Y connection, so the phase shift
matrix corresponds to 1 o’clock is adopted to compensate HV side current. It is 11 o'clock for LV
side relative to HV side, so the phase shift matrix corresponds to 12 (or 0, 11+1=12) o’clock is
adopted to compensate LV side current.
1 0 0
0
(No phase shit) 0 1 0
0 0 1
1 −1 0
1 1
(Shift 30° leading) 0 1 − 1
3
− 1 0 1
0 − 1 0
2 0 0 −1
(shift 60° leading)
− 1 0 0
0 −1 1
3 1
(Shit 90° leading) 1 0 − 1
3
− 1 1 0
Date: 2016-08-16
3 Operation Theory
0 0 1
4
(Shit 120° leading) 1 0 0
0 1 0
−1 0 1
5 1
(Shift 150° leading) 1 −1 0
3
0 1 − 1
− 1 0 0
6 0 − 1 0
(Shift 180° leading)
0 0 − 1
− 1 1 0
1
0 − 1 1
7
(Shift 150° lagging) 3
1 0 − 1
0 1 0
8
(Shift 120° lagging) 0 0 1
1 0 0
0 1 −1
S9 1
(Shift 90° lagging) − 1 0 1
3
1 − 1 0
0 0 −1
10
(Shift 60° lagging) − 1 0 0
0 − 1 0
1 0 −1
11 1
(Shift 30° lagging) − 1 1 0
3
0 − 1 1
NOTICE!
For Y-y and D-d connection the vector group can ONLY BE even number, (i.e. Y-y4,
D-d8), for Y-d and D-y connection the vector group can ONLY BE odd number, (i.e.
Y-d11, D-y5), if the two conditions can not be met, the setting error alarm signal
[87ET.Fail_Settings] will be issued and displayed on LCD and the protective device will
be blocked.
Date: 2016-08-16
3 Operation Theory
I dA I A1 I A2
I = × /I + × /I
dB M 1 I B1 2 bBr1 M 2 I B 2 2 bBr 2 Equation 3.28-4
I dC I C1 I C 2
1 2
I dA = I ′ A1 + I ′ A2
I dB = I ′B1 + I ′B 2 Equation 3.28-5
I = I ′ + I ′
dC C1 C2
Where:
I Am , I Bm , I Cm in the equation are the secondary current vectors of side m (m=1, 2).
I ′ Am , I ′Bm , I ′Cm are corrected secondary current vectors of side m (m=1, 2).
M 1 , M 2 are phase shift matrixes of each side of excitation transformer respectively. Its value is
decided according to the vector group of excitation transformer and please refers to Section
3.28.3.3 for details.
I 2bBr1 , I 2bBr 2 are rated secondary values of each side of excitation transformer respectively.
I rA =
1
( I ′A1 + I ′A2 )
2
I rB = ( I ′B1 + I ′B 2 )
1
Equation 3.28-6
2
I rC = 2 ( I ′C1 + I ′C 2 )
1
Where:
Current compensation process is shown in the flowing figure. The symbol “*” represents the
polarity of CT. If current flowing into the polarity side of CT, the current direction is defined as
positive direction. In an ideal situation, the differential current (i.e. I d = I ′ _ H + I ′ _ L )should be
zero during the normal operation of the excitation transformer or an external fault occurring.
Date: 2016-08-16
3 Operation Theory
Ip_H Ip_L
* * *
* * *
HV side LV side
I_H I_L
PCS-985GE
Phase shift/zero sequence Phase shift/zero sequence
current elimination (*M1) current elimination (*M2)
I'_H I'_L
In above figure:
I’_H, I’_L are secondary corrected current vectors of HV and LV side respectively.
To clarify the principle, in an ideal situation, three important operation conditions are considered.
The direction of I’_H is reverse to that of I’_L, but the amplitude of I’_H is equal to that of I’_L,
i.e. I’_H=–I’_L, |I’_H|=|I’_L|.
Id=|I’_H+I’_L|=|I’_H–I’_H|=0;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|I’_H|)/2=|I’_H|
No differential current (Id=0), restraint current (Ir) is one time of the through-flowing current,
and current differential protection will not operate.
2. Internal short-circuit fault, e.g. the fed currents of two sides are equal:
Id=|I’_H+I’_L|=|I’_H+I’_H|=2|I’_H|;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|I’_H|)/2=|I’_H|
Differential current (Id) is two times of restraint current (Ir) and it corresponds to the total fault
Date: 2016-08-16
3 Operation Theory
The above results show that Id = 2Ir during an internal fault. I.e. the operation characteristic of
current differential protection for internal fault is a straight line with a slope of 2.
Assuming I’_L=0
Id=|I’_H+I’_L|=|I’_H+0|=|I’_H|;
Ir=(|I’_H|+|I’_L|)/2=(|I’_H|+|0|)/2=|I’_H|/2
Differential current (Id) is two times of restraint current (Ir) and it corresponds to fault current of
single side, current differential protection operates sensitively.
The above results show that Id = 2Ir during an internal fault. I.e. the operation characteristic of
current differential protection for internal fault is a straight line with a slope of 2.
1 • •
I r = ( I 1 + I 2 )
2
• •
I = I 1 + I 2
d
Where:
Ii (i = 1, 2) are the corrected secondary currents of HV and LV side of excitation transformer
respectively.
I Diff .Pickup is the pickup current setting of biased differential element [87ET.I_Biased].
Date: 2016-08-16
3 Operation Theory
K bl1 is the initial slope setting of biased differential element, it takes 0.10 generally [87ET.Slope1].
K bl 2 is the maximum slope setting of biased differential element, it takes 0.70 generally
[87ET.Slope2].
n is the restraint current multiple when the restraint coefficient reach to the maximum value. This
internal value is set as 6 fixedly.
Conventional biased differential element with higher pickup current and higher restraint coefficient
comparing with sensitive biased differential element is equipped. Its biased restraint characteristic
can make the differential element not operate due to CT transient and steady-state saturation
during external fault, and it can operate reliably even the CT is seriously saturated during internal
fault. Operation criterion of conventional biased differential element is:
I d > 1.2 × I e
I d > I r Equation 3.28-8
Where:
NOTICE!
The related parameters of conventional biased differential element are set FIXEDLY in
the device. Therefore, the slope and the knee point with constant values do not need to
be set by user.
Where:
Date: 2016-08-16
3 Operation Theory
Id (Ie)
differential Tripping area of
current instantaneous diff.
2
K=
[87ET.I_Inst]
ff.
di
.0 ed f
K bia a o
l re
=1 s
na a
tio ing of f.
a dif
en pp
e
ar d
nv Tri
n g ase
2]
pi e bi
pe
p
co
lo
i
Tr itiv
.S
ET
ns
7
se
[8
1.2Ie
pe1]
T.Slo
[87E
[87ET.I_Biased]
restraint current
0 1Ie 1.2Ie nIe Ir (Ie)
Current differential protection carries out the fault discrimination according to the current of each
phase. If the current criteria are met and no related blocking element(s) operate, differential
protection will operate to trip.
1) Sensitive biased differential element will send tripping signal monitored by CT saturation,
overexcitation, inrush current and CT circuit failure (optional). It can ensure the sensitivity of
differential protection and avoid the unwanted operation when CT is saturated during an
external fault. Its operation area is the tint shadow area in the figure above.
2) Conventional biased differential element will send tripping signal monitored by inrush current
and CT circuit failure (optional). It eliminates the influence of transient and steady-state
saturations of CT during an external fault and ensures differential protection can operate
reliably even if CT is saturated during an internal fault by means of its biased characteristic. Its
operation area is the deeper shadow area in the figure above.
3) Unrestrained instantaneous differential element will send tripping signal without any blocking
element if differential current of any phase is larger than corresponding current setting.
Unrestrained instantaneous differential element is used to cut off the internal serious fault
quickly. Its operation area is over the above two areas with the deepest dark shadow.
Date: 2016-08-16
3 Operation Theory
The logic setting [87ET.Opt_Inrush_Ident] is provided for users to select the inrush current
detection principle. If the logic setting is set as “Waveform”, discrimination by waveform distortion
is enabled, and if it is set as “Hm2”, discrimination by second harmonics is enabled.
The logic setting [87ET.Opt_BlkMode_Inrush] is provided for users to select the inrush current
blocking mode, synthetic blocking mode, cross blocking mode and phase blocking mode can be
selected.
The ratio between second harmonic and fundamental component of three-phase differential
current is used to distinguish inrush current. Its criteria are:
Where:
I1st is the fundamental component of the differential current of the corresponding phase.
[87ET.K_Hm2_Inrush]=0.15 is recommended.
Users can select the second harmonic criterion or wave distortion criterion (see following section)
to distinguish inrush current.
After the transmission of current transformer, the differential current is basically the fundamental
sinusoidal wave during an internal fault. When the excitation transformer is energized, plentiful
harmonics will appear, the waveform will be distorted, the waveform is interrupted and
unsymmetrical.
S > K b * S +
Equation 3.28-11
S > S t
Where:
S + is the full-cycle integral value of (differential current instantaneous value + differential current
instantaneous value a half cycle ago);
Date: 2016-08-16
3 Operation Theory
K b is a fixed coefficient.
Where:
α is a ratio coefficient.
When inrush current appears, the above waveform distinguish expression is not met, current
differential protection will not mal-operate.
Users can select the inrush current blocking mode by the logic setting
[87ET.Opt_BlkMode_Inrush].
If the following criterion is met, the three-phase differential protection will be blocked.
Max{Ia 2 nd ,Ib 2 nd , Ic 2 nd } > [87 ET .K _ Hm2 _ Inrush] × Max( Ia1nd ,Ib1nd , Ic1nd ) Equation 3.28-13
If the following criterion is met, the three-phase differential protection will be blocked.
If one of the following criteria is met, only the corresponding phase differential protection will be
blocked.
Date: 2016-08-16
3 Operation Theory
The synthetic blocking mode is strongly recommended to be selected in the actual application.
Operating experience indicating that the synthetic blocking mode can guarantee the differential
protection not operate under most inrush current situation, and ensure the differential protection
can operate sensitively when the excitation is no-load energized on to a fault.
When an excitation transformer external fault happens, great through-fault current will flowing
through the CT, if the saturation degree of LV side CT is inconsistent with that of HV side CT, great
unbalance differential current will generate in the differential circuit, which will lead to the
mal-operation of differential protection. So the CT saturation detection function is required for
excitation transformer differential protection.
There is a certain time before the CT falling into saturated state, so the changing characteristic of
differential current and restraint current within the initial time of the fault can be used to judge
whether it is an external fault. For an external fault, the deviation of power frequency component
(DPFC) of restraint current appears before the appearance of DPFC of differential current; for an
internal fault, DPFC of restraint current and differential current appear almost simultaneously. If
external fault is detected, CT saturation blocking criterion is enabled.
Where:
If any harmonic of one phase differential current meets the above equation, it will be considered
that it is CT saturation to cause this phase differential current and sensitive biased differential
element will be blocked. The criterion is only enabled when the excitation transformer is in service.
When a excitation transformer is overexcited, the exciting current will increase sharply which may
result in unwanted operation of differential protection. Therefore the overexcitation shall be
discriminated to block differential protection. If overexcitation is detected, then sensitive biased
Date: 2016-08-16
3 Operation Theory
Where:
If the excitation transformer differential current of any phase meets the following criteria and
corresponding differential element is enabled, the excitation transformer differential current
abnormality alarm [87ET.Alm_Diff] with a time delay of 300ms, this alarm signal will not block the
differential element. The signal will reset if the differential current disappears with a time delay of
10s.
Criteria
If any one of following four conditions is satisfied after the fault detector of biased differential
current picks up, it will be determined as fault and differential protection is released, otherwise it
will be determined that the fault detector of biased differential current picks up due to differential
CT circuit failure or short-circuit.
Any phase current of any side increases after the fault detector picks up.
The maximum phase current is larger than 1.2Ie after the fault detector picks up.
Date: 2016-08-16
3 Operation Theory
Among all the current channels, any three phases of the current decrease after fault
detector picks up.
If none of above four conditions is satisfied within 40ms after the fault detector of biased
differential current picks up, it will be determined as differential CT circuit failure and CT circuit
failure alarm will be issued. Then if the logic setting [87ET.En_CTS_Blk] is set as “1”, sensitive and
conventional biased differential element will be blocked, if the logic setting [87ET.En_CTS_Blk] is
set as “0”, sensitive and conventional biased differential element will not be blocked. Excitation
transformer unrestrained instantaneous differential element will not be blocked during CT circuit
failure.
The above conditions contain the voltage criteria and current criteria, which realizes the high
accuracy and sensitivity of the CT circuit failure detection.
The CT circuit failure alarm is latched once issued, it can be reset only after the failure is cleared
and the device is reset (i.e. the binary input [BI_RstTarg] is energized).
No matter whether the abnormality alarm signal makes the differential protection picks up, there
must be some problems in the differential circuit. For example, when the differential circuit fails,
the differential protection will not pick up for light-loaded condition, but the differential current
abnormality alarm signal will be issued. If the abnormality is treated in time, the mal-operation of
differential protection due to increase of load or external fault can be avoided (if the logic setting
[87ET.En_CTS_Blk] is set as “0”).
Once the differential CT circuit failure alarm is issued, the CT circuit should be check carefully, only
if the fault is cleared, the reset operation can be conducted.
3.28.4 Logic
For excitation transformer current differential protection, if following three conditions are met, the
protection will be enabled.
(2) The protection function enabling inputs [87ET.En1], [87ET.En2] are “1”
If excitation transformer differential protection is disabled, all the related output signals will be reset.
If no external input is configured to [87ET.En1] ([87ET.En2]), the default initial value of [87ET.En1]
([87ET.En2]) is “1”; if no external input is configured to [87ET.Blk], the default initial value of
[87ET.Blk] is “0”.
Date: 2016-08-16
3 Operation Theory
En 87ET.En_Biased ≥1
&
SIG Idmax>[87ET.I_Biased]
Figure 3.28-3 Logic diagram of startup of excitation transformer current differential protection
Where:
EN [87ET.En_Inst]
SIG [87ET.En1] &
&
SIG [87ET.En2]
[87ET.Op_Inst]
SIG [87ET.Blk]
SIG Idmax>[87ET.I_Inst]
0ms 500ms
SIG 87ET.FD_Inst
EN [87ET.En_Biased]
SIG [87ET.En1] &
SIG &
[87ET.En2]
SIG [87ET.Blk]
SIG Flg_Inrush_ConvBiasDiff
SET [87ET.En_CTS_Blk] ≥1
[87ET.Op_Biased]
SIG 87ET.FD_Biased 0ms 500ms
EN [87ET.En_Biased]
SIG [87ET.En1] &
SIG [87ET.En2]
SIG [87ET.Blk]
&
SIG Flg_SensBiasDiff
SIG Flg_CTSaturation
SET [87ET.En_CTS_Blk]
SET [87ET.En_OvExc_Blk]
0ms 500ms
SIG 87ET.FD_Biased
Date: 2016-08-16
3 Operation Theory
Where:
Flg_ConvBiasDiff is the internal flag indicating that the operation criteria of conventional biased
differential element are satisfied.
Flg_SensBiasDiff is the internal flag indicating that operation criteria of sensitive biased differential
element are satisfied.
Flg_CTS is the internal flag indicating that differential CT circuit failure is detected.
Flg_Inrush_ConvBiasDiff is the internal flag indicating that inrush current is detected for
conventional biased differential element.
Flg_Inrush_SensBiasDiff is the internal flag indicating inrush current is detected for sensitive
biased differential element.
87ET.FD_Inst is the signal indicating that the fault detector of unrestrained instantaneous
differential element picks up (the fault detector of fault detector DSP module).
87ET.FD_Biased is the signal indicating that the fault detector of biased differential element picks
up (the fault detector of fault detector DSP module).
87ET
87ET.I3P1 87ET.St
87ET.I3P2 87ET.Op_Biased
87ET.En1 87ET.Op_Inst
87ET.En2 87ET.Alm_Diff
87ET.Blk 87ET.Alm_CTS
Figure 3.28-5 Function block diagram of excitation transformer current differential protection
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.28-4 Output signals of excitation transformer current differential protection (event recorder)
Tripping reports
Start signals
Alarm signals
Waveform recording
87ET.Ida
Three-phase differential current amplitude of excitation
1 87ET.Idb pu
transformer.
87ET.Idc
87ET.Ira
Three-phase restraint current amplitude of excitation
2 87ET.Irb pu
transformer.
87ET.Irc
Date: 2016-08-16
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements1-> Exc Values-> Exc AC Values
Main menu -> Measurements -> Measurements2-> Exc Values-> Exc AC Values
87ET.Ang(Ia_Br1-Br2)
Phase angle between HV side corrected current and LV side
3 87ET.Ang(Ib_Br1-Br2) deg
corrected current of the same phase.
87ET.Ang(Ic_Br1-Br2)
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Exc PhaseAngle Values
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Sec Rated Curr Values
Access path:
Main menu -> Measurements -> Measurements2-> Cal Param Display-> Diff Corr Coef Values
87ET.Ida
Three-phase differential current amplitude of excitation
8 87ET.Idb pu
transformer.
87ET.Idc
87ET.Ira
Three-phase restraint current amplitude of excitation
9 87ET.Irb pu
transformer.
87ET.Irc
87ET.Ia_Cr_Br1
Three-phase corrected current of HV side that used for
10 87ET.Ib_Cr_Br1 pu
excitation transformer differential protection.
87ET.Ic_Cr_Br1
87ET.Ia_Cr_Br2
Three-phase corrected current of LV side that used for
11 87ET.Ib_Cr_Br2 pu
excitation transformer differential protection.
87ET.Ic_Cr_Br2
87ET.Ia_Th_Biased_L
Three-phase current threshold of excitation transformer
12 87ET.Ib_Th_Biased_L pu
sensitive biased differential current protection.
87ET.Ic_Th_Biased_L
87ET.Ia_Th_Biased_H
Three-phase current threshold of excitation transformer
13 87ET.Ib_Th_Biased_H pu
conventional biased differential current protection.
87ET.Ic_Th_Biased_H
Date: 2016-08-16
3 Operation Theory
87ET.Ida_Hm2
Second harmonic amplitude of three-phase differential
14 87ET.Idb_Hm2 pu
current of excitation transformer.
87ET.Idc_Hm2
87ET.Ida_Hm3
Third harmonic amplitude of three-phase differential current
15 87ET.Idb_Hm3 pu
of excitation transformer.
87ET.Idc_Hm3
87ET.Ida_Hm5
Fifth harmonic amplitude of three-phase differential current
16 87ET.Idb_Hm5 pu
of excitation transformer.
87ET.Idc_Hm5
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Exc Diff Prot Values
3.28.6 Settings
Table 3.28-6 Settings list of excitation transformer current differential protection
Date: 2016-08-16
3 Operation Theory
element.
NOTICE!
3.29.1 Application
When a fault occurs in power system, the current increases and phase overcurrent protection
operates to avoid damages to protected equipment.
An external fault will result in excitation transformer overload, it will lead to damage of excitation
transformer if the fault can not be cut off quickly, in this case phase overcurrent protection can
operate to trip circuit breaker to avoid physical damage. For small-scale excitation transformer,
phase overcurrent protection can protect excitation transformer from internal fault, for large-scale
excitation transformer, phase overcurrent protection is applied as the backup protection of
excitation transformer differential protection.
Date: 2016-08-16
3 Operation Theory
overcurrent protection, stage x of excitation transformer overcurrent protection will operate with a
settable time delay.
3.29.3 Logic
For stage n of excitation transformer phase overcurrent protection, if following three conditions are
met, stage n of excitation transformer phase overcurrent protection is enabled.
(2) The protection function enabling inputs [Exc.50/51Pn.En1], [Exc.50/51Pn.En2] are “1”.
If excitation transformer phase overcurrent protection is disabled, all the related output signals will
be reset. If no external input is configured to [Exc.50/51Pn.En1] ([Exc.50/51Pn.En2]), the default
initial value of [Exc.50/51Pn.En1] ([Exc.50/51Pn.En2]) is “1”; if no external input is configured to
[Exc.50/51Pn.Blk], the default initial value of [Exc.50/51Pn.Blk] is “0”.
EN [Exc.50/51Pn.En]
SIG [Exc.50/51Pn.En1] &
SIG [Exc.50/51Pn.En2]
SIG [Exc.50/51Pn.Blk]
Figure 3.29-1 Logic diagram of excitation transformer phase overcurrent protection (n=1,2)
Where:
Exc.50/51Pn.FD is the internal signal indicating that stage n of excitation transformer phase
overcurrent protection picks up (the fault detector of fault detector DSP module).
Exc.50/51P
Exc.50/51Pn.I3P Exc.50/51Pn.St
Exc.50/51Pn.En1 Exc.50/51Pn.Op
Exc.50/51Pn.En2
Exc.50/51Pn.Blk
Figure 3.29-2 Function block diagram of excitation transformer phase overcurrent protection
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Table 3.29-3 Output signals of excitation transformer phase overcurrent protection (event recorder)
Tripping reports
Start signals
Waveform recording
3.29.5 Settings
Table 3.29-4 Settings list of excitation transformer phase overcurrent protection
Date: 2016-08-16
3 Operation Theory
3.30.1 Application
If a generator or a generator-transformer unit is connecting with the power network, it is called
“interconnection status”. Some protections (such as startup and shutdown protection) should be
enabled before the interconnection status and disabled after the interconnection status, while
some protections should be enabled after the interconnection status. The device will detect the
position of generator terminal circuit breaker or main transformer HV side circuit breaker and the
current of the CT at the outlet of the circuit breaker, then comprehensively judge whether the
generator or the generator-transformer unit is during interconnection status, the interconnection
status flag can be output for the user to implement logic programming.
Two circuit breaker auxiliary contact inputs, the auxiliary contact of generator terminal circuit
breaker or main transformer HV side circuit breaker can be connected to the device.
Two groups of current inputs respectively correspond to the CT at the outlet of generator
terminal circuit breaker and main transformer HV side circuit breaker.
Date: 2016-08-16
3 Operation Theory
side (it is also called 3/2 breakers wiring), then the auxiliary contact of the two circuit breakers of
main transformer HV side and the current of the two CTs at the outlet of the two circuit breakers
should be input.
3.30.4 Logic
EN [En_GCB] &
[Flg_52a]
SIG BI_52b_CB1
EN [Opt_Conn_Tr] &
EN [En_GCB] &
SIG BI_52b_CB1
≥1
&
[Flg_52a]
&
SIG BI_52b_CB2
EN [Opt_Conn_Tr] &
EN [En_GCB]
SIG Imax1>0.04In ≥1
[CBStatus.Flg_OnLoad]
SIG Imax2>0.04In
Where:
CBStatus
CBStatus.I3P1 Flg_52a
CBStatus.I3P2 CBStatus.Flg_OnLoad
BI_52b_CB1
BI_52b_CB2
Date: 2016-08-16
3 Operation Theory
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
The signal indicating that current of the CT at the outlet of the circuit
2 CBStatus.Flg_OnLoad
breaker is detected.
Access path:
Main menu -> Measurements -> Measurements2-> Prot Values-> Misc Prot Values
3.30.6 Settings
Table 3.30-4 Settings list of interconnection status element
3.31.1 Application
If abnormality happens to voltage transformer, the performance of the voltage related generator
protection (such as impedance protection, loss of excitation protection, out-of-step protection etc.)
will be affected, sometimes these protections even should be blocked during VT circuit failure in
order to prevent mal-operation.
Date: 2016-08-16
3 Operation Theory
For some generator, two groups of VT are equipped, the two groups of VT can be connected into
the generator protection device simultaneously, via comparing, the VT of which abnormality is
detected can be identified, if abnormality happens to one VT, all the protections that use the VT will
be switched to another normal VT automatically, so the performance of the voltage related
protections will not be affected.
Automatic switching function of two groups of VT during VT circuit failure, when VT circuit
failure is detected for one VT, the related protections can be switched to another normal VT
automatically.
Two groups of VT are connected into the generator protection device simultaneously, VT circuit
failure can be detected via comparing the phase-to-phase voltage, positive-sequence voltage and
negative-sequence voltage of the two groups of VT.
Where:
Date: 2016-08-16
3 Operation Theory
If above criterion is met, VT circuit failure alarm signal will be issued with a time delay of 0.42s,
and VT switching will be initiated. When VT circuit failure happens to one VT, impedance
protection, loss of excitation protection, out-of-step protection, overvoltage protection,
overexcitation protection, reverse power protection and frequency protection etc. voltage related
protection will not be affected.
If only one group of VT is equipped at generator terminal, voltage balance protection can be
disabled.
(1) If there have two groups of three-phase voltage transformers, the voltage balance function is
in service.
If above conditions are all met, VT1 primary circuit failure 1 alarm signal will be issued with a short
time delay, generator 3rd harmonic stator ground fault protection (including 3rd harmonic ratio stator
ground fault element and 3rd harmonic differential stator ground fault element) will be blocked
during VT1 primary circuit failure, please refer to Section 3.7.3.5.
(2) If there only has one group of three-phase voltage transformer, the voltage balance function is
not in service.
If above conditions are all met, VT1 primary circuit failure 1 alarm signal will be issued with a short
time delay, generator 3rd harmonic stator ground fault protection (including 3rd harmonic ratio stator
Date: 2016-08-16
3 Operation Theory
ground fault element and 3rd harmonic differential stator ground fault element) will be blocked
during VT1 primary circuit failure, please refer to Section 3.7.3.5.
If the zero sequence voltage is only from the zero sequence voltage input of generator terminal,
the VT circuit failure of generator terminal may cause the mal-operation of the zero sequence
voltage protection of stator. So, it is necessary to block the zero sequence voltage protection of
stator when the VT circuit failure of generator terminal is occurred.
If above two conditions are satisfied, the VT1 circuit failure alarm signal 2 is issued with a short
time delay, and the sensitive and insensitive stages of fundamental zero sequence voltage
protection will be blocked, please refer to Section 3.4.3.3.
(1) If there have two groups of three-phase voltage transformers, the voltage balance function is
in service. The operation criterion is as below.
Criteria 1:
Criteria 2:
Where:
U 2 _ set1 and U 2 _ set 2 are two internal settings which are related to U 0 _ set ;
Date: 2016-08-16
3 Operation Theory
If any of above two criteria is met, VT2 primary circuit failure alarm signal will be issued with a time
delay of 40ms, longitudinal zero-sequence voltage inter-turn protection can be blocked by VT2
primary circuit failure alarm signal, please refer to Section 3.4.3.3.
(2) If there only has one group of three-phase voltage transformer, the voltage balance function is
not in service. The operation criterion is as below.
When the criterion operates, VT2 primary circuit failure alarm will be issued with a time delay of
40ms, longitudinal zero-sequence voltage inter-turn protection can be blocked by VT2 primary
circuit failure alarm signal, please refer to Section 3.4.3.3.
3.31.3.5 Generator Neutral Point VT Circuit Failure and Generator Terminal Broken-delta VT
Circuit Failure
VT circuit failure criteria: the positive-sequence voltage of generator terminal secondary circuit is
larger than 0.9Un, the 3rd harmonic of residual voltage is small than 0.1V, then VT circuit failure
alarm signal will be issued with a time delay of 10s, the alarm signal will reset automatically with a
time delay of 10s once the abnormality disappears.
Generator neutral point VT circuit failure and generator terminal broken-delta VT circuit failure
alarm function can be enabled or disabled by respective logic setting, please refer to Section 3.6
and Section 3.4 related contents for details.
3.31.4 Logic
EN [60.En] &
t [60.VT1.Alm_SwitchVTS]
SIG Flg_VTS1_Init_Switch
EN [60.En] &
t [60.VT2.Alm_SwitchVTS]
SIG Flg_VTS2_Init_Switch
Where:
Flg_VTS1_Init_Switch is the internal signal indicating that the VT1 circuit failure initiating switching
criterion is met.
Date: 2016-08-16
3 Operation Theory
Flg_VTS2_Init_Switch is the internal signal indicating that the VT2 circuit failure initiating switching
criterion is met.
60
60.U3P1 60.U3P
60.U3P2 60.VT1.Alm_SwitchVTS
60.U1P1_Hm 60.VT2.Alm_SwitchVTS
60.U1P2_Hm G_Term.VT1.Alm_VTS_Pri_1
60.U1P3_Hm G_Term.VT1.Alm_VTS_Pri_2
60.Flg_OnLOad G_Term.VT2.Alm_VTS_Pri
Above input and output signals can be used for programmable logic, and following output signals
are only for LCD display and waveform recording function of the device.
Alarm signals
Date: 2016-08-16
3 Operation Theory
The phase angle between phase-A voltage of VT1 and VT2 of deg
1 Ang(Ua_VT1-2_G_Term)
generator terminal
The phase angle between phase-B voltage of VT1 and VT2 of deg
2 Ang(Ub_VT1-2_G_Term)
generator terminal
The phase angle between phase-C voltage of VT1 and VT2 of deg
3 Ang(Uc_VT1-2_G_Term)
generator terminal
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Gen PhaseAngleValues
3.31.6 Settings
Table 3.31-5 Settings list of voltage balance protection
NOTICE!
In Section 3.32, the prefix “Y” in settings (such as [Y.I1n]) and input/output signals (such
as [Y.Ia]) can be G_Term, G_NP, G_Bak, 32, ET_S1, ET_S2. Details of the prefix are
as:
Date: 2016-08-16
3 Operation Theory
3.32.1 Application
Three-phase current element is responsible for pre-processing three phase currents and
calculating sequence components, amplitudes and phases of three phase currents, etc. All
calculated information of three-phase current element is for the protection logic calculation.
3.32.3 Principle
CT circuit abnormality supervision
If the calculated residual current is larger than 0.04In plus 25% of the maximum phase current, the
corresponding CT circuit abnormality alarm signal [Y.AlmL_CTS] will be issued with a time delay of
10s, and it will be reset with a time delay of 10s if the CT circuit returns to normal condition.
Current detection
When any phase current is larger than 0.04In, it will be identified that current is detected for the
corresponding CT, CT having current signal can be used for programmable logic application.
3.32.4 Logic
10s 10s
SIG Y.3I0>0.04In+0.25Imax [Y.AlmL_CTS]
SIG Y.Ia>0.04In
≥1
SIG Y.Ib>0.04In [Y.Flg_OnLoad]
SIG Y.Ic>0.04In
Where:
Y.Ia, Y.Ib, and Y.Ic are sampled three phase current values.
Date: 2016-08-16
3 Operation Theory
Curr3P
Y.ia Y.I3P
Y.ib Y.Ia
Y.ic Y.Ib
Y.Ic
Y.I_Avg
Y.AlmL_CTS
Y.Flg_OnLoad
Above input signals and output signals can be used for programmable logic, and following output
signals are only for LCD display of equipment.
Alarm signals
1 G_Term.Ia
Date: 2016-08-16
3 Operation Theory
7 G_NP.Ia
13 G_Bak.Ia
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values1-> Gen Curr Values
Main menu -> Measurements -> Measurements2-> Gen Values2-> Gen Curr Values
19 ET_S1.Ia
21 ET_S1.Ic
Date: 2016-08-16
3 Operation Theory
transformer
Access path:
Main menu -> Measurements -> Measurements1-> Exc Values1-> Exc AC Values
Main menu -> Measurements -> Measurements2-> Exc Values2-> Exc AC Values
Access path:
Main menu -> Measurements -> Measurements2-> Phase Angle-> Gen PhaseAngleValues
3.32.6 Settings
Table 3.32-5 Settings list of three-phase current element
Date: 2016-08-16
3 Operation Theory
NOTICE!
In Section 3.33, the prefix “Y” in settings (such as [Y.U1n]) and input/output signals
(such as [Y.Ua]) can be G_Term.VT1, G_Term.VT2 and Tr_HVS. Details of the prefix
are as:
3.33.1 Application
Three-phase voltage element is responsible for pre-processing three phase voltages and
calculating sequence components, amplitudes and phases of three phase voltages, etc. All
calculated information of three-phase voltage element is for the protection logic calculation.
3.33.3 Principle
VT circuit abnormality supervision
If one of following two criteria is met and there is no operation of any fault detectors, VT circuit
failure alarm will be issued with a time delay of 10s. The abnormality alarm will be reset with a time
delay of 10s if the VT circuit returns to normal condition.
1) Positive sequence voltage is less than 18V and any phase current is larger than 0.04 In.
2) The three times of negative sequence voltage (3U2) is larger than 8V.
If following two criteria are all met, VT neutral line failure alarm will be issued with a time delay of
20s. The abnormality alarm will be reset with a time delay of 20s if the VT neutral line returns to
normal condition. VT neutral line failure supervision function can be enabled or disabled
independently.
Date: 2016-08-16
3 Operation Theory
2) The third harmonic of calculated residual voltage (3U0_3ω) is larger than K*U1
K is the VT neutral line failure percentage restraint coefficient [Y.K_VTNS], it takes 0.2~0.5
generally.
3.33.4 Logic
SIG 3U2>8V
≥1
10s 10s
SIG U1<18V & [Y.Alm_VTS]
SIG [Y.Flg_OnLoad]
EN Y.En_VTNS
&
20s 20s
SIG U1>48V & [Y.Alm_VTNS]
SIG 3U0_3ω>[Y.K_VTNS]*U1
Where:
U2 and U1 are negative sequence voltage value and positive sequence voltage value respectively.
Volt3P
Y.ua Y.Alm_VTS
Y.ub Y.Alm_VTNS
Y.uc Y.U3P
Y.Flg_OnLoad Y.Ua
Y.Ub
Y.Uc
Y.U_Avg
Date: 2016-08-16
3 Operation Theory
Alarm signals
1 G_Term.VT1.Ua
2 G_Term.VT1.Ub Phase voltage amplitude of VT1 of generator terminal
3 G_Term.VT1.Uc
4 G_Term.VT1.U1 Positive-sequence voltage amplitude of VT1 of generator terminal
7 G_Term.VT1.Uab
8 G_Term.VT1.Ubc Phase-to-phase voltage amplitude of VT1 of generator terminal
9 G_Term.VT1.Uca
10 G_Term.VT2.Ua
11 G_Term.VT2.Ub Phase voltage amplitude of VT2 of generator terminal
12 G_Term.VT2.Uc
13 G_Term.VT2.U1 Positive-sequence voltage amplitude of VT2 of generator terminal
16 G_Term.VT2.Uab
17 G_Term.VT2.Ubc Phase-to-phase voltage amplitude of VT2 of generator terminal
18 G_Term.VT2.Uca
19 Tr_HVS.Ua Phase voltage amplitude of the VT of HV side of main transformer
Date: 2016-08-16
3 Operation Theory
20 Tr_HVS.Ub
21 Tr_HVS.Uc
Positive-sequence voltage amplitude of the VT of HV side of main
22 Tr_HVS.U1
transformer
25 Tr_HVS.Uab
Phase-to-phase voltage amplitude of the VT of HV side of main
26 Tr_HVS.Ubc
transformer
27 Tr_HVS.Uca
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Volt Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Volt Values
3.33.6 Settings
Table 3.33-5 Settings list of three-phase voltage element
Date: 2016-08-16
3 Operation Theory
NOTICE!
In Section 3.34, the prefix “Y” in input/output signals (such as [Y.I1P]) can be 87NTG
and 51GS. Details of the prefix are as:
3.34.1 Application
Single current element with filter is responsible for pre-processing measured single current and
calculating the fundamental component amplitude and 3rd harmonic amplitude of single current,
etc. All calculated information of single current element with filter is for the protection logic
calculation.
CurrFilt1P
Y.in Y.I1P_Hm
Y.I_Hm1
Y.I_Hm3
Figure 3.34-1 Function block diagram of single current element with filter
Date: 2016-08-16
3 Operation Theory
Table 3.34-3 Output signals of single current element with filter (measurements)
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Diff Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Diff Values
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Misc Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Misc Values
3.34.4 Settings
Table 3.34-4 Settings list of single current element with filter
NOTICE!
In Section 3.35, the prefix “Y” in input/output signals (such as [Y.U1P]) can be
G_Term.VT1, G_Term.VT2, G_NP and Tr_HVS. Details of the prefix are as:
3.35.1 Application
Residual voltage element is responsible for pre-processing residual voltage and calculating the
fundamental component amplitude and 3rd harmonic amplitude of residual voltage, etc. All
calculated information of residual voltage element is for the protection logic calculation
Date: 2016-08-16
3 Operation Theory
The residual voltage can select the calculated residual voltage or the broken-delta residual
voltage.
VoltFilt1P
Y.ua Y.U1P_Hm
Y.ub Y.3U0_Hm1
Y.uc Y.3U0_Hm3
Y.3u0
Date: 2016-08-16
3 Operation Theory
Access path:
Main menu -> Measurements -> Measurements1-> Gen Values-> Gen Volt Values
Main menu -> Measurements -> Measurements2-> Gen Values-> Gen Volt Values
3.35.4 Settings
Table 3.35-4 Settings list of residual voltage element
Date: 2016-08-16
3 Operation Theory
Date: 2016-08-16
4 Supervision
4 Supervision
Table of Contents
4 Supervision ........................................................................................ 4-a
4.1 Overview .......................................................................................................... 4-1
4.2 Failure and Abnormality Alarms .................................................................... 4-1
4.3 Relay Self-supervision.................................................................................. 4-12
4.3.1 Relay Hardware Monitoring ............................................................................................... 4-12
List of Tables
Table 4.2-1 Alarm description..................................................................................................... 4-1
Date: 2016-08-16
4 Supervision
4.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before the
LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore, the
automatic supervision function, which checks the health of the protection system when startup and
during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
If the protective device is blocked or alarm signal is sent during operation, please try to
find out its reason with the help of self-diagnostic record. If the failure reason can not be
found at site, please inform the manufacturer NR or the agent for maintenance. Please
DO NOT simply press button “TARGET RESET” on the protection panel or re-energize
on the device.
Hardware circuit and operation status of the device are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts BO_FAIL will be given. The
protective device then can not work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
Blocking
No. Item Description
Device
Fail Signals
The device fails.
1 Fail_Device This signal will be pick up if any fail signal picks up and it Blocked
will drop off when all fail signals drop off.
Blocking
No. Item Description
Device
Set value of any setting is out of scope.
2 Fail_Setting_OvRange This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
Mismatch between the configuration of plug-in modules and
3 Fail_BoardConfig Blocked
the designing drawing of an applied-specific project.
4 Fail_Config_Parsed The configuration file is wrong parsed. Blocked
5 Fail_Board_Regst Any board is failed to register. Blocked
6 Fail_Board_Inited Any board is failed to initialize. Blocked
After config file is updated, settings of the file and settings
saved on the device are not matched.
7 Fail_SettingItem_Chgd Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking memory data (fault detector
DSP module).
8 FDBrd.Fail_Memory Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking settings (fault detector DSP
module).
9 FDBrd.Fail_Settings Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
DSP chip is damaged (fault detector DSP module).
10 FDBrd.Fail_DSP This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
AC current and voltage samplings are abnormal (fault
detector DSP module).
11 FDBrd.Fail_Sample This signal will pick up with a time delay of 50ms and will be Blocked
latched unless the recommended handling suggestion is
adopted.
Error is found during checking memory data (protection
DSP module).
12 ProtBrd.Fail_Memory Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
Error is found during checking settings (protection DSP
module).
13 ProtBrd.Fail_Settings Blocked
This signal will pick up instantaneously and will be latched
unless the recommended handling suggestion is adopted.
DSP chip is damaged (protection DSP module).
14 ProtBrd.Fail_DSP This signal will pick up instantaneously and will be latched Blocked
unless the recommended handling suggestion is adopted.
AC current and voltage samplings are abnormal (protection
15 ProtBrd.Fail_Sample DSP module). Blocked
This signal will pick up with a time delay of 50ms and will be
Date: 2016-08-16
4 Supervision
Blocking
No. Item Description
Device
latched unless the recommended handling suggestion is
adopted.
The HTM bus for data exchange is abnormal (fault detector
16 FDBrd.Fail_HTM Blocked
DSP module).
The HTM bus for data exchange is blocked for a long time
17 ProtBrd.Fail_HTM Blocked
(protection DSP module).
The alarm indicating that the tripping output module located
18 Bn.Fail_Board Blocked
in slot No.n (n=11~14) is in abnormal status.
The alarm indicating that the output contactor of the tripping
19 Bn.Fail_Output output module located in slot No.n (n=11~14) is in abnormal Blocked
status.
Alarm Signals
The device is abnormal.
20 Alm_Device This signal will be pick up if any alarm signal picks up and it Unblocked
will drop off when all alarm signals drop off.
21 Alm_Insuf_Memory The memory of MON plug-in module is insufficient. Unblocked
The device is in the communication test mode.
22 Alm_CommTest This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
23 Alm_Init The device is in initialization process. Unblocked
24 Board_Stall_Flag Any board is abnormal. Unblocked
The error is found during MON module checking settings of
device.
25 Alm_Settings_MON Unblocked
This signal will pick up with a time delay of 10s and will be
latched unless re-powering or rebooting the device.
The error is found during checking the version of software
downloaded to the device.
26 Alm_Version Unblocked
This signal will pick up instantaneously and will drop off
instantaneously.
The active group set by settings in device and that set by
binary input are not matched.
27 Alm_BI_SettingGrp Unblocked
This signal will pick up instantaneously and will drop off
instantaneously.
28 Alm_TimeSyn Time synchronization abnormality alarm. Unblocked
The alarm is to indicate that the IEC103 file in the device is
29 Alm_CfgFile_IEC103 Unblocked
invalid.
The alarm is to indicate that the device is in testing mode for
30 Alm_TestMode Unblocked
signal/trip output.
The alarm is to indicate that the board at slot n (n=6~10, 15)
31 Bn.Alm_Board Unblocked
is in abnormal status.
32 B09.Alm_OptoDC The power supply of BI plug-in module in slot 09 is Unblocked
Blocking
No. Item Description
Device
abnormal.
This signal will pick up with a time delay of 10s and will drop
off with a time delay of 10s.
The power supply of BI plug-in module in slot 14 is
abnormal.
33 B14.Alm_OptoDC Unblocked
This signal will pick up with a time delay of 10s and will drop
off with a time delay of 10s.
The device is in the GOOSE test mode.
34 Alm_GOOSETest This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
The “master” process is alarm.
35 Alm_master This signal will pick up instantaneously and will drop off Unblocked
instantaneously.
Current fault detector element operates for longer than 10s
(fault detector DSP module).
36 FDBrd.Alm_Pkp Unblocked
This signal will pick up with a time delay of 10s and will drop
off with a time delay of 10s.
Current fault detector element operates for longer than 10s
(protection DSP module).
37 ProtBrd.Alm_Pkp Unblocked
This signal will pick up with a time delay of 10s and will drop
off with a time delay of 10s .
Protection Element Alarm Signals
38 G_Term.AlmL_CTS Generator terminal CT secondary circuit abnormality alarm. Unblocked
Generator neutral point CT secondary circuit abnormality
39 G_NP.AlmL_CTS Unblocked
alarm.
Generator backup protection used CT secondary circuit
40 G_Bak.AlmL_CTS Unblocked
abnormality alarm.
Power protection used CT secondary circuit abnormality
41 32.AlmL_CTS Unblocked
alarm.
Excitation transformer side 1 CT secondary circuit
42 ET_S1.AlmL_CTS Unblocked
abnormality alarm.
Excitation transformer side 2 CT secondary circuit
43 ET_S2.AlmL_CTS Unblocked
abnormality alarm.
44 G_Term.VT1.Alm_VTS Generator terminal VT1 secondary circuit failure alarm. Unblocked
45 G_Term.VT1.Alm_VTNS Generator terminal VT1 neutral line failure alarm. Unblocked
46 G_Term.VT2.Alm_VTS Generator terminal VT2 secondary circuit failure alarm. Unblocked
47 G_Term.VT2.Alm_VTNS Generator terminal VT2 neutral line failure alarm. Unblocked
Main transformer HV side VT secondary circuit failure
48 Tr_HVS.Alm_VTS Unblocked
alarm.
49 Tr_HVS.Alm_VTNS Main transformer HV side VT neutral line failure alarm. Unblocked
Generator terminal circuit breaker auxiliary contact
50 Alm_52_GCB Unblocked
abnormality alarm.
Date: 2016-08-16
4 Supervision
Blocking
No. Item Description
Device
51 60.VT1.Alm_SwitchVTS VT1 circuit failure initiating switching alarm. Unblocked
52 60.VT2.Alm_SwitchVTS VT2 circuit failure initiating switching alarm. Unblocked
53 G_Term.VT1.Alm_VTS_Pri_1 Generator terminal VT1 primary circuit failure 1 alarm. Unblocked
54 G_Term.VT1.Alm_VTS_Pri_2 Generator terminal VT1 primary circuit failure 2 alarm. Unblocked
55 G_Term.VT2.Alm_VTS_Pri Generator terminal VT2 primary circuit failure alarm. Unblocked
56 G_Term.VT1.Alm_VTS_Delt Generator terminal VT1 broken-delta circuit failure alarm. Unblocked
57 G_Term.VT2.Alm_VTS_Delt Generator terminal VT2 broken-delta circuit failure alarm. Unblocked
58 G_NP.Alm_VTS Generator neutral point VT circuit failure alarm. Unblocked
Alarm message indicating CT secondary circuit of generator
59 87G.Alm_Diff Unblocked
differential protection is abnormal.
Alarm message indicating that CT secondary circuit of
60 87G.Alm_CTS Unblocked
generator differential protection fails.
Negative-sequence DPFC direction inter-turn element to
61 59NIT.Alm_P2_DPFC Unblocked
issue alarm signal.
The sensitive stage of fundamental zero-sequence voltage
62 64S1.Alm_ROV_L stator ground fault protection operates to issue alarm Unblocked
signal.
The fundamental zero-sequence current stator ground fault
63 64S1.Alm_ROC Unblocked
protection operates to issue alarm signal.
3rd harmonic ratio stator ground fault element operates to
64 64S2.Alm_U_Hm3_Ratio Unblocked
issue alarm signal.
3rd harmonic differential stator ground fault element
65 64S2.Alm_U_Hm3_Diff Unblocked
operates to issue alarm signal.
The alarm stage of stator overload protection operates to
66 49S.Alm Unblocked
issue alarm signal
The alarm stage of generator negative-sequence overload
67 46G.Alm Unblocked
protection operates to issue alarm signal.
Stage 1 of loss of excitation protection operates to issue
68 40G1.Alm Unblocked
alarm signal.
Rotor voltage circuit failure alarm for stage 1 of loss of
69 40G1.Alm_RotVoltCircuit Unblocked
excitation protection.
Stage 2 of loss of excitation protection operates to issue
70 40G2.Alm Unblocked
alarm signal.
Rotor voltage circuit failure alarm for stage 2 of loss of
71 40G2.Alm_RotVoltCircuit Unblocked
excitation protection.
Stage 3 of loss of excitation protection operates to issue
72 40G3.Alm Unblocked
alarm signal.
Rotor voltage circuit failure alarm for stage 3 of loss of
73 40G3.Alm_RotVoltCircuit Unblocked
excitation protection.
Out-of-step protection for external power swing operates to
74 78.Alm_Ext Unblocked
issue alarm signal.
Blocking
No. Item Description
Device
Out-of-step protection for internal power swing operates to
75 78.Alm_Int Unblocked
issue alarm signal.
76 78.Alm_Accel Alarm signal indicating that accelerate out-of-step occurs. Unblocked
77 78.Alm_Decel Alarm signal indicating that decelerate out-of-step occurs. Unblocked
Phase overvoltage protection alarm stage operates to issue
78 Gen.59PAlm.Alm Unblocked
alarm signal.
Phase undervoltage protection alarm stage operates to
79 Gen.27PAlm.Alm Unblocked
issue alarm signal.
The alarm stage of overexcitation protection operates to
80 Gen.24.Alm Unblocked
issue alarm signal
81 32R.CONV.Alm The conventional reverse power element operates to alarm. Unblocked
82 32F.Alm Generator low forward power protection operates to alarm. Unblocked
The sensitive stage of Ping-Pang type rotor one-point
83 64R.1PEF.Alm_Sens Unblocked
ground fault element operates to issue alarm signal.
The insensitive stage of Ping-Pang type rotor one-point
84 64R.1PEF.Alm_Insens Unblocked
ground fault element operates to issue alarm signal.
Rotor voltage circuit failure alarm for Ping-Pang type rotor
85 64R.Alm_RotVoltCircuit Unblocked
one-point ground fault protection.
Sensitive stage of rotor one-point ground fault element (with
86 64RInj.1PEF.Alm_Sens low-frequency square-wave voltage injection) operates to Unblocked
issue alarm signal.
Insensitive stage of rotor one-point ground fault element
87 64RInj.1PEF.Alm_Insens (with low-frequency square-wave voltage injection) Unblocked
operates to issue alarm signal.
The external injected power supply of generator rotor
88 64RInj.Alm_Pwr_Inj ground fault protection (with low-frequency square-wave Unblocked
voltage injection) is abnormal.
Stage 1 of underfrequency protection operates to issue
89 81U.UF1.Alm Unblocked
alarm signal.
Stage 2 of underfrequency protection operates to issue
90 81U.UF2.Alm Unblocked
alarm signal.
Stage 3 of underfrequency protection operates to issue
91 81U.UF3.Alm Unblocked
alarm signal.
Stage 4 of underfrequency protection operates to issue
92 81U.UF4.Alm Unblocked
alarm signal.
Stage 1 of underfrequency band accumulate protection
93 81U.UF1.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 2 of underfrequency band accumulate protection
94 81U.UF2.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 3 of underfrequency band accumulate protection
95 81U.UF3.Alm_Accu Unblocked
operates to issue alarm signal.
Date: 2016-08-16
4 Supervision
Blocking
No. Item Description
Device
Stage 4 of underfrequency band accumulate protection
96 81U.UF4.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 1 of overfrequency protection operates to issue alarm
97 81O.OF1.Alm Unblocked
signal.
Stage 2 of overfrequency protection operates to issue alarm
98 81O.OF2.Alm Unblocked
signal.
Stage 3 of overfrequency protection operates to issue alarm
99 81O.OF3.Alm Unblocked
signal.
Stage 4 of overfrequency protection operates to issue alarm
100 81O.OF4.Alm Unblocked
signal.
Stage 1 of overfrequency band accumulate protection
101 81O.OF1.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 2 of overfrequency band accumulate protection
102 81O.OF2.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 3 of overfrequency band accumulate protection
103 81O.OF3.Alm_Accu Unblocked
operates to issue alarm signal.
Stage 4 of overfrequency band accumulate protection
104 81O.OF4.Alm_Accu Unblocked
operates to issue alarm signal.
Alarm message indicating CT secondary circuit of excitation
105 87ET.Alm_Diff Unblocked
transformer differential protection is abnormal.
Alarm message indicating that CT secondary circuit of
106 87ET.Alm_CTS Unblocked
excitation transformer differential protection fails.
The alarm stage of rotor winding overload protection
107 49E.Alm Unblocked
operates to issue alarm signal
Sensitive stage of generator shaft overcurrent protection
108 51GS.Alm Unblocked
operates to issue alarm signal
Output alarm signal of channel 1 of mechanical protection
109 MR1.Sig1 Unblocked
1.
Output alarm signal of channel 2 of mechanical protection
110 MR1.Sig2 Unblocked
1.
Output alarm signal of channel 3 of mechanical protection
111 MR1.Sig3 Unblocked
1.
Output alarm signal of channel 4 of mechanical protection
112 MR1.Sig4 Unblocked
1.
113 MR1.Alm_PwrLoss Power supervision alarm signal of mechanical protection 1. Unblocked
Output alarm signal of channel 1 of mechanical protection
114 MR2.Sig1 Unblocked
2.
Output alarm signal of channel 2 of mechanical protection
115 MR2.Sig2 Unblocked
2.
Output alarm signal of channel 3 of mechanical protection
116 MR2.Sig3 Unblocked
2.
Blocking
No. Item Description
Device
Output alarm signal of channel 4 of mechanical protection
117 MR2.Sig4 Unblocked
2.
118 MR2.Alm_PwrLoss Power supervision alarm signal of mechanical protection 2. Unblocked
Date: 2016-08-16
4 Supervision
2. check whether the wiring connection between the device and the clock
synchronization source is correct
23 Alm_TimeSyn 3. check whether the setting for selecting clock synchronization (i.e.
[Opt_TimeSyn]) is set correctly. If there is no clock synchronization,
please set the setting [Opt_TimeSyn] as ”No TimeSync”.
27 B09.Alm_OptoDC supply.
2. check whether the voltage of power supply is in the required range.
3. After the voltage for binary input module restores to normal range, the
“ALARM” LED will be extinguished and the corresponding alarm
28 B14.Alm_OptoDC message will disappear and the device will restore to normal operation
state.
Date: 2016-08-16
4 Supervision
If a fault detector on protection or fault detector DSP module keeps picking up for 10s, the
corresponding alarm signal [ProtBrd.Alm_Pkp] or [FDBrd.Alm_Pkp] will be issued without the
device being blocked.
Date: 2016-08-16
4 Supervision
Date: 2016-08-16
5 Management
5 Management
Table of Contents
Date: 2016-08-16
5 Management
Date: 2016-08-16
5 Management
5.1 Overview
The relay also provides some auxiliary functions, such as on-line data metering, binary input
status, event and disturbance recording. All these functions make the relay meet the demands of
the modern power grid requirements.
5.2 Measurement
The device can continuously display the measured analogue input quantities, some internal flags
and calculated value based on the analogue input quantities can also be displayed. The
measurement data are displayed on the LCD of the relay front panel or by the software interface
on the local or remote PC. The analog quantities will be displayed as RMS values of the
secondary side of CT and VT.
The device samples 24 points per cycle. The RMS value is calculated in each interval and the LCD
display will be updated in every 0.5 second.
Users can view the measured data on LCD by navigating the menu “Measurements”, or by
PCS-Explorer2 software or substation automatic system (SAS) software.
The device has two DSP modules that are protection DSP module and fault detector DSP module,
the displayed values of the menu “Measurements->Measurement1” corresponds to the
measurement data of protection DSP module, and the displayed values of the menu
“Measurements->Measurement2” corresponds to the measurement data of fault detector DSP
module.
Please refer to the output signal list (for measurements) of Section “Inputs and Outputs” of each
protection element in Chapter 3 for detailed description and the concrete access path of each
measurement data. For a certain application, some measurement data listed in Chapter 3 may be
eliminated due to the scheme user required, so please look up the device on site for actual
displayed measurement data.
5.3.1 Introduction
Event recording
Present recording
All the recorded information except for waveform can be viewed on local LCD or by printing.
Waveform must be printed or be extracted using PCS-Explorer2 software and a waveform
software.
Date: 2016-08-16
5 Management
When binary input status changes, the changed information will be displayed on LCD and logged
as binary input change report at the same time.
Users can use the disturbance recorder to achieve a better understanding of the behavior of the
power network and related primary and secondary device during and after a disturbance.
Analyzing on the recorded data can help to resolve practical problem.
5.3.3.2 Design
Disturbance recorder is consisted of tripping report and fault waveform and it is triggered by fault
detector. The device can store 64 pieces of trip reports and waveforms in non-volatile memory.
When protection operates, the operating information will be displayed on LCD and logged as trip
record at same time, which can be viewed in trip report. Here fault recording includes two kinds of
cases:
2) The fault detector element operates along with the operation of protective elements.
The device can store 64 pieces of trip reports in non-volatile memory. If a new fault occurs when
the spaces are fully occupied, the oldest will be overwritten by the latest one.
1) Sequence number
Each operation will be recorded with a sequence number in the report and displayed on LCD
screen.
The time resolution is 1 ms using the relay internal clock. Initiating date and time is when a fault
detector picks up. The relative time is the time when protection element operates to send tripping
signal after fault detector picks up.
Date: 2016-08-16
5 Management
3) Operating time
It is the relative time when protection element operates to send tripping signal relative to fault
detector element operating, the operating time of output relay is not included.
4) Protection element
The protection element that issues the tripping command will be shown. If no protection element
operates to trip but only fault detector element operates, the fault report will record the title of fault
detector element.
MON module of the relay can store 64 pieces of fault waveform in non-volatile memory. If a new
fault occurs when 64 fault waveform recorders have been stored, the oldest will be overwritten by
the latest one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, differential current, alarm elements, and binary inputs and etc.
Each time recording includes several-cycle pre-disturbance waveform (the waveform cycle
number before triggering is configured via the communication setting
[Num_Cyc_PreTrigDFR], the default value is 3-cycle) and 8-cycle after-disturbance
waveform.
2) The fault detector element operates along with the operation of protective element.
Each time recording includes several-cycle pre-fault waveform (the waveform cycle number
is configured via the communication setting [Num_Cyc_PreTrigDFR], the default value is
3-cycle), 8-cycle after-fault waveform, several-cycle pre-tripping waveform (the waveform
cycle number is configured via the communication setting [Num_Cyc_PreTrigDFR], the
default value is 3-cycle), 8-cycle after-tripping waveform and all the current and voltage
waveform with disturbance between the fault detector element and the protective element.
Present recording is used to record the waveform of present operating device which can be
triggered manually on LCD of device or remotely through PCS-Explorer2 software. Recording
content of present recording is same to that of disturbance recording. Each time recording
includes several-cycle pre-disturbance waveform (the waveform cycle number is configured via
the communication setting [Num_Cyc_PreTrigDFR], the default value is 3-cycle) and 8-cycle
after-disturbance waveform.
Date: 2016-08-16
5 Management
Date: 2016-08-16
6 Hardware
6 Hardware
Table of Contents
6.4.8 Mechanical Signal Input and Output Module (MR module) ............................................... 6-21
List of Figures
Figure 6.4-1 The module arrangement of PCS-985GE from rear view................................... 6-6
Date: 2019-02-21
6 Hardware
Figure 6.4-11 Pin definition of signal output module NR1523A ........................................... 6-18
Figure 6.4-12 Pin definition of signal output module NR1523B ........................................... 6-19
Figure 6.4-13 Pin definition of signal output module NR1523C ........................................... 6-20
Figure 6.4-14 Pin definition of signal output module NR1523D ........................................... 6-21
Figure 6.4-15 Pin definition of mechanical relay IO module (x=1, 2) ................................... 6-22
Figure 6.4-18 Default terminal definition 1 of two NR1401 modules ................................... 6-26
Figure 6.4-19 Default terminal definition 2 of two NR1401 modules ................................... 6-27
List of Tables
Table 6.4-1 Terminal definition and description of PWR plug-in module ............................. 6-8
Date: 2019-02-21
6 Hardware
6.1 Overview
Output Relay
Binary Input
External
Protection
CT/VT A/D Calculation
DSP
Fault
A/D Detector Pickup
DSP Relay
N
R
H
E
E
T
T
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
R
5
4
J
Keypad
IN
R
P
T
The device adopts 32-bit microchip processor CPU as control core for management and
monitoring function, meanwhile, adopts high-speed digital signal processor DSP to be in charge of
all the protection calculation. 24 points are sampled in every cycle and parallel processing of
sampled data can be realized in each sampling interval to ensure ultra-high reliability and safety of
protection equipment.
The working process of the device is as follows: firstly, the current and voltage is converted into
small voltage signal and sent to DSP module after being filtered and converted by AD for
protection calculation and fault detector respectively. When DSP module completes all the
protection calculation, the result will be sent to 32-bit CPU on MON module to be recorded.
Protection DSP module carries out protection logic calculation, tripping output, and MON module
completes SOE (sequence of event) record, waveform recording, printing, communication
between protection and SAS and communication between HMI and CPU. The work process of
fault detector DSP module is similar to that of protection DSP module, and the only difference is,
when fault detector DSP module decides a fault detector picks up, only positive power supply of
output relay will be switched on.
The device is comprised of intelligent modules, except that few particular modules’ position cannot
be changed in the whole device (please refer to Figure 6.4-1 for details), the others like AI (analog
input) module such as AC current, AC voltage, DC current, and etc., and IO (input and output)
module such as binary input, tripping output, signal output, and etc can be flexibly configured
according to the remained slot positions.
Date: 2019-02-21
6 Hardware
MON module provides functions like management function, completed event record, setting
management, and etc.
DSP modules can carry out filtering, sampling, protection calculation and fault detector
calculation.
AI module converts AC current and voltage to low voltage signals with current transformers
and voltage transformers respectively.
BI module provides binary inputs via opto-couplers with rating voltage among
110V/125V/220V/250V (configurable)
BO module provides all kinds of binary output contacts, including signal output contacts and
tripping output contacts.
PWR module converts DC 250/220/125/110V into different DC voltage levels for various
modules of the device.
HMI module is comprised of LCD, keypad, LED indicator and multiplex RJ45 ports for user as
human-machine interface.
Following figures show front and rear views of the device respectively. Programmable LED
indicators (No.4-No.20) can be defined by user through PCS-Explore2 software.
Date: 2019-02-21
6 Hardware
1 11
HEALTHY
2 12 PCS-985GE
ALARM
3
TRIP
13
GENERATOR RELAY
4 14
5 15
C GRP
6 16
7 17 ENT
ES
8 18
9 19
10 20
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
NR1101F NR1156D NR1156D NR1401 NR1401 NR1418C NR1504A NR1536A NR1521A NR1523A NR1523A NR1301T
5V BJ
1 2 3 1 2 3
4 5 6 4 5 6 BJJ BSJ
ON
OFF
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
10 PWR+
11 PWR-
12 GND
Date: 2019-02-21
6 Hardware
Three-phase current
Ia
Three-phase current
PCS-985GE
input channel 5
BI_TimeSyn 0602
input channel 1
0902 + 0402 Ian Ian
0403 0603
Ib Ib
0903 + BI_Print
0404 0604
Ibn Ibn
BI_Maintenance 0405 0605
0904 + Ic Ic
0406 0606
Icn Icn
0905 + BI_RstTarg
0407
current
Three-phase current
BI_06 Ia 0607
Shaft
0906 + I Rotor ground fault protection input
input channel 2
0408 0608 module
Ian In
0907 + BI_07 0409
Ib B08 NR1418
0410 IR+ 01
Reserved
Ibn
sensitive
Current
0908 Not used 0609
0411 I DC Transducer 02
Ic
0412 0610 In input IR- 03
0909 + BI_08 Icn
04
BI module 1 (NR1504)
Transverse
BI_09 Loss of UR2+ 05
differential
0910 + 0413
current
Ia 0611
Three-phase current
I excitation
06
input channel 3
Three-phase voltage
0417 UR1+ 10
input channel 1
0913 + BI_12 Ic 0614 Uan
0418 11
Icn 0615 Ub
0914 + BI_13 12
0616 Ubn 13
(measurement level CT)
Ia Uc Ping-Pang type
input channel 4
0621
point
3U0
BI_18 22
0920 + Opto+ 0622
3U0n
1401 +
0921 + BI_19
BI_02
Generator
terminal
BI_04
1404 +
BO_FAIL
1109 BI_11 1009 BO_MR1.Sig4_1
P103
1412 + BO_ALM
1110 BO_Trip_2-1
BI_12 1010 Common1
COM P101
1413 +
1111 P105
1011 BO_MR1.Sig1_2 BO_FAIL
1112 BO_Trip_2-2 BI_13
1414 + BO_ALM P106
1012 BO_MR1.Sig2_2
1113 P104
1415 + COM
1114 BO_Trip_2-3 Not used 1013 BO_MR1.Sig3_2
P112
1115 1416 + BI_14 1014 BO_MR1.Sig4_2 Grounding
BO_Trip_2-4 Screw
1116 1015 Common2
1417 + BI_15
1117 1016 BO_MR1.Sig1_3
Grounding
1118 BO_Trip_3-1 BI_16 Bus
1418 + 1017 BO_MR1.Sig2_3
1119
1419 + BI_17 1018 BO_MR1.Sig3_3
1120 BO_Trip_3-2
1019 BO_MR1.Sig4_3 Multiplex
1121 1420 + BI_18
RJ45 (Front)
1122 BO_Trip_3-3 1020 Common3
1421 + BI_19
1021 Pwr+
Module Power Input
Ethernet C
BO_Signal_2-2 BO_Signal_10-2 BO_Signal_18-2 Ethernet to
1208 1308 1508
MON module (NR1101)
SCADA
Ethernet D
1209 1309 1509
BO_Signal_3-1 BO_Signal_11-1 BO_Signal_19-1
COM(optional)
1515
BO_Signal_5 BO_Signal_13 BO_Signal_21 0102 SYN-
1216 1316 1516
0103 SGND
1217 1317 1517
BO_Signal_6 BO_Signal_14 BO_Signal_22 0104
1218 1318 1518
1219 1319 1519 0105 RTS
PRINT
Date: 2019-02-21
6 Hardware
6.3 CT Requirement
-Rated short-time thermal current Ith and rated dynamic current Idyn:
Performance verification
Date: 2019-02-21
6 Hardware
For example:
= 30×5×(1+60/25)=510V
Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn
= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn
= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V
The device consists of PWR plug-in module, MON plug-in module, DSP plug-in module, AI plug-in
module, BI plug-in module, BO plug-in module etc. Terminal definitions and application of each
plug-in module are introduced as follows. Terminal definitions are represents with its slot position
and pin number. For example, contact 1301-1302 means terminal 01-02 of the module located in
slot 13, i.e. 13 represents the slot position, 01(02) represents the pin number on the module.
The module arrangement of the device from rear view is shown in the following figure. The
irremovable modules are power supply module, MON module, DSP module and Rotor ground
fault protection input module.
NR1101F NR1156D NR1156D NR1401 NR1401 NR1418 NR1504A NR1536A NR1521A NR1523A NR1523A NR1504A NR1523C NR1301
protection input module
PWR module
MON module
MR module 1
BI module 2
AI module 1
BI module 1
AI module 2
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Date: 2019-02-21
6 Hardware
Besides the fixed five modules are shown in above figure, there are eleven slots can be flexibly
configured.
AI module can be configured at position between slot 04 to slot 07. The AC AI module can be
configured up to 2 pieces, and each AC AI module occupying 2 slots can provide 12 analog
inputs.
BI module and BO module can be configured at position between slot 09 to slot 15.
The +5V DC output provides power supply for all the electrical elements that need +5V DC power
supply in this device. The +24V DC output provides power supply for the static relays of this
device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.
NR1301
5V OK ALM
BO_ALM BO_FAIL
1 BO_COM1 P101
BO_FAIL
2 BO_FAIL P102
BO_ALM
3 BO_ALM P103
4 BO_COM2 P104
BO_FAIL
5 BO_FAIL P105
BO_ALM
6 BO_ALM P106
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
Date: 2019-02-21
6 Hardware
The standard rated voltage of PWR module is self-adaptive to 88~300Vdc. If the input voltage is
out of the range, an alarm signal (Fail_Device) will be issued. For non-standard rated voltage
power supply module please specify when place order, and check whether the rated voltage of
power supply module is the same as the voltage of power source before the device being put into
service.
PWR module provides terminal 12 and grounding screw for device grounding. Terminal 12 shall be
connected to grounding screw and then connected to the earth copper bar of panel via dedicated
grounding wire.
Effective grounding is the most important measure for a device to prevent EMI, so effective
grounding must be ensured before the device is put into service.
Like almost all electronic relays, PCS-985GE contains electrolytic capacitors. These capacitors
are well known to be subject to deterioration over time if voltage is not applied periodically.
Deterioration can be avoided by powering the relays up once a year.
MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet
interfaces, RS-485 communication interfaces, PPS/IRIG-B differential time synchronization
interface and RS-232 printing interface.
Modules with various combinations of memory and interface are available as shown in the table
Date: 2019-02-21
6 Hardware
below.
TX TX ETHERNET
ETHERNET
RX RX
TX TX
RX RX
ETHERNET
TX
RX
Date: 2019-02-21
6 Hardware
03 SGND
04
05 RTS
RS-232 06 TXD To printer Cable
07 SGND
3 RJ45 Ethernet To SCADA
01 A
02 B
RS-485 To SCADA
03 SGND
04
05 A
06 B Twisted pair wire
RS-485 To SCADA
07 SGND
NR1101F 256M DDR 08
09 SYN+
10 SYN- To clock
RS-485
11 SGND synchronization
12
13 RTS
RS-232 14 TXD To printer Cable
15 SGND
16
The correct method of connection is shown in Figure 6.4-4. Generally, the shielded cables with two
pairs of twisted pairs inside shall be applied. One pair of the twisted pairs is used to connect the “+”
and “–” terminals of difference signal; the other is used to connect the signal ground of the
interface, i.e. connect the signal groundings of all the devices to a bus through the twisted pair.
The module reserves a free terminal for all the communication ports; the free terminal does not
need to be connected.
B 02
COM
cable with single point earthing
To the screen of other coaxial
SGND 03
04
SYN- 02
SGND 03
04
TXD 06
SGND 07
Date: 2019-02-21
6 Hardware
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
DSP module 1 and DSP module 2 have the same hardware configuration and are located in slot
02 and slot 03 respectively. The following figure shows rear view and terminal definition for the
DSP module.
NR1156D
1 2 3
4 5 6
Date: 2019-02-21
6 Hardware
equipped with one device. The rated voltage can be selected to be 110V, 125V, 220V and 250V.
The well-designed debouncing technique is adopted in this device, and the state change of binary
input within “Debouncing time” will be ignored. As shown in Figure 6.4-6.
Each BI module is with a 22-pin connector for 11 binary inputs (NR1503) or 18 binary inputs
(NR1504).
For NR1503, each binary input has independent negative power input of opto-coupler, and can be
configurable. The terminal definition of the connector of BI plug-in module is described as below.
[BI_n] (n=01, 02,…,11 can be configured as a specified binary input by PCS-Explorer2 software.)
BI_01 01
NR1503 Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
Date: 2019-02-21
6 Hardware
For NR1504, all binary inputs share one common negative power input, and is configurable. The
terminal definition of the connector of BI plug-in module is described as below. [BI_n] (n=01,
02,…,19 can be configured as a specified binary input by PCS-Explorer2 software.)
Date: 2019-02-21
6 Hardware
BI_01 01
NR1504 BI_02 02
BI_03 03
BI_04 04
BI_05 05
BI_06 06
BI_07 07
08
BI_08 09
BI_09 10
BI_10 11
BI_11 12
BI_12 13
BI_13 14
15
BI_14 16
BI_15 17
BI_16 18
BI_17 19
BI_18 20
BI_19 21
COM- 22
Date: 2019-02-21
6 Hardware
A default configuration is given for first four binary signals (BI_02, BI_03, BI_04, BI_05) of the first
BI plug-in module (located in slot No.09), and they are, [BI_TimeSyn], [BI_Print], [BI_Maintenance]
and [BI_RstTarg] respectively. They can also be configured as other signals. Because the first
binary signal [BI_02] is set as [BI_TimeSyn] by default (the state change information of binary
signal [BI_TimeSyn] does not need be displayed), new binary signal should be added to state
change message if it is set as other signal.
It is used to receive clock synchronization signal from clock synchronization device, the binary
input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device
adopts “Conventional” mode as clock synchronization mode (refer to section “Communication
Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the
setting [Opt_TimeSyn] is set as other values, this binary input is invalid.
It is used to manually trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_AutoPrint] =1), report will be
printed automatically as soon as it is formed.
It is used to block communication export when this binary input is energized. During device
maintenance or testing, this binary input is then energized not to send reports via communication
port, local display and printing still work as usual. This binary input should be de-energized when
the device is restored back to normal.
It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button
on the panel.
NOTICE!
The rated voltage of binary input is optional: 110V, 125V, 220V or 250V, which MUST be
specified when placing an order. It is necessary to CHECK whether the rated voltage of
BI module complies with site DC supply rating before put the relay in service.
Two standard binary output modules, NR1521A, and NR1521H, can be selected. Output contact
can be configured as a specified tripping output contact by PCS-Explorer2 software according to
user requirement.
Date: 2019-02-21
6 Hardware
Up to two tripping output modules (located in slot 11 and 15 respectively) can be equipped with
one device.
NR1521A
01
BO_Trip_01
NR1521A 02
03
BO_Trip_02
04
05
BO_Trip_03
06
07
BO_Trip_04
08
09
BO_Trip_05
10
11
BO_Trip_06
12
13
BO_Trip_07
14
15
BO_Trip_08
16
17
BO_Trip_09
18
19
BO_Trip_10
20
21
BO_Trip_11
22
NR1521H
NR1521H can provide 11 output contacts controlled by fault detector. The first four output contacts
are in parallel with instantaneous operating contacts which are recommended to be configured as
fast signaling contacts.
Date: 2019-02-21
6 Hardware
01
BO_Trip_01
NR1521H 02
03
BO_Trip_02
04
05
BO_Trip_03
06
07
BO_Trip_04
08
09
BO_Trip_05
10
11
BO_Trip_06
12
13
BO_Trip_07
14
15
BO_Trip_08
16
17
BO_Trip_09
18
19
BO_Trip_10
20
21
BO_Trip_11
22
Four standard binary output modules, NR1523A, NR1523B, NR1523C, and NR1523D, can be
selected to provide protection operation signal and abnormality alarm signal.
Up to three signal output modules (located in slot 12, 13 and 15 respectively) can be equipped
with one device.
NR1523A
The NR1523A module is a standard binary output module for signal, which can provide 8 signal
relays (11 signal output contacts, for the first three signal output relays, each relay includes two
contacts) without controlled by fault detector. All the contacts are normally open (NO) contacts,
and among which, [BO_Signal_6], [BO_Signal_7] and [BO_Siganl_8] are magnetic latched NO
contacts.
All contacts of the module can be configured as specified signal output contacts of certain
protections by PCS-Explorer2 software according to users’ requirement. [BO_Signal_4] and
[BO_Siganl_5] are recommended to be configured as alarm signal output contacts, other contacts
are recommended to be configured as tripping signal output contacts.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1523A
NR1523A
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16
16
17 17
BO_Signal_6 BO_Signal_6
18
18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523B
The NR1523B module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. Among those contacts, [BO_Signal_5] and
[BO_Siganl_6] are normally closed (NC) contacts, others are normally open (NO) contacts. All
contacts of the module can be configured as specified signal output contacts of some protections
by PCS-Explorer2 software according to user requirement. Besides, only the contact
[BO_Siganl_8] is a magnetic latched NO contact.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1523B
NR1523B
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16 16
17 17
BO_Signal_6 BO_Signal_6
18 18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523C
The NR1523C module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. Among those contacts, [BO_Signal_3-2],
[BO_Signal_5] and [BO_Siganl_7] are normally closed (NC) contacts, others are normally open
(NO) contacts. All contacts of the module can be configured as specified signal output contacts of
some protections by PCS-Explorer2 software according to user requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1523C
NR1523C
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16 16
17 17
BO_Signal_6 BO_Signal_6
18 18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1523D
The NR1523D module is a standard binary output module for signal, which can provide 11 signal
output contacts without controlled by fault detector. All the contacts are normally open (NO), and
among which, only [BO_Siganl_8] is magnetic latched NO contact. All contacts of the module can
be configured as specified signal output contacts of certain protections by PCS-Explorer2 software
according to users’ requirement.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1523D
NR1523D
01 01
BO_Signal_1-1 BO_Signal_1-1
02 02
03 03
BO_Signal_1-2 BO_Signal_1-2
04 04
05 05
BO_Signal_2-1 BO_Signal_2-1
06 06
07 07
BO_Signal_2-2 BO_Signal_2-2
08 08
09 09
BO_Signal_3-1 BO_Signal_3-1
10 10
11 11
BO_Signal_3-2 BO_Signal_3-2
12 12
13 13
BO_Signal_4 BO_Signal_4
14 14
15 15
BO_Signal_5 BO_Signal_5
16
16
17 17
BO_Signal_6 BO_Signal_6
18
18
19 19
BO_Signal_7 BO_Signal_7
20 20
21 21
BO_Signal_8 BO_Signal_8
22 22
NR1536A (220Vdc) and NR1536B (110Vdc/125V) are input and output modules (IO module) for
mechanical protection.
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1536A NR1536B
MR IO Module x (NR1536A/B)
0602 MRx.Input1
High Voltage
Binary Input
0603 Signals of MRx.Input2
Mechanical MRx.Input3
0604
protection
0605 MRx.Input4
0606 BO_MRx.Sig1_1
0607 BO_MRx.Sig2_1
0608 BO_MRx.Sig3_1
0609 BO_MRx.Sig4_1
0610 Common1
0611 BO_MRx.Sig1_2
0612 BO_MRx.Sig2_2
0613 BO_MRx.Sig3_2
0614 BO_MRx.Sig4_2
0615 Common2
0616 BO_MRx.Sig1_3
0617 BO_MRx.Sig2_3
0618 BO_MRx.Sig3_3
0619 BO_MRx.Sig4_3
0620 Common3
0621 Pwr+
Module Power Input
0622 Pwr -
Date: 2019-02-21
6 Hardware
17-20 BO_MRx.Sig2_3 Output alarm signal contact 3 of channel 2 of mechanical protection x (NO contact).
18-20 BO_MRx.Sig3_3 Output alarm signal contact 3 of channel 3 of mechanical protection x (NO contact).
19-20 BO_MRx.Sig4_3 Output alarm signal contact 3 of channel 4 of mechanical protection x (NO contact).
The analog input module is applicable for power plant with conventional VT and CT, the module is
not required if the device is used with ECT/EVT. The analog input module can transform these
high AC input values to relevant low AC output value for the DSP module. The transformers are
used both to step-down the currents and voltages to levels appropriate to the electronic circuitry of
this device and to provide effective isolation between this device and the power system. A low
pass filter circuit is connected to each transformer (CT or VT) secondary circuit for reducing the
noise of each analog AC input signal.
NOTICE!
The rated value of the input current transformer is optional: 1A or 5A. The rated value of
the CT MUST be definitely declared in the technical scheme and the contract.
Maximum linear range of the current converter is 40In.
Because the rated value of the input current transformer is optional, it is necessary to
CHECK whether the rated values of the current transformer inputs are accordant to the
demand of the engineering before putting the device into operation.
For AI module, if the plug is not put in the socket, external CT circuit is closed itself. It is shown as
below.
Plug
Socket
In
Out
Date: 2019-02-21
6 Hardware
In
Out
The analog input module NR1401 can provide 12-channel analog signal inputs and each channel
can be configured as a specified current or voltage channel by PCS-Explorer2 software according
to user requirements. Up to two NR1401 modules can be configured for the device. Three kinds of
AI modules can be used for PCS-985GE:
1) 12I-A: 12-channel current AI module, all current channels are for protection;
2) 12I-D: 12-channel current AI module, the first 9 current channels are for protection and the
last 3 current channels for metering.
3) 9I3U: 9-channel current and 3-channel voltage AI module, the rated voltages of all voltage
channels are 100~130V.
4) 6I6U-I: 6-channel current and 6-channel voltage AI module. It includes 4 current channels for
protection, one high sensitive current channel and one current channel for metering. And the
rated voltages of all voltage channels are 100~130V and the 5th current channel is for zero
sequence current inputting of zero sequence overcurrent protection of stator ground fault.
5) 6I6U-I: 6-channel current and 6-channel voltage AI module. It includes 4 current channels for
protection and two high sensitive current channels. And the rated voltages of all voltage
channels are 100~130V and the 5th current channel is for zero sequence current inputting of
directional stator ground fault protection.
A 24-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
Date: 2019-02-21
6 Hardware
NR1401
01 02 01 02
level current
I1 I1n 01 02 01 02 I1 I1n 01 02
level current
I1 I1n I1 I1n I1 I1n
Protection
Protection
input
input
I2 03 I2n 04 I2 03 I2n 04 I2 03 I2n 04 I2 03 I2n 04 I2 03 I2n 04
#1
Protection level current input
#1
I4 07 I4n 08 I4 07 I4n 08 I4 07 I4n 08 I4 07 I4n 08 I4 07 I4n 08
#2
#2
I5 09 I5n 10 I5 09 I5n 10 I5 09 I5n 10 I5 09 I5n 10 I5 09 I5n 10
#3
#3
I6 11 I6n 12 I6 11 I6n 12 I6 11 I6n 12 I6 11 I6n 12 I6 11 I6n 12
voltage input
voltage input
I9 17 I9n 18 I9 17 I9n 18 I9 17 I9n 18 U3 17 U3n 18 U3 17 U3n 18
Measurement
voltage input
I10 19 I10n 20 I10 19 I10n 20 U1 19 U1n 20 19 20
level current
U4 U4n U4 19 U4n 20
input
In above figure, I1~I12 and U1~U6 are polarity terminals of corresponding relevant current and
voltage inputs respectively. For the 9I3U 1401 module and 6I6U 1401 module, the rated voltage of
voltage channels is 100~130V.
If user needs other analog input configuration, please declare in the technical scheme and the
contract.
Following two figures shows the default terminal definition of the two NR1401 modules.
Date: 2019-02-21
6 Hardware
AI module 2 (1401T-6I6U-I)
0601
Three-phase current
Ia
input channel 5
0602
Ian
0603
Ib
0604
Ibn
AI module 1 (1401T-12I-D) 0605
Ic
0401 0606
Ia Icn
Three-phase current
input channel 1
0402 Ian
current
0607
Shaft
0403 Ib I
0404 0608 In
Ibn
0405 Ic
64S1 ROC
0406
Current
Icn 0609 I
0610 In
0407
Three-phase current
Ia
input channel 2
0408
Ian
Transverse
differential
current
0409 0611 I
Ib
0410 0612 In
Ibn
0411
Ic
0412 0613 Ua
Icn
Three-phase voltage
input channel 1
0614 Uan
0413 Ia 0615
Three-phase current
Ub
input channel 3
0418
terminal
0620 3U0n
(measurement level CT)
0419
Three-phase current
Ia
input channel 4
0420 Ian
neutral
0621
point
3U0
0421 Ib 0622
3U0n
0422 Ibn
0423 Ic
Generator
terminal
0623 3U0
VT2
0424 Icn
0624 3U0n
Three-phase current input channel 4 (AI module 1) can be used as the measurement level CT
input for power calculation (if the configuration setting [PowerCal.En_CT_Measmt] is set as “1”).
Date: 2019-02-21
6 Hardware
AI module 2 (1401T-6I6U-I)
0601
Three-phase current
Ia
input channel 4
0602
Ian
0603
Ib
0604
Ibn
AI module 1 (1401T-9I3U-A)
0605
Ic
0401 Ia 0606
Three-phase current
input channel 1 Icn
0402 Ian
0403 Ib
current
0607
Shaft
I
0404 Ibn 0608 In
0405 Ic
0406
64S1 ROC
Icn
Current
0609 I
0407 0610
Three-phase current
Ia In
input channel 2
0408
Ian
Transverse
differential
0409
Ib
current
0611 I
0410
Ibn 0612 In
0411
Ic
0412
Icn 0613 Ua
Three-phase voltage
input channel 1
0614 Uan
0413 Ia
Three-phase current
0615 Ub
input channel 3
0414 Ian
0616 Ubn
0415 Ib
0617 Uc
0416 Ibn
0618 Ucn
0417 Ic
0418
residual VT residual VT residual VT
Icn
Generator Generator
terminal
0619 3U0
VT1
0620 3U0n
0419
Three-phase voltage
Ua
input channel 2
0420 Uan
neutral
0621
point
0421 Ub 3U0
0622
0422 Ubn 3U0n
0423 Uc
Generator
terminal
0624 3U0n
Three-phase voltage input channel 2 (AI module 1) can be used as the second VT input for voltage
balance protection (if the generator system setting [60.En] is set as “1”).
The generator shaft overcurrent protection used CT is configured to pin 07-08 (high-sensitivity
CT1) of the AI module located in slot 06 by default.
The rotor ground fault protection input module NR1417 or NR1418 is generally located in slot 08.
For rotor ground fault protection with low-frequency square-wave voltage injection, NR1417
module should be selected. For Ping-Pang type rotor ground fault protection rotor earth-fault
Date: 2019-02-21
6 Hardware
A 22-pin connector is fixed on the front of this module. The pin definition of the connector is
described as below.
In NR1417 module, UR2+ should be connected to positive pole of rotor winding, and UR2- should
be connected to negative pole of rotor winding. The rotor voltage is not only used for rotor low
voltage element of loss of excitation protection, it is also used to calculate the ground fault location
for rotor ground fault protection with low-frequency square-wave voltage injection. UOUT is the
input terminal of big power resistor (47kΩ). RGND is applied to connect the shaft of rotor winding.
TEST is the test terminal (the test resistor is 18kΩ). UIN+ and UIN- are applied to connect to the
external power supply, the external power supply can be 220V (NR1417E) or 110V (NR1417F)
(predetermined when ordering) DC power supply.
In NR1418 module, UR2+ should be connected to positive pole of rotor winding, and UR2- should
be connected to negative pole of rotor winding, the rotor voltage is used for rotor low voltage
element of loss of excitation protection. UR1+ and UR1- are the input terminals of big power
resistor (13.6kΩ), UR1+ and UR1- are connected to the positive and negative pole of rotor winding
respectively via the big power resistor. RGND is applied to connect the shaft of rotor winding.
TEST is the test terminal (the test resistor is 18kΩ).
The display panel consists of liquid crystal display module, keyboard, LED and ARM processor.
The functions of ARM processor include display control of the liquid crystal display module,
keyboard processing, and exchanging data with the CPU through serial port etc. The liquid crystal
Date: 2019-02-21
6 Hardware
display module is a high-performance grand liquid crystal panel with soft back lighting, which has a
user-friendly interface and an extensive display range.
Date: 2019-02-21
6 Hardware
Date: 2019-02-21
7 Settings
7 Settings
Table of Contents
7 Settings .............................................................................................. 7-a
7.1 Overview .......................................................................................................... 7-1
7.2 System Settings .............................................................................................. 7-1
7.2.1 Setting List ........................................................................................................................... 7-1
List of Tables
Table 7.2-1 List of system settings ............................................................................................ 7-1
Date: 2016-08-16
7 Settings
7.1 Overview
Settings are classified into two kinds, protection settings and common settings. Each protection
element has its independent setting menu which are given detailed description in Chapter 3. In this
chapter only common settings are introduced. Common settings consist of device settings,
communication settings, label settings, system settings and configuration settings.
PCS-985GE has ten protection setting groups to coordinate with the different modes of power
system operation. One of these setting groups is assigned to be active. However, common
settings are shared by all protection setting groups, and settings of protection element are set
according to secondary values.
MainMenuSettingsSystem Settings
Date: 2016-08-16
7 Settings
1: enable protection
excitation transformer, tripping logics. Configuration settings are usually configured in factory or
configured by field commission engineer according to the design drawing and project requirement.
Modifying configuration settings need special warrant to input the special password.
Date: 2016-08-16
7 Settings
MainMenuSettingsConfig Settings
1. [HDR_EncodedMode]
Default value of [HDR_EncodedMode] is 1 (i.e. UTF-8 code) and please set it to 0 (i.e. GB18030)
according to the special requirement.
2. [Opt_Caption_103]
3. [En_MDisk]
A moveable mdisk is implemented on the MON plug-in module to backup and restore programs,
settings and configurations.
Date: 2016-08-16
7 Settings
If MON plug-in module is broken, remove the mdisk and put it into a new MON plug-in module, use
the menu on HMI to restore the backup programs and configurations. If DSP plug-in module is
broken, after a new DSP plug-in module is installed, use the menu on HMI to restore the backup
programs and configurations. If the moveable mdisk is broken, after a new mdisk is installed on
the MON plug-in module, use the menu on HMI to back up the current programs and
configurations into the new mdisk.
000.000.000.000~
1 IP_LAN1 IP address of Ethernet port 1.
255.255.255.255
000.000.000.000~
2 Mask_LAN1 Subnet mask of Ethernet port 1.
255.255.255.255
000.000.000.000~
3 IP_LAN2 IP address of Ethernet port 2.
255.255.255.255
000.000.000.000~
4 Mask_LAN2 Subnet mask of Ethernet port 2.
255.255.255.255
000.000.000.000~
6 IP_LAN3 IP address of Ethernet port 3.
255.255.255.255
000.000.000.000~
7 Mask_LAN3 Subnet mask of Ethernet port 3.
255.255.255.255
000.000.000.000~
9 IP_LAN4 IP address of Ethernet port 4.
255.255.255.255
000.000.000.000~
10 Mask_LAN4 Subnet mask of Ethernet port 4.
255.255.255.255
000.000.000.000~
12 Gateway Gateway of router.
255.255.255.255
4800,9600,19200,
19 Baud_RS485A 38400,57600,115200 Baud rate of rear RS-485 serial port 1.
(bps)
0: IEC103;
1: MODBUS;
20 Protocol_RS485A Communication protocol of rear RS-485 serial port 1.
2: DNP;
3: DLT645.
4800,9600,19200,
22 Baud_RS485B 38400,57600,115200 Baud rate of rear RS-485 serial port 2.
(bps)
0: IEC103;
1: MODBUS;
23 Protocol_RS485B Communication protocol of rear RS-485 serial port 2.
2: DNP;
3: DLT645.
4800,9600,19200,
27 Baud_Printer 38400,57600,115200 Baud rate of printer port.
(bps)
0: disable
28 En_AutoPrint Enable/disable automatic printing function.
1: enable
Conventional
29 Opt_TimeSyn Select the mode of time synchronization of equipment.
SAS
Date: 2016-08-16
7 Settings
Advanced
NoTimeSyn
1. [En_LANx] (x= 2, 3, 4)
“1”: enable the IP address of Ethernet port and the corresponding IP address setting is need to be
set.
“0”: disable the IP address of Ethernet port and the corresponding IP address setting is not need to
be set.
2. [En_Broadcast]
This setting is only used for IEC 103 protocol. If NR network IEC103 protocol is used, the setting
must be set as “1”.
3. [Protocol_RS485x] (x=A, B)
The setting is used to select the communication protocol of rear RS-485 serial port x.
1: Modbus protocol
2: DNP protocol
3: DLT645
4. [Format_Measmt]
The setting is used to select the format of measurement data sent to SCADA through IEC103
protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard.
5. [En_AutoPrint]
If automatic print is required for disturbance report after protection operating, the setting should be
set as “1”.
6. [Opt_TimeSyn]
There are four selections for clock synchronization of device, each selection includes different time
clock synchronization signals shown in following table.
Item Description
PPS(RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B(RS-485): IRIG-B via RS-485 differential level.
Conventional
PPM(DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS(DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
SAS SNTP(BC): Broadcast SNTP mode via Ethernet network.
Message (IEC103): Clock messages through IEC103 protocol.
IEEE1588: Clock message via IEEE1588.
Advanced IRIG-B(Fiber): IRIG-B via optical-fibre interface.
PPS(Fiber) PPS: Pulse per second (PPS) via optical-fibre interface.
When no time synchronization signal is connected to the equipment, please select
NoTimeSyn
this option and the alarm message [Alm_TimeSyn] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by device, but “Advanced” mode
is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be
issued to remind user loss of time synchronization signals.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] being issued simultaneously.
3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time
synchronization signal. But the device can be still synchronized if receiving time
synchronization signal.
The clock message via IEC103 protocol is invalid when the device receives the IRIG-B signal
through RS-485 port.
Date: 2016-08-16
7 Settings
7. [IP_Server_SNTP]
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
8. OffsetHour_UTC, OffsetMinute_UTC
If the IEC61850 protocol is adopted in substations, the time tags of communication messages are
required according to UTC (Universal Time Coordinated) time.
The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is
east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the
minute offset of the current time zone to the GMT zone.
st nd rd th th
Time zone GMT zone East 1 East 2 East 3 East 4 East 5
Setting 0 1 2 3 4 5
th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11th
Setting 6 7 8 9 10 11
th st nd rd th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5th
Setting -12/12 -1 -2 -3 -4 -5
th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11th
Setting -6 -7 -8 -9 -10 -11
Date: 2016-08-16
8 Human Machine Interface
Table of Contents
Date: 2016-08-16
8 Human Machine Interface
List of Figures
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-4
Figure 8.1-5 Rear view and terminal definition of NR1102M .................................................. 8-5
Figure 8.3-3 LCD display 2 of trip report and alarm report ................................................... 8-20
Date: 2016-08-16
8 Human Machine Interface
List of Tables
Date: 2016-08-16
8 Human Machine Interface
Date: 2016-08-16
8 Human Machine Interface
The operator can access the protective device from the front panel. Local communication with the
protective device is possible using a computer via a multiplex RJ45 port on the front panel.
Furthermore, remote communication is also possible using a PC with the substation automation
system via rear RS485 port or rear Ethernet port. The operator is able to check the protective
device status at any time.
This chapter describes human machine interface (HMI), and give operator an instruction about
how to display or print event report, setting and so on through HMI menu tree and display metering
value, including RMS current, voltage and frequency etc. through LCD. Procedures to change
active setting group or a settable parameter value through keypad are also described in details.
8.1 Overview
NOTICE!
The LCD interface in this chapter is ONLY a reference and available for explaining
specific definition of LCD. The displayed interface of the actual protection device may
be some DIFFERENT from it.
1 11
5
HEALTHY
2 12 PCS-985GE
ALARM
3
TRIP
13
GENERATOR RELAY
4 14
5 15
C GRP
6 16
7 17 ENT
ES
8 18
9 19 1
4
3
10 20
Date: 2016-08-16
8 Human Machine Interface
Press “+”, “”, “”, “-“, “ENT” IN SEQUENCE to confirm the setting change and press
“+”, “-“, “+”, “-“, “ENT” IN SEQUENCE to execute the report deletion.
+
P
GR
ENT
ESC -
1. “ESC”:
2. “ENT”:
3. “GRP”
Page up/down
Date: 2016-08-16
8 Human Machine Interface
13 ALA RM
03
Recommended 02
04 14
05 15 03 TRIP
06 16
LED_03 is configured as shown in the right
07 17
side, and other LEDs (LED_04~LED_20)
08 18 are configured according to the practical
09 19 requirement through the PCS-Explorer2
10 20 software.
Steady Green Lit when the device is in service and ready for operation.
“HEALTHY” LED can only be turned on by energizing the device and no abnormality detected.
“ALARM” LED is turned on when abnormalities of device occurs like above mentioned and can be
turned off after abnormalities are removed except CT circuit failure alarm signal which can only be
reset when the failure is removed and the device is rebooted or re-energized.
“TRIP” LED is turned on and latched once any protection element operates and can be turned off
by pressing the signal RESET button on the front panel.
Other LED indicators with no labels are configurable and user can configure them to be lit by
signals of operation element, alarm element and binary output contact according to requirement
through PCS-Explorer2 software, and there are three colors (green, yellow and red) for user
selection.
Date: 2016-08-16
8 Human Machine Interface
P2
P1
P3
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
MON plug-in module is equipped with two or four 100Base-TX Ethernet interface, takes NR1102M
as an example, its rear view and the definition of terminals is shown in Figure 8.1-5.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer2)
after connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-Explorer2). At first, the connection between the protection device and
PC must be established. Through setting the IP address and subnet mask of corresponding
Ethernet interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured
that the protection device and PC are in the same network segment. For example, setting the IP
address and subnet mask of network A. (using network A to connect with PC)
Date: 2016-08-16
8 Human Machine Interface
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled. If using
other Ethernet port, for example, Ethernet port B, the logic setting [En_LAN2] must be set as “1”.
NR1102M
ETHERNET
Network A
Network B
ETHERNET
Network C
Network D
SYN+
SYN-
SGND
RTS
TXD
SGND
8.2.1 Overview
Pressing “▲” at any running interface can return to the main menu. Select different submenu by
“▲” and “▼”. Enter the selected submenu by pressing “ENT” or “►”. Press “◄” and return to the
previous menu. Press “ESC” and exit the main menu directly. For fast return to the command
menu, one command menu will be recorded in the quick menu after its first execution. Up to five
latest menu commands can be recorded in the quick menu by “first in first out” principle. It is
arranged from top to bottom and in accordance with the execution order of command menus.
Press “▲” to enter the main menu, the interface is shown in the following diagram:
Date: 2016-08-16
8 Human Machine Interface
Quick Menu
Language
Clock
Device Settings
Mainmenu
If the protective device is powered for the first time, there is no recorded shortcut menu. Press “▲”
to enter the main menu with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
NOTICE!
The menu shown in following figure is NOT the specific-application menu. For each
project, the menu VARIES with the protection configuration.
Date: 2016-08-16
8 Human Machine Interface
MAIN MENU
Internal Signal
Language
DC Zero Adjust
Disturb Item
HMI Setup
BackLitDur
Contrast
SupervLCD
SupervLED
Under the main interface, press “▲” to enter the main menu, and select submenu by pressing “▲”,
Date: 2016-08-16
8 Human Machine Interface
“▼” and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all the submenus under menu tree of the protection device.
8.2.2 Measurements
This menu is mainly used to display the real time sampling value of current, voltage and phase
angle. This menu and “Status” menu can fully reflects of the running environment of the protection
device. As long as the displayed values consist with the actual running situation, basically, the
protection device can work normally. This menu is set to greatly facilitate the debugging and
maintenance of people on site. Please refer to Section “Inputs and Outputs” of each protection
element about the detailed description of each sampled values.
8.2.2.1 Measurements1
(1) The submenu “Gen Values” includes the following command menus.
2 Gen Curr Values Display magnitude of AC current of generator on protection DSP module.
3 Gen Volt Values Display magnitude of AC voltage of generator on protection DSP module.
(2) The submenu “Exc Values” includes the following command menus.
8.2.2.2 Measurements2
Date: 2016-08-16
8 Human Machine Interface
(1) The submenu “Gen Values” includes the following command menus.
(2) The submenu “Exc Values” includes the following command menus.
(3) The submenu “Phase Angle” includes the following command menus.
(4) The submenu “Cal Param Display” includes the following command menus.
(5) The submenu “Prot Values” includes the following command menus.
Date: 2016-08-16
8 Human Machine Interface
8.2.3 Status
This menu is mainly used to display the real time input signals and output signals of the device.
This menu and “Measurements” menu fully reflects the running environment of the protection
device. As long as the displayed signals are in accordance with the actual running situation,
basically, the protection device can work normally. This menu is set to greatly facilitate the
debugging and maintenance of people on site.
Date: 2016-08-16
8 Human Machine Interface
8.2.3.1 Inputs
8.2.3.2 Outputs
8.2.4 Records
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
8.2.5 Settings
This menu is used to browse, modify and set all settings including device setup parameters,
protection settings and system parameters etc. Moreover, it can also execute the setting copy
between different setting groups.
2 Gen Sys Settings To display and modify the system settings of generator protection.
5 Prot Settings To display and modify the settings of each protection elements.
6 Device Setup To display and modify the settings related to device setup
Date: 2016-08-16
8 Human Machine Interface
1 Gen Diff Settings To display and modify the settings of generator differential protection.
2 Gen IntTurn Settings To display and modify the settings of generator inter-turn protection.
5 Gen Impedance Settings To display and modify the settings of impedance protection.
To display and modify the settings of generator 3rd harmonic stator ground
7 Gen Hm3StaEF Settings
fault protection.
To display and modify the settings of generator Ping-Pang type rotor ground
8 Gen SwitchRotEF Settings
fault protection.
To display and modify the settings of generator rotor ground fault protection
9 Gen InjRotEF Settings
(with low-frequency square-wave voltage injection).
10 Gen StaOvLd Settings To display and modify the settings of generator stator overload protection.
12 Gen ExcLoss Settings To display and modify the settings of loss of excitation protection.
13 Gen OOS Settings To display and modify the settings of generator out-of-step protection.
14 Gen OV Settings To display and modify the settings of phase overvoltage protection.
16 Gen OvExc Settings To display and modify the settings of overexcitation protection.
17 Gen RevPower Settings To display and modify the settings of generator reverse power protection.
22 Gen AccEnerg Settings To display and modify the settings of inadvertent energization protection.
23 Gen BFP Settings To display and modify the settings of breaker failure protection.
24 Gen Shaft OC Settings To display and modify the settings of generator shaft overcurrent protection.
25 Exc Diff Settings To display and modify the settings of excitation transformer current
Date: 2016-08-16
8 Human Machine Interface
differential protection.
27 Exc OvLd Settings To display and modify the settings of rotor winding overload protection.
3 Label Settings To display and modify the label settings of the output signals.
8.2.6 Print
This menu is used for printing device description, setting, all kinds of records, waveform and
information related with 103 Protocol.
4 Superv Events To print self-check alarm and device operation abnormal alarm reports.
Date: 2016-08-16
8 Human Machine Interface
8.2.6.1 Settings
3 Exc Sys Settings To print the system settings of excitation transformer protection.
(1) The submenu “Prot Settings” includes the following command menus.
1 Gen Diff Settings To print the settings of differential protection of main transformer.
10 Gen StaOvLd Settings To print the settings of generator stator overload protection.
11 Gen NegOC Settings To print the settings of generator negative-sequence overload protection.
17 Gen RevPower Settings To print the settings of generator reverse power protection.
18 Gen FwdPower Settings To print the settings of generator low forward power protection.
Date: 2016-08-16
8 Human Machine Interface
21 Gen StShut Settings To print the settings of generator startup and shutdown protection.
24 Gen Shaft OC Settings To print the settings of generator shaft overcurrent protection.
25 Exc Diff Settings To print the settings of excitation transformer current differential protection.
27 Exc OvLd Settings To print the settings of rotor winding overload protection.
(2) The submenu “Device Setup” includes the following command menus.
2 Gen Curr Wave To print the recorded current waveforms of generator protection.
3 Gen Volt Wave To print the recorded voltage waveforms of generator protection.
4 Gen Misc Wave To print the recorded miscellaneous waveforms of generator protection.
This menu is used for resetting the tripping relay with latch, protection device signal lamp, LCD
display, as the same as the resetting function of binary input. Record the currently acquired
waveform data of the protection device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download.
1 Reset Target Reset the local signal, the signal indicator lamp and the LCD display
Date: 2016-08-16
8 Human Machine Interface
8.2.8 Information
In this menu the LCD displays software information of DSP module, MON module and HMI module,
which consists of version, creating time of software, CRC codes and management sequence
number. Besides, hardware board information can also be viewed.
8.2.9 Test
This menu is used for developers to debug the program and for engineers to maintain the device.
It can be used to check item fault message, and fulfill the communication test function. It is also
used to generate all kinds of report or event to transmit to the SAS without any external input, so
as to debug the communication on site.
Date: 2016-08-16
8 Human Machine Interface
8.2.10 Clock
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
8.2.11 Language
This menu is mainly used for set LCD display language.
8.3.1 Overview
There are five kinds of LCD display: SLD (single line diagram) display, tripping reports, alarm
reports, binary input changing reports and device logs. Tripping reports and alarm reports will not
disappear until these reports are acknowledged by pressing the “RESET” button in the protection
panel (i.e. energizing the binary input [BI_RstTarg]). User can press “ESC” first then “ENT”
simultaneously to switch the display among trip reports, alarm reports and the SLD display. Binary
change reports will be displayed for 5s and then it’ll return to the previous display interface
automatically. Device logs will not pop up and can only be viewed by navigating the corresponding
menu.
After the protection device is powered and turns into the initiating interface, it takes 45 seconds to
complete the initialization of protection device. During the initialization, the “HEALTHY” indicator of
the protection device goes out.
Under normal condition, the LCD will display the interface similar as Figure 8.3-1. The LCD adopts
white color as its backlight that is activated if once there is any keyboard operation, and is
extinguished automatically after 60 seconds of no operation.
Date: 2016-08-16
8 Human Machine Interface
When the device is powered on, the LCD will display single line diagram as following:
Communication address Addr:102 2014-10-28 10:10:00 Group 01 Active setting group number
f: 0.00Hz Frequency
Generator terminal current 0.00A
P: 0.00% Active power
Q: 0.00% Reactive power
Neutral point current 0.00A Ug: 0.00V Average value of generator
terminal three-phase voltage
The displayed content of the interface contains: the current date and time of the protection device
(with a format of yy-mm-dd hh:mm:ss:), the currently valid setting group number, the three-phase
current and voltage sampled values (phase-to-phase voltage), differential current etc.
If the device has no self-check report, the display interface will only show the fault report.
Disturb Records NO.2 shows the title and SOE number of the report.
Date: 2016-08-16
8 Human Machine Interface
2014-11-28 07:10:00:200 shows the time when fault detector picks up, the format is
year–month-date and hour: minute:second:millisecond.
0000ms TrigDFR shows fault detector of protection element and operation time of fault detector is
fixed as 0ms.
0024ms 87G.Op_Biased shows the relative operation time and operation element of protection
element
All the protection elements have been listed in Chapter 3 “Operation Theory”, and please refer to
Section “Inputs and Outputs” of each protection element for details. Operation reports of fault
detector and the reports related to oscillography function are shown in the following table.
For the situation that the fault report and the self-check alarm report occur simultaneously in the
following figure, the upper half part is fault report, and the lower half part is self-check report. As to
the upper half part, it displays separately the record number of fault report, fault name, generating
time of fault report (with a format of yy-mm-dd hh:mm:ss:), protection element and tripping element.
If there is protection element, there is relative time on the basis of fault detector element. At the
same time, if the total lines of protection element and tripping element are more than 3, a scroll bar
will appear at the right. The height of the black part of the scroll bar basically indicates the total
lines of protection element and tripping element, and its position suggests the position of the
currently displayed line in the total lines. The scroll bar of protection element and tripping element
will roll up at the speed of one line per time. When it rolls to the last three lines, it’ll roll from the
earliest protection element and tripping element again. The displayed content of the lower half part
is similar to that of the upper half part.
Date: 2016-08-16
8 Human Machine Interface
0000ms TrigDFR
0024ms 87G.Op_Biased
Superv Events
24.Alm
This protection device can store 1024 self-check reports. During the running of protection device,
the self-check report of hardware errors or system running abnormity will be displayed
immediately.
Settings_Chgd 0 1
Superv Events NO.4 shows the SOE number and title of the report
2014-11-29 09:18:47:500 shows the data and time of the report occurred: year–month-date
and hour:minute:second:millisecond
Date: 2016-08-16
8 Human Machine Interface
event report will be automatically displayed on LCD as follows. This protective equipment can
store 1024 events of binary signals. During the running of the equipment, the binary signals will be
displayed once the input signal state changes.
IO Events NO.4
2014-11-29 09:18:47:500ms
BI_Maintenance 0 1
2014-11-29 09:18:47:500 shows the date and time of the report occurred, the format is
year–month-date and hour:minute:second:millisecond
BI_Maintenance 0->1 shows the state change of binary input, including binary input name,
original state and final state
Contact inputs and contact outputs are listed in the following two tables, and user can define
undefined binary inputs as the specific binary inputs via PCS-Explorer2 software.
NOTICE!
The binary input number of BI intelligent module of different type may be DIFFERENT
and signals list in following table are just for reference, please refer to Chapter
“Hardware” for details.
Date: 2016-08-16
8 Human Machine Interface
Date: 2016-08-16
8 Human Machine Interface
This protection device can store 1024 pieces of equipment logs. During the running of the
protection device, equipment logs will be displayed after user operations.
Device Logs NO. 4 shows the title and the number of the report
2008-11-28 10:18:47:569 shows the date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
Date: 2016-08-16
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Measurements” menu, and then
press the “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu).
2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).
2. Press the key “▲” or “▼” to move the cursor to the “Records” menu, and then press the
key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
key “ENT” to enter the submenu.
Date: 2016-08-16
8 Human Machine Interface
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ENT” or “ESC” to exit this menu (returning to the “Records” menu).
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
key “ENT” to enter the menu.
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ESC” to exit this menu (returning to the menu “Settings”).
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side of
the LCD to indicate the quantity of all displayed information of the command menu and the
relative location of information where the current cursor points at.
2. Press the key “▲” or “▼” to move the cursor to the “Print” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu.
Press the “+” or “-” to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing... ”, and then automatically exit this menu
(returning to the menu “Print”). If the printer doesn’t complete its current print task
and re-start it for printing, and the LCD will display “Printer Busy…”. Press the key
“ESC” to exit this menu (returning to the menu “Print”).
Selecting the command menu “Superv Events” or “IO Events”, and then press the
key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and
ending numbers of printing message. After pressing the key “ENT”, the LCD will
display “Start Printing…”, and then automatically exit this menu (returning to the
menu “Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”).
Date: 2016-08-16
8 Human Machine Interface
4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103 Info”, press
the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu
(returning to the menu “Print”).
5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.
6. After entering the submenu of “Settings”, press the key “▲” or “▼” to move the cursor,
and then press the key “ENT” to print the corresponding default value. If selecting any
item to printing:
Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu
(returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the
menu “Settings”).
7. After entering the submenu “Waveforms”, press the key “ENT” or “►” to enter the next
level of menu. After entering the submenu of “Waveforms”, press the “+” or “-” to
select the waveform item to be printed and press “ENT” to enter. If there is no any
waveform data, the LCD will display “No Waveform Data!” (If there is no any waveform
data, users can execute the command menu “Trig Oscillograph” in the menu “Local
Cmd”, then waveform data can be generated). With waveform data existing:
Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”,
the LCD will display “Start Printing…”, and then automatically exit this menu (returning to
the menu “Waveforms”). If the printer does not complete its current print task and
re-start it for printing, and the LCD will display “Printer Busy…”. Press the key “ESC” to
exit this menu (returning to the menu “Waveforms”).
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press
the key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu, and then press
the key “ENT” to enter the menu.
6. Press the key “◄” or “►” to select pervious or next command menu.
7. Press the key “ESC” to exit this menu (returning to the menu “Settings”).
8. Select the command menu “Device Settings” “Comm Settings” or “Label Settings”,
users need to enter the submenu “Device Setup” firstly.
Date: 2016-08-16
8 Human Machine Interface
9. Selecting the command menu “Device Settings”, move the cursor to the setting item
to be modified, and then press the key “ENT”.
Press the key “+” or “-” to modify the value (if the modified value is of multi-bit, press
the key “◄” or “►” to move the cursor to the digit bit, and then press the “+” or “-” to
modify the value), press the key “ESC” to cancel the modification and return to the
displayed interface of the command menu “Device Settings”. Press the key “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu
“Device Settings”).
Move the cursor to continue modifying other setting items. After all setting values are
modified, press the key “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”.
Directly press the “ESC” or press the key “◄” or “►” to move the cursor. Select the
“Cancel”, and then press the key “ENT” to automatically exit this menu (returning to the
displayed interface of the command menu “Device Settings”).
Press the key “◄” or “►” to move the cursor. Select “No” and press the key “ENT”, all
modified setting item will restore to its original value, exit this menu (returning to the
menu “Settings”).
Press the key “◄” or “►” to move the cursor to select “Yes”, and then press the key
“ENT”, the LCD will display password input interface.
Password:
____
Input a 4-bit password (“+”, “◄”, “▲” or “-”). If the password is incorrect, continue
inputting it, and then press the “ESC” to exit the password input interface and return to
the displayed interface of the command menu “Device Settings”. If the password is
correct, LCD will display “Save Settings…”, and then exit this menu (returning to the
displayed interface of the command menu “Device Settings”), with all modified setting
items as modified values.
10. If selecting the command menu of protection element such as “Gen Diff Settings”,
the LCD will display the following interface:
Date: 2016-08-16
8 Human Machine Interface
Active Group: 01
Selected Group: 02
Then move the cursor to the modified value and press “ENT” to enter. If the setting
[87G.I_Biased] is selected to modify, then press the “ENT” to enter and the LCD will
display the following interface. is shown the “+” or “-” to modify the value and then press
the “ENT” to enter.
87G.I_Biased
11. If selecting the other menus, move the cursor to the setting to be modified, and then
press the “ENT”.
For different setting items, their displayed interfaces are different but their modification methods
are the same.
After modifying the settings (except for communication settings), the “HEALTHY” indicator of the
protection device will go out, and the protection device will automatically restart and re-check the
protection setting. If the check doesn’t pass, the protection device will be blocked.
Date: 2016-08-16
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
key “ENT” or “►” to enter the menu;
3. Press the key “▲” or “▼” to move the cursor to the command menu “Copy Settings”,
and then press the key “ENT” to enter the menu. The following display will be shown on
LCD.
Copy Settings
Active Group: 01
Copy To Group: 02
Press the key “+” or “-” to modify the value. Press the key “ESC”, and return to the
menu “Settings”. Press the “ENT”, the LCD will display the interface for password input,
if the password is incorrect, continue inputting it, press the key “ESC” to exit the
password input interface and return to the menu “Settings”. If the password is correct,
the LCD will display “Copy Settings Success!”, and exit this menu (returning to the menu
“Settings”).
Date: 2016-08-16
8 Human Machine Interface
Active Group: 01
Change To Group: 02
Press the “+” or “-” to modify the value, and then press the key “ESC” to exit this menu
(returning to the main menu). After pressing the key “ENT”, the LCD will display the password
input interface. If the password is incorrect, continue inputting it, and then press the key “ESC” to
exit the password input interface and return to its original state. If the password is correct, the
“HEALTHY” indicator of the protection device will go out, and the protection device will re-check
the protection setting. If the check doesn’t pass, the protection device will be blocked. If the check
is successful, the LCD will return to its original state.
The operation of deleting device records will delete ALL messages saved by the
protection device, including disturbance records, supervision events and binary events,
but it will NOT DELETE the user operation reports (i.e. device logs). Furthermore, all
deleted records are IRRECOVERABLE after deletion, please do the operation with
great cautious.
2. Press the “+”, “-”, “+”, “-” and key “ENT”; Press the key “ESC” to exit this menu
(returning to the original state). Press the key “ENT” to carry out the deletion.
Date: 2016-08-16
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Clock” menu, and then press the key
“ENT” to enter clock display.
Clock
Year 2008
Month 11
Day 28
Hour 20
Minute 59
Second 14
3. Press the key “▲” or “▼” to move the cursor to the date or time to be modified.
4. Press the key “+” or “-”, to modify value, and then press the key “ENT” to save the
modification and return to the main menu.
5. Press the key “ESC” to cancel the modification and return to the main menu.
Date: 2016-08-16
8 Human Machine Interface
2. Press the key “▲” or “▼” to move the cursor to the “Information” menu, and then press
the “ENT” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and
then press the key “ENT” to display the software version.
2. Press the key “▲” or “▼” to move the cursor to the “Information” menu, and then press
the key “ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “Board Info”, and
then press the “ENT” to enter the menu.
5. Press the key “ENT” or “ESC” to exit this menu (returning to the “Information” menu).
2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and
then press the key “ENT” to enter the menu and the following display will be shown on
LCD.
Date: 2016-08-16
8 Human Machine Interface
1 中文
2 English
3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press
the key “ENT” to execute language switching. After language switching is finished, LCD
will return to the menu “Language”, and the display language is changed. Otherwise,
press the key “ESC” to cancel language switching and return to the menu “Language”.
Date: 2016-08-16
8 Human Machine Interface
Date: 2016-08-16
9 Configurable Function
9 Configurable Function
Table of Contents
9 Configurable Function ...................................................................... 9-1
9.1 General Description ........................................................................................ 9-1
9.2 Introduction on PCS-Explorer2 Software ...................................................... 9-1
9.3 Device Setup.................................................................................................... 9-1
9.3.1 Device Information ............................................................................................................... 9-1
List of Figures
Figure 9.3-1 Setting device information .................................................................................... 9-2
Figure 9.5-2 The editing page of the “Setting” node ............................................................. 9-10
Date: 2019-02-21
9 Configurable Function
Overall functions:
Click “Device Config”→“Device Information” in the left part to view the basic information of the
device. All these information are default settings in the selected driver package for creating the
device. Part of the basic information can be modified including “Config File Version”, “Modify Time”
and “User Information”.
Click “Device Config”→“Global Config”→“MOT” in the left part to enter MOT configuration interface
as shown below. According to the selected series number of MOT, the application scenario, some
software and hardware related function can be configured.
Date: 2019-02-21
9 Configurable Function
Click “Device Config”→“Global Config”→“System” in the left part to enter system configuration
interface as shown below (the content may vary subject to created projects). Click the pull-down
list in “Option” column to perform system configuration.
Click “Device Config”→“Global Config”→“Function” in the left part to enter function group
configuration interface as shown below (the content may vary subject to created projects). Click
the pull-down list in “Code” column to perform function group configuration.
On front panel of the device, two columns of indicators are normally provided. The first two
indicators indicate device running status (Healthy) and alarm status (Alarm). Colors of these
indicators may vary with functions of device.
The third LED (i.e. in3) is configured as the protection tripping LED indicator (TRIP) as default. If
Date: 2019-02-21
9 Configurable Function
user want to configure the third LED as other functions, please inform manufacturer when placing
an order.
Double click LED element to open its attributes setup window. users can see that it consists of 3
sub-pages. Here, indicators LED3~20 can be set.
Each indicator has two items to be set: Parameter “Latched”: click corresponding entry under
“Latched” to select “yes” or “no”. If “yes” is selected, indicator attribute is “latched”, indicating that
after this indicator is lit, it will remain on even the initiation signal disappears until it is reset. If “no”
is selected, indicator attribute is “un-latched”, indicating that the indicator status will follow the
change of its initiation signal.
The other parameter is “Color”: The color of indicator can be selected as required: green, yellow,
and red.
After completion of setup, click “OK” to close attributes setup window. The set parameters will be
displayed on the element, as shown below.
Next, indicators initiation signals should be placed on the page and connect them to corresponding
input interfaces of LED element: select the output signal from the “Out” tab (under the subnode of
“B02: PROT_DSP”) at the right side of the window to be used as input source. Press and hold left
button of mouse, and directly drag it to the page. When this signal passes input signal connection
point, a red dot will appear to prompt connection. After placing it at a suitable position, connection
line will be automatically generated to connect this input signal.
The device is normally configured with a number of IO modules. Quantities may vary with different
project.
Date: 2019-02-21
9 Configurable Function
9.4.2.1 Configuration of BI
Click “Program” node. Unfold module node “B10:BI_S09”, one page node: “NR1504” is shown.
Click the page “NR1504”, the corresponding BI configuration graph is shown in an editing window.
In the graph, numbers in the “PIN” column are input terminal numbers of NR1504 module, and
name or function of each pin is described in the “BI_NAME” column.
All configurable binary inputs can be viewed in the “In” tab (under the subnode of “B02:
PROT_DSP”) at the right side of the window (variable library). The input signals of BI modules can
be configured or modified according to the application or drag the required signals from the
variable library.
Please refer to the input signals table in Section “Inputs and Outputs” of each protection element in
Chapter 3 for the detailed description of each configurable binary inputs.
9.4.2.2 Configuration of BO
Click “Program” node. Unfold module node “B13:BO_S13”, one page node: “NR1523A” is shown.
In the graph, numbers in the “PIN” column are input terminal numbers of NR1523A module, and
name or function of each pin is described in the “BO_NAME” column.
Inputs of all configurable binary outputs can be viewed in the “Out” tab (under the subnode of “B02:
PROT_DSP”) at the right side of the window (variable library). As shown in the figure, each input
corresponds to one output contact of the BO module. The output contact of BO module will
operate (output relay pickup or reset) in response to the status change of corresponding input
signal. The output contacts of BO modules can be configured or modified according to the
application or drag the required signals from the variable library.
Please refer to the output signals table in Section “Inputs and Outputs” of each protection element
in Chapter 3 for the detailed description of each configurable binary outputs.
Click “Setting” node to enter “Settings” interface. Several sub-nodes: “Global” and “Group x” (x:
1~10). Among them, global settings (the sub-node “Global”) are common for all setting groups. In
setting groups Group 1~Group 10, only one group is the current active setting group used in
device operation, and mainly includes protection settings, the current active setting group can be
switched among Group 1~Group 10 when required.
Date: 2019-02-21
9 Configurable Function
Click “Setting”→“Global” node, several sub-nodes are unfolded (number of sub-nodes may vary
with different device models) in the edit window. These sub-nodes are used to set system settings,
configuration settings, device settings, communication settings and label settings.
Click “Settings”→“Group x” node, all the protective settings of corresponding group can be shown
by clicking corresponding setting menu item.
Although there are many setting group nodes, settings under these nodes have the same layout in
editing page. Therefore, steps of modification of settings are basically the same. It is seen from the
graph that when any setting node is clicked and open, the editing page will display name, default
value, value, range, step, and unit of the settings in this sequence. Here, user can modify name
and set value of the settings according to actual application requirements.
The name of a setting is the name user will finally see on the device. Users can suitably modify
this name according to actual project requirements: right click on the name entry to be modified to
pop up a right-key context menu, execute the command “Set Description”; the following window
will pop up:
In the “Set Description” dialog box, users will see two entries, “Original Name” is the default name
of this setting in the symbol library, and “Name” is the name currently used, and can be modified.
Modified setting value must not exceed its range (if there has an ordain). There are two types of
set value modification operation: direct input of the value after double clicking corresponding entry
of the setting value, or selection from a pull-down menu.
User can also right click the entry of set value and select “Load Default Value” in the right-key
context menu, so as to obtain default set value of this entry from the symbol library.
Date: 2019-02-21
10 Communication
10 Communication
Table of Contents
10 Communication ............................................................................. 10-a
10.1 General Description .................................................................................... 10-1
10.2 Rear Communication Port Information ..................................................... 10-1
10.2.1 RS-485 Interface.............................................................................................................. 10-1
List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements ..................................................... 10-2
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance ......................... 10-9
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance ..................... 10-10
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances .................. 10-11
Date: 2016-08-16
10 Communication
This section introduces NR’s remote communications interfaces. The protective device is
compatible with three protocols via the rear communication interface (RS-485 or Ethernet). The
protocol provided by the protective device is indicated in the submenu in the “Comm Settings”
column. Using the keypad and LCD to set the parameter [Protocol_RS485A] and
[Protocol_RS485B], the corresponding protocol will be selected.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection no matter
whichever protocol is selected. It has advantage that 32 protective devices can be “daisy chained”
together in electrical connection using a twisted pair.
It should be noted that the descriptions in this section do not aim to fully introduce the protocol
itself. The relevant documentation for the protocol should be referred for this information. This
section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, but
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so an external termination resistor is required when it is located at the bus terminus.
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 requires that each device is directly connected to the physical cable i.e. the
communications bus. Stubs and tees are strictly forbidden, such as star topologies. Loop bus
topologies are not part of the EIA RS-485 standard and are forbidden also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length
must not exceed 500m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especially
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. The signal ground shall not be connected to the cables screen or to
the product’s chassis at any stage. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state due to inactively driven of tubs. This can occur when all the slaves
are in receive mode and the master unit is slow to turn from receive mode to transmit mode. The
reason is that the master purposefully waits in receive mode, or even in a high impedance state,
until it has something to transmit. Jabber can result in the loss of first bits of the first character in
the packet for receiving device(s), which will lead to the rejection of messages for slave units,
causing non-responding between master unit and slave unit. This could brings poor response
times (due to retries), increase in message error counters, erratic communications, and even a
complete failure to communicate.
Biasing requires that the signal lines shall be weakly pulled to a defined voltage level of about 1V.
There should be only one bias point on the bus, which is best situated at the master connection
point. The DC source used for the bias must be clean; otherwise noise will be injected. Please
note that some devices may (optionally) be able to provide the bus bias that the external
components will not be required.
NOTICE!
It is extremely IMPORTANT that the 120Ω termination resistors are fitted. Failure to do
Date: 2016-08-16
10 Communication
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR CANNOT assume
responsibility for any damage that may occur to a device connected to the network as a
result of incorrect application of this voltage.
ENSURE that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each device is connected with an exchanger via communication cable, and thereby it forms a star
structure network. Dual-network is recommended in order to increase reliability. SCADA is also
connected to the exchanger acting as the master station, and every device which has been
connected to the exchanger will act as a slave unit.
SCADA
Exchanger A
Exchanger B
To use the rear port with IEC60870-5-103 communication, the relevant settings of the protective
device must be configured by using keypad and LCD user interface. In the submenu “Comm
Settings”, set the parameters [Protocol_RS485A], [Protocol_RS485B] and [Baud_RS485]. To use
the Ethernet port with IEC60870-5-103 communication, the IP address and the submask of each
Ethernet port shall be set in the same submenu. Please refer to the corresponding section in
Chapter “Settings” for further details.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface and the
protective device is the slave device.
Initialization (reset)
Time synchronization
General interrogation
General commands
Date: 2016-08-16
10 Communication
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
When the protective device is powered up, or the communication parameters are changed, a reset
command is required to initialize the communications. The protective device will respond to either
of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU will clear
any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input, the protection device will not
be able to set the time using the IEC60870-5-103 interface. For attempt to set the time via the
interface, the protective device will create an event with the date and time taken from the IRIG-B
synchronized internal clock.
The complete list of all events produced by the protective device can be printed by choosing the
submenu “IEC103 Info” in the menu “Print”.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
Generic service group numbers supported by the relay can be printed by the submenu “IEC103
Info” in the menu “Print”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. All the functions provided by this relay are based on generic functions of the
IEC60870-5-103. This relay will send all the relevant information on group caption to SAS or RTU
after establishing a successful communication link.
10.5.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
device to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
Date: 2016-08-16
10 Communication
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder device - Principles
and models
IEC 61850-7-2: Basic communication structure for substation and feeder device - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder device – Common
data classes
IEC 61850-7-4: Basic communication structure for substation and feeder device – Compatible
logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation device such as
protection relays, meters, RTUs, instrument transformers, tap changers, or bay controllers.
Please note that gateways can be considered as clients and servers subject to the communication
object. When retrieving data from IEDs within the substation, the gateways are considered as
servers whereas transmitting data to control centers, the gateways are considered as clients.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the following items: individual ICD files, SSD file, communication
system parameters (MMS, GOOSE control block, SV control block), as well as GOOSE/SV
connection relationship amongst IEDs.
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
Hereinafter, the normal operation status of net means the physical link and TCP link are both OK.
The abnormal operation status of net means physical link or TCP link is broken.
1) Mode 1: Dual-net full duplex mode sharing the same RCB instance
Date: 2016-08-16
10 Communication
Client Client
TCP Link
MMS Link
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of mode 1, IED provides the same MMS service for Net A and Net B. If
one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the working
mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In mode 1, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Client Client
TCP Link
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance
In mode 2, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
In mode 1 and mode 2, Net A IED host address and Net B IED host address must be the same.
E.g.: if the subnet mask is 255.255.0.0, network prefix of Net A is 198.120.0.0, network prefix of
Net B is 198.121.0.0, Net A IP address of the IED is 198.120.1.2, and then Net B IP address of the
IED must be configured as 198.121.1.2, i.e.: Net A IED host address =1x256+2=258, Net B IED
host address =1x256+2=258, Net A IED host address equals to Net B IED host address.
Date: 2016-08-16
10 Communication
Client Client
TCP Link
MMS Link
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances
In mode 3, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of one net will not affect the other net at all.
In this mode, 2 report instances are required for each client. Therefore, the IED may be unable to
provide enough report instances if there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion:
In mode 3, the IED may be unable to provide enough report instances if too many clients are
applied on site.
For the consideration of client treatment and IED implementation, mode 1 (Dual-net full duplex
mode sharing the same report instance) is recommended for MMS communication network
deployment.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
information about the IED logical device.
The GGIO logical node is used to provide access to digital status points (including general I/O
inputs and warnings) and associated timestamps and quality flags. The data content must be
configured before using. GGIO provides digital status points for access by clients. It is intended for
the use of GGIO by client to access to digital status values from PCS-985GE relays. Clients can
utilize the IEC61850 buffered report from GGIO to build sequence of events (SOE) logs and HMI
display screens. Buffered reporting should generally be used for SOE logs since the buffering
capability reduces the chances of missing data state changes. All needed status data objects are
transmitted to HMI clients via buffered reporting, and the corresponding buffered reporting control
block (BRCB) is defined in LLN0.
Most of measured analog values are available through the MMXU logical nodes, and m etering
values in MMTR, the others in MMXN, MSQI and so on. Data of each MMXU logical node is
provided from a IED current/voltage “source”. There is one MMXU available for each configurable
source. Data of MMXU1 is provided from CT/VT source 1 (usually for protection purpose), and
data of MMXU2 is provided from CT/VT source 2 (usually for monitor and display purpose). All
these analog data objects are transmitted to HMI clients via unbuffered reporting periodically, and
the corresponding unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical
nodes provide the following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for PCS-985GE relays. The specified relay will
Date: 2016-08-16
10 Communication
RBRF:Breaker failure
PTOF: Overfrequency
PTUF: Underfrequency
PTUV: Undervoltage
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PDIF1 is “PDIF1.ST.Op.general”. For
PCS-985GE relay protection elements, these flags take their values from related module for the
corresponding element. Similar to digital status values, the protection trip information is reported
via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defined for the whole device; the
common settings include all the setting items of communication settings, system settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked until Loc is changed to false. In PCS-985GE relays, besides the logical nodes
described above, there are some other logical nodes in the IEDs:
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it is used to connect the “operate” outputs of one or more
protection functions to a common “trip” to be transmitted to XCBR. In addition or alternatively, any
combination of “operate” outputs of protection functions may be combined to a new “operate” of
PTRC.
RDRE: Disturbance recorder function. It triggers fault wave recorder and its output refers to
the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System” (IEC
60255-24). All enabled channels are included in the recording and is independent of the trigger
mode.
ZGEN: Generator
IEC61850 buffered and unbuffered reporting control blocks are located in LLN0, they can be
configured to transmit information of protection trip information (in the Protection logical nodes),
binary status values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and
MSQI). The reporting control blocks can be configured in CID files, and then be sent to the IED via
an IEC61850 client. The following items can be configured.
- Bit 1: Data-change
Date: 2016-08-16
10 Communication
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services allows transfer of oscillography, event record or other files from a PCS-985GE
relay.
10.5.5.3 Timestamps
The timestamp values associated with all IEC61850 data items represent the time of the last
change of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are in the form of xxxxxxPTOC1, where the xxxxxx character string is
configurable. Details regarding the logical node naming rules are given in IEC61850 parts 6 and
7-2. It is recommended that a consistent naming convention be used for an entire substation
project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link
settings in device.
The relay supports IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-985GE relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Client-Server Roles
SCSMS Supported
Where:
Date: 2016-08-16
10 Communication
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
Reporting
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y N
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M16 Time M M Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
Date: 2016-08-16
10 Communication
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O Y
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Reporting
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M N
S24-3 data-update M N
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M N
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
S35 SendGOOSEMessage M Y
S36 GetGoReference O Y
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M N
Control
S51 Select O N
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O N
File transfer
S58 SetFile O N
S59 DeleteFile O N
Time
SNTP M Y
The relay support IEC61850 logical nodes as indicated in the following table. Note that the actual
instantiation of each logical node is determined by the product order code.
Nodes PCS-985GE
Date: 2016-08-16
10 Communication
Nodes PCS-985GE
PTUC: Undercurrent -
Nodes PCS-985GE
RREC: Autoreclosing -
CILO: Interlocking -
IARC: Archiving -
MMTR: Metering -
Date: 2016-08-16
10 Communication
Nodes PCS-985GE
ZBAT: Battery -
ZBSH: Bushing -
ZCON: Converter -
ZMOT: Motor -
ZREA: Reactor -
10.6.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of
the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical)
at the rear side of this relay.
The supported object groups and object variations are show in the following table.
Date: 2016-08-16
10 Communication
Date: 2016-08-16
10 Communication
Date: 2016-08-16
10 Communication
This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP
related communication parameters respectively and be selected the user-defined communication
table. This relay supports a default communication table and 4 user-defined communication tables,
and the default communication table is fixed by the manufacturer and not permitted to configure by
the user.
The user can configure the user-defined communication table through the PCS-Explorer2
configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog
Input” and “Analog Output” can be configured according to the practical engineering demand.
To the analog inputs, the attributes “deadband” and “factor” of each analog input can be configured
independently. To the analog outputs, only the attribute “factor” of each analog output needs to be
configured. If the integer mode is adopted for the data formats of analog values (to “Analog Input”,
“Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.), the analog
values will be multiplied by the “factor” respectively to ensure their accuracy. And if the float mode
is adopted for the data formats of analog values, the actual float analog values will be sent directly.
The judgment method of the analog input change is as below: Calculate the difference between
the current new value and the stored history value and make the difference value multiply by the
“factor”, then compare the result with the “deadband” value. If the result is greater than the
“deadband” value, then an event message of corresponding analog input change will be created.
In normal communication process, the master can online read or modify a “deadband” value by
reading or modifying the variation in “Group34”.
The remote control signals, logic links and external extended output commands can be configured
into the “Binary Output” group. The supported control functions are listed as below.
Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null
Remote Control Not supported Close Trip Close Trip
Logic Link Not supported Set Clear Set Clear
Extended Output See following description
This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the
unsolicited messages want to be transmitted, the related logic setting should be set as “1” or the
DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function Code
20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference value of
the “Analog Input” is greater than the “deadband” value, this device will transmit unsolicited
messages. If the DNP3.0 master needs not to receive the unsolicited messages, it should forbid
this relay to transmit the unsolicited messages by setting the related logic setting as “0” or through
the “Function Code 21” (Disable Unsolicited Messages).
If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog
Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input”
can be defined by modifying relevant settings. In communication process, the DNP3.0 master can
online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22” (Assign
Class).
Date: 2016-08-16
11 Installation
11 Installation
Table of Contents
11 Installation ...................................................................................... 11-a
11.1 Overview ....................................................................................................... 11-1
11.2 Safety Information ........................................................................................ 11-1
11.3 Check the Shipment ..................................................................................... 11-2
11.4 Material and Tools Required ........................................................................ 11-2
11.5 Device Location and Ambient Conditions .................................................. 11-2
11.6 Mechanical Installation ................................................................................ 11-3
11.7 Electrical Installation and Wiring ................................................................ 11-4
11.7.1 Grounding Guidelines .......................................................................................................11-4
List of Figures
Figure 11.6-1 Dimensions and panel cut-out of PCS-985GE ................................................ 11-3
Figure 11.6-2 Demonstration of plugging a board into its corresponding slot .................. 11-3
Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7
Date: 2016-08-16
11 Installation
11.1 Overview
The device must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the device. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the device and terminated correctly and
pay special attention to grounding. Strictly observe the corresponding guidelines contained in this
section.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
WARNING!
ONLY insert or withdraw a module while the device power supply is switched off. To this
end, disconnect the power supply cable that connects with the PWR module.
NOTICE!
Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic
equipment. Electronic components are sensitive to electrostatic discharge when not in
the unit's housing.
NOTICE!
NOTICE!
A module can ONLY be inserted in the slot designated in the chapter 6. Components
can be damaged or destroyed by inserting module in a wrong slot.
Should boards have to be removed from this device installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on the board which has been removed from the cubicle on a workbench designed
for electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this device is mounted in cubicles).
Excessively high temperature can appreciably reduce the operating life of this device.
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Surge voltages of high amplitude and short rise time, extreme changes of temperature, high
levels of humidity, severe vibration and strong induced magnetic fields should be avoided as
far as possible.
Date: 2016-08-16
11 Installation
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of this device.
The device is made of one 4U height 19" chassis with 8 connectors on its rear panel. Following
figure shows the dimensions and cut-out size in the cubicle of this device for reference in
mounting.
482.6 (290.0)
465.0
101.6
177.0
465.0±0.2
+0.4
451.0 -0.0
4-Φ6.8
+0.4
179.0 -0.0
101.6±0.1
Following figure shows the installation way of a module being plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
All these precautions can only be effective if the station ground is of good quality.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTICE!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
Date: 2016-08-16
11 Installation
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There are some ground terminals on some connectors of this device, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this device. Therefore, the ground terminal on the
rear panel (see Figure 11.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
There are several types of cables that are used in the connection of this device: braided copper
cable, serial communication cable etc. Recommendation of each cable:
Power supply, binary inputs & outputs: brained copper cable, 1.0mm 2 ~ 2.5mm 2
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
A female connector is used for connecting the wires with it, and then a female connector plugs into
a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.
The following figure shows the glancing demo about the wiring for the electrical cables.
Date: 2016-08-16
11 Installation
01 02
03 04
Tighten 05 06
07 08
09 10
11 12
01
13 14
15 16
17 18
19 20
21 22
23 24
Figure 11.7-4 Glancing demo about the wiring for electrical cables
Date: 2016-08-16
12 Commissioning
12 Commissioning
Table of Contents
12 Commissioning ............................................................................ 12-a
12.1 Overview ...................................................................................................... 12-1
12.2 Safety Instructions ...................................................................................... 12-1
12.3 Commission Tools ...................................................................................... 12-1
12.4 Setting Familiarization ................................................................................ 12-2
12.5 Product Checks ........................................................................................... 12-2
12.5.1 With the Device De-energized ......................................................................................... 12-3
Date: 2016-08-16
12 Commissioning
12.1 Overview
This device is numerical in their design, implementing all functions in software. The device
employs a high degree self-checking, so in the unlikely event of a failure, it will give an alarm.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the device, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the device’s rating label.
DANGER!
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This
personnel MUST be familiar with all safety regulations and service procedures
described in this manual. During operating of electrical device, certain part of the
device is under high voltage. Severe personal injury and significant device damage
could result from improper behavior.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!).
The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
may be close commands to the circuit breakers and other primary switches are disconnected
from the device unless expressly stated.
NOTICE!
Modern test set may contain many of the above features in one unit.
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
Tester: HELP-9000.
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
If the application-specific settings have been applied to the device prior to commissioning, it is
Date: 2016-08-16
12 Commissioning
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the device itself via printer or manually creating a setting record.
This device is fully numerical and the hardware is continuously monitored. Commissioning tests
can be kept to a minimum and need only include hardware tests and conjunctive tests. The
function tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware
defect. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based.
Timers test
Conjunctive tests
The tests are performed after the device is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed are
necessary.
Device panel
Carefully examine the device panel, device inside and other parts inside to see that no
physical damage has occurred since installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
Carefully examine the wiring to see that they are no connection failure exists.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Output contacts
Communication ports
Test method:
To unplug all the terminals sockets of this device, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly
reconnected to the device.
Check that the external wiring is correct to the relevant device diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
Date: 2016-08-16
12 Commissioning
WARNING!
Energize this device ONLY if the power supply is within the specified operating range in
the Chapter “Technical Data”.
The device only can be operated under the auxiliary power supply depending on the device’s
nominal power supply rating.
The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the device, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.
The following groups of checks verify that the device hardware and software is functioning
correctly and should be carried out with the auxiliary supply applied to the device.
The current and voltage transformer connections must remain isolated from the device for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the device to DC power supply correctly and turn the device on. Check program version
and forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date
will be maintained. Therefore when the auxiliary supply is restored the time and date will be
correct and not need to set again.
To test this, remove the auxiliary supply from the device for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the device is healthy.
The device has latched signal devices which remember the state of the trip, auto-reclose when
the device was last energized from an auxiliary supply. Therefore these indicators may also
illuminate when the auxiliary supply is applied. If any of these LEDs are on then they should be
reset before proceeding with further testing. If the LED successfully reset, the LED goes out.
There is no testing required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will
light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the devices menu.
This test checks that all the binary inputs on the equipment are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using device menu. Sign “1” denotes an energized
input and sign “0” denotes a de-energized input.
1. Confirm the external wiring to the current and voltage inputs is correct.
Date: 2016-08-16
12 Commissioning
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the device in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and
voltage transformer wiring.
If the device is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the device is put into service.
Ensure that all event records, fault records and alarms have been cleared and LED’s has been
reset before leaving the device.
Date: 2016-08-16
13 Maintenance
13 Maintenance
Table of Contents
13 Maintenance .................................................................................. 13-a
13.1 Appearance Check ...................................................................................... 13-1
13.2 Failure Tracing and Repair ......................................................................... 13-1
13.3 Replace Failed Modules ............................................................................. 13-2
13.4 Cleaning ....................................................................................................... 13-3
13.5 Storage ......................................................................................................... 13-3
Date: 2016-08-16
13 Maintenance
This device is designed to require no special maintenance. All measurement and signal
processing circuit are fully solid state. All input modules are also fully solid state. The output relays
are hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw device board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the
primary system is live when withdrawing an AC module. Never try to insert or withdraw the
device board when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “Superv State” screen on the LCD.
WARNING!
Module can ONLY be replaced while the device power supply is switched off.
ONLY appropriately trained and qualified personnel can perform the replacement by
strictly observing the precautions against electrostatic discharge.
WARNING!
Five seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Take anti-static measures such as wearing an earthed wristband and placing modules
on an earthed conductive mat when handling a module. Otherwise, electronic
components could be damaged.
CAUTION!
If the failure is identified to be in the device module and the user has spare modules, the user can
recover the device by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, MON, BI, BO, etc.)
and hardware type-form as the removed module. Furthermore, the MON module replaced should
have the same software version. In addition, the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Information”->“Version Info”.
1) Replacing a module
Short circuit all AC current inputs and disconnect all AC voltage inputs
Date: 2016-08-16
13 Maintenance
After replacing the MON module, input the application-specific setting values again.
Unplug the ribbon cable on the front panel by pushing the catch outside.
13.4 Cleaning
Before cleaning the device, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
13.5 Storage
The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40°C to +70°C, but the temperature of from 0°C
to +40°C is recommended for long-term storage.
Date: 2016-08-16
14 Decommissioning and Disposal
Table of Contents
14 Decommissioning and Disposal ................................................. 14-a
14.1 Decommissioning ....................................................................................... 14-1
14.2 Disposal ....................................................................................................... 14-1
Date: 2016-08-16
14 Decommissioning and Disposal
14.1 Decommissioning
DANGER!
Switch OFF the circuit breaker for primary CTs and VTs BEFORE disconnecting the
cables of AI module.
WARNING!
Switch OFF the external miniature circuit breaker of device power supply BEFORE
disconnecting the power supply cable connected to the PWR module.
WARNING!
1. Switching off
To switch off this device, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
3. Dismantling
The device rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
14.2 Disposal
NOTICE!
Strictly observe all local and national laws and regulations when disposing the device.
Date: 2016-08-16
15 Manual Version History
Date: 2019-02-21