Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
2 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0 Issued: 2011-05-09
Revision: D
Description Std.conf.
Voltage and frequency based protection and measurement functions, synchrocheck and load shedding A
ABB 3
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Functionality A B
Protection1)
Three-phase thermal overload protection for power transformers, two time constants - ●
4 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Control
Circuit-breaker control ● ●
Condition Monitoring
Measurement
Disturbance recorder ● ●
ABB 5
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
RTD/mA measurement - o
Frequency measurement ● -
● = included, o = optional at the time of order
1) The instances of a protection function represent the number of identical function blocks available in a standard configuration. By setting the
application specific parameters of an instance, a protection function stage can be established.
2) U 0 selectable by parameter, U 0 measured as default.
3) Light only.
4) Multi-purpose protection is used for, for example, RTD/mA based protection.
5) Available in IED and SMT but not connected to anything in logic.
6 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-5E258DF3-B410-4FEE-9925-A8FC9C3617CE V2 EN
ABB 7
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-DCA293F5-58D2-4CE8-9602-842A6498F9ED V2 EN
8 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-CA7B4D3E-1269-450F-A061-5A404FF52455 V2 EN
Figure 3. Busbar protection and supervision using REU615 with the standard configuration A. The arc protection
schemes of REU615 and REF615 are employed for busbar protection for the voltage measurement bay
and related parts of the busbar. Apart from the busbar protection and supervision the REU615 IED is
utilized for centralized load shedding (disconnection) and restoration (reconnection) of one of the
outgoing feeders. The synchro-check and energizing check functions incorporated in REU615 are
employed for ensuring a safe connection of the outgoing feeder, including distributed generation, to the
network.
ABB 9
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-A90B4035-68B9-4264-83C5-DD791DDEDAB0 V2 EN
Figure 4. Tap changer control and power transformer thermal overload protection using REU615 with the
standard configuration B. The tap changer position information is received as a mA-signal from the tap
changer operation mechanism. The position value is sent to the transformer differential protection
function of the RET615 IED using GOOSE messaging. Further, the analog GOOSE messaging enables
the tap changer control of the two parallel running power transformers. The RTD inputs complement the
thermal overload protection by measuring the oil and ambient temperature of the power transformer.
10 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
diagrams, thus enabling convenient information performance calculations with real-time and
accessibility. To enhance personnel safety, the history values. Better understanding of the
web HMI also enables remote access to process behaviour by joining time-based process
substation devices and processes. Furthermore, measurements with production and maintenance
COM600 can be used as a local data warehouse events helps the user in understanding the
for technical documentation of the substation and process dynamics.
for network data collected by the IEDs. The
collected network data facilitates extensive COM600 also features gateway functionality
reporting and analyzing of network fault situations providing seamless connectivity between the
using the data historian and event handling substation IEDs and network-level control and
features of COM600. The data historian can be management systems such as MicroSCADA Pro
used for accurate process performance and System 800xA
monitoring by following process and equipment
Product Version
GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V3 EN
Figure 5. Utility power distribution network example using 615 series IEDs, Grid Automation controller COM600
and MicroSCADA Pro
ABB 11
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V3 EN
Figure 6. Industrial power system example using 615 series IEDs, Grid Automation controller COM600 and
System 800xA
12 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
remotely using the web-browser based user record includes current, voltage and angle values,
interface. time stamp, etc. The fault recording can be
triggered by the start signal or the trip signal of a
protection block, or by both. The available
8. Disturbance recorder
measurement modes include DFT, RMS and peak-
The IED is provided with a disturbance recorder
to-peak. In addition, the maximum demand
featuring up to 12 analog and 64 binary signal
current with time stamp is separately recorded.
channels. The analog channels can be set to
By default, the records are stored in a non-volatile
record either the waveform or the trend of the
memory.
currents and voltage measured.
The analog channels can be set to trigger the 11. Condition monitoring
recording function when the measured value falls The condition monitoring functions of the IED
below or exceeds the set values. The binary constantly monitors the performance and the
signal channels can be set to start a recording on condition of the circuit breaker. The monitoring
the rising or the falling edge of the binary signal or comprises the spring charging time, SF6 gas
both. pressure, the travel-time and the inactivity time of
the circuit breaker.
By default, the binary channels are set to record
external or internal IED signals, for example the The monitoring functions provide operational
start or trip signals of the IED stages, or external circuit breaker history data, which can be used for
blocking or control signals. Binary IED signals scheduling preventive circuit breaker maintenance.
such as a protection start or trip signal, or an
external IED control signal over a binary input can
be set to trigger the recording. The recorded 12. Trip-circuit supervision
information is stored in a non-volatile memory and The trip-circuit supervision continuously monitors
can be uploaded for subsequent fault analysis. the availability and operability of the trip circuit. It
provides open-circuit monitoring both when the
circuit breaker is in its closed and in its open
9. Event log position. It also detects loss of circuit-breaker
To collect sequence-of-events (SoE) information, control voltage.
the IED incorporates a non-volatile memory with a
capacity of storing 1024 events with associated
time stamps. The non-volatile memory retains its 13. Self-supervision
data also in case the IED temporarily loses its The IED’s built-in self-supervision system
auxiliary supply. The event log facilitates detailed continuously monitors the state of the IED
pre- and post-fault analyses of feeder faults and hardware and the operation of the IED software.
disturbances. The increased capacity to process Any fault or malfunction detected is used for
and store data and events in the IED offers alerting the operator.
prerequisites to support the growing information
A permanent IED fault will block the protection
demand of future network configurations.
functions to prevent incorrect operation.
The SoE information can be accessed locally via
the user interface on the IED front panel or 14. Fuse failure supervision
remotely via the communication interface of the The fuse failure supervision detects failures
IED. The information can further be accessed, between the voltage measurement circuit and the
either locally or remotely, using the web-browser IED. The failures are detected by the negative-
based user interface. sequence based algorithm or by the delta voltage
and delta current algorithm. Upon the detection of
10. Recorded data a failure the fuse failure supervision function
The IED has the capacity to store the records of activates an alarm and blocks voltage-dependent
128 latest fault events. The records enable the protection functions from unintended operation.
user to analyze the power system events. Each
ABB 13
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
15. Current circuit supervision The residual current input and the phase-current
Current circuit supervision is used for detecting inputs are rated 1/5 A. The three phase-voltage
faults in the current transformer secondary inputs and the residual-voltage input covers the
circuits. On detecting of a fault the current circuit rated voltages 60-210 V. Both phase-to-phase
supervision function activates an alarm LED and voltages and phase-to-earth voltages can be
blocks certain protection functions to avoid connected.
unintended operation. The current circuit
supervision function calculates the sum of the The phase-current input 1 A or 5 A, the residual-
phase currents from the protection cores and current input 1 A or 5 A, and the rated voltage of
compares the sum with the measured single the residual voltage input are selected in the IED
reference current from a core balance current software. In addition, the binary input thresholds
transformer or from separate cores in the phase 18…176 V DC are selected by adjusting the IED’s
current transformers. parameter settings.
A - 5 - – 12 10
1) The optional I/O module and the optional RTD/mA modules are mutually exclusive
2) Optional
3) With optional binary I/O module ( )
14 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
ABB 15
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
connections are supported. Termination and pull- With special time synchronization wiring:
up/down resistors can be configured with jumpers • IRIG-B (Inter-Range Instrumentation Group -
on the communication card so external resistors Time Code Format B)
are not needed.
The IED supports the following time In addition, the IED supports time synchronization
synchronization methods with a time-stamping via the following serial communication protocols:
resolution of 1 ms: • Modbus
• DNP3
Ethernet-based: • IEC 60870-5-103
• SNTP (Simple Network Time Protocol)
Client A Client B
Network
Network
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V3 EN
16 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
IEC 61850 ● ● - -
MODBUS RTU/ASCII - - ● ●
MODBUS TCP/IP ● ● - -
DNP3 (serial) - - ● ●
DNP3 TCP/IP ● ● - -
IEC 60870-5-103 - - ● ●
● = Supported
ABB 17
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Table 6. Dimensions
Description Value
case 164 mm
case 160 mm
Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 24, 30, 48, 60 V DC
60 Hz
Burden of auxiliary voltage supply DC < 12.0 W (nominal)/< 18.0 W (max) DC < 12.0 W (nominal)/< 18.0 W (max)
under quiescent (Pq)/operating AC< 16.0 W (nominal)/< 21.0W (max)
condition
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
18 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Description Value
Thermal withstand
capability:
• Continuously 20 A
• For 1 s 500 A
Voltage withstand:
• Continuous 240 V AC
• For 10 s 360 V AC
Description Value
Reaction time 3 ms
ABB 19
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Description Value
RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760)
sensors 250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
Supported resistance
range 0...2 kΩ
Maximum lead
resistance (three-
wire measurement) 25 Ω per lead
RTD/resistance
sensing current Maximum 0.33 mA rms
± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C
Current input
impedance 44 Ω ± 0.1%
Description Value
20 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Description Value
Description Value
Description Value
Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s
ABB 21
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)
Description Value
Modulation Unmodulated
Table 18. Lens sensor and optical fibre for arc protection
Description Value
Description Value
Front side IP 54
Description Value
Altitude Up to 2000 m
22 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C
ABB 23
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
• Contact discharge 8 kV
• Air discharge 15 kV
• All ports 4 kV
• 2s 100 A/m
24 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
150 V rms
• Conducted
• Radiated
Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27
ABB 25
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Description Reference
LV directive 2006/95/EC
Description Reference
Description
26 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Protection functions
Characteristic Value
PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
x In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
ABB 27
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
PHHPTOC 40...200000 ms 10
PHIPTOC 20...200000 ms 10
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 x Un, Voltage before fault = 0.9 x U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 x U n, Start value multiples in range of 1.10 to 2.00
28 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 x Un, Voltage before fault = 1.1 x U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20
ABB 29
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase
angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
30 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
ABB 31
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
Table 41. Thermal overload for protection, two time constants (T2PTTR) main settings
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
32 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
Characteristic Value
ABB 33
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
f< < 80 ms
34 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
ABB 35
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Control functions
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
36 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
ABB 37
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Table 52. Synchronism and energizing check (SECRSYN) main settings, continued
Parameter Values (Range) Unit Step Default Description
Characteristic Value
Operate time accuracy in definite time mode2) + 4.0% / - 0% of the set value
Operate time accuracy in inverse time mode2) + 8.5% / - 0% of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time (IDMT) 1 s.
38 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Table 54. On-load tap changer control with voltage regulator (OLATCC) main settings
ABB 39
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Measurement functions
Characteristic Value
±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)
Characteristic Value
±1.0% or ±0.002 x In
at currents in the range of 0.01...4.00 x In
Characteristic Value
±0.5% or ±0.002 x Un
Characteristic Value
±1.0% or ±0.002 x Un
40 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Characteristic Value
Description Value
RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760)
sensors 250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427
Supported resistance
range 0...2 kΩ
Maximum lead
resistance (three-
wire measurement) 25 Ω per lead
RTD/resistance
sensing current Maximum 0.33 mA rms
± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C
Current input
impedance 44 Ω ± 0.1%
Characteristic Value
ABB 41
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Supervision functions
Characteristic Value
Characteristic Value
Operate time1)
1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
42 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
20. Local HMI default single line diagram. The SLD view can also
The IED is available with two optional displays, a be accessed using the web-browser based user
large one and a small one. The large display is interface. The default SLD can be modified
suited for IED installations where the front panel according to user requirements by using the
user interface is frequently used and a single line graphical display editor in PCM600.
diagram is required. The small display is suited for
remotely controlled substations where the IED is The local HMI includes a push button (L/R) for
only occasionally accessed locally via the front local/remote operation of the IED. When the IED
panel user interface. is in the local mode, the IED can be operated only
by using the local front panel user interface. When
Both LCD displays offer front-panel user interface the IED is in the remote mode, the IED can
functionality with menu navigation and menu execute commands sent from a remote location.
views. However, the large display offers increased The IED supports the remote selection of local/
front-panel usability with less menu scrolling and remote mode via a binary input. This feature
improved information overview. In addition, the facilitates, for example, the use of an external
large display includes a user-configurable single switch at the substation to ensure that all IEDs
line diagram (SLD) with position indication for the are in the local mode during maintenance work
associated primary equipment. Depending on the and that the circuit breakers cannot be operated
chosen standard configuration, the IED displays remotely from the network control centre.
the related measuring values, apart from the
IECA070904 V3 EN IECA070901 V3 EN
ABB 43
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
190
6
18
164
177 25°
160
160
177
230
177
107
133
98
48
1 53
103
IECA070902 V4 EN
IECA070900 V4 EN IECA070903 V4 EN
Figure 12. Semi-flush with a 25º
Figure 10. Flush mounting Figure 11. Semi-flush mounting tilt
44 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
22. IED case and IED plug-in unit on the upper part of the plug-in-unit. An order
For safety reasons, the IED cases for current number label is placed on the side of the plug-in
measuring IEDs are provided with automatically unit as well as inside the case. The order number
operating contacts for short-circuiting the CT consists of a string of codes generated from the
secondary circuits when a IED unit is withdrawn IED's hardware and software modules.
from its case. The IED case is further provided
with a mechanical coding system preventing Use the ordering key information to generate the
current measuring IED units from being inserted order number when ordering complete IEDs.
into a IED case for a voltage measuring IED unit
and vice versa, i.e. the IED cases are assigned to
a certain type of IED plug-in unit.
H B U BCCAHBCC1BBN1XE
# Description
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired and in -
K
stalled in a 19” equipment panel
615 series IED (including case) with test switch, wired and in -
stalled in a mounting bracket for CombiFlex rack mounting (RGHT L
19” 4U variant C)
2 Standard
IEC B
3 Main application
Voltage protection and control U
GUID-AD8D5903-41C6-4187-A02A-1F5C3407E335 V2 EN
The standard configuration determines the I/O hardware and available options. HBU BCCAH NBA1ABN1XE
The example below shows standard configuration “B” with chosen options.
# Description
4-8 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Voltage and frequency based protection and measurement functions,
synchro-check, load shedding and CB control
B = Automatic voltage regulator, CB control and with the optional I/O module
control of one network object
Std. conf. I/O options
A 5U + 12 BI + 10 BO AEAAD
B 4I (Io 1/5 A) + 3U + 8 BI + 10 BO BCAAH
B 4I (Io 1/5 A) + 3U + 14 BI + 13 BO BCABB*
B 4I (Io 1/5 A) + 3U + 6 RTD + 2 mA + 8 BI + 10 BO BCCAH
ABB 45
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
The communication module hardware determines the available communication proto - HBUBCCAH BC C1BBN1XE
cols. Choose the hardware from one of the rows below to define the digits # 9-10.
# Description
9 Communication modules (Serial/Ethernet)
-
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
10 AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1
AB
x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST), incl. an RS-485 connector and an input for
BN
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (1 x RJ-45) + Serial
RS-485 connector, RS-232/485 D-Sub 9 connector + input for BB
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (3 x RJ-45) BD
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC
+ 1 x LC)
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE
+ 2 x LC)
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX (2 x RJ-45 + 1 x LC) NC
Ethernet 100Base-TX (3 x RJ-45) ND
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) NE
No communication module NN
If serial communication is chosen, please choose a serial communication module including Ethernet (for example “BC”) if a service
bus for PCM600 or the WebHMI is required.
GUID-A54E91E4-EB6B-45BD-9BC7-DA4EE4295CAF V2 EN
HBUBCCAHBC C 1BBN1XE
# Description
11 Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a com - A
munication module )
Modbus
B
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + Modbus
C
(for Ethernet or serial + Ethernet communication modules)
IEC 60870-5-103
D
(for serial or Ethernet + serial communication modules)
DNP3
E
(for Ethernet/serial or Ethernet + serial communication modules)
GUID-5B4CE02E-BA34-4AA7-A6E6-8408A3C1763D V2 EN
46 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
HBU BCCAHBCC 1 B B N 1 XE
# Description
12 Language
English 1
English and German 3
English and Swedish 4
English and Spanish 5
English and Russian 6
English and Polish 7
English and Portuguese (Brazilian) 8
English and Italian A
English and French C
English and Czech E
13 Front panel
Small LCD A
Large LCD with single line diagram (SLD) B
14 Option 1
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-28A75E3D-BF45-42F0-90D8-B142E3EA28F3 V2 EN
ABB 47
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
19” rack mounting kit with cut-out for one IED 1MRS050694
19” rack mounting kit with cut-out for two IEDs 1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001
Mounting bracket for one IED in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001
19” rack mounting kit for one IED and one RTXP18 test switch (the test switch is not 2RCA021952A0003
included in the delivery)
19” rack mounting kit for one IED and one RTXP24 test switch (the test switch is not 2RCA022561A0003
included in the delivery)
Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the 2RCA027871A0001
installation plate)
Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of 2RCA027874A0001
the installation plate)
19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001
19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001
48 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
The Protection and Control IED Manager PCM600 The IED connectivity package is a collection of
is available in two different variants, that is software and specific IED information, which
PCM600 Basic/Engineering and PCM600 enable system products and tools to connect and
Engineering Pro. Depending on the chosen interact with the IED. The connectivity packages
variant, PCM600 offers extensive IED reduce the risk of errors in system integration,
configuration functions such as IED signal minimizing device configuration and set-up times.
configuration, application configuration, graphical Further, the Connectivity Packages for the 615
display configuration including single line diagram series IEDs include a flexible update tool for
configuration, and IEC 61850 communication adding one additional local HMI language to the
configuration including horizontal GOOSE IED. The update tool is activated using PCM600
communication. and enables multiple updates of the additional
HMI language, thus offering flexible means for
When the web-browser based user interface is possible future language updates.
used, the IED can be accessed either locally or
ABB 49
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Signal monitoring ● ● ●
Modbus® communication
configuration (communication
management) - ● ●
Application configuration - ● ●
Event viewing ● ● ●
50 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN
ABB 51
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN
52 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
27. References The download area on the right hand side of the
The www.abb.com/substationautomation portal web page contains the latest product
offers you information about the distribution documentation, such as technical manual,
automation product and service range. installation manual, operation manual, etc.
You will find the latest relevant information on the The Features and Application tabs contain
REU615 protection IED on the product page. product related information in a compact format.
GUID-2ECAAEFE-CEF1-4A31-97F4-B88FCF66DB8E V1 EN
ABB 53
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Protection
54 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
Control
Condition monitoring
Measurement
ABB 55
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0
56 ABB
57