Relion® 615 series

Voltage Protection and Control


REU615
Product Guide
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Contents

1. Description.....................................................................3 16. Access control............................................................14


2. Standard configurations.................................................3 17. Inputs and outputs......................................................14
3. Protection functions........................................................6 18. Station communication................................................15
4. Application.....................................................................8 19. Technical data.............................................................18
5. Supported ABB solutions.............................................10 20. Local HMI....................................................................43
6. Control.........................................................................12 21. Mounting methods......................................................44
7. Measurement...............................................................12 22. IED case and IED plug-in unit......................................45
8. Disturbance recorder....................................................13 23. Selection and ordering data.........................................45
9. Event log......................................................................13 24. Accessories and ordering data....................................48
10. Recorded data............................................................13 25. Tools...........................................................................49
11. Condition monitoring...................................................13 26. Terminal diagrams.......................................................51
12. Trip-circuit supervision.................................................13 27. References..................................................................53
13. Self-supervision...........................................................13 28. Functions, codes and symbols....................................54
14. Fuse failure supervision...............................................13 29. Document revision history...........................................56
15. Current circuit supervision...........................................14

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
© Copyright 2012 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

2 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0 Issued: 2011-05-09
Revision: D

1. Description been given the application-specific settings, it can


The voltage protection and control IED, REU615 directly be put into service.
is available in two standard configurations,
denoted A and B. Configuration A is preadapted The 615 series IEDs support a range of
for voltage and frequency-based protection communication protocols including IEC 61850
schemes in utility and industrial power systems with GOOSE messaging, IEC 60870-5-103,
and distribution systems including networks with Modbus ® and DNP3.
distributed power generation. The B configuration
is designed for automatic voltage regulation of 2. Standard configurations
power transformers equipped with an on-load tap- REU615 is available in two standard
changer. Both configurations also feature configurations. The standard signal configuration
additional CB control, measuring and supervising can be altered by means of the graphical signal
functions. REU615 is a member of ABB’s Relion ® matrix or the graphical application functionality of
product family and part of its 615 protection and the Protection and Control IED Manager PCM600.
control product series. The 615 series IEDs are Further, the application configuration functionality
characterized by their compactness and of PCM600 supports the creation of multi-layer
withdrawable–unit design. logic functions using various logical elements,
including timers and flip-flops. By combining
Re-engineered from the ground up, the 615 series
protection functions with logic function blocks,
has been designed to unleash the full potential of
the IED configuration can be adapted to user-
the IEC 61850 standard for communication and
specific application requirements.
interoperability between substation automation
devices. Once the standard configuration IED has

Table 1. Standard configurations

Description Std.conf.

Voltage and frequency based protection and measurement functions, synchrocheck and load shedding A

Automatic voltage regulator B

ABB 3
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 2. Supported functions

Functionality A B

Protection1)

Three-phase non-directional overcurrent protection, low stage, instance 1 - ●

Three-phase non-directional overcurrent protection, high stage, instance 1 - ●

Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 - ●

Residual overvoltage protection, instance 1 ●2) -

Residual overvoltage protection, instance 2 ●2) -

Residual overvoltage protection, instance 3 ●2) -

Three-phase undervoltage protection, instance 1 ● ●

Three-phase undervoltage protection, instance 2 ● ●

Three-phase undervoltage protection, instance 3 ● ●

Three-phase overvoltage protection, instance 1 ● ●

Three-phase overvoltage protection, instance 2 ● ●

Three-phase overvoltage protection, instance 3 ● ●

Positive-sequence undervoltage protection, instance 1 ● -

Positive-sequence undervoltage protection, instance 2 ● -

Negative-sequence overvoltage protection, instance 1 ● -

Negative-sequence overvoltage protection, instance 2 ● -

Frequency protection, instance 1 ● -

Frequency protection, instance 2 ● -

Frequency protection, instance 3 ● -

Frequency protection, instance 4 ● -

Frequency protection, instance 5 ● -

Frequency protection, instance 6 ● -

Three-phase thermal overload protection for power transformers, two time constants - ●

Master trip, instance 1 ● ●

Master trip, instance 2 ● ●

Arc protection, instance 1 o3) -

Arc protection, instance 2 o3) -

Arc protection, instance 3 o3) -

Multi-purpose protection, instance 14) - o5)

Multi-purpose protection, instance 24) - o5)

Multi-purpose protection, instance 34) - o5)

Multi-purpose protection, instance 44) - o5)

Multi-purpose protection, instance 54) - o5)

4 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 2. Supported functions, continued


Functionality A B

Multi-purpose protection, instance 64) - o5)

Load shedding and restoration, instance 1 ● -

Load shedding and restoration, instance 2 ● -

Load shedding and restoration, instance 3 ● -

Load shedding and restoration, instance 4 ● -

Load shedding and restoration, instance 5 ● -

Control

Circuit-breaker control ● ●

Disconnector control, instance 1 ●5) ●5)

Disconnector control, instance 2 ●5) ●5)

Earthing switch control ●5) ●5)

Disconnector position indication, instance 1 ● ●5)

Disconnector position indication, instance 2 ●5) ●5)

Disconnector position indication, instance 3 ●5) ●5)

Earthing switch indication, instance 1 ●5) ●5)

Earthing switch indication, instance 2 ●5) ●5)

Tap changer position indication - ●

Tap changer control with voltage regulator - ●

Synchronism and energizing check ● -

Condition Monitoring

Trip circuit supervision, instance 1 ● ●

Trip circuit supervision, instance 2 ● ●

Current circuit supervision - ●

Fuse failure supervision - ●

Measurement

Disturbance recorder ● ●

Three-phase current measurement, instance 1 - ●

Sequence current measurement - ●

Three-phase voltage measurement ● ●

Residual voltage measurement ● -

Sequence voltage measurement ● ●

Three-phase power and energy measurement, including power factor - ●

ABB 5
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 2. Supported functions, continued


Functionality A B

RTD/mA measurement - o

Frequency measurement ● -
● = included, o = optional at the time of order
1) The instances of a protection function represent the number of identical function blocks available in a standard configuration. By setting the
application specific parameters of an instance, a protection function stage can be established.
2) U 0 selectable by parameter, U 0 measured as default.
3) Light only.
4) Multi-purpose protection is used for, for example, RTD/mA based protection.
5) Available in IED and SMT but not connected to anything in logic.

3. Protection functions When an arc arises the detection signal is sent to


Standard configuration A the protection IED(s) of the incoming feeder(s) as
a binary signal using either hardwired signalling or
Standard configuration A is intended for busbar horizontal GOOSE messaging. By simultaneous
voltage supervision, load shedding utilization of the overcurrent condition of the
(disconnection) and restoration (reconnection) incoming feeder protection IED and the received
applications. It is also used for overfrequency and arc detection signal, the circuit breakers of the
underfrequency protection of power generators incoming feeders can selectively be tripped thus
and for other AC equipment, e.g. capacitor isolating the fault.
banks, requiring three-phase overvoltage
protection, three-phase undervoltage protection, The arc detection/protection schemes of the IEDs
residual overvoltage protection, positive phase increase personnel safety and limit material
sequence undervoltage protection, negative damage within the switchgear in an arc fault
phase sequence overvoltage protection and situation.
frequency supervision.
Standard configuration B
The integrated load shedding and restoration
functionality offers five instances for Standard configuration B is intended for
disconnection and reconnection of less-important automatic voltage regulation of power
loads in network overload situations. The five transformers equipped with an on-load tap-
instances enable the connected feeders to be changer. It also features three-stage three-phase
more thoroughly prioritized and grouped thus non-directional overcurrent protection, three-
facilitating the securing of critical applications. phase undervoltage and overvoltage protection.
The IED also incorporates a thermal overload
If the restoration process is coordinated by an protection function, which supervises the thermal
automation system or process control system, the stress of the transformer windings to prevent
IED’s load shedding and restoration function can premature aging of the winding's insulation.
send a signal to the system when the
prerequisites for network restoration are fulfilled. The use of the multi-purpose protection function
requires that the optional RTD/mA input module
Enhanced with optional hardware and software, has been chosen when ordering. The multi-
standard configuration A also features three light purpose protection function enables protection
detection channels for arc fault detection in the based on analog values from the IEDs RTD/mA
metering cubicle or busbar compartment of metal- input module, or from other IEDs using analog
enclosed switchgear. The arc-fault detection horizontal GOOSE messaging. The protection
sensor interface is available on the optional function includes three instances, and the used
communication module. analog values may, for example, consist of
temperature, current, voltage or pressure values.
By using the analog values, the set limit values

6 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

and the timers of the protection function can be


set to operate when the input values are below or
exceeds the set values.

GUID-5E258DF3-B410-4FEE-9925-A8FC9C3617CE V2 EN

Figure 1. Protection function overview of standard configuration A

ABB 7
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

GUID-DCA293F5-58D2-4CE8-9602-842A6498F9ED V2 EN

Figure 2. Protection function overview of standard configuration B

4. Application networks containing distributed power generation


Standard configuration A REU615 can be used for loss-of-mains (LOM)
protection for single power generating units.
The A configuration of REU615 is intended to be
used in medium voltage switchgear, supplied with Standard configuration B
a dedicated voltage measurement cubicle. The A
configuration of REU615 provides busbar The B configuration of REU615 including voltage
overvoltage and undervoltage supervision, regulation is intended for automatic and manual
network residual overvoltage supervision and voltage regulation of power transformers
frequency supervision. REU615 offers the equipped with motor driven on-load tap-
functionality needed to provide load shedding or changers. In small substations with a single
generation rejection to enhance network stability. power transformer, REU615 can be used for load-
In generator and motor applications REU615 side voltage regulation. For substations with two
provides supplementary protection by detecting or more power transformers operating in parallel
any deviation from the permitted frequency and three alternative voltage regulation principles are
voltage values. An integrated synchro-check available, i.e. the master/follower principle, the
function ensures a synchronized connection of negative reactance principle (NRP) and the
the equipment into the network. In distribution minimizing circulating current (MCC) principle.

8 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

GUID-CA7B4D3E-1269-450F-A061-5A404FF52455 V2 EN

Figure 3. Busbar protection and supervision using REU615 with the standard configuration A. The arc protection
schemes of REU615 and REF615 are employed for busbar protection for the voltage measurement bay
and related parts of the busbar. Apart from the busbar protection and supervision the REU615 IED is
utilized for centralized load shedding (disconnection) and restoration (reconnection) of one of the
outgoing feeders. The synchro-check and energizing check functions incorporated in REU615 are
employed for ensuring a safe connection of the outgoing feeder, including distributed generation, to the
network.

ABB 9
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

GUID-A90B4035-68B9-4264-83C5-DD791DDEDAB0 V2 EN

Figure 4. Tap changer control and power transformer thermal overload protection using REU615 with the
standard configuration B. The tap changer position information is received as a mA-signal from the tap
changer operation mechanism. The position value is sent to the transformer differential protection
function of the RET615 IED using GOOSE messaging. Further, the analog GOOSE messaging enables
the tap changer control of the two parallel running power transformers. The RTD inputs complement the
thermal overload protection by measuring the oil and ambient temperature of the power transformer.

5. Supported ABB solutions peer-to-peer communication over a switched


ABB’s 615 series protection and control IEDs Ethernet LAN offers an advanced and versatile
together with the Grid Automation controller platform for power system protection. Fast
COM600 constitute a genuine IEC 61850 solution software-based communication, continuous
for reliable power distribution in utility and supervision of the integrity of the protection and
industrial power systems. To facilitate and communication system, and inherent flexibility for
streamline the system engineering ABB’s IEDs are reconfiguration and upgrades are among the
supplied with Connectivity Packages containing a distinctive features of the protection system
compilation of software and IED-specific approach enabled by the full implementation of
information including single-line diagram the IEC 61850 substation automation standard.
templates, a full IED data model including event
and parameter lists. By utilizing the Connectivity At the substation level COM600 uses the data
Packages the IEDs can be readily configured via content of the bay level IEDs to offer enhanced
the PCM600 Protection and Control IED Manager substation level functionality. COM600 features a
and integrated with the Grid Automation controller web-browser based HMI providing a
COM600 or the MicroSCADA Pro network control customizable graphical display for visualizing
and management system. single line mimic diagrams for switchgear bay
solutions. The SLD feature is especially useful
The 615 series IEDs offer native support for the when 615 series IEDs without the optional single
IEC 61850 standard also including binary and line diagram feature are used. Further, the web
analog horizontal GOOSE messaging. Compared HMI of COM600 offers an overview of the whole
with traditional hard-wired inter-device signaling, substation, including IED-specific single line

10 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

diagrams, thus enabling convenient information performance calculations with real-time and
accessibility. To enhance personnel safety, the history values. Better understanding of the
web HMI also enables remote access to process behaviour by joining time-based process
substation devices and processes. Furthermore, measurements with production and maintenance
COM600 can be used as a local data warehouse events helps the user in understanding the
for technical documentation of the substation and process dynamics.
for network data collected by the IEDs. The
collected network data facilitates extensive COM600 also features gateway functionality
reporting and analyzing of network fault situations providing seamless connectivity between the
using the data historian and event handling substation IEDs and network-level control and
features of COM600. The data historian can be management systems such as MicroSCADA Pro
used for accurate process performance and System 800xA
monitoring by following process and equipment

Table 3. Supported ABB solutions

Product Version

Grid Automation controller COM600 3.5 or later

MicroSCADA Pro SYS 600 9.3 FP1 or later

System 800xA 5.0 Service Pack 2

GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V3 EN

Figure 5. Utility power distribution network example using 615 series IEDs, Grid Automation controller COM600
and MicroSCADA Pro

ABB 11
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V3 EN

Figure 6. Industrial power system example using 615 series IEDs, Grid Automation controller COM600 and
System 800xA

6. Control voltage and voltage phase sequence component


The IED offers control of one circuit breaker with measurement. In addition, the standard
dedicated push-buttons for circuit breaker configuration includes frequency measurement.
opening and closing. Further, the optional large
graphical LCD of the IED’s HMI includes a single- IEDs with standard configuration B measure the
line diagram (SLD) with position indication for the three phase-currents and the symmetrical
relevant circuit breaker. Interlocking schemes components of the currents, the phase voltages,
required by the application are configured using the symmetrical components of the voltage and
the signal matrix or the application configuration the phase unbalance value based on the ratio
feature of PCM600. between the negative phase-sequence and
positive phase-sequence current. Furher, the IED
Standard configuration A incorporates a synchro- offers three-phase power and energy
check function to ensure that the voltage, phase measurement including power factor. In addition,
angle and frequency on either side of an open the IED calculates the demand value of current
circuit breaker satisfy the conditions for safe over a userselectable pre-set time frame and the
interconnection of two networks. Standard thermal overload of the protected object.
configuration B includes functionality for
controlling the voltage on the load side of the For standard configuration B, RTD/mA inputs are
power transformer. Based on the measured offered as an option. By means of the optional
values the IED sends control commands to the RTD/mA module the IED can measure up to eight
tap changer thus enabling automatic voltage analog signals such as temperature, pressure and
regulation. tap changer position values via the six RTD inputs
or the two mA inputs using transducers.

7. Measurement The values measured can be accessed locally via


The offered measurement functions depend on the user interface on the IED front panel or
the chosen standard configuration. Standard remotely via the communication interface of the
configuration A offers phase voltage, residual IED. The values can also be accessed locally or

12 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

remotely using the web-browser based user record includes current, voltage and angle values,
interface. time stamp, etc. The fault recording can be
triggered by the start signal or the trip signal of a
protection block, or by both. The available
8. Disturbance recorder
measurement modes include DFT, RMS and peak-
The IED is provided with a disturbance recorder
to-peak. In addition, the maximum demand
featuring up to 12 analog and 64 binary signal
current with time stamp is separately recorded.
channels. The analog channels can be set to
By default, the records are stored in a non-volatile
record either the waveform or the trend of the
memory.
currents and voltage measured.

The analog channels can be set to trigger the 11. Condition monitoring
recording function when the measured value falls The condition monitoring functions of the IED
below or exceeds the set values. The binary constantly monitors the performance and the
signal channels can be set to start a recording on condition of the circuit breaker. The monitoring
the rising or the falling edge of the binary signal or comprises the spring charging time, SF6 gas
both. pressure, the travel-time and the inactivity time of
the circuit breaker.
By default, the binary channels are set to record
external or internal IED signals, for example the The monitoring functions provide operational
start or trip signals of the IED stages, or external circuit breaker history data, which can be used for
blocking or control signals. Binary IED signals scheduling preventive circuit breaker maintenance.
such as a protection start or trip signal, or an
external IED control signal over a binary input can
be set to trigger the recording. The recorded 12. Trip-circuit supervision
information is stored in a non-volatile memory and The trip-circuit supervision continuously monitors
can be uploaded for subsequent fault analysis. the availability and operability of the trip circuit. It
provides open-circuit monitoring both when the
circuit breaker is in its closed and in its open
9. Event log position. It also detects loss of circuit-breaker
To collect sequence-of-events (SoE) information, control voltage.
the IED incorporates a non-volatile memory with a
capacity of storing 1024 events with associated
time stamps. The non-volatile memory retains its 13. Self-supervision
data also in case the IED temporarily loses its The IED’s built-in self-supervision system
auxiliary supply. The event log facilitates detailed continuously monitors the state of the IED
pre- and post-fault analyses of feeder faults and hardware and the operation of the IED software.
disturbances. The increased capacity to process Any fault or malfunction detected is used for
and store data and events in the IED offers alerting the operator.
prerequisites to support the growing information
A permanent IED fault will block the protection
demand of future network configurations.
functions to prevent incorrect operation.
The SoE information can be accessed locally via
the user interface on the IED front panel or 14. Fuse failure supervision
remotely via the communication interface of the The fuse failure supervision detects failures
IED. The information can further be accessed, between the voltage measurement circuit and the
either locally or remotely, using the web-browser IED. The failures are detected by the negative-
based user interface. sequence based algorithm or by the delta voltage
and delta current algorithm. Upon the detection of
10. Recorded data a failure the fuse failure supervision function
The IED has the capacity to store the records of activates an alarm and blocks voltage-dependent
128 latest fault events. The records enable the protection functions from unintended operation.
user to analyze the power system events. Each

ABB 13
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

15. Current circuit supervision The residual current input and the phase-current
Current circuit supervision is used for detecting inputs are rated 1/5 A. The three phase-voltage
faults in the current transformer secondary inputs and the residual-voltage input covers the
circuits. On detecting of a fault the current circuit rated voltages 60-210 V. Both phase-to-phase
supervision function activates an alarm LED and voltages and phase-to-earth voltages can be
blocks certain protection functions to avoid connected.
unintended operation. The current circuit
supervision function calculates the sum of the The phase-current input 1 A or 5 A, the residual-
phase currents from the protection cores and current input 1 A or 5 A, and the rated voltage of
compares the sum with the measured single the residual voltage input are selected in the IED
reference current from a core balance current software. In addition, the binary input thresholds
transformer or from separate cores in the phase 18…176 V DC are selected by adjusting the IED’s
current transformers. parameter settings.

All binary inputs and outputs contacts are freely


16. Access control configurable with the signal matrix or application
To protect the IED from unauthorized access and configuration functionality of PCM600.
to maintain information integrity, the IED is
provided with a four-level, role-based As an option for standard configurations B the
authentication system with administrator- IED offers six RTD inputs and two mA inputs. By
programmable individual passwords for the means of the optional RTD/mA module the IED
viewer, operator, engineer and administrator level. can measure up to eight analog signals such as
The access control applies to the front-panel user temperature, pressure and tap changer position
interface, the web-browser based user interface values via the six RTD inputs or the two mA
and the PCM600 tool. inputs using transducers. The values can, apart
from measuring and monitoring purposes, be
used for tripping and alarm purposes using the
17. Inputs and outputs offered optional multipurpose protection functions.
Depending on the standard configuration
selected, the IED is equipped with three phase- Please refer to the Input/output overview table
voltage inputs and one residual current input or and the terminal diagrams for more detailed
three phase current inputs, one residual-current information about the inputs and outputs.
input and three phase voltage inputs.

Table 4. Input/output overview

Standard Analog inputs Binary inputs/outputs


configuration
CT VT RTD inputs mA inputs BI BO

A - 5 - – 12 10

B1) 4 3 62) 22) 8 (14)3) 10 (13)3)

1) The optional I/O module and the optional RTD/mA modules are mutually exclusive
2) Optional
3) With optional binary I/O module ( )

14 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

18. Station communication The self-healing Ethernet ring solution enables a


The IED supports a range of communication cost efficient communication ring controlled by a
protocols including IEC 61850, IEC 60870-5-103, managed switch with rapid spanning tree protocol
Modbus ® and DNP3. Operational information and (RSTP) support to be created. The managed
controls are available through these protocols. switch controls the consistency of the loop,
However, some communication functionality, for routes the data and corrects the data flow in case
example, horizontal communication between the of a communication disturbance. The IEDs in the
IEDs, is only enabled by the IEC 61850 ring topology act as unmanaged switches
communication protocol. forwarding unrelated data traffic. The Ethernet
ring solution supports the connection of up to
The IEC 61850 communication implementation thirty 615 series IEDs. If more than 30 IEDs are to
supports all monitoring and control functions. be connected, it is recommended that the
Additionally, parameter settings, disturbance network is split into several rings with no more
recordings and fault records can be accessed than 30 IEDs per ring. The self-healing Ethernet
using the IEC 61850 protocol. Disturbance ring solution avoids single point of failure
recordings are available to any Ethernet-based concerns and improves the reliability of the
application in the standard COMTRADE file communication. The solution can be applied for
format. The IED supports simultaneous event the Ethernet-based IEC 61850, Modbus and
reporting to five different clients on the station DNP3 protocols.
bus.
All communication connectors, except for the
The IED can send binary signals to other IEDs (so front port connector, are placed on integrated
called horizontal communication) using the IEC optional communication modules. The IED can be
61850-8-1 GOOSE (Generic Object Oriented connected to Ethernet-based communication
Substation Event) profile. Binary GOOSE systems via the RJ-45 connector (100Base-TX) or
messaging can, for example, be employed for the fibre-optic LC connector (100Base-FX). If
protection and interlocking-based protection connection to a serial bus is required, the 10-pin
schemes. The IED meets the GOOSE RS-485 screw-terminal or the fibre-optic ST
performance requirements for tripping connector can be used.
applications in distribution substations, as defined
by the IEC 61850 standard. Further, the IED Modbus implementation supports RTU, ASCII and
supports the sending and receiving of analog TCP modes. Besides standard Modbus
values using GOOSE messaging. Analog GOOSE functionality, the IED supports retrieval of time-
messaging enables fast transfer of analog stamped events, changing the active setting
measurement values over the station bus, thus group and uploading of the latest fault records. If
facilitating for example sharing of RTD input a Modbus TCP connection is used, five clients
values, such as surrounding temperature values, can be connected to the IED simultaneously.
to other IED applications. In REU615 analog Further, Modbus serial and Modbus TCP can be
GOOSE messaging is employed in control used in parallel, and if required both IEC 61850
schemes of parallel running transformers where and Modbus protocols can be run simultaneously.
measured values are exchanged between the
IEDs. The IEC 60870-5-103 implementation supports
two parallel serial bus connections to two
For a self-healing Ethernet solution the IED offers different masters. Besides basic standard
an optional fibre-optic communication module functionality, the IED supports changing of the
providing two optical and one galvanic Ethernet active setting group and uploading of disturbance
network interfaces. Alternatively, the IED features recordings in IEC 60870-5-103 format.
an optional galvanic communication module with
two galvanic and one optical Ethernet network DNP3 supports both serial and TCP modes for
interfaces or three galvanic interfaces. The third connection to one master. Further, changing of
Ethernet interface provides connectivity of any the active setting group is supported.
other Ethernet devices to an IEC 61850 station
When the IED uses the RS-485 bus for the serial
bus inside of a switchgear bay.
communication, both two- and four wire

ABB 15
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

connections are supported. Termination and pull- With special time synchronization wiring:
up/down resistors can be configured with jumpers • IRIG-B (Inter-Range Instrumentation Group -
on the communication card so external resistors Time Code Format B)
are not needed.

The IED supports the following time In addition, the IED supports time synchronization
synchronization methods with a time-stamping via the following serial communication protocols:
resolution of 1 ms: • Modbus
• DNP3
Ethernet-based: • IEC 60870-5-103
• SNTP (Simple Network Time Protocol)

Client A Client B

Network

Network

Managed Ethernet switch Managed Ethernet switch


with RSTP support with RSTP support

RED615 REF615 RET615 REU615 REM615

GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V3 EN

Figure 7. Self-healing Ethernet ring solution

16 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 5. Supported station communication interfaces and protocols

Interfaces/Protocols Ethernet Serial

100BASE-TX RJ-45 100BASE-FX LC RS-232/RS-485 Fibre-optic ST

IEC 61850 ● ● - -

MODBUS RTU/ASCII - - ● ●

MODBUS TCP/IP ● ● - -

DNP3 (serial) - - ● ●

DNP3 TCP/IP ● ● - -

IEC 60870-5-103 - - ● ●
● = Supported

ABB 17
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

19. Technical data

Table 6. Dimensions

Description Value

Width frame 177 mm

case 164 mm

Height frame 177 mm (4U)

case 160 mm

Depth 201 mm (153 + 48 mm)

Weight complete IED 4.1 kg

plug-in unit only 2.1 kg

Table 7. Power supply

Description Type 1 Type 2

Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 24, 30, 48, 60 V DC
60 Hz

48, 60, 110, 125, 220, 250 V DC

Maximum interruption time in the 50 ms at Unrated


auxiliary DC voltage without
resetting the IED

Uauxvariation 38...110% of Un (38...264 V AC) 50...120% of Un (12...72 V DC)

80...120% of Un (38.4...300 V DC)

Start-up threshold 19.2 V DC (24 V DC * 80%)

Burden of auxiliary voltage supply DC < 12.0 W (nominal)/< 18.0 W (max) DC < 12.0 W (nominal)/< 18.0 W (max)
under quiescent (Pq)/operating AC< 16.0 W (nominal)/< 21.0W (max)
condition

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)

Fuse type T4A/250 V

18 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 8. Energizing inputs

Description Value

Rated frequency 50/60 Hz ± 5 Hz

Current inputs Rated current, In 1/5 A1)

Thermal withstand
capability:

• Continuously 20 A

• For 1 s 500 A

Dynamic current withstand:

• Half-wave value 1250 A

Input impedance <20 mΩ

Voltage inputs Rated voltage 60...210 V AC

Voltage withstand:

• Continuous 240 V AC

• For 10 s 360 V AC

Burden at rated voltage <0.05 VA

1) Residual current and/or phase current

Table 9. Binary inputs

Description Value

Operating range ±20% of the rated voltage

Rated voltage 24...250 V DC

Current drain 1.6...1.9 mA

Power consumption 31.0...570.0 mW

Threshold voltage 18...176 V DC

Reaction time 3 ms

ABB 19
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 10. RTD/mA measurement (XRGGIO130)

Description Value

RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760)
sensors 250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427

Supported resistance
range 0...2 kΩ

Maximum lead
resistance (three-
wire measurement) 25 Ω per lead

Isolation 2 kV (inputs to protective earth)

Response time <4 s

RTD/resistance
sensing current Maximum 0.33 mA rms

Operation accuracy Resistance Temperature

± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C

mA inputs Supported current


range 0…20 mA

Current input
impedance 44 Ω ± 0.1%

Operation accuracy ±0.5% or ±0.01 mA

Table 11. Signal output X100: SO1

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/ 1 A/0.25 A/0.15 A


R<40 ms

Minimum contact load 100 mA at 24 V AC/DC

20 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 12. Signal outputs and IRF output

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 15 A

Breaking capacity when the control-circuit time constant L/ 1 A/0.25 A/0.15 A


R<40 ms, at 48/110/220 V DC

Minimum contact load 10 mA at 5 V AC/DC

Table 13. Double-pole power output relays with TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/ 5 A/3 A/1 A


R<40 ms, at 48/110/220 V DC (two contacts connected in
series)

Minimum contact load 100 mA at 24 V AC/DC

Trip-circuit supervision (TCS):

• Control voltage range 20...250 V AC/DC

• Current drain through the supervision circuit ~1.5 mA

• Minimum voltage over the TCS contact 20 V AC/DC (15...20 V)

Table 14. Single-pole power output relays

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/ 5 A/3 A/1 A


R<40 ms, at 48/110/220 V DC

Minimum contact load 100 mA at 24 V AC/DC

Table 15. Front port Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

Front TCP/IP protocol Standard Ethernet CAT 5 cable with RJ-45 connector 10 MBits/s

ABB 21
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 16. Station communication link, fibre-optic

Connector Fibre type1) Wave length Max. distance Permitted path attenuation2)

LC MM 62.5/125 or 50/125 1300 nm 2 km <8 dB


μm glass fibre core

ST MM 62.5/125 or 50/125 820-900 nm 1 km <11 dB


μm glass fibre core

1) (MM) multi-mode fibre, (SM) single-mode fibre


2) Maximum allowed attenuation caused by connectors and cable together

Table 17. IRIG-B

Description Value

IRIG time code format B004, B0051)

Isolation 500V 1 min.

Modulation Unmodulated

Logic level TTL Level

Current consumption 2...4 mA

Power consumption 10...20 mW

1) According to 200-04 IRIG -standard

Table 18. Lens sensor and optical fibre for arc protection

Description Value

Fibre-optic cable including lens 1.5 m, 3.0 m or 5.0 m

Normal service temperature range of the lens -40...+100°C

Maximum service temperature range of the lens, max 1 h +140°C

Minimum permissible bending radius of the connection 100 mm


fibre

Table 19. Degree of protection of flush-mounted IED

Description Value

Front side IP 54

Rear side, connection terminals IP 20

Table 20. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude Up to 2000 m

Transport and storage temperature range -40...+85ºC

22 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 21. Environmental tests

Description Type test value Reference

Dry heat test • 96 h at +55ºC IEC 60068-2-2


• 16 h at +85ºC1)

Dry cold test • 96 h at -25ºC IEC 60068-2-1


• 16 h at -40ºC

Damp heat test • 6 cycles (12 h + 12 h) at +25°C… IEC 60068-2-30


+55°C, humidity >93%

Change of temperature test • 5 cycles (3 h + 3 h) IEC60068-2-14


at -25°C...+55°C

Storage test • 96 h at -40ºC IEC 60068-2-1


• 96 h at +85ºC IEC 60068-2-2

1) For IEDs with an LC communication interface the maximum operating temperature is +70 o C

ABB 23
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 22. Electromagnetic compatibility tests

Description Type test value Reference

1 MHz/100 kHz burst disturbance IEC 61000-4-18


test: IEC 60255-22-1, class III
IEEE C37.90.1-2002

• Common mode 2.5 kV

• Differential mode 2.5 kV

3 MHz, 10 MHz and 30 MHz burst IEC 61000-4-18


disturbance test: IEC 60255-22-1, class III

• Common mode 2.5 kV

Electrostatic discharge test: IEC 61000-4-2


IEC 60255-22-2
IEEE C37.90.3-2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference test:

10 V (rms) IEC 61000-4-6


f=150 kHz...80 MHz IEC 60255-22-6, class III

10 V/m (rms) IEC 61000-4-3


f=80...2700 MHz IEC 60255-22-3, class III

10 V/m ENV 50204


f=900 MHz IEC 60255-22-3, class III

20 V/m (rms) IEEE C37.90.2-2004


f=80...1000 MHz

Fast transient disturbance test: IEC 61000-4-4


IEC 60255-22-4
IEEE C37.90.1-2002

• All ports 4 kV

Surge immunity test: IEC 61000-4-5


IEC 60255-22-5

• Communication 1 kV, line-to-earth

• Other ports 4 kV, line-to-earth


2 kV, line-to-line

Power frequency (50 Hz) magnetic IEC 61000-4-8


field immunity test:

• Continuous 300 A/m


• 1...3 s 1000 A/m

Pulse magnetic field immunity test: 1000 A/m IEC 61000-4-9


6.4/16 µs

Damped oscillatory magnetic field IEC 61000-4-10


immunity test:

• 2s 100 A/m

• 1 MHz 400 transients/s

24 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 22. Electromagnetic compatibility tests, continued


Description Type test value Reference

Voltage dips and short interruptions: 30%/10 ms IEC 61000-4-11


60%/100 ms
60%/1000 ms
>95%/5000 ms

Power frequency immunity test: Binary inputs only IEC 61000-4-16


• Common mode IEC 60255-22-7, class A
300 V rms
• Differential mode

150 V rms

Conducted common mode 15 Hz...150 kHz IEC 61000-4-16


disturbances: Test level 3 (10/1/10 V rms)

Emission tests: EN 55011, class A


IEC 60255-25

• Conducted

0.15-0.50 MHz < 79 dB(µV) quasi peak


< 66 dB(µV) average

0.5-30 MHz < 73 dB(µV) quasi peak


< 60 dB(µV) average

• Radiated

30-230 MHz < 40 dB(µV/m) quasi peak, measured at


10 m distance

230-1000 MHz < 47 dB(µV/m) quasi peak, measured at


10 m distance

Table 23. Insulation tests

Description Type test value Reference

Dielectric tests 2 kV, 50 Hz, 1 min IEC 60255-5 and


500 V, 50 Hz, 1 min, communication IEC 60255-27

Impulse voltage test 5 kV, 1.2/50 μs, 0.5 J IEC 60255-5 and
1 kV, 1.2/50 μs, 0.5 J, communication IEC 60255-27

Insulation resistance measurements >100 MΏ, 500 V DC IEC 60255-5 and


IEC 60255-27

Protective bonding resistance <0.1 Ώ, 4 A, 60 s IEC 60255-27

Table 24. Mechanical tests

Description Reference Requirement

Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc) Class 2


IEC 60255-21-1

Shock and bump test IEC 60068-2-27 (test Ea shock) Class 2


IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2

Seismic test IEC 60255-21-3 Class 2

ABB 25
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 25. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)


EN 60255-1 (2009)

Table 26. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)


EN 60255-26 (2007)

Table 27. RoHS compliance

Description

Complies with RoHS directive 2002/95/EC

26 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Protection functions

Table 28. Three-phase non-directional overcurrent protection (PHxPTOC)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn


±2 Hz

PHLPTOC ±1.5% of the set value or ±0.002 x In

PHHPTOC ±1.5% of set value or ±0.002 x In


and (at currents in the range of 0.1…10 x In)
PHIPTOC ±5.0% of the set value
(at currents in the range of 10…40 x In)

Start time 1)2) Minimum Typical Maximum

PHIPTOC:
IFault = 2 x set Start value 16 ms 19 ms 23 ms
IFault = 10 x set Start value
11 ms 12 ms 14 ms

PHHPTOC and PHLPTOC:


IFault = 2 x set Start value
22 ms 24 ms 25 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0
x In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact

ABB 27
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) main settings

Parameter Function Value (Range) Step

Start Value PHLPTOC 0.05...5.00 x In 0.01

PHHPTOC 0.10...40.00 x In 0.01

PHIPTOC 1.00...40.00 x In 0.01

Time multiplier PHLPTOC 0.05...15.00 0.01

PHHPTOC 0.05...15.00 0.01

Operate delay time PHLPTOC 40...200000 ms 10

PHHPTOC 40...200000 ms 10

PHIPTOC 20...200000 ms 10

Operating curve type1) PHLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15,
17, 18, 19

PHHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time

1) For further reference please refer to the Operating characteristics table

Table 30. Three-phase overvoltage protection (PHPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 x set Start value 22 ms 24 ms 26 ms

Reset time < 40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 x Un, Voltage before fault = 0.9 x U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 x U n, Start value multiples in range of 1.10 to 2.00

28 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 31. Three-phase overvoltage protection (PHPTOV) main settings

Parameter Function Value (Range) Step

Start value PHPTOV 0.05...1.60 x Un 0.01

Time multiplier PHPTOV 0.05...15.00 0.01

Operate delay time PHPTOV 40...300000 ms 10

Operating curve type1) PHPTOV Definite or inverse time


Curve type: 5, 15, 17, 18, 19, 20

1) For further reference please refer to the Operating characteristics table

Table 32. Three phase undervoltage protection (PHPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 0.9 x set Start value 62 ms 64 ms 66 ms

Reset time < 40 ms

Reset ratio Depends on the set Relative hysteresis

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 x Un, Voltage before fault = 1.1 x U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20

Table 33. Three-phase undervoltage protection (PHPTUV) main settings

Parameter Function Value (Range) Step

Start value PHPTUV 0.05...1.20 x Un 0.01

Time multiplier PHPTUV 0.05...15.00 0.01

Operate delay time PHPTUV 60...300000 ms 10

Operating curve type1) PHPTUV Definite or inverse time


Curve type: 5, 15, 21, 22, 23

1) For further reference please refer to the Operating characteristics table

ABB 29
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 34. Positive-sequence undervoltage protection (PSPTUV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 0.99 x set Start


51 ms 53 ms 54 ms
value
43 ms 45 ms 46 ms
UFault = 0.9 x set Start value

Reset time < 40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x U n, f n = 50 Hz, positive sequence undervoltage with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 35. Positive-sequence undervoltage protection (PSPTUV) main settings

Parameter Function Value (Range) Step

Start value PSPTUV 0.010...1.200 x Un 0.001

Operate delay time PSPTUV 40...120000 ms 10

Voltage block value PSPTUV 0.01...1.0 x Un 0.01

Table 36. Negative-sequence overvoltage protection (NSPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz

±1.5% of the set value or ±0.002 × Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 × set Start value 33 ms 35 ms 37 ms


UFault = 2.0 × set Start value 24 ms 26 ms 28 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase
angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

30 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 37. Negative-sequence overvoltage protection (NSPTOV) main settings

Parameter Function Value (Range) Step

Start value NSPTOV 0.010...1.000 x Un 0.001

Operate delay time NSPTOV 40...120000 ms 1

Table 38. Frequency protection (FRPFRQ)

Characteristic Value

Operation accuracy f>/f< ±10 mHz

df/dt ±100 mHz/s (in range |df/dt| < 5 Hz/s)


± 2.0% of the set value (in range 5 Hz/
s < |df/dt| < 15 Hz/s)

Start time f>/f< < 80 ms

df/dt < 120 ms

Reset time < 150 ms

Operate time accuracy ±1.0% of the set value or ±30 ms

Table 39. Frequency protection (FRPFRQ) main settings

Parameter Values (Range) Unit Step Default Description

Operation mode 1=Freq< 1=Freq< Frequency protection


2=Freq> operation mode
3=df/dt selection
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt

Start value Freq> 0.900...1.200 xFn 0.001 1.050 Frequency start


value overfrequency

Start value Freq< 0.800...1.100 xFn 0.001 0.950 Frequency start


value underfrequency

Start value df/dt -0.200...0.200 xFn /s 0.005 0.010 Frequency start


value rate of change

Operate Tm Freq 80...200000 ms 10 200 Operate delay time


for frequency

Operate Tm df/dt 120...200000 ms 10 400 Operate delay time


for frequency rate of
change

ABB 31
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 40. Thermal overload protection, two time constants (T2PTTR)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn


±2 Hz

Current measurement: ±1.5% of the set value or ±0.002


x In (at currents in the range of 0.01...4.00 x In)

Operate time accuracy1) ±2.0% of the theoretical value or ±0.50 s

1) Overload current > 1.2 x Operate level temperature

Table 41. Thermal overload for protection, two time constants (T2PTTR) main settings

Parameter Function Value (Range) Step

Temperature rise T2PTTR 0.0...200.0oC 0.1

Max temperature T2PTTR 0.0...200.0oC 0.1

Operate temperature T2PTTR 80.0...120.0 % 0.1

Weighting factor p T2PTTR 0.00...1.00 0.01

Short time constant T2PTTR 6...60000 s 1

Current reference T2PTTR 0.05...4.00 x In 0.01

Operation T2PTTR Off -


On

Table 42. Residual overvoltage protection (ROVPTOV)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz

±1.5% of the set value or ±0.002 x Un

Start time1)2) Minimum Typical Maximum

UFault = 1.1 x set Start value 55 ms 56 ms 58 ms

Reset time < 40 ms

Reset ratio Typical 0.96

Retardation time < 35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

1) Residual voltage before fault = 0.0 x U n , f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

32 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 43. Residual overvoltage protection (ROVPTOV) main settings

Parameter Function Value (Range) Step

Start value ROVPTOV 0.010...1.000 x Un 0.001

Operate delay time ROVPTOV 40...300000 ms 1

Table 44. Arc protection (ARCSARC)

Characteristic Value

Operation accuracy ±3% of the set value or ±0.01 x In

Operate time Minimum Typical Maximum

Operation mode = "Light 9 ms 10 ms 12 ms


only"

Reset time < 40 ms

Reset ratio Typical 0.96

Table 45. Arc protection (ARCSARC) main settings

Parameter Function Value (Range) Step

Phase start value ARCSARC 0.50...40.00 x In 0.01


(Operating phase current)

Ground start value ARCSARC 0.05...8.00 x In 0.01


(Operating residual current)

Operation mode ARCSARC 2=Light only


3=BI controlled

Table 46. Multipurpose protection (MAPGAPC)

Characteristic Value

Operation accuracy ±1.0% of the set value or ±20 ms

Table 47. Multipurpose analog protection (MAPGAPC) main settings

Parameter Function Value (Range) Step

Start value MAPGAPC -10000.0...10000.0 0.1

Operate delay time MAPGAPC 0...200000 ms 100

Operation mode MAPGAPC Over -


Under

ABB 33
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 48. Load shedding (LSHDPFRQ)

Characteristic Value

Operation accuracy f< ±10 mHz

df/dt ±100 mHz/s (in range |df/dt| < 5 Hz/s)


± 2.0% of the set value (in range 5 Hz/
s < |df/dt| < 15 Hz/s)

f< < 80 ms

df/dt < 120 ms

Reset time < 150 ms

Operate time accuracy ±1.0% of the set value or ±30 ms

Table 49. Load shedding (LSHDPFRQ) main settings

Parameter Function Value (Range) Step

Load shed mode LSHDPFRQ Freq< -


Freq< AND df/dt
Freq< OR df/dt

Restore mode LSHDPFRQ Disabled -


Auto
Manual

Start value Freq LSHDPFRQ 0.800...1.200 x Fn 0.001

Start value df/dt LSHDPFRQ -0.200...-0.005 x Fn 0.005

Operate Tm Freq LSHDPFRQ 80...200000 ms 10

Operate Tm df/dt LSHDPFRQ 120...200000 ms 10

Restore start Val LSHDPFRQ 0.800...1.200 x Fn 0.001

Restore delay time LSHDPFRQ 80...200000 ms 10

34 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 50. Operation characteristics

Parameter Values (Range)

Operating curve type 1=ANSI Ext. inv.


2=ANSI Very. inv.
3=ANSI Norm. inv.
4=ANSI Mod inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type

Operating curve type (voltage protection) 5=ANSI Def. Time


15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
21=Inv. Curve A
22=Inv. Curve B
23=Programmable

ABB 35
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Control functions

Table 51. Synchrocheck (SECRSYN)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±1 Hz

Voltage: ±3.0% of the set value or ±0.01 x Un


Frequency: ±10 mHz
Phase angle: ±3°

Reset time < 50 ms

Reset ratio Typical 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

36 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 52. Synchronism and energizing check (SECRSYN) main settings

Parameter Values (Range) Unit Step Default Description

Live dead mode -1=Off 1=Both Dead Energizing check


1=Both Dead mode
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L Any
5=Dead L, Bus Any
6=One Live, Dead
7=Not Both Live

Difference voltage 0.01...0.50 xUn 0.01 0.05 Maximum voltage


difference limit

Difference 0.001...0.100 xFn 0.001 0.001 Maximum


frequency frequency
difference limit

Difference angle 5...90 deg 1 5 Maximum angle


difference limit

Synchrocheck 1=Off 2=Synchronous Synchrocheck


mode 2=Synchronous operation mode
3=Asynchronous

Control mode 1=Continuous 1=Continuous Selection of the


2=Command synchrocheck
command or
continuous
control mode

Dead line value 0.1...0.8 xUn 0.1 0.2 Voltage low-limit


line for energizing
check

Live line value 0.2...1.0 xUn 0.1 0.5 Voltage high-limit


line for energizing
check

Close pulse 200...60000 ms 10 200 Breaker-closing


pulse duration

Max energizing V 0.50...1.15 xUn 0.01 1.05 Maximum voltage


for energizing

Phase shift -180...180 deg 1 180 Correction of


phase difference
between
measured
U_BUS and
U_LINE

Minimum Syn time 0...60000 ms 10 0 Minimum time to


accept
synchronizing

ABB 37
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 52. Synchronism and energizing check (SECRSYN) main settings, continued
Parameter Values (Range) Unit Step Default Description

Maximum Syn 100...6000000 ms 10 2000 Maximum time to


time accept
synchronizing

Energizing time 100...60000 ms 10 100 Time delay for


energizing check

Closing time of CB 40...250 ms 10 60 Closing time of


the breaker

Table 53. Tap changer control with voltage regulator (OLATCC)

Characteristic Value

Operation accuracy1) Depending on the frequency of the current measured: fn


±2 Hz

Differential voltage Ud = ± 0.5% of the measured value or


± 0.005 x Un (in measured voltages < 2.0 x Un)
Operation value = ± 1.5% of the Ud for Us = 1.0 x Un

Operate time accuracy in definite time mode2) + 4.0% / - 0% of the set value

Operate time accuracy in inverse time mode2) + 8.5% / - 0% of the set value
(at theoretical B in range of 1.1…5.0)
Also note fixed minimum operate time (IDMT) 1 s.

Reset ratio for control operation Typical 0.80 (1.20)


Reset ratio for analogue based blockings (except run Typical 0.96 (1.04)
back raise voltage blocking)

1) Default setting values used


2) Voltage before deviation = set Band center voltage.

38 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 54. On-load tap changer control with voltage regulator (OLATCC) main settings

Parameter Function Value (Range) Step

Band center voltage OLATCC 0.000...2.000 x Un 0.001

Control delay time 1 OLATCC 1000...300000 ms 100

Control delay time 2 OLATCC 1000...300000 ms 100

Line drop V Ris OLATCC 0.0...25.0 % 0.1

Line drop V React OLATCC 0.0...25.0 % 0.1

Load phase angle OLATCC -89...89 deg 1

Stability factor OLATCC 0.0...70.0 % 0.1

Auto parallel mode OLATCC Auto master -


Auto follower
NRP
MCC

Operation mode OLATCC Manual -


Auto single
Auto parallel
Input control

Delay characteristics OLATCC Inverse time -


Definite time

LCT pulse time OLATCC 500...10000 ms 100

Band width voltage OLATCC 1.20...18.00 % Un 0.01

Custom Man blocking OLATCC 1=Custom disabled -


2=OC
3=UV
4=OC, UV
5=EXT
6=OC, EXT
7=UV, EXT
8=OC, UV, EXT

Load current limit OLATCC 0.10...5.00 x In 0.01

Block lower voltage OLATCC 0.10...1.20 x Un 0.01

Runback raise volt OLATCC 0.80...2.40 x In 0.01

Cir current limit OLATCC 0.10...5.00 x In 0.01

Lower block tap OLATCC -36...36 -

Raise block tap OLATCC -36...36 -

LDC limit OLATCC 0.00...2.00 x Un 0.01

LDC enable OLATCC False -


True

Follower delay time OLATTC 6...20 s -

ABB 39
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Measurement functions

Table 55. Three-phase current measurement (CMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: fn


±2 Hz

±0.5% or ±0.002 x In
(at currents in the range of 0.01...4.00 x In)

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 56. Current sequence components (CSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the current measured: f/fn


= ±2 Hz

±1.0% or ±0.002 x In
at currents in the range of 0.01...4.00 x In

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

Table 57. Three-phase voltage measurement (VMMXU)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz
At voltages in range 0.01…1.15 x Un

±0.5% or ±0.002 x Un

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 58. Voltage sequence components (VSMSQI)

Characteristic Value

Operation accuracy Depending on the frequency of the voltage measured: fn


±2 Hz
At voltages in range 0.01…1.15 x Un

±1.0% or ±0.002 x Un

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

40 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 59. Three-phase power and energy (PEMMXU)

Characteristic Value

Operation accuracy At all three currents in range 0.10…1.20 x In


At all three voltages in range 0.50…1.15 x Un
At the frequency fn ±1 Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71

±1.5% for power (S, P and Q)


±0.015 for power factor
±1.5% for energy

Suppression of harmonics DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,…

Table 60. RTD/mA measurement (XRGGIO130)

Description Value

RTD inputs Supported RTD 100 Ω platinum TCR 0.00385 (DIN 43760)
sensors 250 Ω platinum TCR 0.00385
100 Ω nickel TCR 0.00618 (DIN 43760)
120 Ω nickel TCR 0.00618
250 Ω nickel TCR 0.00618
10 Ω copper TCR 0.00427

Supported resistance
range 0...2 kΩ

Maximum lead
resistance (three-
wire measurement) 25 Ω per lead

Isolation 2 kV (inputs to protective earth)

Response time <4 s

RTD/resistance
sensing current Maximum 0.33 mA rms

Operation accuracy Resistance Temperature

± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C

mA inputs Supported current


range 0…20 mA

Current input
impedance 44 Ω ± 0.1%

Operation accuracy ±0.5% or ±0.01 mA

Table 61. Frequency measurement (FMMXU)

Characteristic Value

Operation accuracy ±10 mHz


(in measurement range 35 - 75 Hz)

ABB 41
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Supervision functions

Table 62. Current circuit supervision (CCRDIF)

Characteristic Value

Operate time1) < 30 ms

1) Including the delay of the output contact.

Table 63. Current circuit supervision (CCRDIF) main settings

Parameter Values (Range) Unit Description

Start value 0.05...0.20 x In Minimum operate current


differential level

Maximum operate current 1.00...5.00 x In Block of the function at


high phase current

Table 64. Fuse failure supervision (SEQRFUF)

Characteristic Value

Operate time1)

• NPS function UFault = 1.1 x set Neg Seq < 33 ms


voltage Lev
UFault = 5.0 x set Neg Seq < 18 ms
voltage Lev

• Delta function ΔU = 1.1 x set Voltage < 30 ms


change rate
ΔU = 2.0 x set Voltage < 24 ms
change rate

1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements

42 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

20. Local HMI default single line diagram. The SLD view can also
The IED is available with two optional displays, a be accessed using the web-browser based user
large one and a small one. The large display is interface. The default SLD can be modified
suited for IED installations where the front panel according to user requirements by using the
user interface is frequently used and a single line graphical display editor in PCM600.
diagram is required. The small display is suited for
remotely controlled substations where the IED is The local HMI includes a push button (L/R) for
only occasionally accessed locally via the front local/remote operation of the IED. When the IED
panel user interface. is in the local mode, the IED can be operated only
by using the local front panel user interface. When
Both LCD displays offer front-panel user interface the IED is in the remote mode, the IED can
functionality with menu navigation and menu execute commands sent from a remote location.
views. However, the large display offers increased The IED supports the remote selection of local/
front-panel usability with less menu scrolling and remote mode via a binary input. This feature
improved information overview. In addition, the facilitates, for example, the use of an external
large display includes a user-configurable single switch at the substation to ensure that all IEDs
line diagram (SLD) with position indication for the are in the local mode during maintenance work
associated primary equipment. Depending on the and that the circuit breakers cannot be operated
chosen standard configuration, the IED displays remotely from the network control centre.
the related measuring values, apart from the

IECA070904 V3 EN IECA070901 V3 EN

Figure 8. Small display Figure 9. Large display

Table 65. Small display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6x12 pixels) 5 20

Large, variable width (13x14 pixels) 4 8 or more

1) Depending on the selected language

ABB 43
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 66. Large display

Character size1) Rows in the view Characters per row

Small, mono-spaced (6x12 pixels) 10 20

Large, variable width (13x14 pixels) 8 8 or more

1) Depending on the selected language

21. Mounting methods Mounting methods:


By means of appropriate mounting accessories
the standard IED case for the 615 series IED can • Flush mounting
be flush mounted, semi-flush mounted or wall • Semi-flush mounting
mounted. The flush mounted and wall mounted • Semi-flush mounting in a 25° tilt
IED cases can also be mounted in a tilted position • Rack mounting
(25°) using special accessories. • Wall mounting
• Mounting to a 19" equipment frame
Further, the IEDs can be mounted in any standard • Mounting with a RTXP 18 test switch to a
19” instrument cabinet by means of 19” mounting 19" rack
panels available with cut-outs for one or two
IEDs. Alternatively, the IED can be mounted in 19” Panel cut-out for flush mounting:
instrument cabinets by means of 4U Combiflex • Height: 161.5±1 mm
equipment frames. • Width: 165.5±1 mm

For the routine testing purposes, the IED cases


can be equipped with test switches, type RTXP
18, which can be mounted side by side with the
IED cases.

190

6
18

164
177 25°
160
160

177

230
177

107
133
98
48
1 53
103
IECA070902 V4 EN

IECA070900 V4 EN IECA070903 V4 EN
Figure 12. Semi-flush with a 25º
Figure 10. Flush mounting Figure 11. Semi-flush mounting tilt

44 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

22. IED case and IED plug-in unit on the upper part of the plug-in-unit. An order
For safety reasons, the IED cases for current number label is placed on the side of the plug-in
measuring IEDs are provided with automatically unit as well as inside the case. The order number
operating contacts for short-circuiting the CT consists of a string of codes generated from the
secondary circuits when a IED unit is withdrawn IED's hardware and software modules.
from its case. The IED case is further provided
with a mechanical coding system preventing Use the ordering key information to generate the
current measuring IED units from being inserted order number when ordering complete IEDs.
into a IED case for a voltage measuring IED unit
and vice versa, i.e. the IED cases are assigned to
a certain type of IED plug-in unit.

23. Selection and ordering data


The IED type and serial number label identifies the
protection IED. The label is placed above the HMI

H B U BCCAHBCC1BBN1XE

# Description
1 IED
615 series IED (including case) H
615 series IED (including case) with test switch, wired and in -
K
stalled in a 19” equipment panel
615 series IED (including case) with test switch, wired and in -
stalled in a mounting bracket for CombiFlex rack mounting (RGHT L
19” 4U variant C)
2 Standard
IEC B
3 Main application
Voltage protection and control U
GUID-AD8D5903-41C6-4187-A02A-1F5C3407E335 V2 EN

The standard configuration determines the I/O hardware and available options. HBU BCCAH NBA1ABN1XE
The example below shows standard configuration “B” with chosen options.

# Description
4-8 Standard configurations, analog and binary I/O options
Standard configuration descriptions in short:
A = Voltage and frequency based protection and measurement functions,
synchro-check, load shedding and CB control
B = Automatic voltage regulator, CB control and with the optional I/O module
control of one network object
Std. conf. I/O options
A 5U + 12 BI + 10 BO AEAAD
B 4I (Io 1/5 A) + 3U + 8 BI + 10 BO BCAAH
B 4I (Io 1/5 A) + 3U + 14 BI + 13 BO BCABB*
B 4I (Io 1/5 A) + 3U + 6 RTD + 2 mA + 8 BI + 10 BO BCCAH

* = The optional I/O module included


GUID-D50DDBD0-0BBE-4347-9FBB-1BFD2BE7ECB5 V2 EN

ABB 45
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

The communication module hardware determines the available communication proto - HBUBCCAH BC C1BBN1XE
cols. Choose the hardware from one of the rows below to define the digits # 9-10.

# Description
9 Communication modules (Serial/Ethernet)
-
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-FX
10 AA
(1 x LC)
Serial RS-485, incl. an input for IRIG-B + Ethernet 100Base-TX (1
AB
x RJ-45)
Serial RS-485, incl. an input for IRIG-B AN
Serial glass fibre (ST), incl. an RS-485 connector and an input for
BN
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (1 x RJ-45) + Serial
RS-485 connector, RS-232/485 D-Sub 9 connector + input for BB
IRIG-B (cannot be combined with arc protection)
Serial glass fibre (ST) + Ethernet 100Base-TX (3 x RJ-45) BD
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (2 x RJ-45
BC
+ 1 x LC)
Serial glass fibre (ST) + Ethernet 100Base-TX and -FX (1 x RJ-45
BE
+ 2 x LC)
Ethernet 100Base-FX (1 x LC) NA
Ethernet 100Base-TX (1 x RJ-45) NB
Ethernet 100Base-TX (2 x RJ-45 + 1 x LC) NC
Ethernet 100Base-TX (3 x RJ-45) ND
Ethernet 100Base-TX and -FX (1 x RJ-45 + 2 x LC) NE
No communication module NN

If serial communication is chosen, please choose a serial communication module including Ethernet (for example “BC”) if a service
bus for PCM600 or the WebHMI is required.
GUID-A54E91E4-EB6B-45BD-9BC7-DA4EE4295CAF V2 EN

HBUBCCAHBC C 1BBN1XE

# Description
11 Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs without a com - A
munication module )
Modbus
B
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + Modbus
C
(for Ethernet or serial + Ethernet communication modules)
IEC 60870-5-103
D
(for serial or Ethernet + serial communication modules)
DNP3
E
(for Ethernet/serial or Ethernet + serial communication modules)
GUID-5B4CE02E-BA34-4AA7-A6E6-8408A3C1763D V2 EN

46 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

HBU BCCAHBCC 1 B B N 1 XE

# Description
12 Language
English 1
English and German 3
English and Swedish 4
English and Spanish 5
English and Russian 6
English and Polish 7
English and Portuguese (Brazilian) 8
English and Italian A
English and French C
English and Czech E
13 Front panel
Small LCD A
Large LCD with single line diagram (SLD) B
14 Option 1

Arc protection (only for std conf “A”, requires a communication


module, cannot be combined with communication modules BN B
or BB)
None N
15 Option 2
None N
16 Power supply
48...250 V DC, 100...240 V AC 1
24...60 V DC 2
17 Version
-
18 Version 4.0 XE
GUID-AC8BE0B1-072C-4907-92D3-3720E344F94E V2 EN

Example code: HBUBCCAHBCC1BBN1XE

Your ordering code:

Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Code
GUID-28A75E3D-BF45-42F0-90D8-B142E3EA28F3 V2 EN

Figure 13. Ordering key for complete IEDs

ABB 47
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

24. Accessories and ordering data

Table 67. Cables

Item Order number

Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5

Cable for optical sensors for arc protection 3.0 m 1MRS120534-3.0

Cable for optical sensors for arc protection 5.0 m 1MRS120534-5.0

Table 68. Mounting accessories

Item Order number

Semi-flush mounting kit 1MRS050696

Wall mounting kit 1MRS050697

Inclined semi-flush mounting kit 1MRS050831

19” rack mounting kit with cut-out for one IED 1MRS050694

19” rack mounting kit with cut-out for two IEDs 1MRS050695

Mounting bracket for one IED with test switch RTXP in 4U Combiflex (RHGT 19” variant C) 2RCA022642P0001

Mounting bracket for one IED in 4U Combiflex (RHGT 19” variant C) 2RCA022643P0001

19” rack mounting kit for one IED and one RTXP18 test switch (the test switch is not 2RCA021952A0003
included in the delivery)

19” rack mounting kit for one IED and one RTXP24 test switch (the test switch is not 2RCA022561A0003
included in the delivery)

Replacement kit for a Strömberg SP_J40 series relay (cut-out in the center of the 2RCA027871A0001
installation plate)

Replacement kit for a Strömberg SP_J40 series relay (cut-out on the left or the right of 2RCA027874A0001
the installation plate)

Replacement kit for two Strömberg SP_J3 series relays 2RCA027880A0001

19” rack replacement kit for Strömberg SP_J3/J6 series relays (one cut-out) 2RCA027894A0001

19” rack replacement kit for Strömberg SP_J3/J6 series relays (two cut-outs) 2RCA027897A0001

Replacement kit for a Strömberg SP_J6 series relay 2RCA027881A0001

Replacement kit for three BBC S_ series relays 2RCA027882A0001

Replacement kit for a SPA 300 series relay 2RCA027885A0001

48 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

25. Tools remotely using a web browser (IE 7.0 IE 8.0 or IE


The IED is delivered as a pre-configured unit. The 9.0). For security reasons, the web-browser
default parameter setting values can be changed based user interface is disabled by default. The
from the front-panel user interface, the web- interface can be enabled with the PCM600 tool or
browser based user interface (WebHMI) or the from the front panel user interface. The
PCM600 tool in combination with the IED-specific functionality of the interface can be limited to read-
connectivity package. only access by means of PCM600.

The Protection and Control IED Manager PCM600 The IED connectivity package is a collection of
is available in two different variants, that is software and specific IED information, which
PCM600 Basic/Engineering and PCM600 enable system products and tools to connect and
Engineering Pro. Depending on the chosen interact with the IED. The connectivity packages
variant, PCM600 offers extensive IED reduce the risk of errors in system integration,
configuration functions such as IED signal minimizing device configuration and set-up times.
configuration, application configuration, graphical Further, the Connectivity Packages for the 615
display configuration including single line diagram series IEDs include a flexible update tool for
configuration, and IEC 61850 communication adding one additional local HMI language to the
configuration including horizontal GOOSE IED. The update tool is activated using PCM600
communication. and enables multiple updates of the additional
HMI language, thus offering flexible means for
When the web-browser based user interface is possible future language updates.
used, the IED can be accessed either locally or

Table 69. Tools

Configuration and setting tools Version

PCM600 2.4 SP1 or later

Web-browser based user interface IE 7.0, IE 8.0 or IE 9.0

REU615 Connectivity Package 4.0 or later

ABB 49
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 70. Supported functions

Function WebHMI PCM600 Basic/ PCM600 Engineering


Engineering Pro

IED parameter setting ● ● ●

Saving of IED parameter settings in


the IED ● ● ●

Signal monitoring ● ● ●

Disturbance recorder handling ● ● ●

Alarm LED viewing ● ● ●

Access control management ● ● ●

IED signal configuration (signal


matrix) - ● ●

Modbus® communication
configuration (communication
management) - ● ●

DNP3 communication configuration


(communication management) - ● ●

IEC 60870-5-103 communication


configuration (communication
management) - ● ●

Saving of IED parameter settings in


the tool - ● ●

Disturbance record analysis - ● ●

XRIO parameter export/import - ● ●

Graphical display configuration - ● ●

Application configuration - ● ●

IEC 61850 communication


configuration, GOOSE
(communication configuration) - - ●

Phasor diagram viewing ● - -

Event viewing ● ● ●

Saving of event data on the user's


PC ● - -
● = Supported

50 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

26. Terminal diagrams

GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN

Figure 14. Terminal diagram of standard configuration A

ABB 51
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN

Figure 15. Terminal diagram of standard configuration B

52 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

27. References The download area on the right hand side of the
The www.abb.com/substationautomation portal web page contains the latest product
offers you information about the distribution documentation, such as technical manual,
automation product and service range. installation manual, operation manual, etc.

You will find the latest relevant information on the The Features and Application tabs contain
REU615 protection IED on the product page. product related information in a compact format.

GUID-2ECAAEFE-CEF1-4A31-97F4-B88FCF66DB8E V1 EN

Figure 16. Product page

ABB 53
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

28. Functions, codes and symbols

Table 71. REU615 functions, codes and symbols

Function IEC 61850 IEC 60617 IEC-ANSI

Protection

Three-phase non-directional overcurrent protection, low


PHLPTOC1 3I> (1) 51P-1 (1)
stage

Three-phase non-directional overcurrent protection,


PHHPTOC1 3I>> (1) 51P-2 (1)
high stage

Three-phase non-directional overcurrent protection,


PHIPTOC1 3I>>> (1) 50P/51P (1)
instantaneous stage

Residual overvoltage protection ROVPTOV1 Uo> (1) 59G (1)

ROVPTOV2 Uo> (2) 59G (2)

ROVPTOV3 Uo> (3) 59G (3)

Three-phase undervoltage protection PHPTUV1 3U< (1) 27 (1)

PHPTUV2 3U< (2) 27 (2)

PHPTUV3 3U< (3) 27 (3)

Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1)

PHPTOV2 3U> (2) 59 (2)

PHPTOV3 3U> (3) 59 (3)

Positive-sequence undervoltage protection PSPTUV1 U1< (1) 47U+ (1)

PSPTUV2 U1< (2) 47U+ (2)

Negative-sequence overvoltage protection NSPTOV1 U2> (1) 47O- (1)

NSPTOV2 U2> (2) 47O- (2)

Frequency protection FRPFRQ1 f>/f<,df/dt (1) 81 (1)

FRPFRQ2 f>/f<,df/dt (2) 81 (2)

FRPFRQ3 f>/f<,df/dt (3) 81 (3)

FRPFRQ4 f>/f<,df/dt (4) 81 (4)

FRPFRQ5 f>/f<,df/dt (5) 81 (5)

FRPFRQ6 f>/f<,df/dt (6) 81 (6)

Three-phase thermal overload protection for power


T2PTTR1 3Ith>T 49T
transformers, two time constants

Master trip TRPPTRC1 Master Trip (1) 94/86 (1)

TRPPTRC2 Master Trip (2) 94/86 (2)

Arc protection ARCSARC1 ARC (1) 50L/50NL (1)

ARCSARC2 ARC (2) 50L/50NL (2)

ARCSARC3 ARC (3) 50L/50NL (3)

54 ABB
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 71. REU615 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Multi-purpose protection MAPGAPC1 MAP (1) MAP (1)

MAPGAPC2 MAP (2) MAP (2)

MAPGAPC3 MAP (3) MAP (3)

MAPGAPC4 MAP (4) MAP (4)

MAPGAPC5 MAP (5) MAP (5)

MAPGAPC6 MAP (6) MAP (6)

Load shedding and restoration LSHDPFRQ1 UFLS/R (1) 81LSH (1)

LSHDPFRQ2 UFLS/R (2) 81LSH (2)

LSHDPFRQ3 UFLS/R (3) 81LSH (3)

LSHDPFRQ4 UFLS/R (4) 81LSH (4)

LSHDPFRQ5 UFLS/R (5) 81LSH (5)

Control

Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB

Disconnector control DCXSWI1 I <-> O DCC (1) I <-> O DCC (1)

DCXSWI2 I <-> O DCC (2) I <-> O DCC (2)

Earthing switch control ESXSWI1 I <-> O ESC I <-> O ESC

Disconnector position indication DCSXSWI1 I <-> O DC (1) I <-> O DC (1)

DCSXSWI2 I <-> O DC (2) I <-> O DC (2)

DCSXSWI3 I <-> O DC (3) I <-> O DC (3)

Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1)

ESSXSWI2 I <-> O ES (2) I <-> O ES (2)

Tap changer position indication TPOSSLTC1 TPOSM 84M

Tap changer control with voltage regulator OLATCC1 COLTC 90V

Synchronism and energizing check SECRSYN1 SYNC 25

Condition monitoring

Trip circuit supervision TCSSCBR1 TCS (1) TCM (1)

TCSSCBR2 TCS (2) TCM (2)

Current circuit supervision CCRDIF1 MCS 3I MCS 3I

Fuse failure supervision SEQRFUF1 FUSEF 60

Measurement

Disturbance recorder RDRE1 - -

Three-phase current measurement CMMXU1 3I 3I

Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0

Three-phase voltage measurement VMMXU1 3U 3U

ABB 55
Voltage Protection and Control 1MRS757058 D
REU615
Product version: 4.0

Table 71. REU615 functions, codes and symbols, continued


Function IEC 61850 IEC 60617 IEC-ANSI

Residual voltage measurement RESVMMXU1 Uo Vn

Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0

Three-phase power and energy measurement PEMMXU1 P, E P, E

RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

Frequency measurement FMMXU1 f f

29. Document revision history

Document revision/date Product version History

A/2010-06-11 3.0 First release

B/2010-06-29 3.0 Terminology updated

C/2010-09-07 3.0 Content updated

D/2012-05-11 4.0 Content updated to correspond to the product


version

56 ABB
57