THE FOLLOWING NEW ALTERNATORS / GENERATOR ENDS ARE AVAILABLE FOR


SALE WITH US WITH IMMEDIATE DELIVERY:

19 Nos. – NEW Leroy Somer & Stamford make Alternators / Generators Ends as per
technical details below:

LIST OF ALTERNATOR / GENERATOR ENDS AVAILABLE FOR


SALE.

Make Model KVA V KW RPM YOM


Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012
Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012
Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012
Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012
Leroy Somer LSA51.2M60 2300 480 1968,6 1800 2012
Stamford PI734E1 2600 480 1840 1800 2012
Stamford PI734E1 2600 480 1840 1800 2012
Stamford PI734E1 2600 480 1840 1800 2012
Stamford PI734E1 2600 480 1840 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Stamford PI734F1 2600 480 2080 1800 2012
Leroy Somer LSA51.2S55 1800 380 1440 1800 2009
Leroy Somer LSA51.2S55 1800 380 1440 1800 2009
Leroy Somer LSA51.2M60 2300 480 1600 1800 2012
Réf. 3367 GB - 2.33 / b - 04.02

35

30

25

N
O
20

TI
15
RA
10
O
RP
CO
IN
IT
N

ALTERNATORS
LSA 51.2 - 4 Pole
Electrical and mechanical data
ALTERNATORS
LSA 51.2 - 4P
50 Hz - 1500 r.p.m.
ELECTRICAL DATA
Insulation class H Excitation system A R E P + PMI
Winding pitch - Code 2/3 - (N° 6S) A.V.R. model R 449
Leads 6 Voltage regulation (steady state) ± 0,5 %
Drip proof IP 23 Sustained short-circuit current 300% (3 IN) : 10s
Altitude ≤ 1000 m Total harmonic (*) TGH / THC < 2,5 %
Overspeed 2250 min -1 Waveform : NEMA = TIF - (*) < 50
Air flow 2,5 m3 /s Waveform : I.E.C. = THF - (*) <2%
(*) Total harmonic content line to line, at no load or full rated linear and balanced load

RATINGS : kVA / kW - Power factor = 0,8


Duty/Ambiant T° Continuous / 40°C Stand-by / 40°C Stand-by / 27°C
Class/T° rise H / 125° K F / 105° K H / 150° K H / 163° K
Phase 3 ph. 3 ph. 3 ph. 3 ph.
Y 380V 400V 415V 380V 400V 415V 380V 400V 415V 380V 400V 415V
∆ 220V 230V 240V 220V 230V 240V 220V 230V 240V 220V 230V 240V

51.2 S55 kVA 1800 1620 1890 1980

N
kW 1440 1296 1512 1584

51.2 M60 kVA 2000 1800 2100 2200

O
kW 1600 1440 1680 1760

TI
51.2 L70 kVA 2150 1935 2255 2365

kW 1720 1548 1804 1892


RA
51.2 VL 85 kVA 2250 2025 2360 2475

kW 1800 1620 1888 1980


O

EFFICIENCIES (%) - Class H / 40° C


Three phase : 400 V
RP

P.F. = 0,8 P.F. = 1


1/4 2/4 3/4 4/4 St.by 1/4 2/4 3/4 4/4 St.by
CO

51.2 S55 94,9 96,2 96,1 95,7 95,4 95,4 97 97,2 97,1 97

51.2 M60 95 96,2 96,2 95,8 95,6 95,5 97 97,3 97,2 97,1

51.2 L70 95 96,4 96,4 96,1 96 95,4 97,1 97,4 97,3 97,3
IN

51.2 VL 85 94,8 96,5 96,7 96,5 96,4 95,2 97,1 97,5 97,6 97,5

REACTANCES (%) - TIME CONSTANTS (ms) - CLASS H / 400 V


IT

51.2 S55 51.2 M60 51.2 L70 51.2 VL 85


Kcc Short-circuit ratio 0,34 0,36 0,39 0,45
Xd Direct axis synchronous reactance unsaturated 362 348 320 278
N

Xq Quadrature axis synchronous reactance unsaturated 217 209 192 167


T'do Open circuit time constant 2660 2770 2910 3050
X'd Direct axis transient reactance saturated 27,4 26,2 23,8 20,4
T'd Short circuit transient time constant 237 245 254 263
X"d Direct axis subtransient reactance saturated 14,2 13,6 12,4 10,6
T"d Subtransient time constant 22 23 24 26
X"q Quadrature axis subtransient reactance saturated 17,8 17 15,5 13,2
Xo Zero sequence reactance unsaturated 3,4 3,2 2,9 2,5
X2 Negative sequence reactance saturated 16 15,3 13,9 12
Ta Armature time constant 38 41 44 48
OTHER DATA - CLASS H / 400 V
io (A) No load excitation current 1,5 1,5 1,6 1,6
ic (A) Full load excitation current 6 5,9 5,5 5
uc (V) Full load excitation voltage 63 62 60 56
ms Recovery time (∆U = 20 % transient) < 700 < 700 < 700 < 700
kVA Motor start. (∆U = 20% sust.) or (∆U = 50% Transient) 3600 4000 4300 4500
% Transient dip (rated step load) - PF : 0,8 LAG 12 12 11 10
kW No load losses 16 17,5 19,2 21,7
kW Heat rejection 64,7 70,1 69,8 65,2
According to : I.E.C. 34.1/34.2 - U.T.E. : NF C 51.111 - V.D.E. 0530 - B.S. 4999 & 5000 - NEMA : MG 1.22 - ISO 8528 . 3 - CSA (C22.2 + UL 2200).
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
LSA 51.2 - 4P
50 Hz - 1500 r.p.m.
TRANSIENT VOLTAGE VARIATION - 400V

Load application Load rejection S 55 M 60


25 25
S 55
L 70
M 60
20 20
L 70 VL 85

% Voltage rise
VL 85
% Voltage dip

15 15

10 10

N
5 5

O
TI
0 0
0 500 1000 1500 2000 2500 3000 3500 4000 0 500 1000 1500 2000 2500 3000
RA
kVA at 0,8 power factor kVA at 0,8 power factor
O

Motors starting
30 S 55
RP

M 60
CO

L 70

VL 85
IN

20
% Voltage dip

IT
N

10

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
Locked rotor - kVA at 0,6 power factor

1) For a starting P.F. differing from 0,6 the starting kVA have to be multiplied by (Sine Ø /0,8)
2) If voltage is not 400V(Y) , 230V(∆) at 50 Hz then kVA must be multiplied by (400/U)2 or (230/U)2.

Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
LSA 51.2 - 4P
60 Hz - 1800 r.p.m
ELECTRICAL DATA
Insulation class H Excitation system A R E P + PMI
Winding pitch - Code 2/3 - (N° 6S) A.V.R. model R 449
Leads 6 Voltage regulation (steady state) ± 0,5 %
Drip proof IP 23 Sustained short-circuit current 300% (3 IN) : 10s
Altitude ≤ 1000 m Total harmonic (*) TGH / THC < 2,5 %
Overspeed 2250 min -1 Waveform : NEMA = TIF - (*) < 50
Air flow 2,8 m3 /s Waveform : I.E.C. = THF - (*) <2%
(*) Total harmonic content line to line, at no load or full rated linear and balanced load

RATINGS : kVA / kW - Power factor = 0,8


Duty/Ambiant T° Continuous / 40°C Stand-by / 40°C Stand-by / 27°C
Class/T° rise H / 125° K F / 105° K H / 150° K H / 163° K
Phase 3 ph. 3 ph. 3 ph. 3 ph.
Y 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V 380V 416V 440V 480V
∆ 240V 240V 240V 240V

51.2 S55 kVA 1710 1870 1980 2160 1540 1685 1780 1945 1795 1965 2080 2265 1880 2060 2175 2375

N
kW 1368 1496 1584 1728 1232 1348 1424 1556 1436 1572 1664 1812 1504 1648 1740 1900

51.2 M60 kVA 1900 2080 2200 2400 1710 1870 1980 2160 1995 2185 2310 2520 2090 2285 2420 2640

O
kW 1520 1664 1760 1920 1368 1496 1584 1728 1596 1748 1848 2016 1672 1828 1936 2112

TI
51.2 L70 kVA 2045 2235 2365 2580 1840 2010 2130 2320 2145 2350 2485 2710 2245 2460 2600 2835

kW 1636 1788 1892 2064 1472 1608 1704 1856 1716 1880 1988 2168 1796 1968 2080 2268
RA
51.2 VL 85 kVA 2140 2340 2475 2700 1925 2105 2230 2430 2245 2455 2600 2835 2350 2575 2720 2970

kW 1712 1872 1980 2160 1540 1684 1784 1944 1796 1964 2080 2268 1880 2060 2176 2376
O

EFFICIENCIES (%) - Class H / 40° C


Three phase : 480 V
RP

P.F. = 0,8 P.F. = 1


1/4 2/4 3/4 4/4 St.by 1/4 2/4 3/4 4/4 St.by
CO

51.2 S55 93,4 95,5 95,8 95,6 95,4 93,8 96,2 96,8 96,8 96,8

51.2 M60 93,6 95,6 95,9 95,6 95,5 94 96,3 96,8 96,9 96,8

51.2 L70 93,6 95,8 96,1 96 95,8 94 96,4 97 97,1 97,1


IN

51.2 VL 85 93,4 95,8 96,3 96,3 96,2 93,8 96,3 97 97,2 97,3

REACTANCES (%) - TIME CONSTANTS (ms) - CLASS H / 480 V


IT

51.2 S55 51.2 M60 51.2 L70 51.2 VL 85


Kcc Short-circuit ratio 0,34 0,36 0,39 0,45
Xd Direct axis synchronous reactance unsaturated 362 348 320 278
N

Xq Quadrature axis synchronous reactance unsaturated 217 209 192 167


T'do Open circuit time constant 2660 2770 2910 3050
X'd Direct axis transient reactance saturated 27,4 26,2 23,8 20,4
T'd Short circuit transient time constant 237 245 254 263
X"d Direct axis subtransient reactance saturated 14,2 13,6 12,4 10,6
T"d Subtransient time constant 22 23 24 26
X"q Quadrature axis subtransient reactance saturated 17,8 17 15,5 13,2
Xo Zero sequence reactance unsaturated 3,4 3,2 2,9 2,5
X2 Negative sequence reactance saturated 16 15,3 13,9 12
Ta Armature time constant 38 41 44 48
OTHER DATA - CLASS H / 480 V
io (A) No load excitation current 1,5 1,5 1,6 1,6
ic (A) Full load excitation current 6 5,9 5,5 5
uc (V) Full load excitation voltage 63 62 60 56
ms Recovery time(∆U = 20 % transient) < 700 < 700 < 700 < 700
kVA Motor start. (∆U = 20% sust.) or (∆U = 50% Transient) 4320 4800 5160 5400
% Transient dip (rated step load) - PF : 0,8 LAG 12 12 11 10
kW No load losses 28,2 30,1 32,5 36
kW Heat rejection 79,5 88,3 86 83
According to : I.E.C. 34.1/34.2 - U.T.E. : NF C 51.111 - V.D.E. 0530 - B.S. 4999 & 5000 - NEMA : MG 1.22 - ISO 8528 . 3 - CSA (C22.2 + UL 2200).
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
LSA 51.2 - 4P
60 Hz - 1800 r.p.m.
TRANSIENT VOLTAGE VARIATION - 480 V

Load application Load rejection M 60


S 55
25 25
L 70
S 55

20 M 60 20 VL 85

L 70

% Voltage rise
% Voltage dip

15 15
VL 85

10 10

N
5 5

O
0 0

TI
0 500 1000 1500 2000 2500 3000 3500 4000 4500 0 500 1000 1500 2000 2500 3000 3500
RA
kVA at 0,8 power factor kVA at 0,8 power factor
O

Motor starting
30 S 55
RP

M 60
CO

L 70

VL 85
20
IN
% Voltage dip

IT
N

10

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
Locked rotor - kva at 0,6 power factor

1) For a starting P.F. differing from 0,6 the starting kVA have to be multiplied by (Sine Ø /0,8)
2) If voltage is not 480V(Y), 277V(∆), 240V(YY ) at 60 Hz then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.

Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
LSA 51.2 - 4P
Single bearing
DIMENSIONS

L S DIA,XBG Eq. Sp. holes on M P.C.D.


LB 1080
680 ß
AH V IP 23 Option

Option
12 Xg
PMG Option
+110
Cables

895
Ø N - 0,127

holes on U P.C.D.
- 0,050
Ø BX - 0,100

YDIA, X Eq. Sp.

1395
0

Ø 975
Ø 871
Ø 998

+1
500 0
35
AIR OUTLET 220 220 AIR INLET 140 610 140
7 260 150 B 150 195

N
60 4 holes Ø 33 80 750 80
4 holes Ø 14,5
4 holes Ø M24
910

O
40

60

TI
FRAME DIMENSIONS (mm) Mass (kg) Coupling
L Flange SAE SAE
RA
TYPE without PMG LB B V Xg M
Flex plate 00 0
LSA 51.2 S55 1677 1655 900 744 735 3745
SAE 24 •
LSA 51.2 M60 1777 1755 1000 844 770 4040
SAE 21 •
O

LSA 51.2 L70 1877 1855 1100 944 825 4445


LSA 51.2 VL85 1977 1955 1200 1044 885 4995 SAE 18 • •
RP

FLANGE DIMENSIONS (mm) FLEX PLATE DIMENSIONS (mm)


S.A.E. N M XBG S ß S.A.E. BX U X Y AH
00 787,4 850,9 16 14 11° 15' 18 571,5 542,9 6 18 15,8
CO

0 647,7 679,5 16 14 11° 15' 21 673,1 641,3 12 18 0


24 733,4 692,1 12 21 0

TORSIONAL ANALYSIS DATA


IN

Xr
IT
N

Ø 225
Ø 240
Ø 220

Ø 170

Ø 140

Lr

CENTRE OF GRAVITY : Xr (mm) - ROTOR LENGTH : Lr (mm) - MASS : M (kg) - MOMENTS OF INERTIA : J (kgm2) : (4J = MD2)
Flex plate S.A.E. 18 Flex plate S.A.E. 21 Flex plate S.A.E. 24
TYPE Xr Lr M J Xr Lr M J Xr Lr M J
LSA 51.2 S55 661 1555,5 1357 41,1 643 1555,5 1359 41,9 640 1555,5 1365 42,6
LSA 51.2 M60 703 1655,5 1475 44,8 685 1655,5 1479 45,6 682 1655,5 1483 46,3
LSA 51.2 L70 754 1755,5 1630 50 736 1755,5 1632 50,8 734 1755,5 1638 51,6
LSA 51.2 VL85 819 1855,5 1833 57,2 801 1855,5 1835 58 799 1855,5 1841 58,8
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
ALTERNATORS
LSA 51.2 - 4P
Two bearing
DIMENSIONS
L M12 DIA, 16 Eq. Sp. on Ø 850,9
LB 1080
V 680 ß

250 Xg

Option
PMG option
+110

895
Câbles
M30
f8

1395
20
Ø 787,4

Ø 975
Ø 871
Ø 985

Ø 150 m6

+1
36

500 0
138

35
AIR OUTLET 220 220 AIR INLET
B 140 610 140
7 260 150 150 195

N
60 4 holes Ø 33 80 750 80
4 holes Ø 14,5
4 holes Ø M24 910

O
40

60

TI
FRAME DIMENSIONS (mm) Mass (kg)
L
RA
TYPE wihout PMG LB B V Xg M

LSA 51.2 S55 1905 1655 900 744 735 3725

LSA 51.2 M60 2005 1755 1000 844 770 4020


O

LSA 51.2 L70 2105 1855 1100 944 825 4425


RP

LSA 51.2 VL85 2205 1955 1200 1044 885 4975


CO

TORSIONAL ANALYSIS DATA


IN

Xr
IT

315
N

Ø 225
Ø 240
Ø 182

Ø 170
Ø 160

Ø 140
Ø 150

Lr

CENTRE OF GRAVITY : Xr (mm) - ROTOR LENGTH : Lr (mm) - MASS : M (kg) - MOMENTS OF INERTIA : J (kgm2) : (4J = MD2)

TYPE Xr Lr M J

LSA 51.2 S55 605,6 1783,5 1281 38,9

LSA 51.2 M60 647,6 1883,5 1398 42,6

LSA 51.2 L70 698,8 1983,5 1553 47,8

LSA 51.2 VL85 763,3 2083,5 1766 55,1

Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments, improve the design or change the conditions of utilisation.
Their description cannot in any case engage Leroy-Somer's liability. The values indicated are typical values .
N
O
TI
RA
O
RP
CO
IN
IT
N

MOTEURS LEROY-SOMER 16015 ANGOULÊME CEDEX - FRANCE


http://www.leroy-somer.com
PI734E - Winding 312
APPROVED DOCUMENT
Technical Data Sheet

N
O
TI
RA
O
RP
CO
IN
IT
N
PI734E
SPECIFICATIONS & OPTIONS
STANDARDS TERMINALS & TERMINAL BOX
Stamford industrial generators meet the requirements of BS Standard generators feature a main stator with 6 ends
EN 60034 and the relevant sections of other national and brought out to the terminals, which are mounted on the
international standards such as BS5000, VDE 0530, NEMA frame at the non-drive end of the generator. A sheet steel
MG1-32, IEC60034, CSA C22.2-100, AS1359. terminal box contains the AVR and provides ample space
Other standards and certifications can be considered on for the customers' wiring and gland arrangements. It has
request. removable panels for easy access.

DESCRIPTION SHAFT & KEYS


The STAMFORD PI range of synchronous ac generators are All generator rotors are dynamically balanced to better
brushless with a rotating field. They are separately excited than BS6861:Part 1 Grade 2.5 for minimum vibration in
by the STAMFORD Permanent Magnet Generator (PMG). operation. Two bearing generators are balanced with a
This is a shaft mounted, high frequency, pilot exciter which half key.
provides a constant supply of clean power via the Automatic
Voltage Regulator (AVR) to the main exciter. The main INSULATION/IMPREGNATION
exciter output is fed to the main rotor, through a full wave The insulation system is class 'H', and meets the
bridge rectifier, protected by surge suppression. requirements of UL1446.
All wound components are impregnated with materials
VOLTAGE REGULATORS APPROVED DOCUMENT and processes designed specifically to provide the high

N
The PI range generators, complete with a PMG, are available build required for static windings and the high mechanical
with one of two AVRs. Each AVR has soft start voltage build strength required for rotating components.

O
up and built in protection against sustained over-excitation,
which will de-excite the generator after a minimum of 8 QUALITY ASSURANCE

TI
seconds. Generators are manufactured using production
Underspeed protection (UFRO) is also provided on both procedures having a quality assurance level to
AVRs. The UFRO will reduce the generator output voltage
RA
BS EN ISO 9001.
proportional to the speed of the generator below a pre-
settable level. NOTE ON REGULATION
The stated voltage regulation may not be maintained in
O

The MX341 AVR is two phase sensed with a voltage the presence of certain radio transmitted signals. Any
regulation of ± 1 %. (see the note on regulation). change in performance will fall within the limits of Criteria
RP

'B' of EN 61000-6-2:2001. At no time will the steady-state


The MX321 AVR is 3 phase rms sensed with a voltage voltage regulation exceed 2%.
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled
CO

DE RATES
recovery from step loads. An over voltage protection circuit All values tabulated on page 8 are subject to the following
will shutdown the output device of the AVR, it can also trip an reductions
optional excitation circuit breaker if required. As an option,
short circuit current limiting is available with the addition of 5% when air inlet filters are fitted.
IN

current transformers. 10% when IP44 Filters are fitted.


3% for every 500 metres by which the operating altitude
Both the MX341 and the MX321 need a generator mounted
IT

exceeds 1000 metres above mean sea level.


current transformer to provide quadrature droop 3% for every 5°C by which the operational ambient
characteristics for load sharing during parallel operation. temperature exceeds 40°C.
N

Provision is also made for the connection of the STAMFORD


power factor controller, for embedded applications, and a Note: Requirement for operating in an ambient
remote voltage trimmer. temperature exceeding 60°C must be referred to the
factory.
WINDINGS & ELECTRICAL PERFORMANCE
All generator stators are wound to 2/3 pitch. This eliminates
triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches. Note: Continuous development of our products entitles us to
A fully connected damper winding reduces oscillations during change specification details without notice, therefore they must
paralleling. This winding, with the 2/3 pitch and carefully not be regarded as binding.
selected pole and tooth designs, ensures very low levels of
voltage waveform distortion. Front cover drawing is typical of the product range.

2
PI734E
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321

VOLTAGE REGULATION ±1% ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

MAIN STATOR RESISTANCE 0.00093 Ohms PER PHASE AT 22°C STAR CONNECTED

MAIN ROTOR RESISTANCE


APPROVED DOCUMENT 2.17 Ohms at 22°C

N
EXCITER STATOR RESISTANCE 17.5 Ohms at 22°C

O
EXCITER ROTOR RESISTANCE 0.063 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

TI
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
RA
MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6228 C3

BEARING NON-DRIVE END BALL. 6319 C3


O

1 BEARING 2 BEARING
RP

WEIGHT COMP. GENERATOR 3556 kg 3506 kg

WEIGHT WOUND STATOR 1747 kg 1747 kg

WEIGHT WOUND ROTOR 1494 kg 1432 kg


CO

2
WR² INERTIA 45.49 kgm 44.4891 kgm2
SHIPPING WEIGHTS in a crate 3629kg 3575kg

PACKING CRATE SIZE 216 x 105 x 154(cm) 216 x 105 x 154(cm)


IN

50 Hz 60 Hz

TELEPHONE INTERFERENCE THF<2% TIF<50


IT

COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm

VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
N

kVA BASE RATING FOR REACTANCE


1845 1900 1900 1865 2070 2210 2255 2300
VALUES
Xd DIR. AXIS SYNCHRONOUS 3.18 2.96 2.75 2.40 3.84 3.67 3.42 3.21

X'd DIR. AXIS TRANSIENT 0.19 0.18 0.17 0.15 0.23 0.22 0.21 0.19

X''d DIR. AXIS SUBTRANSIENT 0.14 0.13 0.12 0.11 0.17 0.16 0.15 0.14

Xq QUAD. AXIS REACTANCE 2.04 1.90 1.76 1.54 2.47 2.36 2.20 2.06

X''q QUAD. AXIS SUBTRANSIENT 0.29 0.27 0.25 0.22 0.35 0.33 0.31 0.29

XL LEAKAGE REACTANCE 0.04 0.03 0.03 0.03 0.04 0.04 0.04 0.04
X2 NEGATIVE SEQUENCE 0.20 0.19 0.17 0.15 0.24 0.23 0.22 0.20
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.149s
T''d SUB-TRANSTIME CONST. 0.02s
T'do O.C. FIELD TIME CONST. 2.46s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd

3
PI734E
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

4
PI734E
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

5
PI734E
Winding 312

Locked Rotor Motor Starting Curve


50
Hz 346V 380V 400V 415V 440V
30

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15
APPROVED DOCUMENT

N
O
10

TI
RA
5
O

0
RP

0 500 1000 1500 2000 2500 3000 3500 4000 4500


LOCKED ROTOR kVA

60
CO

30
Hz 380V 416V 440V 460V 480V
IN

25
IT
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
LOCKED ROTOR kVA

6
PI734E

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50
Hz 100000

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

APPROVED DOCUMENT

N
O
TI
1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 6,250 Amps
RA
60 100000
Hz
O
RP

SYMMETRICAL

ASYMMETRICAL
CO
CU RR E NT (Am p s)

10000
IN
IT
N

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 7,500 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

7
PI734E
Winding 312 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

kVA 1715 1770 1770 1735 1845 1900 1900 1865 1920 1980 1980 1940 1975 2035 2035 1995

kW 1372 1416 1416 1388 1476 1520 1520 1492 1536 1584 1584 1552 1580 1628 1628 1596

Efficiency (%) 95.9 96.0 96.1 96.3 95.7 95.8 96.0 96.1 95.6 95.7 95.8 96.1 95.5 95.6 95.8 96.0

kW Input 1431 1475 1473 1441 1542 1587 1583 1553 1607 1655 1653 1615 1654 1703 1699 1663

60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480

N
kVA 1935 2055 2100 2140 2070 2210 2255 2300 2155 2300 2345 2395 2215 2365 2415 2465

O
kW 1548 1644 1680 1712 1656 1768 1804 1840 1724 1840 1876 1916 1772 1892 1932 1972

TI
Efficiency (%) 95.8 95.9 96.0 96.1 95.7 95.8 95.9 95.9 95.6 95.7 95.8 95.9 95.5 95.6 95.7 95.8
RA
kW Input 1616 1714 1750 1781 1730 1846 1881 1919 1803 1923 1958 1998 1855 1979 2019 2058

DIMENSIONS
O
RP
CO
IN
IT
N

8
APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

Head Office Address:


Barnack Road, Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100

www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

PI7E-312-TD-EN-SG-A
PI734F - Winding 312
APPROVED DOCUMENT
Technical Data Sheet

N
O
TI
RA
O
RP
CO
IN
IT
N
PI734F
SPECIFICATIONS & OPTIONS
STANDARDS TERMINALS & TERMINAL BOX
Stamford industrial generators meet the requirements of BS Standard generators feature a main stator with 6 ends
EN 60034 and the relevant sections of other national and brought out to the terminals, which are mounted on the
international standards such as BS5000, VDE 0530, NEMA frame at the non-drive end of the generator. A sheet steel
MG1-32, IEC60034, CSA C22.2-100, AS1359. terminal box contains the AVR and provides ample space
Other standards and certifications can be considered on for the customers' wiring and gland arrangements. It has
request. removable panels for easy access.

DESCRIPTION SHAFT & KEYS


The STAMFORD PI range of synchronous ac generators are All generator rotors are dynamically balanced to better
brushless with a rotating field. They are separately excited than BS6861:Part 1 Grade 2.5 for minimum vibration in
by the STAMFORD Permanent Magnet Generator (PMG). operation. Two bearing generators are balanced with a
This is a shaft mounted, high frequency, pilot exciter which half key.
provides a constant supply of clean power via the Automatic
Voltage Regulator (AVR) to the main exciter. The main INSULATION/IMPREGNATION
exciter output is fed to the main rotor, through a full wave The insulation system is class 'H', and meets the
bridge rectifier, protected by surge suppression. requirements of UL1446.
All wound components are impregnated with materials
VOLTAGE REGULATORS APPROVED DOCUMENT and processes designed specifically to provide the high

N
The PI range generators, complete with a PMG, are available build required for static windings and the high mechanical
with one of two AVRs. Each AVR has soft start voltage build strength required for rotating components.

O
up and built in protection against sustained over-excitation,
which will de-excite the generator after a minimum of 8 QUALITY ASSURANCE

TI
seconds. Generators are manufactured using production
Underspeed protection (UFRO) is also provided on both procedures having a quality assurance level to
AVRs. The UFRO will reduce the generator output voltage
RA
BS EN ISO 9001.
proportional to the speed of the generator below a pre-
settable level. NOTE ON REGULATION
The stated voltage regulation may not be maintained in
O

The MX341 AVR is two phase sensed with a voltage the presence of certain radio transmitted signals. Any
regulation of ± 1 %. (see the note on regulation). change in performance will fall within the limits of Criteria
RP

'B' of EN 61000-6-2:2001. At no time will the steady-state


The MX321 AVR is 3 phase rms sensed with a voltage voltage regulation exceed 2%.
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled
CO

DE RATES
recovery from step loads. An over voltage protection circuit All values tabulated on page 8 are subject to the following
will shutdown the output device of the AVR, it can also trip an reductions
optional excitation circuit breaker if required. As an option,
short circuit current limiting is available with the addition of 5% when air inlet filters are fitted.
IN

current transformers. 10% when IP44 Filters are fitted.


3% for every 500 metres by which the operating altitude
Both the MX341 and the MX321 need a generator mounted
IT

exceeds 1000 metres above mean sea level.


current transformer to provide quadrature droop 3% for every 5°C by which the operational ambient
characteristics for load sharing during parallel operation. temperature exceeds 40°C.
N

Provision is also made for the connection of the STAMFORD


power factor controller, for embedded applications, and a Note: Requirement for operating in an ambient
remote voltage trimmer. temperature exceeding 60°C must be referred to the
factory.
WINDINGS & ELECTRICAL PERFORMANCE
All generator stators are wound to 2/3 pitch. This eliminates
triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches. Note: Continuous development of our products entitles us to
A fully connected damper winding reduces oscillations during change specification details without notice, therefore they must
paralleling. This winding, with the 2/3 pitch and carefully not be regarded as binding.
selected pole and tooth designs, ensures very low levels of
voltage waveform distortion. Front cover drawing is typical of the product range.

2
PI734F
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321

VOLTAGE REGULATION ± 1% ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

MAIN STATOR RESISTANCE 0.00076 Ohms PER PHASE AT 22°C STAR CONNECTED

MAIN ROTOR RESISTANCE


APPROVED DOCUMENT 2.31 Ohms at 22°C

N
EXCITER STATOR RESISTANCE 17.5 Ohms at 22°C

O
EXCITER ROTOR RESISTANCE 0.063 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

TI
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
RA
MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6232 C3

BEARING NON-DRIVE END BALL. 6319 C3


O

1 BEARING 2 BEARING
RP

WEIGHT COMP. GENERATOR 3840 kg 3807 kg

WEIGHT WOUND STATOR 1908 kg 1908 kg

WEIGHT WOUND ROTOR 1609 kg 1565 kg


CO

2
WR² INERTIA 49.3409 kgm 48.424 kgm2
SHIPPING WEIGHTS in a crate 3913kg 3876kg

PACKING CRATE SIZE 216 x 105 x 154(cm) 216 x 105 x 154(cm)


IN

50 Hz 60 Hz

TELEPHONE INTERFERENCE THF<2% TIF<50


IT

COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm

VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
N

kVA BASE RATING FOR REACTANCE


2020 2080 2080 2040 2345 2500 2550 2600
VALUES
Xd DIR. AXIS SYNCHRONOUS 2.93 2.73 2.53 2.21 3.55 3.38 3.16 2.96

X'd DIR. AXIS TRANSIENT 0.18 0.17 0.15 0.13 0.21 0.20 0.19 0.18

X''d DIR. AXIS SUBTRANSIENT 0.13 0.12 0.11 0.10 0.16 0.15 0.14 0.13

Xq QUAD. AXIS REACTANCE 1.89 1.75 1.63 1.42 2.28 2.18 2.03 1.90

X''q QUAD. AXIS SUBTRANSIENT 0.26 0.25 0.23 0.20 0.32 0.31 0.29 0.27

XL LEAKAGE REACTANCE 0.03 0.03 0.03 0.03 0.04 0.04 0.04 0.03
X2 NEGATIVE SEQUENCE 0.19 0.17 0.16 0.14 0.23 0.22 0.20 0.19
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.02 0.02

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.154s
T''d SUB-TRANSTIME CONST. 0.02s
T'do O.C. FIELD TIME CONST. 2.54s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd

3
PI734F
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

4
PI734F
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

5
PI734F
Winding 312

Locked Rotor Motor Starting Curve


50
30
Hz 346V 380V 400V 415V 440V

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15 APPROVED DOCUMENT

N
O
10

TI
RA
5
O

0
RP

0 1000 2000 3000 4000 5000 6000


LOCKED ROTOR kVA

60
CO

30
Hz 380V 416V 440V 460V 480V
IN

25
IT
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0
0 1000 2000 3000 4000 5000 6000 7000
LOCKED ROTOR kVA

6
PI734F
Winding 312
Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed
Based on star (wye) connection.
50
Hz
100000

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

APPROVED DOCUMENT

N
O
TI
1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 6,850 Amps
RA
60 100000
Hz
O
RP

SYMMETRICAL

ASYMMETRICAL
CO
CU RR E NT (Am p s)

10000
IN
IT
N

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 8,900 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

7
PI734F
Winding 312 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

kVA 1880 1935 1935 1900 2020 2080 2080 2040 2105 2170 2170 2125 2165 2250 2250 2185

kW 1504 1548 1548 1520 1616 1664 1664 1632 1684 1736 1736 1700 1732 1800 1800 1748

Efficiency (%) 96.1 96.2 96.3 96.4 96.0 96.0 96.1 96.3 95.9 95.9 96.0 96.2 95.8 95.8 96.0 96.2

kW Input 1565 1609 1607 1577 1683 1733 1732 1695 1756 1810 1808 1767 1808 1878 1876 1817

60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480

N
kVA 2190 2325 2370 2420 2345 2500 2550 2600 2435 2600 2650 2705 2505 2675 2730 2785

O
kW 1752 1860 1896 1936 1876 2000 2040 2080 1948 2080 2120 2164 2004 2140 2184 2228

TI
Efficiency (%) 96.0 96.1 96.1 96.2 95.9 95.9 96.0 96.1 95.8 95.8 95.9 96.0 95.7 95.8 95.9 95.9
RA
kW Input 1825 1935 1973 2012 1957 2086 2125 2164 2033 2171 2211 2254 2094 2234 2277 2323

DIMENSIONS
O
RP
CO
IN
IT
N

8
APPROVED DOCUMENT

N
O
TI
RA
O
RP
CO
IN
IT
N

Head Office Address:


Barnack Road, Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100

www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

PI7F-312-TD-EN-SG-A