Professional Documents
Culture Documents
Chapter 2
2.1 Bubbles and Symbols
2.2 Tag Numbers
Piping and instrumentation (P&I) diagrams are the same set of symbols, signals and letter codes
of fundamental importance in process automation is sufficient to enable elements to be represented
and are discussed, for example, by Coulson (2004). whether the version of P&I diagram be outline or
Their formulation is a major stage in the design detailed.
of a process plant. They are subsequently used as Consider Figure 2.1 which is a section of an out-
the basis for the detailed design of the plant’s con- line P&I diagram that depicts a flow control loop
trol system, and become reference documents for associated with a centrifugal pump.
other purposes such as HAZOP studies. P&I dia-
grams depict, from a process point of view, mea-
FC
surements and control schemes in relation to items
of plant and their interconnecting pipework. They
are represented by means of symbols and tag num-
bers.
Fig. 2.1 P&I diagram of flow control loop
Broken lines are used in Figure 2.1 to depict the The process stream flows through a sight glass FG
signals. Strictly speaking, broken lines should only 47, an orifice plate FE 47 and a control valve FV
be used for electrical signals. However, on outline 47. These are all in-line elements. Note the differ-
P&I diagrams it is common practice to use broken ent use of the bubbles: as a symbol for the sight
lines for most signals on the basis that they will glass but as an identification for the orifice plate
probably be electrical anyway. Representations for and control valve. Note also that hand operated
the most common signal types are as shown in valves are indicated on either side of all these ele-
Table 2.1. ments so that they can be isolated prior to removal
for maintenance or repair.Additionally, the control
Table 2.1 Representation of signal types valve has a bypass line to enable flow to continue
under manual control in the event of the control
Signal type Representation
valve having to be removed.
Capillary The pressure drop across the orifice plate is
Data link measured using a dp cell FT 47 which transmits the
Electrical flow rate as an electrical signal to the totaliser FQR
47, the low level switch FSL 47 and the controller
Electromagnetic
FIC 47. If the flow drops below some pre-set lower
Hydraulic limit the flow switch FSL 47 will activate a low level
Mechanical alarm FAL 47. The controller indicates the current
Pneumatic value of the flow rate and generates a control signal
Process which is transmitted, via an I/P converter FY 47, to
the control valve. FV 47 is a pneumatically actu-
Consider Figure 2.2 which is a section of a detailed ated diaphragm type of regulatory valve. It has a
P&I diagram that depicts the same flow control positioner attached, as indicated by the box on the
loop. stem of the valve symbol. The arrow on the stem
FSL FAL
47 47
FQR
47 FIC
47
FT FY
FE 47 47 FV
47 47
FG
47
indicates that, in the event of a loss of air supply, verter is designated FY 47 although its input is a
the valve will fail shut. current and its output a pressure.
Information about the location of an element Within the letter code,modifiers must immedi-
is indicated by the presence or otherwise of a line ately follow the letter that they qualify.For example,
through its bubble. No line means that the element the modifier Q changes the measured variable F of
is field mounted, i.e. it is installed on or adjacent to element FQR 47 into a totalised flow. In addition,
a pipe, vessel or some other item of plant. A single the modifier L states that the alarm FAL 47 will
line through the bubble, as with FAL 47 and FIC only be activated by low flows.
47, means that the element is located in a central If a loop contains two or more elements with
control room. And a double line, as with FQR 47, the same function they may be distinguished by
means that it is panel mounted elsewhere, say on a means of suffixes. For example, if the flow loop had
field termination cabinet. two control valves in a duplex arrangement, they
could have been designated as FV 47A and FV 47B.
Sometimes the letter code is insufficient to give
an adequate description of the function of an el-
ement. Additional information may be provided,
2.2 Tag Numbers either in a box attached to its bubble or as adjacent
There are several national standards which relate text. For example, FT 47 has a square root function
to the representation of instrumentation and con- to compensate for the square relationship inher-
trol schemes. The most important English lan- ent in the flow measurement by the orifice plate.
guage ones are BS 1646 and ISA S5.1. Also, most The total flow computed by FQR 47 is obtained
major companies have their own internal stan- by means of an integral function. Some of the
dards. Whilst there are many differences in detail more common functional designations are given
between them, the basic symbols and letter code in Table 2.3.
structure are essentially the same. Numbering of elements is in accordance with
ISA S5.1 is used throughout this guide on the some plant based convention. There are two ap-
grounds that it is the most widely used standard in proaches, serial and parallel, of which serial is the
practice. Its letter code structure is as indicated in more common. On a serial basis each channel, loop
Table 2.2 which also lists the meaning of the more or scheme is allocated a unique number, 47 in the
commonly used letters. case of Figure 2.2. Regardless of the letter code, all
Letter codes are configured according to func- its elements then assume the same number. On a
tion. The first letter corresponds to the measured parallel basis, blocks of numbers are allocated ac-
variable and, if necessary, may be qualified by a cording to instrument type or function, depending
modifier. Succeeding letters describe an element’s on its letter code. This results in similar elements
readout or control functions; these may themselves in different loops having contiguous numbers.
have modifiers. A certain amount of judgement The bubbles used in Figure 2.2 indicate the
may be necessary to establish the most appropriate function of the elements. It is implied that each el-
letter code for an element. ement is a discrete item of instrumentation which
It is important to appreciate that the letter code may be either analogue or digital in nature. With
is determined by the function of the element and computer-based control systems many of these in-
not by its design or installation.For example,the dp dividual functions are realised by means of config-
cell in Figure 2.2 is designated as a flow transmitter urable software in common hardware. For repre-
FT 47 rather than as PDT 47 even though it mea- sentation of such functions, ISA S5.1 recommends
sures differential pressure across the orifice plate. a different set of symbols. These are listed in Ta-
The first letter of all elements within a loop is ble 2.4: note that the symbols listed for input and
that of the measured variable. Thus the I/P con- output (I/O) channels are non-standard but are
12 2 P&I Diagrams
A Analysis Alarm
B Burner or combus- User’s choice User’s choice User’s choice
tion
C User’s choice, e.g. Control
conductivity
D User’s choice, e.g. Differential
density
E Voltage or emf Sensor or primary
element
F Flow rate Ratio or fraction
G User’s choice Sight glass or view-
ing device
H Hand High
I Current (electrical) Indicate
J Power Scan
K Time or schedule Rate of change Control station
L Level Light (pilot) Low
M User’s choice, e.g. Momentary Middle or inter-
moisture mediate
N User’s choice User’s choice User’s choice User’s choice
O User’s choice Orifice or restric-
tion
P Pressure or vacuum Point (test)
Q Quantity Integrate or
totalise
R Radiation Record or print
S Speed or frequency Safety Switch
T Temperature Transmit
U Multivariable Multifunction Multifunction Multifunction
V Vibration Valve or damper
W Weight or force Well or pocket
X Unclassified X axis Unclassified Unclassified Unclassified
Y Event or state Y axis Relay, compute or
convert
Z Position or dimen- Z axis Driver, actuator or
sion other control ele-
ment
2.2 Tag Numbers 13
Table 2.3 Additional functions for use with tag numbers Table 2.4 P&I diagram symbols for computer-based systems
Function Symbol Configurable functions Symbol
Average AVG
Bias + or − Shared display and control
Boost 1: 1
Characterise f (x)
Derivative d Computer function
dt
Difference
Divide ÷
Programmable logic controller
High select >
Integrate
Low select < Undefined logic
Multiply × or sequence control
Raise to power xn
Input channel
Ratio 1: n
Reverse REV
√
Square root Output channel
Sum
nevertheless commonly used. A solid line across Figure 2.3 shows an implementation of the previ-
the symbol means that the function has a shared, ous flow control loop by means of a distributed
screen based display: the absence of a line means control system (DCS). The square root extraction
that the function is inaccessible to the operator. previously associated with FT 47, the shared dis-
FQR
47
FICA LOW
47
FT FY
47 47 FV
FE
47
47
FG
47
play and control functions, and the low flow alarm The reader is encouraged to browse through the
previously handled by FSL 47 and FAL 47 are now appendix to ISA S5.1 which contains a host of ex-
all realised by FICA 47. The integration is realised amples on the use of symbols,signals and tag num-
by FQR 47 which logs, but does not display, the bers in a variety of contexts. The reader is also re-
totalised flow. ferred to ISA S5.3 on symbols for computer control
systems.