You are on page 1of 6

100 percent Australian Owned

TECHNICAL NEWS Issue 28 April 1999

Please circulate to

_________________________
_________________________
Quarterly Technical
Newsletter of Australia’s
leading supplier of
low-voltage motor
How does _________________________
_________________________
_________________________
control and switchgear.
electrical
equipment
rate ?
By Bill Mairs
Technical Manager
NHP Electrical Engineering
Products Pty Ltd

Electrical equipment is defined by a


bewildering array of ratings. Few people
fully understand these ratings as some of
even the fundamental ratings have a
IN THIS history of international manipulation and Device rating needs to be understood
ISSUE compromise. This has resulted in to make correct selections.
obscure meanings that can leave the
newcomer totally confused. Ratings based on current
While the international playing field
Current influences the temperature rise,
might be more level with Australia
electromagnetic forces and the contact
basically adopting IEC standards the
life of a device. There is a range of
placement of the goal posts is by no
How does electrical 1 means fixed. The manufacturers and
ratings based on current for normal and
abnormal operating conditions.
equipment rate users of electrical equipment often find
themselves aiming for different ends of
Conventional enclosed 2 the field.
Conventional free air thermal
current (Ith)
thermal current
The early Australian standards had a
Voltage ratings 3 strong British influence and were full of
practical approaches. In those days for
This is most fundamental of all the
ratings as the $/amp is usually the first
comparison made when selecting
Rated impulse instance the small wiring cables only
withstand voltage 4 had one current rating. Technical
between products from different
suppliers. Given its basic importance it
correctness had been put aside for the is easy to see that if the Ith is increased
What needs to happen
5 sake of simple understanding. This paper
looks at a few of the ratings with some
so the price equation improves. It is not
Reader surprising therefore that when IEC
response 6 explanation of how we got where we are
today.
principles were adopted, equipment
2 (Continued from Page 1
Circuit breaker enclosure

ratings increased. It would


seem that the pressure groups
Test current
at the time ensured that the 2000 amps
test methods maximized the
results that could be obtained
in the standard tests. To
achieve this the standard test 3–100 x 5 Cu
conductors were made large bars for test.
In free air AS3000
and thus provided heat sinking
lists 2 – 63 x 6.3
of the device under test. The as suitable. 2m
temperature restrictions were
also increased to allow hotter
running. The problem was Typical test arrangement for enclosed current rating.
compounded when the Test busbars are of large cross section.
Australian Wiring Rules performance standards for
included tables for busbar Rated operational current (Ie)
Moulded Case Circuit
ratings which implied busbar The operational current relates Breakers (MCCB) and Air
temperature rises of 70o C to the devices switching ability Circuit Breakers (ACB). The
were acceptable. This is in at its operational voltage. It is term Air Circuit Breaker
stark contrast to the often less than the thermal referred to the fact that the
temperature rise of test current rating. breaking process was in air as
conductors. These are against the old oil immersed
proportioned to give a Rated service short-circuit
style. A more accurate
temperature rise of about 20o C breaking capacity (Ics) and
distinction between the two
in the test configuration. Rated ultimate short-circuit
would have been metal clad as
breaking capacity (Icu)
Conventional enclosed compared to moulded case.
thermal current (Ithe) Before the adoption of IEC
While in principle the two
standards there were separate
This is the value of current the
device can carry when
mounted in a defined
enclosure. While most
electrical switchgear is
intended to be enclosed, Ithe is
not normally quoted. The
variations caused to the actual
temperature rise by the
enclosure design and the
heating caused by other
equipment means that in most
situations Ithe will also vary.
Manufacturers can provide
some guide to a suitable
derating of enclosed
equipment but the designer of
the assembly must take
responsibility for the final
outcome.
Circuit breakers can be selected on the basis of Icu.
Actual fault currents are normally less than the circuit prospective.

NHP Technical News, issue 28


on the basis of the Ultimate
rating. There are very few
3
MCCB problems that have
resulted from the MCCB
being selected on the basis of
the Ultimate rating instead of
400. the Service rating.
Voltage ratings
200.
The voltage ratings are critical
0. to the performance of
electrical switchgear. While
-200. the IEC standards show a
consistent treatment of the
voltage ratings, modifications
introduced by Australia have
distorted the concepts to some
degree.
Rated operational voltage
(Ue)
Transient voltage recorded during short circuit testing of a miniature circuit This is the voltage at which
breaker. Actual peak is off scale. the operational tests are
styles of circuit breaker were difference in the number of performed. Several ratings
much the same the ACB was close open operations required may be applied for use at
considered more robust and at the rated short circuit level. different supply voltages. This
had the ability to withstand For the MCCB, to increase the rating is fairly straight
short duration fault currents number of operations would forward.
with the contacts remaining have meant the short circuit Rated insulation
closed. rating would need to be voltage (Ui)
This ability allows time reduced. For the ACB, to
reduce the number would This rating is equal to or
grading with down stream
remove one of the main greater than Ue and relates to
circuit breakers. The ACB was
differences between the two the voltage at which the
also expected to withstand an
styles of breaker. This issue dielectric and creepage
extra operation at maximum
was resolved by introducing distances are referred. Testing
fault levels.
the concept of Ultimate (Icu) for this rating includes
The ACB was generally and Service (Ics) short circuit allowances for overvoltages.
applied at the main ratings. The Ultimate rating As the standards specify a
switchboard and MCCBs used particular test voltage as
requiring an open / close open
for lower rated distribution covering a range of Ui ratings
test sequence while the
circuits. As product ranges it is normal to specify Ui as
Service rating an open / close
developed MCCBs increased the highest value in the range.
open / close open sequence.
in current rating and some It should never be assumed
Unfortunately this has resulted
ACBs used an increasing that a device can be operated
in confusion ever since. There at Ui as it may be incapable of
number of mouldings. These is no guide given in the
trends and the similar purpose breaking any current at that
standard as to how to apply voltage.
of the two styles of circuit the two ratings.
breakers resulted in a single Rated impulse withstand
standard being produced. The Based on the history of the
voltage (Uimp)
greatest difficulty in ratings there is no reason why
combining the two was the MCCBs should not be chosen Relates to the peak value of

NHP Technical News, issue 28


voltage that the equipment can
withstand without flashover or
magnitude of possible
transients is considered
4
damage. greatest at the service entrance
level and decreases at the
The occurrence of transient distribution circuit and
overvoltages in electrical equipment levels. Surge
systems is a normal event. arresters are normally required
They are caused by switching for transient control.
transients and induced effects In Australia the use of surge
from lightning strikes. The arresters has not been
voltage withstand of the common and there has been
equipment needs to be high substantial resistance to
enough to prevent flashover. adopting the IEC principles.
If flashover does occur this
can often provide the means The Wiring Rules and the
for a continuing arc to be Australian versions of the
established, resulting in severe switchboard standards have
damage. always specified quite large
creepage and clearance
The IEC approach is to distances. Based on Surge diverters are being used
establish a coordinated experience the values to protect equipment
insulation system. The specified have been sufficient
transients need to be limited to to allow quite high transients of insulation coordination and
a level below the impulse to pass without flashovers. does not set specific
withstand levels of the The basic switchgear standard requirements for Australia.
associated equipment. The AS3947 accepts the principles On the other hand, AS3439,
the switchboard standard, has
been modified away from IEC
IEC preferred values of rated impulse withstand
requirements to require high
voltage when protected by surge-arresters. withstand levels. The impulse
Overvoltage category level has been specified as
10kV and this effectively
I II III IV results in requiring the same
Specially Load Distribution Origin of creepage and clearance
protected (appliance circuit installation distances that have been used
level equipment) level (service for many years. This
difference makes flashover of
level entrance) busbars unlikely but failure of
level the equipment possible. This
can be seen with sensitive
1.5kV 2.5KV 4kV 6kV
electronic equipment as
Minimum clearance required for inhomogeneous damage by electrical
field conditions for above impulse levels. transients is common. The
damage has reached a point
0.5mm 1.5mm 3mm 5.5mm
were the domestic consumer
Impulse level as modified by AS4349 for the live is well aware of the problem
conductors in Australian switchboards. and many surge arresters are
being purchased to prevent
10kV 10kV 10kV loss of expensive equipment
Minimum clearance required by AS3439 or data. In industrial
applications failures are
12mm 12mm 12mm occurring with flashover of
Australian requirements for switchboard surge equipment inside
ratings in not matched in Australian switchgear standards. switchboards. At this level

NHP Technical News, issue 28


5

Flashover of test station terminals caused by a voltage transient. Test duration 0.2 seconds 50kA prospective current.

(Continued from Page 4 selection but a better approach the electrical industry have a
has been published in AS4388 fair understanding of the
-1996. problems of temperature rise
however there seems to be a the causes and remedies of
This standard details a method
lower understanding of the electric flashover are very
for switchboard temperature
problem than at the domestic poorly understood. The
rise assessment and includes
level. There is of course a destruction caused by the arc
more realistic temperatures for
major difference in the often hides the evidence but
the operation of busbars.
consequences of the flashover. breakdown does occur even
Unfortunately, the busbar
An electronic device that has with quite large clearances as
sizes are metric while imperial
been killed by a transient still there is often no surge arrester
bar sizes are still common in
looks the same but a fault in a in the system. As a flashover
Australia. This standard needs
switchboard usually results in often involves substantial
to be revised to include the
extensive arcing damage even financial loss, litigation is
imperial sizes.
though the causes may have often threatened but seldom
been identical. The confusion between undertaken because the issue
ultimate and service short quickly becomes quite
What needs to happen circuit ratings needs to be technical. The presence and
clarified by perhaps a cause of a destructive transient
The thermal performance of statement in the Wiring Rules. is also very difficult to prove
equipment requires a balance For normal distribution after the event. To overcome
between the device, the circuits the prospective short the situation Australian
enclosure and the connecting circuit level of the circuit Standards need to remove the
conductors. The 1991 edition needs only to be matched by fuzzy approach to insulation
of the Wiring Rules was in the ultimate rating. coordination and accept that
conflict with the switchgear
surge arresters should be
standards in regard to busbar While those experienced in
required.

NHP Technical News, issue 28


6
NHP Electrical
Engineering Products
Pty Ltd A.C.N. 004 304 812
www.nhp.com.au
MELBOURNE
43-67 River Street,
Richmond, Vic. 3121
Phone: (03) 9429 2999
Fax (03) 9429 1075
If you would like previous copies of Technical News, please SYDNEY
30-34 Day Street North,
complete the following form and fax to NHP on (03) 9429 1075 Silverwater, N.S.W. 2128
marked to the attention of the Marketing Services Department. Phone: (02) 9748 3444
Fax: (02) 9648 4353
Name: ....................................................Title: .................................. BRISBANE
25 Turbo Drive,
Coorparoo, Qld. 4151
Company: .......................................................................................... Phone: (07) 3891 6008
Fax: (07) 3891 6139
Address: ............................................................................................ ADELAIDE
50 Croydon Road,
Keswick, S.A. 5035
Telephone: ( ) ................................Fax: ( ) .............................. Phone: (08) 8297 9055
Fax: (08) 8371 0962
PERTH
■ Catalogue CPB 38 Belmont Ave.,
Other titles currently available. Rivervale, W.A. 6103
Phone: (08) 9277 1777
Please tick those you would like to receive. Fax: (08) 9277 1700
■ The quality Switchboard NEWCASTLE
575 Maitland Road,
(Switchgear and protection devices for switchboards) Mayfield West, N.S.W. 2304
■ RCDs are saving lives Phone: (02) 4960 2220
Fax: (02) 4960 2203
(Earth leakage protection; RCDs) TOWNSVILLE
■ Terminations, good or bad? 62 Leyland Street,
(Terminals) Garbutt, Qld. 4814
Phone: (07) 4779 0700
■ Power Factor, what is it? Fax: (07) 4775 1457
(Power Factor Correction) ROCKHAMPTON
208 Denison Street,
■ Talk about torque Rockhampton, Qld. 4700
(Motors and torque) Phone: (07) 4927 2277
Fax: (07) 4922 2947
■ What's the difference about safety TOOWOOMBA
(Safety devices and their application) Cnr Carroll St., & Struan Crt.,
■ Pollution of the airwaves Toowoomba, Qld. 4350
Phone: (07) 4634 4799
(Unwanted signals and their effects on motor protection devices) Fax: (07) 4633 1796
■ Some don't like it hot CAIRNS
(Temperature rise in electrical switchgear) 14/128 Lyons Street,
Bungalow, Qld. 4870
■ The thinking contactor Phone: (07) 4035 6888
(The development of the contactor) Fax: (07) 4035 6999
DARWIN
■ Electrical surges can be expensive 3 Steele Street,
(Electrical surges) Winnellie, N.T. 0820
Phone: (08) 8947 2666
■ Application guide to lamp selection Fax: (08) 8947 2049
(Industrial pushbutton controls)
Agents:
■ Start in the correct gear HOBART
(Application of different motor starters) 199 Harrington Street,
Hobart, Tas. 7000
■ Taking the 'hiss' out of DC switching Phone: (03) 6234 9299
(DC switching principles) Fax: (03) 6231 1693
LAUNCESTON
■ Electrical life of contactors 59 Garfield Street,
(How and why contactors are tested) Launceston, Tas. 7250
■ Don't forget the motor protection Phone: (03) 6344 8811
Fax: (03) 6344 4069
(Motor protection devices and application) BURNIE
■ Utilisation categories 6 Wellington Street,
(Electrical life of switches) Burnie, Tas. 7320
Phone: (03) 6432 2588
■ IP ratings what do they mean? Fax: (03) 6432 2580
(IP Ratings, use and meaning)
■ Set the protection Version 1
(MCCB breakers and application)

Editorial content: - Please address all enquiries to 'The Editor - 'NHP Technical News'
PO Box 199, Richmond Victoria 3121.

NHP Technical News, issue 28 TNL–28-4/99-14M

You might also like