You are on page 1of 2

Application Fixings

Linear Heat Detection Cable LHDC


General guidelines for installation of
LHDC:
The correct size and type of cable gland must
be used on all junction box etc.
Due to the high impedance of the Resettable
(Analogue) system, all connections at EOL, JB
and interposing cable must be protected with
silicone grease.
LHDC should be installed so that it is not
severely compressed and is not in contact with
sharp objects that may damage the outer
sheath.
LHDC minimum bend radius is 10mm
(Analogue) & 50mm (Digital)
LHDC must not be tensioned between supports
especially at changes of direction.
Neoprene sleeves should always be used in
conjunction with cable ties.
The below drawing represents various clips and The distance between supports shall be
fixings that can be used in a typical cable tunnel. between 0.6m and 1.2m depending upon
Patol supply a full range as shown over the page. available fixing positions.
The routing of LHDC shall be chosen to avoid
contact or close proximity with any local sources
of heat e.g. light fixings, steam pipes etc.
The minimum number of joints should be made
in any zone and these connections should be
with the recommended Patol junction box and
cable glands.
LHDC should be fixed using approved clips and
brackets.
In accordance with BS5389 pt1 2002, LHDC
should be spaced no more than 5.3m away from
any zone boundary or wall; and no more than
10.6m between adjacent runs.
Additionally LHDC should be installed such that
it is between 25mm and 150mm from the ceiling.

* The above general recommendations are for guidance


only, there may be conditions at site or client requirements
where some of the above criteria need to be varied.

Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@patol.co.uk D1183-6
Application Fixings
Linear Heat Detection Cable LHDC
Clips & Fixings T-Clip
Plastic
700-620
Upper temperature Limit +85°C
Lower temperature Limit –50°C
Material Degrades at +120°C
* Cable tie supplied separately.
Cable Tie - Black 200mm 700-600**
300mm 700-602**
** Stainless Steel version available
Neoprene Sleeve 700-608
UV / Chemical Resistant
Upper Temperature 120°C
Lower Temperature –40°C
P-Clip 700-639
Zinc with Rubber protection
5mm

Knock on Clip: Side MS Galvanised


2 to 3mm 700-611
3 to 7mm 700-612
8 to 13mm 700-613
14 to 20mm 700-614

Edge Clip MS Galvanised


1.5 to 6mm 700-616

Bracket: V Clip Spring Steel Stainless


700-632

L Bracket Stainless Steel 304*


30 x 30mm 700-640
70 x 25mm 700-645
210 x 25mm 700-646
* Stainless Steel 316 available upon request
Universal Support Stainless Steel 304*
70 x 45 x 25mm 700-635
70 x 100 x 25mm 700-638
200 x 100 x 25mm 700-637
* Stainless Steel 316 available upon request

Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@patol.co.uk D1183-6