Means of Egress system- Exit Access, Exit Door, Exit Staircases & Exit Discharge shall meet clauses to
the requirements of the following: MNBC.
1
Make sure Means of Egress is comply with General Requirements of Means of Egress.
1.A Ceiling Heights. 2.6.2.1
Minimum Ceiling Heights – 7’-6“.
1.B Protruding objects. 2.6.2.2
Horizontal projections shall not be more than 4"over any walking surface .
Exception: Door closer and stops shall not reduce less than 6’-4” .
Any horizontal projections shall not reduce the minimum clear width of accessible routes.
1.C Floor surfaces. 2.6.2.3
Floor surfaces shall be non slip surface.
1.D Level changes. 2.6.2.4
If level changes < 12”, <5% slope
Minimum 2 risers of steps
1.E Egress continuity. 2.6.2.5
The exit egress shall not be interrupted by any building elements.
1.F Elevators, escalators and moving walks. 2.6.2.6
Elevators, escalators and moving walks shall not be used in the exit route.
3 Make sure Exit Access shall not pass through a room which can be locked. 2.6.4
4 Check number of Exits and Exits Access Doorways from Space as per occupant load. 2.6.5
4.A Two Exits are needed, if Occupancy load is more than 50.
4.B If there is only one exit, it needs to comply Table 2.6.2.
4.C If the occupant located exceed 500, 3 Exits are needed. See Table 2.6.3.
8.C If the building is more than 4 storeys or more than 3 basement storeys, Smoke free
approach is needed. Check at 10.
11 External Approach
An External exit passage way or external corridor.
The opening for natural ventilation be face and open upon external open space.
12.B Ventilation
1 Naturally ventilated Smoke Stop Lobby.
minimum permanent fixed opening 15% of stair area.
located not more than 30ft from any part of lobby.
2 Mechanically Ventilated Smoke Stop Lobby.
Check with M&E consultant.
3 Cross-ventilated corridor (Smoke stop lobby).
Fixed opening in 2 External walls and not less than 50% of superficial area.
End of building or corridor of facial wall shall be not more than 30ft from any part of lobby.
Note: External wall of cross ventilated corridor shall be minimum 10ft set back from
boundary.
Doors shall swing in the direction of Egress if occupant load is more than 50 and a group of
Hazardous Occupancy and make sure not to block the Egress way while in open position.
If Building is more than 8 storey, Minimum 1 hr. rated door is needed.
Exception- If smoke stop lobby is provided, Minimum 1/2 hour rated or half of structural
fire resistance of Exist enclosure.
Means of Egress