Delta Remote Monitor Software Quick User Guide

1. Installing The Software


(1) PC is without RMS
(1-1)Install through Soft Disk
Follow the steps described below to install your RMS software
a (a)Turn on the host computer.
b (b)Insert your RMS disk 1 into Drive A or B.
(c)Run Windows.
c (d)From the program Manager select the drive with the RMS Disk1 and run
SETUP.
d (e)Msgbox appears, “Copying files, please stand by” Processing VB6STKIT.dll
(1 of 8)
e (f)Follow the message to insert Disk2, 3, and 4.
f (g)During setup Disk4, if Msgbox appears the following message, please click
‘OK’.
Q1:Setup cannot continue because some system files are out of date on your
system. Click ok if you would like setup to update these files for you now.
You will need to restart windows before you can setup again. Click cancel to
exit setup without updating system files.
A1: Please click ok.
(h)Then, if MsgBox appears the following message, please click ‘Yes’.
Q2:Do you want to restart windows now? If you choose ‘No’, you will not
be able to run setup again until after the system is rebooted at a later time?
A2: Yes
(i)After windows restart, insert Disk1 to run setup.exe again. And follow the
message to complete RMS installation.
(j)During installation process, if your computer appears the described below
message, please follow the given choice.
Q1:
A file being copied is older than the file currently on your system. It is
recommended that you keep your existing file.
Filename: c:\windows\system\MSDATSRC.TLB
Description: “”
Your Version: “”
Do you want to keep this file?
A1: Yes
Q2:

- Page 1 of 11 -
RMS Quick User Guide 112/21/2020

C:\windows\system\MFC42.dll
An access violation occurred while copying the file.
A2: Ignore
Then, the following message will appear.
Q3:
C:\windows\system\MFC42.dll
An access violation occurred while copying the file. If you ignore a copy
error, the file will not be copied. The application may not function properly
as a result. Do you want to ignore the error?
A3: Yes
Q4:
C:\windows\system\MSVCRT.dll
An access violation occurred while copying the file.
A4: Ignore
Q5:
An Error occurred while registering the file
C:\windows\system\EXPSRV.dll
A5: Ignore
(1-2)Install through Hard Disk
Please copy Disk1-4 into Hard Disk. And choose setup.exe to Run Setup.
And follow the steps described in (1).
(2) PC has been with RMS
(1-2)Remove old versions
Old version removed: with Windows menu 'Settings' /
'Control Panel' / 'Add/Remove' Programs -> RMS
Software old version selected and removed

(1-3) New version installed with processing "setup.exe".

(1-4) If you don’t want to remove old version, please install your
new RMS on different directory from your old one. By doing so, we
can avoid some problems from occurring.
2.Signing On to the system
Note: There are 2 levels of security for the software system. The Monitoring Level
allows access to all screens of the program in a view mode only. The Maintenance
level allow access to all screens as well as the ability to change settings, passwords,
etc.
Default passwords: Monitor Level: 12345

- Page 2 of 11 -
RMS Quick User Guide 112/21/2020

Maintenance Level: 67890

3.How to operate RMS


(1)Read online help
If you want to get more information about RMS, please click on the “Help” icon
on the Tool Bar of Fig1 to read Help File.

Fig1: On-line help.

(2)Input Password
After installing RMS successfully, first you must input password before running
RMS.
12345: default monitor password
67890: default maintenance password
(3)Check Connect profile information
(a) Double-click Connect Profile information, set correct data like ComPort (1-
4). For other setting of Connect profile information is similar to “Com port”.
That is, just input your desired data.
(b) Ex: RMS gives COM1 as the default Comport. For example, if you want to
change your COM port from 1 to 2, please modify connect profile
information followed these steps.
a. Click on Connect profile icon to expand connect profile information.
b. Click on “Com port: 1” icon to enter “Edit” mode, like Fig2.
c. Input your desired COM port, 2, number like Fig3. Then, RMS will
automatically attach “COM port:” to this field when you leave this

- Page 3 of 11 -
RMS Quick User Guide 112/21/2020

setting, like Fig4.


Note: Just input 2 and don’t modify “Com port: 1” into “Com port: 2”.

Fig2. Click on “Com port: 1” icon to enter “Edit” mode

Fig3. Just input your desired COM port number, 2.

- Page 4 of 11 -
RMS Quick User Guide 112/21/2020

Fig4. Complete change of COM port

(c) For example, if you want to modify default “Monitor password” form 12345
into “24690”, please just directly input “24690”and RMS will automatically
attach “Monitor Password” to this field.

(4)Create a site
If you use RMS for the first time, you must double click Area Name located on
the list box and click on “AddSite” icon on the Tool Bar of Fig5 to add a new
Site. Then, you will see a Site whose default name is “SiteName” on the list box
like Fig6.

- Page 5 of 11 -
RMS Quick User Guide 112/21/2020

Fig5. Click on “AddSite” icon to create a new site.

Fig6. After clicking “AddSite” icon, a new site, SiteName” is created and its
default information is displayed on the right hand of this screen.

(5)Check office profile information


After adding a new site, user must check the following information. About the
method of modifying site information, please click on Help icon shown on Fig1
to refer to on-line help.
(a) Connection way: Remote (use modem & telephone line) /Local (use null
modem cable)
So, if you don’t use modem to setup connection, please choose “Local” way.
(b) Input correct modem number, if connection way is “Remote” way.
(c) Choose “+24/-48” system based on your actual system.
(d) Select “110/120/220/380/480” AC operation mode based on your actual AC
input.
(e) Set “ES3000/ES1500/ES900/ES750/MCS3000/MCS1800-
Intelligent/MCS1800-Smart/MCS600/MCS5500” product model
According to your product modal, please choose the right product modal.
Ex: for Siemens customers: MCS1800-smart
for ES1500 product modal: ES1500
for ES3000 product modal: ES3000
for MCS3000 product modal: MCS3000
for Origin customers: MCS3000 / MCS1800-smart desponds on your

- Page 6 of 11 -
RMS Quick User Guide 112/21/2020

system
(f) Take some examples
(i) Product modal
If your system is MCS1800-smart, then click on “product model”
icon and a popup menu will appear shown on Fig7 and please choose
“MCS1800-smart”.
(ii) System voltage
Likely, if you want to change system voltage from +24V to –48V,
please click on “+24V” icon and a pop up menu will appear. Then,
choose “-48V” like Fig8.
(iii) Connection way
As for “connection way”, it’s similar to “product modal” & “system
voltage”. For example, if you want to change connection way from
“Remote” to “Local”, please click on “Remote” and a pop up menu
will appear. Please choose “Local” like Fig9.
(iv) AC operation mode
There are five operation modes you can choose, and they are 110Vac,
120Vac, 220Vac, 380Vac and 480Vac. For example, if you want to
change AC mode from “220Vac” to “110Vac”, please click on
“220Vac” and a pop up menu will appear. Please choose “110Vac” like
Fig10. You can refer to Table1 to choose the best choice of your AC
mode.

Fig7. How to change Product modal

- Page 7 of 11 -
RMS Quick User Guide 112/21/2020

Fig8. How to modify system voltage

Fig9. How to change “Connection way”

- Page 8 of 11 -
RMS Quick User Guide 112/21/2020

Fig10. How to change AC operation mode

ACH ACL
110Vac 111-165 55-109
120Vac 121-180 60-119
220Vac 221-330 110-219
380Vac 381-570 190-379
480Vac 481-720 240-479
Table1. List upper & lower limit of ACH & ACL for different AC operation
modes.

(6) Setup Connection


Click desired site, then “Connect” icon located on the Tool Bar will be enabled.
Next, click on “Connect” icon and a “Dialing” window will appear. After
clicking on “Dial” icon, RMS starts trying to setup connection
(7)Check the followings if your connection is failure.
Connection between RMS and CSU can succeed if users make sure the following is
right.
(a) Local way:
Choose correct “Com Port”, “Connection Way is Local” and your Null
modem cable(TXRX, RXTX) are OK.
(b) Remote way:
Choose correct “Com Port” and “Connection Way is Remote”, input the

- Page 9 of 11 -
RMS Quick User Guide 112/21/2020

correct “Modem Number” and every equipment like Modem and RS232
cable (TXTX, RXRX) are OK.
Besides, set right “System voltage: +24V or –48V“ and product modal.
(8)Data of RMS shows
After connection, there are some icons located on the left hand of screen.
For RMS, “---“ is no use piece of information.
(a) CSU Screen:
After clicking “Connect” icon on the tool bar, if the connection is
established and CSU responds, CSU Screen will appear to display a
graphical read time condition of system. Located at the left of the screen
are some buttons allows the user to have the ability to choose more
information.
(b) Rectifier Screen:
Click Rectifier icon to appear Rectifier Screen. The status contained on
the Rectifier screen includes:
(i) The status and output information for each rectifier in the system
(ii) Current Limit
Turn the selector and click the vertical scroll bar to display the
individual rectifier output current in digital and a line graph which is
updated every 5 seconds.
Click rectifier status to allow the maintenance user to quickly verify
the remotely turn off and turn on an individual rectifier.
(c) Alarm Screen
The alarm screen contains the system alarm status. The alarm
information is divided into different groups, like System Alarm Info and
Dc Breaker Trip Info. If system occurs alarm, then LED beside it will
blink.
(d) Print Screen
The Print Screen allows the user to have the ability to preview or print
the Current Data, Current Alarm, or Parm Report to a printer connected
to their PC. Besides, if user sets the proper print schedule, RMS will
automatically to print out Data Reports which is chosen through connect
profile information.
(e) LA Reset
This button turns off the audible Local Alarm of the PC, which is
activated when the user accesses a site in an alarm condition but first
your PC must be with Sound Card.
(f) PARM Screen

- Page 10 of 11 -
RMS Quick User Guide 112/21/2020

The user has the capability to remotely monitor, change parameter


settings except commissioning ones from the PARM screen.
(g) Exit
Click Exit icon to terminate the connection.