You are on page 1of 8

Air System Sizing Summary for Total

Project Name: Namayeshgah-register room 02/21/2020


Prepared by: Masoud 01:02PM

Air System Information


Air System Name Total Number of zones 5
Equipment Class TERM Floor Area 9170.9 ft²
Air System Type 2P-FC Location Isfahan, Iran

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Ventilation Fan Sizing Data


Actual max CFM 1573 CFM Fan motor BHP 0.09 BHP
Standard CFM 1297 CFM Fan motor kW 0.07 kW
Actual max CFM/ft² 0.17 CFM/ft² Fan static 0.20 in wg

Exhaust Fan Sizing Data


Actual max CFM 1573 CFM Fan motor BHP 0.09 BHP
Standard CFM 1297 CFM Fan motor kW 0.07 kW
Actual max CFM/ft² 0.17 CFM/ft² Fan static 0.20 in wg

Outdoor Ventilation Air Data


Design airflow CFM 1573 CFM CFM/person 6.16 CFM/person
CFM/ft² 0.17 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 8


Zone Sizing Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

Air System Information


Air System Name Total Number of zones 5
Equipment Class TERM Floor Area 9170.9 ft²
Air System Type 2P-FC Location Isfahan, Iran

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Small room 20.1 901 901 Jul 1800 10.9 269.1 3.35
Big room 38.4 1724 1724 Jul 1800 17.6 462.8 3.72
Salon 42.5 1910 1910 Jul 1800 27.2 1420.8 1.34
Conference 106.9 4805 4805 Jul 1800 69.2 3089.2 1.56
Lobby 103.1 4635 4635 Jul 1800 84.3 3928.8 1.18

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.0 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Small room 22.3 21.3 78.1 / 60.0 51.6 / 50.2 4.46 Jul 1800
Big room 41.8 40.2 78.2 / 60.2 52.1 / 50.6 8.37 Jul 1800
Salon 53.8 49.7 80.8 / 61.2 51.6 / 50.1 10.77 Aug 1800
Conference 130.4 121.3 80.3 / 61.1 52.0 / 50.5 26.09 Jul 1800
Lobby 131.5 107.9 77.4 / 61.2 51.2 / 50.0 26.31 Jul 1800

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Small room 14.1 69.1 / 86.7 1.41 901 0.000 0.000 69
Big room 22.8 69.4 / 84.2 2.28 1724 0.000 0.000 118
Salon 44.3 62.7 / 88.8 4.43 1910 0.000 0.000 364
Conference 106.6 64.2 / 89.1 10.66 4805 0.000 0.000 791
Lobby 93.1 70.3 / 92.8 9.32 4635 0.000 0.000 232

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Small room
Small room 1 20.1 Jul 1800 901 10.9 269.1 3.35
Big room
Big room 1 38.4 Jul 1800 1724 17.6 462.8 3.72
Salon
Salon 1 42.5 Jul 1800 1910 27.2 1420.8 1.34
Conference
Conference 1 106.9 Jul 1800 4805 69.2 3089.2 1.56
Lobby
Lobby 1 103.1 Jul 1800 4635 84.3 3928.8 1.18

Hourly Analysis Program v4.90 Page 2 of 8


Zone Sizing Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

Hourly Analysis Program v4.90 Page 3 of 8


Ventilation Sizing Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 1573 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Small room
Small room 1 269.1 10.0 901.3 5.30 0.06 0.0 0.0 68.9
Big room
Big room 1 462.8 17.2 1724.0 5.30 0.06 0.0 0.0 118.4
Salon
Salon 1 1420.8 52.8 1909.8 5.30 0.06 0.0 0.0 363.6
Conference
Conference 1 3089.2 114.8 4805.3 5.30 0.06 0.0 0.0 790.6
Lobby
Lobby 1 3928.8 60.8 4634.5 0.00 0.06 0.0 0.0 232.0
Totals (incl. Space Multipliers) 13974.8 1573.5

Hourly Analysis Program v4.90 Page 4 of 8


Air System Design Load Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 1421 ft² 94104 - 1421 ft² - -
Wall Transmission 21 ft² 84 - 21 ft² 245 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 1421 ft² 17427 - 1421 ft² 47643 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 9171 ft² 15954 - 9171 ft² 53175 -
Partitions 13887 ft² 26717 - 13887 ft² 89052 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 22010 W 57038 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 10236 - 0 0 -
People 256 53186 52423 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 8000 6000 - 0 0
Safety Factor 10% / 10% 28275 5842 10% 19012 0
>> Total Zone Loads - 311021 64265 - 209127 0
Zone Conditioning - 308129 64265 - 203545 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 1573 CFM 233 - 1573 CFM -233 -
Ventilation Load 1573 CFM 31816 -24893 1573 CFM 77835 0
Ventilation Fan Load 1573 CFM 233 - 1573 CFM -233 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 340411 39372 - 280913 0
Terminal Unit Cooling - 340411 39323 - 0 0
Terminal Unit Heating - 0 - - 280945 -
>> Total Conditioning - 340411 39323 - 280945 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 5 of 8


Zone Design Load Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

Small room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 74.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 139 ft² 9469 - 139 ft² - -
Wall Transmission 1 ft² 3 - 1 ft² 9 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 139 ft² 1809 - 139 ft² 4947 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 269 ft² 483 - 269 ft² 1609 -
Partitions 563 ft² 1010 - 563 ft² 3366 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 646 W 1674 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 10 2081 2051 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1823 205 10% 993 0
>> Total Zone Loads - 20058 2256 - 10923 0

Big room DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 74.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 326 ft² 21199 - 326 ft² - -
Wall Transmission 7 ft² 28 - 7 ft² 83 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 326 ft² 3977 - 326 ft² 10873 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 463 ft² 332 - 463 ft² 1107 -
Partitions 659 ft² 1182 - 659 ft² 3939 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1111 W 2879 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 500 W 1706 - 0 0 -
People 17 3579 3527 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3488 353 10% 1600 0
>> Total Zone Loads - 38369 3880 - 17603 0

Hourly Analysis Program v4.90 Page 6 of 8


Zone Design Load Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

Salon DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 74.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 1421 ft² 2549 - 1421 ft² 8496 -
Partitions 2422 ft² 4856 - 2422 ft² 16186 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 3410 W 8837 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3412 - 0 0 -
People 53 10985 10828 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 8000 6000 - 0 0
Safety Factor 10% / 10% 3864 1683 10% 2468 0
>> Total Zone Loads - 42503 18510 - 27150 0

Conference DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 74.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 478 ft² 30799 - 478 ft² - -
Wall Transmission 7 ft² 27 - 7 ft² 78 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 478 ft² 5822 - 478 ft² 15916 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 3089 ft² 5542 - 3089 ft² 18472 -
Partitions 4252 ft² 8523 - 4252 ft² 28407 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 7414 W 19214 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3412 - 0 0 -
People 115 23885 23542 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9722 2354 10% 6287 0
>> Total Zone Loads - 106945 25896 - 69160 0

Hourly Analysis Program v4.90 Page 7 of 8


Zone Design Load Summary for Total
Project Name: Namayeshgah-register room 02/21/2020
Prepared by: Masoud 01:02PM

Lobby DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 99.4 °F / 62.4 °F HEATING OA DB / WB 17.8 °F / 13.3 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 74.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 478 ft² 32637 - 478 ft² - -
Wall Transmission 6 ft² 26 - 6 ft² 75 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 478 ft² 5819 - 478 ft² 15907 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 3929 ft² 7048 - 3929 ft² 23492 -
Partitions 5991 ft² 11147 - 5991 ft² 37154 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 9429 W 24435 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 61 12657 12475 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9377 1248 10% 7663 0
>> Total Zone Loads - 103145 13723 - 84290 0

Hourly Analysis Program v4.90 Page 8 of 8