You are on page 1of 2

Line Current Calculator for Three Phase Systems See Dataforth AN110 for Reference

Three-Phase 4-wire Wye System with; Place Curser for Information-Instructions:


1. Individual single-phase line-to-neutral loads
2. Individual single-phase line-to-line loads System Calculation Results: Sequence {1 2 3} V12 at zero degrees
3. Individual balanced 3-phase wye loads Item I1 I2 I3 In P Q VA PF
4. Individual balanced 3-phase delta loads. Units A rms A rms A rms A rms KW KVAR KVA none
Value 320.6 324.9 389.1 89.6 118.7 36.3 124.1 0.956
Angle° -43.2 -167.2 70.1 56.3 0.0 90.0 17.0 LAG
L1, I1
Single Phase
L2, I2 Line-to Neutral Loads
L3, I3 Defines an unbalanced
N, IN 3-Phase Wye System
V31 at 120 degrees  f
radians/sec
L1, I1 Individual Single Phase V3N at 90 degrees
L2, I2 Line-to-Line Loads
L3, I3 Defines an unbalanced
N, IN 3-Phase Delta System

L1, I1 V12 at 0 degrees


Balanced 3-Phase Loads
L2, I2
L3, I3
N, IN

Wye Delta
V2N at -150 V1N at -30
degrees degrees
V AR s

V23 at -120 degrees


Q

PF P Watts

Total System Power Triangle Three-Phase Voltage Vector System


Line Voltage V12 Chosen as Reference
3-Phase System Volts
Line to Line 208 Line to Neutral 120

3-Phase Wye Output Input EFF PF I1 phasor I2 phasor I3 phasor P-wye


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 7 95 20.5 -30.0 20.5 -150.0 20.5 90.0
2 kva 6 0.800 L 16.7 -66.9 16.7 -186.9 16.7 53.1
3 motor 5 87 0.900 L 13.2 -55.8 13.2 -175.8 13.2 64.2
Totals 48.3 -49.03 48.3 -169.03 48.3 70.97

3-Phase Delta Output Input EFF PF I1 phasor I2 phasor I3 phasor P-Delta


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 3.5 100 9.7 -30.0 9.7 -150.0 9.7 90.0
2 kva 10 0.960 C 27.8 -13.7 27.8 -133.7 27.8 106.3
3 motor 7.5 91 0.920 L 18.6 -53.1 18.6 -173.1 18.6 66.9
Totals 53.4 -29.46 53.4 -149.46 53.4 90.54

L1-N Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-1N


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 5 95 43.8 -30.0 Q-1N
2 kva 3 0.950 L 25.0 -48.2
3 motor 4 87 0.900 L 31.7 -55.8 (VI*)
Totals 98.5 -42.68 I1N Totals

L2-N Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-2N


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 3 90 27.8 -150.0 Q-2N
2 kva 6 0.800 L 50.0 -186.9
3 motor 2 87 0.900 L 15.9 -175.8 (VI*)
Totals 89.9 -174.22 I2N Totals

L3-N Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-3N


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 6 95 52.6 90.0
2 kva 7 0.800 L 58.3 53.1
3 motor 7 85 0.850 L 60.2 58.2
Totals 164.5 66.09

L1-L2 Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-12


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 5 80 30.0 0.0 30.0 180.0 Q-12
2 kva 6 0.800 L 28.8 -36.9 28.8 143.1
3 motor 4 87 0.900 L 18.3 -25.8 18.3 154.2 (VI*)
Totals 74.1 -19.97 74.1 160.0 I12 Totals

L2-L3 Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-23


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 5 80 30.0 -120.0 30.0 60.0
2 kva 7 0.800 L 33.7 -156.9 33.7 23.1
3 motor 5 90 0.900 L 22.1 -145.8 22.1 34.2
Totals 82.5 -141.21 82.5 38.8

L3-L1 Loads Output Input EFF PF I1 phasor I2 phasor I3 phasor P-31


Load # Type HP KW KVA % 0 to 1 I or C RMS Angle RMS Angle RMS Angle
1 kw 5 80 30.0 300.0 30.0 120.0
2 kva 3 0.800 L 14.4 263.1 14.4 83.1
3 motor 5 85 0.870 L 24.2 270.5 24.2 90.5
Totals 66.0 281.8 66.0 101.80