Professional Documents
Culture Documents
INTRODUCTION
Historical Perspective
Iron oxides present in boiler water have caused problems since the dawn of boilers. However, in
the beginning, iron deposits were not the major problem or root cause of most boiler tube
failures, as were hardness scale deposits. As the design of boilers evolved from low pressure
riveted drum-type boilers to today’s modern high pressure, high heat flux, thin-walled water tube
boilers, the requirement for higher purity boiler feedwater also occurred. The effective removal
of Ca and Mg from boiler feedwater by pretreatment techniques such as lime softening, sodium
zeolite softening, ion exchange demineralization and reverse osmosis has shifted the cause for
boiler tube failures to be predominately due to iron deposits on the heat transfer surface. These
deposits cause under-deposit corrosion problems and act as insulators, impairing heat transfer
which cause the boiler tube to overheat and ultimately rupture.
The energy crisis in the early 1970s, caused by the OPEC oil embargo, had a major impact on
industry and the Boiler Iron Story. The loss of cheap energy and the need to conserve energy led
industry to focus on returning more and more steam condensate as a source of boiler feedwater
because of its valuable Btu content and relative high purity. However, the consequence of
increasing the amount of returned condensate to the boiler was the increased amount of iron
oxide corrosion products entering the boiler. A majority of the corrosion products that deposit in
the boiler originate in the condensate system. Corrosion of the feedwater piping, economizer and
boiler, as well as the iron entering with the make-up water, are other sources contributing to the
boiler iron deposit problem.
However, since the late 1970s, with the introduction of synthetic polymeric dispersants and
especially with Ondeo Nalco’s introduction of the revolutionary all-polymer treatment program
Transport-Plus in 1982, the term “boiler iron control” has come to mean feeding polymeric
boiler iron dispersants. In general, we have lost focus on prevention and have adopted the single
Over the past 20 years we have learned a lot about iron deposition and control in boilers through
extensive laboratory research, field trials, collaborative research studies with Argonne National
Laboratory and through published literature from EPRI and others. Iron transport studies
conducted in the field and in our laboratory’s experimental boilers (Ondeo Nalco’s and
Calgon’s) indicate that the majority of the iron entering the boiler remains in the boiler even
when dispersants are fed.
A major reason for the poor transport results is due to the fact that boilers are not designed to
effectively remove suspended materials. The boiler continuous blowdown line is designed to
efficiently remove soluble species and is not optimized to remove particulate matter. It will
remove some particulate but it is not isokinetically designed to remove two-phase material
(liquid + solids). This is why intermittent manual blowdown of the mud drum and water wall
headers is practiced. The other reason for poor transport is that iron reaching the steam
generating surfaces of the boiler will deposit there.
Does this mean that polymers don’t work and have no value? No, research work has shown that
polymers do affect the rate of iron deposition on the heat transfer surfaces of boilers and, thus,
are an important aspect of our overall boiler iron control strategy. Polymers can slow down the
rate of iron deposition and help keep the heat transfer surfaces cleaner longer than if they were
not used.
Although the polymers slow the deposition rate down, iron oxide deposition rate follows first-
order kinetics with respect to iron concentration. In addition, the higher the heat flux, the faster
the rate of deposition. These two findings, coupled with the fact that most of the iron doesn’t get
transported through the boiler, means that the primary method to control iron deposits in boilers
is to prevent iron from entering the boiler in the first place. This statement is strongly supported
by the cycle chemistry guidelines published by ASME, EPRI, VGB, Japanese Boiler
Manufacturers and the British Boiler Standards. These guidelines stress the importance of
keeping the feedwater iron concentration very low (ppb).
As a result of this collective knowledge, Ondeo Nalco’s boiler iron control best practices strategy
today concentrates on the “iron control triangle offense” of prevention.
iron
control
PRETREATMENT BOILER
OPTIMIZATION CORROSION
First, prevent iron contribution from the make-up water by optimizing make-up water
pretreatment iron removal. Secondly, minimize iron returned via the steam condensate system
by inhibiting condensate corrosion and maximizing the removal of any iron present in the
returned condensate through use of condensate polishers/filters and automatic dump systems.
The third leg of the triangle offense is to minimize corrosion from boiler feedwater and boiler
water.
Our “triangle offense” requires us to implement the engineering approach or MOC (mechanical,
operational and chemical) approach, not just a chemical treatment approach, to be successful.
For instance, it is critical to do iron profiling or fingerprinting of the make-up water pretreatment
system, the condensate system, at the deaerator, at the inlet and outlet of the economizer and the
boiler blowdown. It is necessary to determine where the iron is coming from, how much iron is
there, and to determine the form of the iron, (soluble (Fe+2 = FeII) vs. particulate) to identify if it
is a result of active corrosion or migration of old iron oxide corrosion products. Determining the
iron removal efficiency of plant equipment, such as condensate polishers, ion exchange units,
carbon or sand filters, magnetic filters, etc., and optimizing their performance is very important.
Determining if these units are back-washed properly and rinsed down long enough prior to
returning the units back into service mode is important because, if done improperly, it may lead
to slugs of particulate iron reaching the boiler. So, you can see that the Engineering Approach is
an integral part of our Boiler Iron Control Triangle Offense!
The iron prevention technologies available in our triangle offense are summarized below.
Caustic
Phosphate Products (i.e., BT line)
Organic and Inorganic Oxygen Scavengers
Sulfite
Erythorbic acid (Sur-Gard)
Carbohydrazide (Elimin-ox)
Diethylhydroxyl Amine (DEHA)
Condensate Neutralizing Amine Products
Filming Amines
Non-amine Filmers (ACT)
Ion Exchange Resin Cleaners (for iron & organic foulant removal)
Iron dispersants are categorized as iron control defensive chemistries. They are the second prong
of Ondeo Nalco’s overall boiler iron control best practice strategy. Ondeo Nalco sells three
different types of polymeric iron dispersants; polyacrylate (Transport-Plus,™ soft water),
polyacrylate styrene sulfonate copolymers (NexGuard™) and polymethacrylate (Transport-Plus,
demineralized water).
Preventing iron from entering the boiler is, by far, the best approach to eliminating boiler tube
failures caused by iron deposits. Feeding small doses of polymeric iron dispersants (sub-
stoichiometric to iron) is warranted because they can slow down the iron deposition rate. It is
also recommended that one not operate the boiler at excessively high boiler cycles because the
deposition rate is iron-concentration dependent. Best practices suggest operating at 2%
blowdown (50 cycles).
IRON
As shown in Table I, iron oxide deposits are insulative with hematite deposits being more
insulative than magnetite. Figures 1 and 2 illustrate the differences in metal temperature
between a clean boiler tube and one bearing a deposit of magnetite.
Figure 1
Table II
Soluble and suspended materials concentrate up at the vapor/liquid interface of the bubble
(meniscus of the steam bubble) as well as at the point of bubble attachment to the boiler tube.
Figure 3
Conceptually, Figure 3 is all right and easy to understand. However, the deposition process is far
more complicated. A collaborative research project conducted in the mid-1990s by Ondeo Nalco
and Argonne National Laboratory, studied the mechanism of iron deposition under nucleate
boiling conditions. Factors affecting deposition of iron were found to include pressure,
temperature, heat flux, iron concentration, pH, surface roughness (macro and micro), time of
bubble attachment, flow rate and other impurities present in the water.
Our research showed that hematite particles tended to agglomerate during the formation, growth
and release of the steam bubble. Interestingly, it was found that the amount of iron deposited on
the surface was sixty times more than what is predicted from the simple evaporation to dryness
deposition model shown in Figure 3. This finding suggests that there is a complex particle-
bubble interaction. It is hypothesized that since the steam vapor inside the bubble is less polar
(more hydrophobic) than the boiler water, this causes the hematite particles in the surrounding
boiler water adjacent to the bubble to migrate toward and concentrate up in the steam bubble
meniscus. Then, through capillary and eddy current effects, the iron is drawn down to the
surface and deposited at the bubble attachment point.
Corrosion of the mild steel components in the pretreatment and boiler system is the major source
of iron entering the boiler. There are a number of corrosion mechanisms, some of which this
paper will focus upon. For a more in-depth coverage of corrosion failures in boilers, refer to the
book “The Nalco Guide to Boiler Failure Analysis” authored by Robert D. Port and Harvey M.
Herro.
Factors affecting mild steel corrosion in boiler systems include pH, temperature, heat flux,
dissolved oxygen and CO2, flow, ionic strength, suspended solids, caustic, acids, and boiler
treatment chemicals such as chelants and polymers.
Mild steel is used in the construction of boiler systems because of its mechanical strength, high
thermal conductivity properties and low cost. In addition, mild steel at high temperature under
alkaline reducing conditions forms a protective thin adherent magnetite oxide (Fe3O4) layer on
the surface which is self limiting and protects the base metal from the corrosive aqueous
environment. This is why the recommended pH range for boiler water is 9 to 12.0. (see curve
below)
Fe + 2 H2O Fe + 2 OH- + H2
+2
(1)
Fe + 2 OH- Fe(OH)
+2
2 (2)
3 Fe(OH)2 Fe3O4 + 2 H2O + H2 (3)
The formation of ferrous hydroxide (Equation 2) is the rate-limiting step to the overall
production of magnetite and it is slow below 200°C. The controlled corrosion process of
passivation is achieved as the metal surface goes from an actively corroding state (Equation 1) to
an inactive steady state (Equation 3). Since hydrogen is released as the metal becomes passive,
hydrogen evolution accompanies the formation of the magnetite film. It has been widely
recognized that monitoring hydrogen in the steam of a boiler is an indirect measure of the boiler
corrosion activity.
In addition, it should be noted that Fe+2, ferrous ions, are the first product of corrosion (Equation
1). Measuring the concentration of Fe+2 is an important method to identify active corrosion in
boiler systems. Quantifying Fe+2 is an important part of our iron control prevention strategy.
Any condition leading to the damage of the magnetite protective oxide film will cause an
increase in corrosion of the base metal. Things such as mechanical and thermal stresses can
fracture the oxide layer, creating micro-cracks which expose the base metal and allow the
corrosion reactions to proceed (i.e., corrosion fatigue cracking and stress corrosion cracking).
These stresses can eventually lead to exfoliation of portions of the oxide layer, which again
exposes the base metal to further corrosion and also allows the potential migration of particulate
iron to reach the boiler and deposit on the steam generating surfaces. For example, when a paper
machine comes back on line after being down because of a paper break or some other reason,
high levels of suspended iron are initially found in the return condensate. The longer the paper
machine is off line, the worse the situation (high iron content for longer period of time in the
condensate). The reason for the iron throw is that the mild steel components went through a
contraction and expansion cycle during the outage/startup period, causing the oxides to fracture
and exfoliate because they are less ductile than mild steel. Additionally, as the system cools
down, air is sucked in and oxygen corrosion attack occurs.
Chemical attack leading to dissolution of the magnetite protective layer will also increase the
corrosion of mild steel. For instance, high concentrations of caustic or acid can lead to severe
corrosion problems in boilers. In addition, chemical species, which interact or complex with the
ferrous ion, such as chelants, chlorides, sulfates, polymers and hydroxyl ions, may prevent the
formation of magnetite by limiting reactions shown in Equations 2 and 3. The net result of this
effect could be an increase in corrosion due to an increase in the rate of metal dissolution.
Anodic reaction:
+2
Fe° ==> Fe + 2e- (Oxidation) (1)
Cathodic reaction:
½ 02 + H20 + 2e- ==> 2(OH-) (Reduction) (2)
Metal loss occurs from the anodic part of the metal (anode). In this case, iron (Fe°) is lost to the
water solution and is oxidized to the Fe+2 ion. As a result of the formation of Fe+2, two electrons
are released to flow through the steel to the cathodic area (cathode) where oxygen is reduced to
hydroxide ions at the surface of the metal.
When dissolved oxygen is present in the feedwater, attack to the feedwater line, feedwater
heaters, and economizer can be expected. The severity of the problem depends on the
concentration of dissolved oxygen and the water temperature. One of the most serious aspects of
oxygen corrosion is that it generally occurs as pitting, so the attack is concentrated in a small
area of the total metal surface. With this type of corrosion, failures can occur even though only a
relatively small portion of the metal has been lost. The corrosion products can also migrate to
the boiler and cause iron deposition problems.
A poorly operating deaerator will admit oxygen to the boiler system. Oxygen corrosion can be
severe in the deaerator, especially along the water line, when scavenging chemicals are not being
fed to the storage section of the unit.
Feeding an oxygen scavenger has the dual purpose of scavenging oxygen and preventing the
generation and migration of iron into the boiler that is a direct result of the oxygen attack of mild
steel. This is why scavengers are listed as being a part of our triangle offense preventative
technologies.
Oxygen scavengers work by scavenging the dissolved oxygen and converting it into water. The
reaction with oxygen is temperature, pH and time dependent. The higher the pH and
temperature, the faster the scavenger reacts with oxygen. The presence of transition metals such
as copper and cobalt are known to catalyze these reactions. Some oxygen scavengers like
erythorbic acid, carbohydrazide, hydrazine and diethylhydroxyl amine are known to promote
mild steel passivation. The passivation mechanism is complex and not fully understood at this
time. However, the resulting benefit of a passivating-type oxygen scavenger is a reduction in
iron contamination of the boiler feedwater which translates into a reduction of iron entering the
boiler.
Oxygen entering the boiler will flash into the steam and travel into the steam/condensate system.
Where the steam condenses, oxygen will partition between the liquid/vapor phase and the
dissolved oxygen will cause corrosion to occur. This, in turn, creates two problems: a loss of
metal in the condensate system, and the return of that iron to the boiler where it will form
deposits, causing loss of heat transfer, and ultimately resulting in overheating of boiler tubes and
metal failure.
Oxygenated treatment involves the addition of oxygen to the boiler feedwater. Under OT
conditions, a mixed oxide matrix consisting of both magnetite (Fe3O4) and hematite (Fe2O3)
protects the mild steel surface.
The following stringent criteria are required for operating boilers on OT:
EPRI feedwater guidelines for drum boilers and once-through boilers are listed below to show
you how pure the feedwater needs to be in order to practice this program.
FAC is a process whereby the normally protective oxide surface dissolves into a moving fluid.
Metal loss occurs by the interaction of electrochemical (corrosion) and physical effects. In the
case of carbon steels, this occurs under very specific, well-defined conditions. Figure 4 shows
the effect temperature and pH have on the solubility of magnetite.
Figure 4
Effect of Temperature and pH on Magnetite Solubility
Note the marked increase in the solubility of magnetite at 300°F (150°C). This explains why
carbon steel piping, carrying water at greater than 8-10 ft/s, at a temperature of 300°F +/- 50°F
and pH below 9.2, is a primary candidate for FAC. This is why it is important to have
feedwater pH above 9.2 to minimize FAC. The presence of complexing agents such as
chelants and polymers can exasperate the severity of FAC attack because of their ability to
solubilize magnetite. EPRI reports that FAC may be worse in the presence of an oxygen
scavenger.
Some components that have experienced FAC include feedwater control valve by-pass lines,
feedwater heater tube sheets and tube-inlet ends, feedwater piping (especially areas in and
Due to the extremely localized nature of FAC and the lack of appropriate sample points, it is
rarely possible to identify individual (local) points of FAC damage in a feedwater system by
performing the Fe+2 test or dissolved H2 testing. It was, however, possible to detect an
appreciable Fe+2 pick-up across an economizer of a system known to be experiencing FAC-type
feedwater piping failures. Apparently, the FAC characteristics of the feedwater, together with
the entrance/exit turbulence conditions, led to additional FAC activity in this economizer.
Feedwater chemistry (i.e., pH and ORP) can be optimized based on this measurement.
There is an engineering solution to this problem. It has been shown that increasing the chrome
and molybdenum concentrations of the carbon steel can drastically reduce FAC rates. It is,
therefore, recommended that carbon steel in susceptible regions be changed-out. New alloys
should have greater than 1% Cr as an alloying addition (>5% Cr + Mo is even better, but more
expensive and, therefore, often not practical). When component thinning is detected,
replacement of the affected component with a higher alloy (1-2% Chromium) such as T-22, T-
11, P-22 or P-11 should be considered.
Graph 1
Graph 2
Graph 4
Since chelants and polymers can be corrosive, it is very important from the iron prevention,
triangle offense perspective, to do iron profile measurements throughout the feedwater system,
downstream of the treatment feed point and in the boiler blowdown. Monitoring the soluble
(Fe+2) and total iron picked up across the economizer vs. treatment dosage will provide the
following information:
a. How much iron is being moved out of the economizer into the boiler?
b. How much of that iron is due to active corrosion (may indicate FAC attack)?
c. Can the product dosage be increased or must it be reduced to avoid corrosion and iron
deposition problems?
d. Does the product feedpoint have to be relocated downstream of the economizer?
e. Similar information can be gathered by monitoring the amount and the form of iron present
in the blowdown.
Figure 5
Figure 6
The most frequently used chemical treatment approach for combating caustic corrosion in high
purity, high-pressure steam boilers/generators, is based on phosphate pH buffer chemistry. A
prerequisite for this treatment approach is that the feedwater must contain no hardness. This type
of chemical treatment utilizes the equilibriums established between the three ortho-phosphate
species found in boiler water in order to provide the necessary pH buffering of the water:
As the hydrogen ions are replaced with sodium, the phosphate basicity increases, i.e.,
monosodium phosphate which has a sodium to phosphate molar ration of 1.0 is more acidic then
tri-sodium phosphate, Na3PO4 (3.0 Na:PO4 molar ratio).
There are four basic types of phosphate/pH control chemistries utilized in the treatment of
industrial high-pressure boiler systems:
Graph 5
Unfortunately, this treatment program did not totally eliminate caustic corrosion problems in
boilers due to problems caused by phosphate hideout. Dirty boilers and boilers that experience
steam load swings are primary candidates for phosphate hideout. What happens during
phosphate hideout? The boiler water pH increases with a corresponding decrease in the boiler
water phosphate concentration. Under these conditions, boiler operators would feed di-sodium
or mono-sodium phosphate to the boiler in an attempt to keep the boiler water in their operating
control ranges for pH and PO4. When the boiler steaming load returns to normal or the boiler is
taken off-line, the boiler water pH would drop and the PO4 concentration increase. The drop in
boiler pH can be significant, with boiler water reaching a pH of 7.0 or below. As a result,
hideout can cause significant boiler corrosion and iron deposition problems. The practice of
chasing phosphate hideout by feeding an acid phosphate is dangerous because it can cause
localized acid phosphate attack.
The hideout problem was originally thought to be due to the hydrolysis products of tri-sodium
phosphate having different solubilities, resulting in incongruent precipitation of ortho-
phosphates. As boiler water is evaporated and solids concentrate locally (e.g., beneath a porous
deposit in a water wall tube), the dibasic phosphate (Na2HPO4) reaches its solubility limit first
and begins to precipitate. The remaining solution becomes rich in free caustic soda with the
potential to produce localized corrosion. When the steaming load drops, the precipitated acid
Subsequent studies by Westinghouse and others showed that, at higher temperatures, the
incongruent point could be at an Na:PO4 ratio as low as 2.6. This information led to the
development of Congruent Phosphate Control for high-pressure boilers operating on
demineralized feedwater. Congruent control programs typically operate between Na:PO4 molar
ratios of 2.3 and 2.6 as shown in Graph 5. Control is based entirely on the relationships of boiler
water pH and PO4 readings. Direct measurements of boiler water sodium are not used in
congruent control. If sodium were directly measured, misleading Na:PO4 ratios might be
obtained due to the presence of neutral sodium salts.
Recent work by EPRI and CEA (Canadian Electric Association) found the primary mechanism
for phosphate hideout was the chemical reaction between sodium phosphate (mono and di) and
magnetite to form the iron sodium phosphate compound called marcite. This led to the
development of EPT. As phosphate concentrates and reacts or precipitates locally, phosphate is
removed from the bulk boiler water down to very low remaining equilibrium levels. Thus, boiler
water PO4 might drop from a normal 5 ppm down to 1 ppm or less during hideout. Attempts to
maintain original boiler water PO4 levels by adding phosphate during hideout are usually futile
because the ongoing reaction or precipitation simply continues to remove boiler water PO4 down
to the equilibrium level. Adding phosphate just adds to the fouling of tube surfaces at the
localized precipitation sites and may actually initiate corrosion by contributing to the generation
of free caustic or acid phosphate.
Equilibrium phosphate control (EPT), therefore, makes no attempt to carry boiler water PO4
above its hideout equilibrium level, how ever low that may be. Equilibrium PO4 levels vary
from boiler to boiler, depending on the severity of hideout conditions. The EPRI guideline for
EPT control is shown in Graph 6.
Only tri-sodium phosphate and (when needed) caustic are recommended for equilibrium
phosphate treatment. Monosodium, di-sodium, or polyphosphates are not recommended.
BT Products
Feeding BT products with TRASAR technology differentiates us from our competitors and those
feeding commodity phosphates. It allows us to automate the chemical feed of the product,
determine boiler cycles and control boiler cycles, and it gives us a tremendous advantage in
troubleshooting boiler water changes. For instance, if boiler water pH increases and goes out of
the pH vs. the PO4 control box, is it due to hideout? Having TRASAR gives us the ability to
quickly answer that question. If the boiler water PO4 concentration equals that predicated by the
TRASAR reading, the pH change is not due to hideout. It is also not due to a cooling water leak
since hardness contamination would have caused the boiler PO4 to precipitate, resulting in lower
than TRASAR-predicted levels. Consequently, in this example, the pH change is most likely
due to Na leakage from the demineralizer and/or condensate polisher, or some type of process
contaminant.
CONDENSATE CORROSION
A majority of the corrosion products that deposit in the boiler originate in the condensate system.
Preventing condensate iron corrosion and the migration of the iron hydroxides and oxides,
produced by the corrosion process, to the boiler feedwater is critical to our iron control
strategy! The major cause of iron corrosion in steam condensate systems is dissolved CO2
(forms carbonic acid) and dissolved oxygen. The CO2 comes from the breakdown of organics,
carbonates and bicarbonates present in the boiler feedwater. Since condensate is extremely pure,
even small quantities of carbon dioxide can significantly lower condensate pH and increase its
corrosivity. Air in-leakage to the boiler system is also a route in which CO2 contamination can
enter, in addition to oxygen. The CO2 corrosion reactions are shown below.
Carbon dioxide in the steam can be decreased by removal of bicarbonate and carbonate alkalinity
in the feedwater. This can be accomplished by a well-controlled lime softening program, or by
dealkalization, demineralization, or degasification processes. (A small amount may also be lost
by deaeration, depending on make-up water pH.) Although alkalinity in the feedwater can be
reduced, a certain amount is typically retained to maintain proper boiler water alkalinity. Thus,
some CO2 will always be present in the steam.
When oxygen is present in condensate systems, the source should be located and corrected.
Filming inhibitors like Ondeo Nalco’s ACT (non-nitrogen) or filming amines are used to form a
protective film on the metal surfaces. Volatile oxygen scavengers/metal passivators can also be
used. For large complex steam condensate systems, satellite feeding additional condensate
corrosion inhibitors to troubled areas is often practiced.
The above treatment programs are a part of our preventative iron control triangle offense
strategy! For a more detailed discussion on condensate treatment, refer to Boiler Best Practices
Chapter 7 and the WWTS Document Library.
Ammonia
Ammonia is present in some raw waters. Another source is chemical breakdown of boiler water
additives such as hydrazine or hydrazine alternatives (ELIMIN-OX, DEHA (diethyl
hydroxylamine), MEKOR (Drew’s methylethylketoxime), some polymers (e.g., acrylamide-
based TRANSPORT-PLUS for soft water systems) and amines. Ondeo Nalco’s ACT and
NexGuard programs provide no ammonia to the boiler system. You should be familiar with the
ammonia contributions from these chemicals.
Ammonia has a high volatility and will distribute unevenly across a condensate system, raising
the condensate pH only at certain areas of the system (typically, the final condensation
locations). This can give a false sense of corrosion protection for the entire system if an
inadequate number of sample points are monitored.
The main source(s) of ammonia present in a condensate system should be located and reduced or
eliminated whenever possible. In systems with mixed metallurgy and/or insufficient sample
points, the Ondeo Nalco proprietary filming echnology will provide protection against ammonia
if the proper application pH range is maintained.
Good corrosion control in the condensate system requires a thorough and accurate understanding
of the condensate system. The identification of system components where phase changes take
place (flashing, condensing and venting) are critical to understanding a system’s treatment
requirements. A complete system profile of pH, iron, silica, hardness and conductivity is a great
starting point for benchmarking performance. Properly cooled sample points need to be
strategically located throughout the system to do this profiling.
Some condensate systems have condensate polishers, carbon filters, or magnetic filters to remove
iron from the returned condensate. It is important to monitor and optimize the performance of
these units with respect to iron removal. Using iron resin cleaners to maintain the cation resin
integrity is important. Installation of automatic condensate dump systems, based on
conductivity, turbidity or particle monitoring, is an important method of insuring only good
quality condensate is being returned back to the boiler. Tracking the frequency of dumping can
help identify problem sections in the condensate system and can provide guidance on where to
focus problem-solving efforts.
Polymers do play a role in our iron control best practices strategy. We look at them as our last
defense. Polymers have the ability to inhibit agglomeration of iron particles, keeping them
dispersed in the boiler water, and to reduce the rate of iron oxide deposition on the heat transfer
surfaces. The three types of polymers we use are polyacrylate, polymethacrylate, and
copolymers of acrylate/styrene sulfonate. These anionic polymers absorb onto the negatively
charged iron particles and prevent the particles from agglomerating through charge-charge
repulsion and by steric hindrance.
Figure 8 illustrates the polymer iron particle interaction. Molecular weight and pH can affect the
dispersant properties of anionic polymers. In general, as the pH goes up, the dispersant activity
It doesn’t take much polymer to effectively disperse the iron. Sub-stoichiometeric amounts are
effective. Graph 7 illustrates this point. These results are from experiments run in our laboratory
boilers. Boilers were operated for two hours at a heat flux of 140,000 Btu/ft2/hr and the amount
of iron deposited during that time period was determined.
At the start of each experiment, the boiler water suspended iron was 11 ppm. The polymers were
dosed on a ppm active polymer basis. Both polymers were effective in reducing the rate of iron
deposition, with polymethacrylate being slightly better.
Graph 7
Consequently, these polymers can cause feedwater and boiler water corrosion problems. It is
important to monitor the generation of soluble iron (Fe+2 = Fe II, ferrous) and total iron (Fe+2 +
Fe+3) in the feedwater and blowdown when feeding polymers to determine what should be the
optimum product dosage. Total iron testing alone of the feedwater and blowdown cannot
differentiate between iron oxide particulate and active corrosion. Graph 8 shows iron
concentration in the blowdown of a paper mill boiler.
Graph 8
As the dosage of the polymer treatment increases, the concentration of particulate iron, Fe(III),
increases in the blowdown, then plateaus and remains constant regardless of increases in
dispersant dosage. The initial increase represented the improvement in iron oxide particle
dispersion caused by the polymer. As the polymer dosage was increased further, ferrous iron,
[Fe(II) or Fe+2] concentration began to rise in the blowdown, until a near linear relationship
between increased dosage and increased Fe(II) was established. This data showed that
Another rule of thumb is that the boiler water Fe+2 concentration should never be greater than the
feedwater Fe+2 concentration times cycles. And feedwater Fe+2 should be low (2-5 ppb) in a
well-protected system.
Molecular weight, flow, temperature, pH and polymer concentration affect the corrosivity of
anionic polymers toward mild steel. Low molecular weight anionic polymers were found to be
more corrosive than high molecular weight polymers. Designing a polymeric iron dispersant for
boiler applications requires optimizing chemical structure and molecular weight.
Competitive Polymers
All of our competitors have the ability to use polyacrylate-, polymethacrylate- and
polyacrylamide-based polymers since we do not have a unique patent position covering these
polymers. Some competitors use maleic anhydride polymers and copolymers; however, our
studies indicate that maleic anhydride polymers are not thermally stable and cannot be used in
high pressure boilers.
Even though our competitors can sell polymers similar to ours, it doesn’t necessarily mean
that they are equal to our polymers, especially with respect to their potential corrosivity.
This is why it is important to do iron profile studies of any competitively held account that is
feeding a polymer (or chelant). We need to ascertain whether their polymer (chelant) is eating
up the feedwater system, economizer and/or the boiler. If it is generating more iron in the boiler,
it is also increasing the potential of iron deposition on the critical heat transfer surfaces!
Furthermore, we have the advantage since the competition doesn’t believe in testing for Fe(II).
They focus only on total iron analysis. As a result, we could point out a problem to the
customer, of which the competition is unaware, and possibly obtain the business.
GE Betz came out in the early-/mid-1990s with two new polymer products: Ultrasperse (a
copolymer of acrylate and an allyl polyether) is for use in boilers operating on soft water as an
all-polymer treatment and HPT-2 (polyisopropenyl phosphonic acid) is marketed as an iron
dispersant for medium to high pressure boilers. HTP-2’s structure is shown in Figure 10. GE
Betz also holds a patent for methacrylate styrene sulfonate copolymers as iron dispersants but, to
our knowledge, they are not practicing this expensive technology.
The corrosiveness of polyacrylate vs HTP-2 was determined using our experimental boilers. The
boiler test results are shown in Graph 9. Under these test conditions HTP-2 was found to be
seven times more corrosive then our polyacrylate.
Graph 9
Ultrasperse was tested as an all-polymer boiler internal treatment in our experimental boilers and
its performance was compared to TRANSPORT-PLUS. The tests showed that Ultrasperse gave
poor calcium and magnesium transport results. Iron deposition studies also showed that the
Ultrasperse product was not as good as our polymethacrylate product N-7205 (see Graph 10).
The Helamin boiler products, sold by Filtro S. A., Switzerland, represent a line of
multifunctional products that contain one or more of the following components: polyacrylate,
neutralizing amines, organic oxygen scavengers and the filming amine Duomeen OL. The
Helamin literature claims that the products can improve boiler iron transport, cleanliness and
corrosion protection. However, with the exception of the particular filming amine, all other
components have been used as boiler treatments for a long time. As a result, one would expect
the products to provide a degree of good performance because they are using currently practiced
boiler technology. The question is whether their filming amine provides exceptional boiler iron
control performance with respect to iron deposition and corrosion inhibition compared to our
technology.
As a result, research work was conducted to determine the mild steel corrosion inhibition and
iron dispersion properties of Duomeen OL. Its performance was benchmarked against Ondeo
Nalco’s filming amine and polymer technology. Structures of the two filming amines are shown
below. One can see that they are very similar in structure.
C18
C18
Internal Use Only
Helamin filming amine (Duomeen OL or N-oleyl-1,3-propanediamine)
Boiler iron control test results indicate that both amines agglomerate and plate out iron on the
steaming surface (heat transfer surface), as well as on other boiler surfaces, and are poor iron
dispersants. Duomeen OL was slightly less agglomerating than our filmer was.
Polymethacrylate (N-7205) was found to be a much more effective iron dispersant than either
amine (see Graphs 11 and 12). Since Helamin products are multifunction, the combination of
Duomeen OL plus polymethacrylate was evaluated to determine if this improves the iron
deposition control properties.
Graph 11
Graph 13 shows that combining the filmer with polymethacrylate is less effective than
polymethacrylate alone. Results from the electrochemical and condensate simulation corrosion
studies indicate that the inhibitor performance of Duomeen OL does not exceed that of our amine
filmer and may be slightly less effective. The overall conclusion from our investigation is
that the Helamin filmer did not provide any significant improvement in iron control for
boilers and that our technology was better.
Graph 13
Careful sampling is necessary to ensure that the sample is representative and does not become
contaminated. For a detailed explanation of proper sampling techniques, please refer to Ondeo
Nalco Technifax® 141. However, a brief description of sampling follows.
Samples should be continuously running. Stainless steel sample lines (¼ to ⅜-inch) must be
installed to ensure that corrosion products (iron oxide and copper oxide) are not contributing to
the sample by the sample line. Sample line lengths should be minimized to minimize the time
lag and the potential of contaminates adhering to the piping and coming out of the sample
stream. The sample should be cooled to below 90°F (32°C) to prevent flashing of the volatile
components (i.e., NH3, CO2, amines) that would cause a change in sample characteristics. The
sample line should flow on a continuous basis at a rate of 2-6 feet/second (preferably 4-6
feet/second) to prevent the accumulation of deposits or non-representative conditions that would
interfere with the test results. The correct way to sample for particulate iron is to install an
isokinetic sample nozzle and follow proper isokinetic sampling flow rates. Most industrial
systems are not set up to do isokinetic sampling of feedwater, blowdown or condensate, thus it is
important to have a good continuous sample flow rate.
pH
soluble iron
total iron
dissolved oxygen
suspended iron (0.45 micron Millipore filtration)
treatment chemical
In addition, grab samples can be sent to Customer Analytical for ICP or AA analysis. For
information on selecting the right container, test code and other important information on
submitting samples to Analytical refer to the Ondeo Nalco booklet “Shipping Samples Safely” to
the Naperville Technical Center.
There are integrated corrosion product samplers available from companies such as Sentry
Equipment Corporation. These units have a membrane filter followed by an ion exchange resin
filter, in series, to collect particulate iron and soluble iron. The units have flow indicator/control
valves and a flow totalizer to accurately quantify the amount of flow the unit has seen over time
so accurate iron averages can be calculated. The units are costly, but if iron transport studies are
being done, this is the best way to collect the iron.
In closing, remember the three words for Boiler Iron Control: Prevention, Prevention,
Prevention! Use the Boiler Iron Control Triangle Offense and, the Engineering Approach as
your comprehensive primary strategy. Feeding polymer dispersant is secondary but still a
necessary part of the whole strategy!
Acknowledgements:
The author would like to express his sincere appreciation and thanks to the following individuals
for their valuable input, suggestions and editing of the many drafts to create this important
document.
Roger Fowee, Anton Banweg, George Totura, Anne Wilson Burt, Peter Hicks, Martin Godfrey,
John Diambri, Barbara Davis and Rhonda Consalvo.