Professional Documents
Culture Documents
protection
Wenbin Cao1 , Xinaggen Yin1, Xuanwei Qi1, Yuxue Wang2, Wei Liu2, Yuanlin Pan1
1State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan,
E-mail: 1019097704@qq.com
Abstract: Large-scale electricity has fed into Central and Southern China through DC transmission lines. Any one of the DC
transmission lines suddenly outage will result in a large proportion of power-shortage. Recently, there are many DC harmonic
protection misoperations caused by AC disturbance, resulting in DC transmission line exit operation. Therefore, it is necessary
to analyse the effect of AC disturbance on DC harmonics and study methods for DC harmonic protections. In this study, based
on the theory of switching function, the harmonics interaction in AC–DC systems is studied. The cause of DC line harmonic
protection misoperation during unusual AC disturbances, such as inrush current and short circuit, is revealed. The DC line 50 Hz
harmonic protection misoperates frequently due to inrush current on site. Taking it for example, an improved method using the
second harmonic voltage in AC system bus is proposed. In this method, the 50 Hz harmonics generated by inrush current can
be accurately identified by judging the correlation between the AC harmonic voltage and the DC line harmonic current. By
automatically adjusting the threshold value of protection, the misoperation can be prevented effectively without affecting the
original protection performance. The simulation results verify the correctness of the method.
4 3 + 2 3 N2
Sua = cos ω1t im_ac = I cos ωm + ω1 t + α (5)
π π N1 m_dc
4 3 2π 2 3 N2
Sub = cos ω1t − (2) −
im_ac = I cos ωm + ω1 t + α (6)
π 3 π N1 m_dc
4 3 2π
Suc = cos ω1t − where, Im_dc and α are the amplitude and phase of harmonic current
π 3
in DC side, ωm is the angular frequency of harmonic current in DC
where, ω1 is angular frequency under power frequency. +
side, im_ac −
and im_ac i - are the positive- and negative-sequence
Assuming there is there-phase unbalanced voltage in AC side, it current in AC side, ω1 is the angular frequency under power
can be decomposed into positive-sequence and zero-sequence frequency, N1 and N2 are the winding turns in AC side and valve
components, which are shown in (3).
side of converter transformer, respectively.
∞ ∞ By analysing (5) and (6), mth-degree harmonic current will
ua = ∑ Um_accos(ωmt + α ) + ∑ Um_accos(ωmt + α )
+ + 0 0 produce (m − 1)th-degree negative harmonic current and (m + 1)th-
degree positive-sequence harmonic current.
m=1 m=1
∞
+ ∑ Um_accos(ωmt + α )
− −
3 Analytical calculation and simulation
m=1 comparison for transfer process of AC second
∞ ∞
2π harmonic in AC–DC system
ub = ∑ Um_accos ωmt + α
+ +
−
3
+ ∑ Um_ac
0
cos(ωmt + α0)
m=1 m=1 3.1 Calculation of AC system harmonic equivalent
∞
(3) impedance
2π
+ ∑ Um_accos ωmt + α
− −
+
3 The harmonic equivalent impedance of AC system Zac is shown in
m=1
Fig. 1, the equivalent impedance converted from AC system to DC
∞ ∞
2π system.
uc = ∑ Um_accos ωmt + α
+ +
+
3
+ ∑ Um_ac
0
cos(ωmt + α0) Assuming that the harmonic current im_ac of which frequency is
m=1 m=1
∞
ωm flows through the DC system in Fig. 1:
2π
+ ∑ Um_accos ωmt + α
− −
−
3 im_dc = Im_dccos(ωmt + α)
m=1 (7)
+
where, Um_ac 0
, Um_ac −
, and Um_ac are the amplitude of positive-, According to (5) and (6), the time-domain expression of harmonic
zero-, and negative-sequence harmonic voltage in AC side, α +, α0, current im_ac can be derived, of which the positive-sequence current
and α - are the phase of positive-, zero-, and negative-sequence angular frequency is ωm + ω1 and the negative sequence current
harmonic voltage in AC side, ωm is the angular frequency of angular frequency is ωm − ω1.
harmonic voltage, which often is m times of ω1. When the system frequency is ω, set the converter transformer
Substituting (3) and (2) into (1), the harmonic voltage impedance as ZT(ω) and the equivalent impedance of AC system as
relationship between 12-phase converter AC side and DC side is ZS(ω). Considering that there does not exist harmonic voltage
shown in (4). By analysing (4), it can be found that mth-degree source which has another angular frequency in the AC side, the
positive-sequence harmonic in AC side will produce (m − 1)th- circuit in Fig. 1 can be transformed as Fig. 2:
degree harmonic voltage in DC side, and mth-degree negative From Fig. 2, in the AC side of converter, the harmonic voltage
harmonic voltage will produce (m + 1)th-degree harmonic voltage. um_ac caused by im_ac is shown as (8) and (9):
− 2 3 N2
um_ac = I cos ωm − ω1 t + α + γ −
π N1 m_dc (9)
× 0.5ZT ωm − ω1 + ZS ωm − ω1
+ −
where, um_ac and um_ac are the AC system positive- and negative-
sequence harmonic voltage caused by positive- and negative-
sequence harmonic current, respectively, γ+ is the impedance angle
to 0.5ZT(ωm + ω1) + ZS(ωm + ω1) and γ- is impedance to 0.5ZT(ωm
− ω1) + ZS(ωm − ω1).
+
According to (8), the angular frequency of um_ac is ωm + ω1.
+
Then, it can be concluded from (4) that um_ac will produce Fig. 3 Equivalent circuit of the DC transmission system during inrush
harmonic voltage of which angular frequency is ωm in DC side. In current
− −
the same way, the angular frequency of um_ac is ωm − ω1 and um_ac (a) Wiring diagram of DC transmission system, (b) 50 Hz harmonic DC equivalent
will produce harmonic voltage of which angular frequency is ωm in circuit
DC side too. In conclusion, the DC side harmonic voltage um_dc
can be expressed as follows: into 50 Hz harmonic equivalent impedance in DC side, which is
′
noted as ZS_rec ′ . In the same way, the converter
+ 0.5ZT_rec
36 N2 2 transformer internal impedance ZT_inv in inverter side and AC
um_dc = Im_dccos(ωmt + α + γ +) system internal impedance ZS_inv in inverter side can be converted
π2 N1
into 50 Hz harmonic equivalent impedance in DC side, which is
× 0.5ZT ωm + ω1 + ZS ωm + ω1 ′
noted as ZS_inv ′ .
+ 0.5ZT_inv
(10)
36 N2 2 The concrete calculation process is as follows:
+ Im_dccos(ωmt + α + γ −)
π2 N1
6 3 N2_rec
× 0.5ZT ωm − ω1 + ZS ωm − ω1 U̇ dc_50Hz = U̇ (12)
π N1_rec ac_100Hz +
Transferring the time domain expression of DC side harmonic
current and voltage in (7) and (10) into phasor expression, the (see (13) and (14)) (see (14)) where, U̇ ac_100Hz + is the positive-
harmonic equivalent impedance of AC system Zac can be expressed sequence 100 Hz harmonic voltage of AC bus in rectifier side
as follows: produced by transformer magnetising inrush current, N1_rec and
N2_rec represent the AC side and converter valve side winding turns
U̇ m_dc 36 N2 2 of rectifier station converter transformer, respectively, NT_rec(ω)
Zac = 0.5ZT ωm + ω1 + ZS ωm + ω1 and NS_rec(ω) represent the equivalent impedance of converter
I˙m_dc π 2 N1 (11)
transformer and AC system of rectifier side when the angular
+0.5ZT ωm − ω1 + ZS ωm − ω1 frequency is ω, N1_inv and N2_inv represent the AC side and
converter valve side winding turns in inverter station converter
3.2 Analytic calculation of AC side positive-sequence second transformer, respectively, ZT_inv(ω) and Zs_inv(ω) represent the
harmonic transferring process equivalent impedance of converter transformer and AC system of
During the transformer energisation nearby the rectification station, inverter side when the angular frequency is ω. As U̇ ac_100Hz + will
the AC bus of converter station will produce positive-sequence transfer into 50 Hz harmonic voltage, ωm = ω1 = 100π rad/s.
second harmonic voltage. As is shown in Fig. 3a, assuming that the As the DC transmission line is too long, the influence of
AC bus in rectifier side is superimposed a harmonic voltage source distributed capacitive current to ground cannot be neglected [15].
U̇ ac_100Hz + , combined with the analysis of converter influence to Therefore, as shown in Fig. 3b, we can take two-port network to
harmonic transfer and the calculation of AC system harmonic analyse the distributed parameter characteristics of DC
equivalent impedance, the AC system can be converted in the DC transmission line. The whole loop equivalent impedance Zeq(l) is as
side, which is shown as Fig. 3b. follows:
In Fig. 3b, the positive-sequence second harmonic voltage of
the AC bus of the rectifier station is passed through the inverter Z2 + Zctanh(γl)
Zeq(l) = Z′S_rec + 0.5Z′T_rec + jωLP + Zc
and then converted to 50 Hz harmonic voltage, which can be Zc + Z2tanh(γl) (15)
equivalently substituted as source U̇ dc_50Hz and the conversion Z2 = jωLP + (Z′S_inv + 0.5Z′T_inv)
equation is shown in (4). According to (11), the converter
transformer internal impedance ZT_rec in rectifier side and AC
system internal impedance ZS_rec in rectifier side can be converted
2
36 N2_rec
Z′S_rec + 0.5Z′T_rec = [0.5ZT_rec(ωm + ω1)
π N1_rec
2
(13)
+ZS_rec(ωm + ω1) + 0.5ZT_rec(ωm − ω1) + ZS_rec(ωm − ω1)]
2
36 N2_inv
Z′S_inv + 0.5Z′T_inv = [0.5ZT_inv(ωm + ω1)
π N1_inv
2
(14)
+ZS_inv(ωm + ω1) + 0.5ZT_inv(ωm − ω1) + ZS_inv(ωm − ω1)]
1058 J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061
This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
where, Z2 is the load connected at the terminal of transmission line,
Zc is the characteristic impedance of DC transmission line, γ is the
transmission coefficient.
The DC line current I˙rec and voltage U̇ rec in rectifier side are
(see (16))
U̇ rec
I˙inv = I˙reccosh(γl) − sinh(γl) (18)
Zc
U̇ dc_50Hz
I˙rec = (16)
Z′S_rec + 0.5Z′T_rec + jωLP + Zc Z2 + Zctanh(γl) / Zc + Z2tanh(γl)
J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061 1059
This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
The paper takes α to represent the attenuation of Uac_100 Hz + , as
shown in (22). When α < 1, it is in an attenuation state. So
attenuation state of Uac_100Hz + can be determined according to the
criterion shown in (23) and judge whether the magnetising inrush
current is generated or not. When (23) is satisfied, turn to Step 4.
Otherwise, return to Step 2.
int(n/N) × N
α= ∑ ∑ Uac_ 100 HZ + (k)
Fig. 5 Electrical connection diagram of transformer energisation nearby
k = int(n/N) × N − 4 × N + 1
int(n/N) × N − 4 × N (22) rectifier station
∑ Uac_100 HZ + (k)
k = int(n/N) × N − 8 × N + 1
where, αset is the setting value (αset < 1). It is set as 0.97. tset1 is the
time delay and it is set 0.2 s.
Step 4: Judge whether the DC 50 Hz harmonic is generated by the
magnetising inrush current.
Measure the 50 Hz harmonic current on the rectifier and
inverter side. The coefficients βrec and βinv are used to characterise
the correlation between the DC 50 Hz harmonic current and Fig. 6 Simulation results when the magnetising inrush current occurs
Uac_100HZ + (k) on the rectifier and inverter side. The specific nearby the rectifier station
(a) Three-phase voltage of AC bus in rectifier station during magnetising inrush
algorithm is shown in (24) and (25).
current, (b)Positive-sequence second harmonic voltage of AC bus in rectifier station,
(c) 50 Hz harmonic current of DC line in rectifier station, (d) The comparison between
Uac_100 Hz+ and Iinv_50 Hz
βrec
n
Uac_100Hz + (k) Irec_50Hz + (k) 2 Irec_50Hz > Id_set2 (28)
= ∑ −
Uac_100Hz + (n − N + 1) Irec_50Hz + (n − N + 1)
k =n−N+1 When (27) is satisfied, adjust the DC 50 Hz harmonic protection
(24) criterion in inverter side to