You are on page 1of 6

The Journal of Engineering

The 14th IET International Conference on AC and DC Power


Transmission (ACDC 2018)

Analysis for DC transmission line harmonics eISSN 2051-3305


Received on 23rd August 2018
Accepted on 19th September 2018
originated from AC transformer inrush current E-First on 10th December 2018
doi: 10.1049/joe.2018.8523
and improved method for DC harmonic www.ietdl.org

protection
Wenbin Cao1 , Xinaggen Yin1, Xuanwei Qi1, Yuxue Wang2, Wei Liu2, Yuanlin Pan1
1State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan,

People's Republic of China


2Power dispatching control center of Guangdong power grid, Guangzhou, People's Republic of China

E-mail: 1019097704@qq.com

Abstract: Large-scale electricity has fed into Central and Southern China through DC transmission lines. Any one of the DC
transmission lines suddenly outage will result in a large proportion of power-shortage. Recently, there are many DC harmonic
protection misoperations caused by AC disturbance, resulting in DC transmission line exit operation. Therefore, it is necessary
to analyse the effect of AC disturbance on DC harmonics and study methods for DC harmonic protections. In this study, based
on the theory of switching function, the harmonics interaction in AC–DC systems is studied. The cause of DC line harmonic
protection misoperation during unusual AC disturbances, such as inrush current and short circuit, is revealed. The DC line 50 Hz
harmonic protection misoperates frequently due to inrush current on site. Taking it for example, an improved method using the
second harmonic voltage in AC system bus is proposed. In this method, the 50 Hz harmonics generated by inrush current can
be accurately identified by judging the correlation between the AC harmonic voltage and the DC line harmonic current. By
automatically adjusting the threshold value of protection, the misoperation can be prevented effectively without affecting the
original protection performance. The simulation results verify the correctness of the method.

1 Introduction DC harmonic protection is a typical protection involving AC–


DC system. Furthermore, 50 Hz harmonic protection is the backup
In this century, DC transmission technology has been rapidly protection to bridge differential protection and commutation failure
developed in the world [1]. Especially in China, with a large protection [13]. It can quickly detect continuous commutation
number of high-voltage direct current (HVDC) and ultra high- failure or trigger system failure. However, when the disturbances
voltage direct current (UHVDC) transmission projects put into occur to the AC system and the AC protection cannot operate in
operation, AC–DC hybrid power grid has been gradually forming time, DC harmonic protection may misoperate. For this
[2]. However, the increasingly complex power grid structure and misoperation, Chong et al. [8] proposed blocking positive-
parameters bring new issue that is the coordination of AC and DC sequence second harmonic voltage to prevent the misoperation
system protection and control, which seriously affect the safety of during the magnetising inrush current. By detecting the content of
the grid. If a single fault occurred in the power grid cannot be cut positive-sequence, second harmonic of the AC system to
in time, it will cause a complex accident process of the linkage in distinguish whether the converter valve is pulsed or the AC system
AC–DC systems. The emergency shutdown of DC system will has a positive-sequence second harmonic. This method can
cause huge loss of power in AC receiving-end grid, which is a effectively avoid the misoperation of the harmonic protection
serious threat to the safe and stable operation of the AC–DC hybrid during the inrush current. However, the criterion of blocking the
grid [3–5]. Therefore, it is necessary to study the interaction positive-sequence second harmonic directly may lead to the failure
mechanism of AC–DC system and its impact on the protection. of operation in some cases. Tian and Liu [7] proposed installing an
In actual operation, there have been many DC harmonic AC filter which is capable of filtering the second harmonic to
protection–misprotections caused by the energised transformer suppress the influence of the second harmonic on the DC system
inrush current in the rectifier side, which may cause DC bipolar caused by the distortion of the AC bus voltage. However, the
block and other serious consequences [6–9]. When the transformer method needs to add primary equipment which will increase the
is energised, the inrush current will cause the AC bus voltage cost. It is not conducive to engineering.
distortion in rectifier side. The distorted voltage contains abundant In this paper, based on the theory of switching function, the
second harmonics. The transfer process of harmonics in AC–DC transfer and interaction mechanism of harmonics in AC–DC
system is very complex, and the harmonics generated by AC side systems is analysed. Based on a HVDC project in Central China,
faults or other processes of AC–DC hybrid power grid will be the correctness of the analysis results is verified by digital
transferred to the DC side, which will cause the misoperation of simulation. The cause of DC harmonic protection misoperation
harmonic protection. In Hu et al. [10–12], the transfer mechanism during unusual transient process in AC system, such as inrush
of AC and DC harmonics in HVDC transmission system under current and short circuit fault, is revealed. Based on the
unbalanced state is deduced using switching function theory, and clarification of the harmonic transfer mechanism in AC–DC
then the equations of voltage harmonics transfer from AC to DC systems, a new method using the second harmonic voltage in AC
system and current harmonics from DC to AC side are obtained. bus is proposed to solve the problem of DC 50 Hz harmonic
However, it failed to analyse the complete transfer process. The protection misoperation during AC inrush current. In this method,
complete transfer process is as follows: the harmonic voltage is the 50 Hz harmonics generated by inrush current can be accurately
transferred from the AC side to DC side, which will generate identified by judging the correlation between the AC harmonic
harmonic current, then, the generated harmonic current on the voltage and the DC line harmonic current. By automatically
equivalent impedance is transferred back to the AC side. adjusting the threshold value of protection, the misoperation can be

J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061 1056


This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
prevented effectively without affecting the original protection
performance. The simulation results verify the correctness of the
method.

2 Analysis of AC–DC system harmonic transfer


through the converter
Fig. 1  Equivalent impedance of the AC system
When the transformer nearby the rectifier station is energised, the
magnetising inrush current will produce the distortion in the AC
bus voltage. Especially when the AC system at the sending end is
weak, the voltage distortion factor can reach up to 30% [6]. The
distorted voltage contains abundant second harmonics.
The switching function theory [10, 14] is often used to analyse
the converter impact on harmonic transfer. The theory believes that
the converter is considered as a non-linear modulation switching
circuit to connect the AC–DC system. By modulating the switching Fig. 2  Calculating circuit for the equivalent impedance
function, the voltage or current in AC and DC sides can be flexibly

converted to each other. 6 3 N2
π N1 m∑
+
Based switching function theory, the converter voltage and um_dc = Um_accos ωm − ω1 t + α+
=1 (4)
current can be expressed as (1):

+Um_accos (ωm + ω1)t + α−
udc = uaSua + ubSub + ucSuc
ia = idc ⋅ Sia where, um_dc is the harmonic voltage in DC side, N1 and N2 are the
(1) winding turns in AC side and valve side of converter transformer,
ib = idc ⋅ Sib respectively.
ic = idc ⋅ Sic Also, by using the switching function theory, the relation
between harmonic current in DC side and AC side of 12-pluse
For 12-pluse converter, Sua, Sub, Suc can be expressed as (2): converter is shown in (5) and (6).

4 3 + 2 3 N2
Sua = cos ω1t im_ac = I cos ωm + ω1 t + α (5)
π π N1 m_dc

4 3 2π 2 3 N2
Sub = cos ω1t − (2) −
im_ac = I cos ωm + ω1 t + α (6)
π 3 π N1 m_dc
4 3 2π
Suc = cos ω1t − where, Im_dc and α are the amplitude and phase of harmonic current
π 3
in DC side, ωm is the angular frequency of harmonic current in DC
where, ω1 is angular frequency under power frequency. +
side, im_ac −
and im_ac i - are the positive- and negative-sequence
Assuming there is there-phase unbalanced voltage in AC side, it current in AC side, ω1 is the angular frequency under power
can be decomposed into positive-sequence and zero-sequence frequency, N1 and N2 are the winding turns in AC side and valve
components, which are shown in (3).
side of converter transformer, respectively.
∞ ∞ By analysing (5) and (6), mth-degree harmonic current will
ua = ∑ Um_accos(ωmt + α ) + ∑ Um_accos(ωmt + α )
+ + 0 0 produce (m − 1)th-degree negative harmonic current and (m + 1)th-
degree positive-sequence harmonic current.
m=1 m=1

+ ∑ Um_accos(ωmt + α )
− −
3 Analytical calculation and simulation
m=1 comparison for transfer process of AC second
∞ ∞
2π harmonic in AC–DC system
ub = ∑ Um_accos ωmt + α
+ +

3
+ ∑ Um_ac
0
cos(ωmt + α0)
m=1 m=1 3.1 Calculation of AC system harmonic equivalent

(3) impedance

+ ∑ Um_accos ωmt + α
− −
+
3 The harmonic equivalent impedance of AC system Zac is shown in
m=1
Fig. 1, the equivalent impedance converted from AC system to DC
∞ ∞
2π system.
uc = ∑ Um_accos ωmt + α
+ +
+
3
+ ∑ Um_ac
0
cos(ωmt + α0) Assuming that the harmonic current im_ac of which frequency is
m=1 m=1

ωm flows through the DC system in Fig. 1:

+ ∑ Um_accos ωmt + α
− −

3 im_dc = Im_dccos(ωmt + α)
m=1 (7)
+
where, Um_ac 0
, Um_ac −
, and Um_ac are the amplitude of positive-, According to (5) and (6), the time-domain expression of harmonic
zero-, and negative-sequence harmonic voltage in AC side, α +, α0, current im_ac can be derived, of which the positive-sequence current
and α - are the phase of positive-, zero-, and negative-sequence angular frequency is ωm + ω1 and the negative sequence current
harmonic voltage in AC side, ωm is the angular frequency of angular frequency is ωm − ω1.
harmonic voltage, which often is m times of ω1. When the system frequency is ω, set the converter transformer
Substituting (3) and (2) into (1), the harmonic voltage impedance as ZT(ω) and the equivalent impedance of AC system as
relationship between 12-phase converter AC side and DC side is ZS(ω). Considering that there does not exist harmonic voltage
shown in (4). By analysing (4), it can be found that mth-degree source which has another angular frequency in the AC side, the
positive-sequence harmonic in AC side will produce (m − 1)th- circuit in Fig. 1 can be transformed as Fig. 2:
degree harmonic voltage in DC side, and mth-degree negative From Fig. 2, in the AC side of converter, the harmonic voltage
harmonic voltage will produce (m + 1)th-degree harmonic voltage. um_ac caused by im_ac is shown as (8) and (9):

J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061 1057


This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
+ 2 3 N2
um_ac = I cos ωm + ω1 t + α + γ +
π N1 m_dc (8)
× 0.5ZT ωm + ω1 + ZS ωm + ω1

− 2 3 N2
um_ac = I cos ωm − ω1 t + α + γ −
π N1 m_dc (9)
× 0.5ZT ωm − ω1 + ZS ωm − ω1
+ −
where, um_ac and um_ac are the AC system positive- and negative-
sequence harmonic voltage caused by positive- and negative-
sequence harmonic current, respectively, γ+ is the impedance angle
to 0.5ZT(ωm + ω1) + ZS(ωm + ω1) and γ- is impedance to 0.5ZT(ωm 
− ω1) + ZS(ωm − ω1).
+
According to (8), the angular frequency of um_ac is ωm + ω1.
+
Then, it can be concluded from (4) that um_ac will produce Fig. 3  Equivalent circuit of the DC transmission system during inrush
harmonic voltage of which angular frequency is ωm in DC side. In current
− −
the same way, the angular frequency of um_ac is ωm − ω1 and um_ac (a) Wiring diagram of DC transmission system, (b) 50 Hz harmonic DC equivalent
will produce harmonic voltage of which angular frequency is ωm in circuit
DC side too. In conclusion, the DC side harmonic voltage um_dc
can be expressed as follows: into 50 Hz harmonic equivalent impedance in DC side, which is

noted as ZS_rec ′ . In the same way, the converter
+ 0.5ZT_rec
36 N2 2 transformer internal impedance ZT_inv in inverter side and AC
um_dc = Im_dccos(ωmt + α + γ +) system internal impedance ZS_inv in inverter side can be converted
π2 N1
into 50 Hz harmonic equivalent impedance in DC side, which is
× 0.5ZT ωm + ω1 + ZS ωm + ω1 ′
noted as ZS_inv ′ .
+ 0.5ZT_inv
(10)
36 N2 2 The concrete calculation process is as follows:
+ Im_dccos(ωmt + α + γ −)
π2 N1
6 3 N2_rec
× 0.5ZT ωm − ω1 + ZS ωm − ω1 U̇ dc_50Hz = U̇ (12)
π N1_rec ac_100Hz +
Transferring the time domain expression of DC side harmonic
current and voltage in (7) and (10) into phasor expression, the (see (13) and (14)) (see (14)) where, U̇ ac_100Hz + is the positive-
harmonic equivalent impedance of AC system Zac can be expressed sequence 100 Hz harmonic voltage of AC bus in rectifier side
as follows: produced by transformer magnetising inrush current, N1_rec and
N2_rec represent the AC side and converter valve side winding turns
U̇ m_dc 36 N2 2 of rectifier station converter transformer, respectively, NT_rec(ω)
Zac = 0.5ZT ωm + ω1 + ZS ωm + ω1 and NS_rec(ω) represent the equivalent impedance of converter
I˙m_dc π 2 N1 (11)
transformer and AC system of rectifier side when the angular
+0.5ZT ωm − ω1 + ZS ωm − ω1 frequency is ω, N1_inv and N2_inv represent the AC side and
converter valve side winding turns in inverter station converter
3.2 Analytic calculation of AC side positive-sequence second transformer, respectively, ZT_inv(ω) and Zs_inv(ω) represent the
harmonic transferring process equivalent impedance of converter transformer and AC system of
During the transformer energisation nearby the rectification station, inverter side when the angular frequency is ω. As U̇ ac_100Hz + will
the AC bus of converter station will produce positive-sequence transfer into 50 Hz harmonic voltage, ωm = ω1 = 100π rad/s.
second harmonic voltage. As is shown in Fig. 3a, assuming that the As the DC transmission line is too long, the influence of
AC bus in rectifier side is superimposed a harmonic voltage source distributed capacitive current to ground cannot be neglected [15].
U̇ ac_100Hz + , combined with the analysis of converter influence to Therefore, as shown in Fig. 3b, we can take two-port network to
harmonic transfer and the calculation of AC system harmonic analyse the distributed parameter characteristics of DC
equivalent impedance, the AC system can be converted in the DC transmission line. The whole loop equivalent impedance Zeq(l) is as
side, which is shown as Fig. 3b. follows:
In Fig. 3b, the positive-sequence second harmonic voltage of
the AC bus of the rectifier station is passed through the inverter Z2 + Zctanh(γl)
Zeq(l) = Z′S_rec + 0.5Z′T_rec + jωLP + Zc
and then converted to 50 Hz harmonic voltage, which can be Zc + Z2tanh(γl) (15)
equivalently substituted as source U̇ dc_50Hz and the conversion Z2 = jωLP + (Z′S_inv + 0.5Z′T_inv)
equation is shown in (4). According to (11), the converter
transformer internal impedance ZT_rec in rectifier side and AC
system internal impedance ZS_rec in rectifier side can be converted

2
36 N2_rec
Z′S_rec + 0.5Z′T_rec = [0.5ZT_rec(ωm + ω1)
π N1_rec
2
(13)
+ZS_rec(ωm + ω1) + 0.5ZT_rec(ωm − ω1) + ZS_rec(ωm − ω1)]

2
36 N2_inv
Z′S_inv + 0.5Z′T_inv = [0.5ZT_inv(ωm + ω1)
π N1_inv
2
(14)
+ZS_inv(ωm + ω1) + 0.5ZT_inv(ωm − ω1) + ZS_inv(ωm − ω1)]
1058 J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061
This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
where, Z2 is the load connected at the terminal of transmission line,
Zc is the characteristic impedance of DC transmission line, γ is the
transmission coefficient.
The DC line current I˙rec and voltage U̇ rec in rectifier side are
(see (16))

U̇ rec = U̇ dc_50Hz − I˙rec[(ZS_rec


′ ′ ) + jωLP]
+ 0.5ZT_rec (17)

According to transmission line equation, we can deduce DC line


current I˙inv and voltage U̇ inv in the inverter side.

U̇ rec
I˙inv = I˙reccosh(γl) − sinh(γl) (18)
Zc

U̇ inv = U̇ reccosh(γl) − ZcI˙recsinh(γl) (19)

3.3 Analytic calculation of AC side positive-sequence second


harmonic transferring process Fig. 4  Equivalent circuit of the DC transmission system during
magnetising inrush current
Building digital transient simulation model of the HVDC project in (a) 50 Hz harmonic current I˙rec in DC line nearby the rectifier station, (b) 50 Hz
Central China, we can verify the accuracy of the above-mentioned harmonic voltage U̇ rec in DC line nearby the rectifier station, (c) 50 Hz harmonic
analytic calculation of the harmonic transfer mechanism in AC–DC current I˙inv in DC line nearby the inverter station, (d) 50 Hz harmonic voltage U̇ inv in
hybrid power grid. DC line nearby the inverter station
In the model, add positive-sequence second harmonic voltage
with different amplitude on converter station AC bus in rectifier
current can be judged. Thereby, appropriate measures to prevent
side. The voltage and current on both sides of DC transmission line
the potential misoperation of DC 50 Hz harmonic protection can be
can be obtained from simulation to compare with analytic
taken.
calculation result. The comparison diagram is shown in Fig. 4.
Based on the above analysis, an anti-misoperation method for
It can be seen from Fig. 4 that the simulation results
DC 50 Hz harmonic is proposed. The method uses AC harmonic
approximately agree with the analytic calculation result. Moreover,
voltage to make up the new criterion. The specific implementation
there is a good linear relation between AC bus second harmonic
methods include the following five steps.
and DC line harmonic. As we use a 50 Hz harmonic DC equivalent
circuit to simplify the actual DC transmission system, the influence
Step 1: execute the normal function of 50 Hz harmonic protection
of AC filter and DC filter is not in consideration, which cause the
The operation criterion of normal 50 Hz harmonic protection is
error between the calculation result and the simulation result. In
shown (20):
addition, by comparing (b) and (d), it can be found that the 50 Hz
harmonic current on the rectification side is amplified when
IdCN_50 > Id_set (20)
conducted to the inverter side through the long-distance DC
transmission line, indicating that the 50 Hz harmonic protection on
the inverter side is more likely to misoperate. The actual 50 Hz where, IdCN_50 is the amplitude of 50 Hz harmonic in DC current;
harmonic protection misoperation [6, 16] also shows that the Id_set is the restraint current and it is 0.0333 times the rate current.
magnetising inrush of energised transformer in rectifier side often Detect the value at every sample time Ts. Once the criterion is
leads to the DC harmonic protection misoperation in inverter side. satisfied and last for 0.5 s, the protection operates.
The Step 2 is executed at every sample interval and set flag = 0.
4 Method to improve the DC 50 Hz harmonic Step 2: Judge whether the rectifier bus generates the positive-
sequence second harmonic voltage
protections
Measure the three-phase voltage of the AC bus in the rectifier
According to the harmonic transfer mechanism of the converter, station and calculate the positive-sequence second harmonic
the positive-sequence second harmonics of the AC side will amplitude of the measured voltage, which is referred to as
produce 50 Hz harmonics on the DC side. The DC 50 Hz harmonic Uac_100 Hz + . When (21) is satisfied, it means positive-sequence
protection may misoperate when the magnetising inrush current second harmonic voltage begin to occur. If flag = 0 this moment,
has large amplitude and decay slowly. In this article, a method turn to Step 3 and set flag = 1; and start timing from 0, timing result
against the misoperation for 50 Hz harmonic protection is proposed recorded as t; start counting from 1, counting result recorded as n,
based on theoretical basis. Digital simulation is carried out to add 1 to it every other sampling point. When (21) is satisfied and
verify the feasibility of the method. flag = 1, turn to Step 3 directly and keep on timing and counting.
The analysis shows that there is good linear correlation between When (21) is not satisfied, return to Step 1.
positive-sequence second harmonic of AC bus and 50 Hz harmonic
of DC line. Therefore, the performance of DC 50 Hz harmonic Uac_100 Hz + > Uset (21)
protection could be improved by introducing the amplitude
Uac_100Hz + of positive-sequence second harmonic in AC bus of where, Uac_100 Hz + is the amplitude of positive-sequence second
rectifier station. When a transformer is energised, the magnetising harmonic voltage of AC bus in rectifier station; Uset is a setting
inrush current decays slowly and Uac_100Hz + generated by the value and usually 0.05 times the rate voltage (25 kV).
magnetising inrush current decays slowly. As a result, whether Step 3: Judge whether the inrush current is generated.
there is inrush current generated or not can be judged by the The inrush current decays slowly after transformer switching-
attenuation of Uac_100Hz + . Then the correlation between Uac_100Hz + on. So whether the magnetising inrush current is generated or not
and 50 Hz harmonic in DC line current can be detected and can be judged by the attenuation of Uac_100 Hz + .
whether the DC 50 Hz harmonic is generated by transformer inrush

U̇ dc_50Hz
I˙rec = (16)
Z′S_rec + 0.5Z′T_rec + jωLP + Zc Z2 + Zctanh(γl) / Zc + Z2tanh(γl)
J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061 1059
This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
The paper takes α to represent the attenuation of Uac_100 Hz + , as
shown in (22). When α < 1, it is in an attenuation state. So
attenuation state of Uac_100Hz + can be determined according to the
criterion shown in (23) and judge whether the magnetising inrush
current is generated or not. When (23) is satisfied, turn to Step 4.
Otherwise, return to Step 2.
int(n/N) × N
α= ∑ ∑ Uac_ 100 HZ + (k)
Fig. 5  Electrical connection diagram of transformer energisation nearby
k = int(n/N) × N − 4 × N + 1
int(n/N) × N − 4 × N (22) rectifier station
∑ Uac_100 HZ + (k)
k = int(n/N) × N − 8 × N + 1

where, N is the number of sampling points each cycle; n represents


the number of the sampling point; function int(x) represents the
rounding operation. Uac_100HZ + (k) represents the number k of
sampling point after turning to step 3

α αset&&t tset1 (23)

where, αset is the setting value (αset < 1). It is set as 0.97. tset1 is the
time delay and it is set 0.2 s.
Step 4: Judge whether the DC 50 Hz harmonic is generated by the
magnetising inrush current.
Measure the 50 Hz harmonic current on the rectifier and
inverter side. The coefficients βrec and βinv are used to characterise
the correlation between the DC 50 Hz harmonic current and Fig. 6  Simulation results when the magnetising inrush current occurs
Uac_100HZ + (k) on the rectifier and inverter side. The specific nearby the rectifier station
(a) Three-phase voltage of AC bus in rectifier station during magnetising inrush
algorithm is shown in (24) and (25).
current, (b)Positive-sequence second harmonic voltage of AC bus in rectifier station,
(c) 50 Hz harmonic current of DC line in rectifier station, (d) The comparison between
Uac_100 Hz+ and Iinv_50 Hz
βrec
n
Uac_100Hz + (k) Irec_50Hz + (k) 2 Irec_50Hz > Id_set2 (28)
= ∑ −
Uac_100Hz + (n − N + 1) Irec_50Hz + (n − N + 1)
k =n−N+1 When (27) is satisfied, adjust the DC 50 Hz harmonic protection
(24) criterion in inverter side to

Iinv_50Hz > Id_set2 (29)


βinv
n 2 where, Id_set2 is the modified action current and it is set 0.06 times
Uac_100Hz + (k) Iinv_50Hz + (k)
= ∑ −
Uac_100Hz + (n − N + 1) Iinv_50Hz + (n − N + 1)
the rate current according to engineering experience. When
k =n−N+1 Uac_100Hz + < Uset, return to Step 1.
(25)
5 Simulation verification
where, Irec_50Hz and Iinv_50Hz represent the amplitude of DC 50 Hz
harmonic current on the rectifier and inverter side. The paper uses the digital transient simulation model of the HVDC
The closer βrec and βinv are to zero, the more synchronised the project in Central China to verify the validity of the proposed
attenuation of Uac_100Hz + with the DC 50 Hz harmonic current. method. Simulation model and the diagram of electrical quantity
measurement are shown as Fig. 5. The measure point of Uac_100 Hz
Compare βrec and βinv with the setting value βset, when the (26) is
satisfied, it could be judged that the 50 Hz harmonic current on the + is on AC bus in rectifier side of pole I. The measure point of
rectifier side is generated by the inrush current. Then, turn to Step Iinv_50 Hz is on DC line in inverter side of pole I. The reference
5. Similarly, when (27) is satisfied, it is judged that the 50 Hz direction is indicated by an arrow in Fig. 5.
harmonic current on the inverter side is generated by the At 0 s, transformer A is energised nearby the AC bus of rectifier
magnetising inrush current. station. The magnetising inrush current occurs at AC system. The
AC bus voltage produces a large degree of distortion and the
βrec < βset&&tset2 (26) positive-sequence second harmonic voltage Uac_100Hz + which
decays slowly, as shown in Figs. 6a and b. The DC 50 Hz
βinv < βset&&tset2 (27) harmonic current Iinv_50Hz is larger than the original setting value
(0.0333 times the rate DC current) and lasts for 1.2 s. The DC
where, tset2 is the time delay and it is set 0.2 s according to harmonic protection may misoperate, as shown in Fig. 6c.
engineering experience. βset is the set value to determine the degree The scaled amplitude of Uac_100 Hz + and Iinv_50 Hz, is shown in
of similarity of the waveform and it is set as 0.01 according to Fig. 6d. The analysis shows that the two curves are much
engineering experience. consistent which indicate that the attenuation of Uac_100 Hz + and
Step 5: Adjust the harmonic protection action criterion to prevent Iinv_50 Hz is much synchronised.
misoperation. The following describes the operation performance of the
Judging that the DC line 50 Hz harmonic current is generated improved harmonic protection. At 0 s, Uac_100 Hz + > Uset, as shown
by the magnetising inrush current, then raise the threshold value of in Fig. 6. So the criterion is satisfied and the flag changes from 0 to
action to prevent misoperation. 1 at this time. Start timing as t and start counting as n. Add 1 every
When (26) is satisfied, adjust the DC 50 Hz harmonic sampling time. Then turn to Step 3.
protection criterion in rectifier side to

1060 J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061


This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)
side is superimposed on the positive-sequence second
harmonic voltage of different amplitudes. Comparing the
simulated DC voltage and current values with the theoretical
calculation, it is uncovered that there is a good linear
relationship between the second harmonic and the DC line
harmonic. In addition, it has been found that the DC long-
distance transmission lines amplify the harmonic current.
When the AC bus of rectified side generates the positive-
sequence second harmonic voltage, the DC 50 Hz harmonic
protection of the inverter side is more likely to misoperate,
Fig. 7  Attenuation α of Uac_100 Hz+; βinv between Iinv_50 Hz and which is consistent with the site fault.
Uac_100 Hz+ iii. Aiming at the shortcomings of the common DC 50 Hz
harmonic protection, an improved method is proposed to
prevent the protection from misoperation caused by inrush
current in AC bus. In this method, the 50 Hz harmonics
generated by inrush current can be accurately identified by
judging the correlation between the AC harmonic voltage and
the DC line harmonic current. By automatically adjusting the
threshold value of protection, the misoperation can be
prevented effectively without affecting the original protection
performance. The simulations results verify its feasibility.

Fig. 8  Operation performance of improved 50 Hz harmonic protection


7 Acknowledgments
nearby the inverter station
This work was supported by the National Key Research and
Voltage decay rate α calculated in Step 3 is shown in Fig. 7. α Development Plan of China (2016YFB0900600) and Guangdong
sustained less than αset(αset = 0.97). When t > 0.2S, Uac_100 Hz + Power Grid Science & Technology Project (GDKJXM20162461).
begin to come into the attenuation state, turn to Step 4.
In Step 4, the relative coefficient βinv between Iinv_50 Hz and 8 References
Uac_100 Hz+ is shown in Fig. 7. It can be seen that the value βinv is [1] Zhou, X.X., Lu, Z.X., Liu, Y.M., et al.: ‘Development models and key
far less than the setting value 0.01, which shows a high correlation technologies of future grid in China’, Proc. CSEE, 2014, 34, (29), pp. 4999–
between Iinv_50 Hz and Uac_100 Hz+, so to determine that the 50 Hz 5008
[2] Liu, Z.Y.: ‘UHV DC transmission technology research results album’ (China
harmonic current on the inverter side is due to the inrush current on Electric Power Press, Beijing, 2009)
the rectifier side. Then turn to Step 5. [3] Karawita, C., Annakkage, U.D.: ‘Multi-Infeed HVDC interaction studies
In Step 5, the 50 Hz harmonic protection changed to (29), as using small signal stability assessment’, IEEE Trans. Power Deliv., 2009, 24,
shown in Fig. 8. The analysis shows that the lasting time of which (2), pp. 910–918
[4] Rahimi, E., Gole, A.M., Davies, J.B., et al.: ‘Commutation failure analysis in
50 Hz harmonic current larger than the setting value is <0.5 s and multi-infeed HVDC systems’, IEEE Trans. Power Deliv., 2011, 26, (1), pp.
the protection will not misoperate. At 1.34 s, Uac_100 Hz+ is <25 kV. 378–384
Exit the improved 50 Hz harmonic protection criterion and restore [5] Aik, D.L.H., Andersson, G.: ‘Power stability analysis of multi-infeed HVDC
systems’, IEEE Trans. Power Deliv., 1998, 13, (3), pp. 923–931
the original 50 Hz harmonic protection action characteristics, as [6] Fan, L.J., Huang, Y., Xu, D.Z., et al.: ‘Impact of magnetizing inrush current at
shown in Fig. 8. sending end on 50 Hz protection of Xiluodu HVDC transmission project’,
From the above analysis, it can be seen the proposed method South. Power Syst. Technol., 2015, 9, (6), pp. 34–38
can effectively prevent the misoperation of the DC line harmonic [7] Tian, Y.G., Liu, Z.S.: ‘Causes aanlysis and treatment of DC harmonic
protection action for converter station’, Qinghai Electr. Power, 2014, 33,
protection during transformer inrush current. (Special), pp. 66–68
[8] Chong, Z.Y., Li, X.H., Liu, B.H.: ‘Analysis and countermeasures of qinghai-
Tibet DC blocking caused by main transformer charging in northwest power
6 Conclusion grid’, Electr. Power Constr., 2013, 34, (3), pp. 88–91
In this paper, focusing on the mechanism of harmonic transfer and [9] Zhou, P.P., Xiang, Z.T., Du, N.: ‘Analysis on blocking of qinghai-Tibet DC
system caused by transformer energizing in northwest China 750 kV grid’,
the DC 50 Hz harmonic protection misoperation due to Autom. Electr. Power Syst., 2013, 37, (10), pp. 129–133
magnetising inrush current, related researches are carried out. The [10] Hu, L., Yacamini, R.: ‘Harmonic transfer through converters and HVDC
following main conclusions are obtained: links’, IEEE Trans. Power Electron., 1992, 7, (3), pp. 514–525
[11] Hu, L.H., Morrison, R.E.: ‘The use of modulation theory to calculate the
harmonic distortion in HVDC systems operating on an unbalanced supply’,
i. Using the switching function theory, the mechanism of IEEE Trans. Power Syst., 1997, 12, (2), pp. 973–980
harmonics transfer through converter is analysed. The [12] Hu, L.H., Yacamini, R.: ‘Calculation of harmonic interference in HVDC
harmonic equivalent impedance is obtained. DC equivalent systems with unbalance’. Int. Conf. on AC and DC Power Transmission,
circuit for harmonic transfer is built. Based on AC positive- London, UK, September 1997, pp. 390–394
[13] Fu, C., Rao, H., Li, X.L.: ‘HVDC 50 and 100 Hz protection of AC/DC hybrid
sequence second harmonic, the harmonic transfer in the AC– transmission system’, Autom. Electr. Power Syst., 2008, 32, (12), pp. 57–60
DC system is analysed in detail. The expression of DC 50 Hz [14] Ma, Y.L.: ‘Stability analysis of HVDC transmission system’. PhD.
harmonic voltage and current on rectifier and inverter sides are dissertation, Department Electronic Engineering, NCEPU, Beijing, 2006
obtained. The interaction between the AC and DC systems is [15] Zhao, W.J., Xie, G.E., Zeng, N.C.: ‘HVDC engineering technology’ (China
Electric Power Press, Beijing, 2004)
revealed, and the influence of the AC inrush current on the DC [16] Yang, F.Y., Zhu, T.X., Ding, X.B., et al.: ‘Research on 50 Hz component in
harmonics is explained. HVDC transmission lines considering the influence of inrush current’, High
ii. The electromagnetic transient model of AC–DC hybrid power Volt. Eng., 2015, 41, (10), pp. 3363–3371
grid is built. In the simulation model, the AC bus of rectifier

J. Eng., 2019, Vol. 2019 Iss. 16, pp. 1056-1061 1061


This is an open access article published by the IET under the Creative Commons Attribution-NoDerivs License
(http://creativecommons.org/licenses/by-nd/3.0/)

You might also like