LOAD SCHEDULE

CCT. NO. L.O. C.O. OTHERS VOLTS WATTS AMP. BREAKER


1 24 230 2400 10.43478 2P, 16AT, 50AF
2 32 230 3200 13.91304 2P, 16AT, 50AF
3 34 230 3400 14.78261 2P, 16AT, 50AF
4 9 230 1800 7.826087 2P, 20AT, 50AF
5 26 230 5200 22.6087 2P, 20AT, 50AF
6 22 230 4400 19.13043 2P, 20AT, 50AF
7 ACU 230 1500 6.521739 2P, 32AT, 50AF
8 ACU 230 1500 6.521739 2P, 32AT, 50AF
9 ACU 230 1500 6.521739 2P, 32AT, 50AF
10 REF 230 1000 4.347826 2P, 20AT, 50AF
11 RANGE 230 2500 10.86957 2P, 32AT, 50AF
12 WATER HEATER 230 2500 10.86957 2P, 32AT, 50AF
13 SPARE 230 1500 6.521739
14 SPARE 230 1500 6.521739
TOTAL 90 57 230 33900 147.3913

TOTAL LOAD CONNECTED:


TOTAL
SERVICE
DEMAND FACTOR
SIZE OF WIRE SIZE OF PROTECTION TOTAL LOAD CONNECTED
2-3.5mm2 THHN 30 ATCB, 2P TOTAL 33900
2-3.5mm2 THHN 31 ATCB, 2P SERVICE 230V
2-3.5mm2 THHN 32 ATCB, 2P DEMAND FACTOR 80%
2-3.5mm2 THHN 33 ATCB, 2P 33900 x 80%
117.91 AMP
2-3.5mm2 THHN 34 ATCB, 2P 230V
2-5.5mm2 THHN 35 ATCB, 2P
2-5.5mm2 THHN 36 ATCB, 2P FOR MAIN CIRCUIT BREAKER
2-5.5mm2 THHN 37 ATCB, 2P USE 200 AMP. CIRCUIT BREAKER
2-5.5mm2 THHN 38 ATCB, 2P 2-38mm2 TW Copper Wire
2-5.5mm2 THHN 39 ATCB, 2P 1-22mm2 THW Copper Wire
2-5.5mm2 THHN 40 ATCB, 2P Protection shall be 1" dia. RSC
2-5.5mm2 THHN 41 ATCB, 2P