INI-VG Series (Third Generation)

Intelligent Network Interface-Voice Gateway


Product Installation Document
CAUTION: STATIC SENSITIVE EQUIPMENT:
! THIS EQUIPMENT IS SENSITIVE TO STATIC ELECTRICITY. IT MAY BE DAMAGED IF NOT PROPERLY HANDLED.
TRANSPORT AND STORE THIS UNIT IN A STATIC-SHIELDING BAG.
FAILURE TO OBSERVE THIS REQUIREMENT COULD CAUSE LATENT DAMAGE TO THE EQUIPMENT WHICH
MIGHT NOT MANIFEST ITSELF UNTIL AFTER THE EQUIPMENT IS PLACED IN SERVICE.

CAUTION: DISCONNECT ALL POWER:


! REMOVE ALL SOURCES OF POWER BEFORE YOU SERVICE, REMOVE OR INSTALL ANY UNITS.

Section 1: Description
The INI-VG Series sub-assembly provides the audio network interface for the E3 Series® Expandable Emergency Evacuation and
Mass Notification Systems. It provides the connection for the remote microphone, fire fighter telephone, one signaling line circuit,
and supports the connection for one NGA sub-assembly.

NOTE: INI-VG Series (Third Generation-Disclaimer):


The INI-VGC, INI-VGX, and INI-VGE have been redesigned to allow for fiber-optic plug-in modules. To provide fiber-optic
connectivity, either an FML-E3 (Multi-Mode Fiber-Optic Module) or an FSL-E3 (Single-Mode Fiber-Optic Module) must be
used per the network channel to transmit/receive. The INI-VGC, INI-VGX, and INI-VGE, in combination with the FML-E3 or
FSL-E3, replaces the INI-VGC-FO, INI-VGX-FO, and INI-VGC-FO.
For information on the INI-VGC-FO, INI-VGX-FO, and INI-VGE-FO, refer to the INI-VG Series Installation Instructions,
P/N: 9000-0549.
For information on the FML-E3 and FSL-E3, refer to the FML-E3/FSL-E3 Installation Instructions, P/N: LS10046-000GF-E.

Because the INI-VG Series sub-assembly is a modular design, it can be used in any type of system configuration to function as a
Fire Command Center and/or ACU, LOC-TEL or LOC-MIC for the Mass Notification System. This sub-assembly is factory pro-
grammed to operate as any of the following network interfaces and accommodates either fiber-optic cable or unshielded twisted-
pair copper-pair wires.
• INI-VGC is the network interface for the E3 Series Broadband Voice Command Center System. It provides the expanded
switch controls for the Autonomous Control Unit (ACU).
• INI-VGE is the network interface for the E3 Series Classic Voice Command Center System. It provides one audio channel for
the Bulk Amplification Systems used in Fire applications only.
• INI-VGX is the network interface for the E3 Series Broadband Voice Command Center System. It controls up to four external
AM-50 Series amplifiers (with a combined total maximum audio output of 150 Watts) for the Distributed Amplification
Systems.

Figure 1.1 INI-VG Series (Third Generation)

Document LS10218-000GF-E:C 05/17/19 ECN 19-0691


1.1 INI-VG Series (Intelligent Network Interface-Voice Gateway)
Use the INI-VG Series as the E3 Network interface for the Voice Evacuation Command Center (INCC). The INCC is the
primary component for the ACU that provides recorded message control and live voice audio paging in the Mass Notifica-
tion System. The INI-VG Series provides the following functions:
• Provides the connection to the system's microphone and fire fighter's handset.
• Includes the following:
– One Style 4 Signaling Line Circuit (SLC) with a capacity of up to sixteen AOM-TELF
(fire fighter's communication circuit) sub-assemblies.
– Thirty-two AOM-2SF (single-channel, speaker circuits).
• Supports the MMO-6SF, six-circuit single-channel, speaker circuit modules
(INI-VGE and INI-VGX (First, Second and Third Generations).
Each MMO-6SF takes up to six addresses on the SLC and is used for fire evacuation use only.
(INI-VGE and INI-VGX (First, Second and Third Generations).
• Contains one fire fighter communications riser.
• Stores up to sixteen custom digital tones/messages with a combined total length of three minutes.
Table 1.1.1 describes the functionality of the INI-VG Series (First, Second and Third Generations).
INI-VGC (Third Generation) INI-VGE (Third Generation) INI-VGX (Third Generation)
• Monitors and controls up to sixteen • Monitors and controls up to six ASM- • Monitors and controls up to six ASM-
ASM-16 or ANU-48 modules, 16 16 or ANU-48 modules and one NGA. 16 or ANU-48 modules and one NGA.
AOM-TELF modules and one NGA.
• The sixteen ASM-16 modules provide • Supports 16 AOM-TELF modules, as • Supports 16 AOM-TELF modules, as
up to 256 switch inputs. The ANU-48 well as 32 AOM-2SF or AOM-MUXF well as 32 AOM-2SF or AOM-MUXF
module provides up to 128 switch modules. modules.
inputs.
• Both the ASM-16 and ANU-48 module • The six ASM-16 or ANU-48 sub- • The six ASM-16 or ANU-48 sub-
types control a maximum of 768 assemblies provide up to a total of 96 assemblies provide up to a total of 96
LEDs. programmable control switches. programmable control switches.
• The ASM-16 has RED, GREEN and
YELLOW LEDs built.
• The ANU-48 drives user supplied
external lights.
• Occupies one node on the E3 • Both the ASM-16 and ANU-48 • Both the ASM-16 and ANU-48
Broadband network. modules control a maximum of 288 modules control a maximum of 288
LEDs. LEDs.
– The ASM-16 has RED, GREEN – The ASM-16 has RED, GREEN
and YELLOW LEDs built. and YELLOW LEDs built.
– The ANU-48 drives user supplied – The ANU-48 drives user supplied
external lights. external lights.
• Occupies one node on the E3 Series • Occupies one node on the E3
Classic network. Broadband network.
(Used in Fire applications only).
• Provides one voice channel per each • Monitors and controls up to four AM-
INI-VGE node that is capable of 50 Series amplifiers configured as any
commanding up to twenty AA-100 or of the following:
AA-120 amplifiers. • A total of 4 main amplifiers (without a
backup amplifier) where the audio
output power cannot exceed 150
Watts maximum or 3 main amplifiers
max. with 1 standby amplifier or
• 2 main amplifiers with 2 standby
amplifiers or
• 1 main amplifier with 1 standby
amplifier
• 1, 2, 3 main amplifiers with no standby
amplifier
Table 1.1.1 INI-VG Series (Third Generation) Module Features

2 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
1.2 Mass Notification System (MNS)
The Gamewell-FCI, Mass Notification System (MNS) is a Combination In-Building Fire and Mass Notification System. It com-
prises the E3 Series Broadband Emergency Voice Evacuation and the E3 Series Broadband Networked Fire Alarm Systems. This
design allows a wide range of configurations to form an integrated, distributed fire alarm system in combination with the audio
evacuation for both Fire and Mass Notification functions as desired. The design also allows for its use as a dedicated standalone
Mass Notification System without the fire alarm service. The network communication conveys all Fire Alarm and Mass Notifica-
tion control functions, audio evacuation, voice paging, and fire fighter communications over a single pair of wires or fiber-optic
cable. The modular design offers several configurations to accommodate the following audio components:
• Autonomous Control Unit (ACU), (Main Command Center)
• Local Operating Console (LOC), (Remote Command Center)
• E3 Series Broadband Voice Evacuation System
Table 1.2.1 lists the E3 Series sub-assemblies that can be used in the Gamewell-FCI, MNS (Mass Notification System).

Autonomous Control Unit (ACU) E3 Broadband System


E3 LOC Remote Command Center
(Main Command Center) (Distributed System)
AM-50 Series Amplifiers AOM-TELF/AOM-2SF AM-50 Series Amplifiers
ANU-48 (Remote Annunciator) ASM-16 (Addressable Switch Module) ANU-48 (Remote Annunciator)
ASM-16 (Addressable Switch Module) INI-VG Series (First/Second/Third ASM-16 (Addressable Switch Module)
Generation) (Intelligent Network Interface
Voice Gateway)
ILI-MB-E3 INCC-MIC (Microphone) ILI-MB-E3
(Intelligent Loop Interface-Main Board) (Intelligent Loop Interface-Main Board)
ILI-S-E3 NGA (Network Graphic Annunciator) ILI-S-E3
(Intelligent Loop Interface-Expansion (Intelligent Loop Interface-Expansion
Board) Board)
ILI95-MB-E3 INCC-TEL (Telephone) ILI95-MB-E3
(Intelligent Loop Interface-Main Board) (Intelligent Loop Interface-Main Board)
ILI95-S-E3 (Intelligent Loop Interface95- ILI95-S-E3 (Intelligent Loop Interface95-
Expansion Board) Expansion Board)
INCC-MIC (Microphone) INCC-MIC (Microphone)
INCC-TEL (Telephone) INCC-TEL (Telephone)
INI-VG Series (First/Second/Third INI-VGC (First/Second/Third Generation)
Generation) (Intelligent Network Interface (Intelligent Network Interface Voice
Voice Gateway) Gateway)
NGA (Network Graphic Annunciator) INI-VGX (First/Second/Third Generation)
(Intelligent Network Interface Voice
Gateway)
PM-9/PM-9G (Power Supply) NGA (Network Graphic Annunciator)
RPT-E3 (Communication Circuit) PM-9/PM-9G (Power Supply)
RPT-E3 (Communication Circuit)
Note: In the E3 Series, Mass Notification System, the LCD-E3, LCD-SLP, LCD-7100/RAN-7100 display panels are not used.
Table 1.2.1 E3 Series Modules Used in an MNS System

1.2.1 Mass Notification System - Documentation


The following MNS System information is available in the Gamewell-FCI, Mass Notification System (MNS) Installation/Operation
Manual, Part Number:LS10013-000GF-E.
• System Configurations • Class 2 Power-Limited Requirements • System Operation
• Cabinets Installations • Wiring • Testing/Maintenance

E3 Series® IS a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.


©2019 Copyright by Honeywell International, Inc. All rights reserved.

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 3
Section 2: Installation
2.1 Standards
These modules comply with the following Standards:
National Fire Protection Association
• AHJ Authority Having Jurisdiction • NFPA 72 National Fire Alarm Code
• NFPA 70 National Electrical Code • NFPA 101 Life Safety Code
UL Standards UL 864 9th Edition
2.2 Installation Requirements
All components of the E3 Series® Fire Alarm and Mass Notification Systems should be installed per the following
requirements:
• Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that
could cause condensation. Equipment must be securely mounted on rigid, permanent walls.
• Operating temperature shall not exceed the range of 32° to 120° F (0 to 49° C).
• Operating humidity not to exceed 93% non-condensing at 90° F (32° C).
• There should be adequate space around the installation to allow easy access for operation and servicing.
• All sub-assemblies and components are to be located in compliance with the local, the national codes and the
manufacturer’s recommendations.
• All installation field wiring shall be in compliance with the local code, the national code and the manufacturer’s
recommendations.
• Use the Architects and Engineering Specifications for detailed information on your Facility’s Configuration.
• Installers must be Gamewell-FCI Factory Certified to program this product. For additional information on this
product, contact the Gamewell-FCI Customer Support to schedule the Factory Certified Training.
IMPORTANT NOTE: COLD WATER/EARTH GROUND STANDARD:
Per Article 760 of the National Electrical Code, the following terminal blocks must be connected to an Earth Ground
connection:
- Terminal TB3-3 on the ILI-MB-E3/ILI95-MB-E3
- Terminal TB3-3 on the INI-VG Series (First/Second Generation)
- Terminal TB1-5 on the INI-VG Series (Third Generation)
Failure to make a proper earth ground connection from a metallic cold water pipe or driven ground rod to this
terminal will result in loss of lightning protection, reduce the tolerance of the system to transients, and will adversely
affect the operation of the system. Panel neutral or conduit ground is not acceptable; minimum wire size is 14 AWG.

4 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
2.3 INI-VG Series Installation
NOTE: The INI-VG Series sub-assembly can be installed in several types of configurations in the E3 Series cabinets. To
determine the INI-VG Series installation you require, refer to the following documents:
- E3 Series Cabinets B, C, D, Retrofit, DR-C4/DR-D4 & EQ Cabinets Installation Instructions,
P/N:LS10082-000GF-E
- E3 Series, Remote Annunciator Display and Retrofit Cabinets Installation Instructions,
P/N: LS10083-000GF-E
- Mass Notification System (MNS) Installation/Operation Manual, P/N: LS10013-000GF-E

1. Remove the unit from its static-shield bag, observing proper static protection measures.
2. Visually inspect the unit for damage.
If any components are damaged, notify the shipping carrier immediately. Report missing components to
Gamewell-FCI Customer Service.
3. Use the Hardware Kit provided with the unit.
4. Place the unit into position on the sub-chassis as shown in Figure 2.3.1. To secure the unit, use six, (#4-40 x 1/4") screws.
SUB-CHASSIS

CHASSIS GROUNDING SCREWS


MUST BE PROPERLY SECURED

FIBER MODULE
(FML-E3/FSL-E3)

FIBER MODULE
(FML-E3/FSL-E3)

INI-VG SERIES
MOUNTING SCREW LOCATIONS

Figure 2.3.1 INI-VG Series (Third Generation) Installation


5. If the network connection requires copper wiring, wire the Terminal Block TB1 inside the enclosure at any time.
6. If the connection requires fiber-optic wiring, install the desired type of fiber module (FML-E3 or FSL-E3) in the Fiber Module
#1 and/or Fiber Module #2 location. Then, refer to the Cable Manufacturer's Instructions for information on how to terminate
the cable, assemble the connector, and install the cable to the appropriate fiber-optic connector. (INI-VG Series Third
Generation only).
2.3.1 INI-VGX Installation
1. The INI-VGX mounts at the top of the sub-chassis inside the Intelligent
Network Transponder cabinet.The Intelligent Network Transponder cabinet also
contains the PM-9/PM-9G power supply, up to four AM-50 Series amplifiers
along with the standby batteries. (Batteries not included).
2. The installation of the INI-VGX does not require the removal of the sub-chassis
from the enclosure. However, for a new installation, you must remove the sub- F E R R IT E
chassis before you install the PM-9/PM-9G power supply. CLAM P

3. Connect the 20-conductor ribbon cable to J16 and then connect the cable to the 1
AM-50 Series amplifiers as shown in Figure 2.3.1.1.
4. If you use the AM-50-70 amplifier, attach each ferrite clamp to each ribbon
cable as shown in in Figure 2.3.1.1.
5. To set the address, use the Address Switch, SW1. Do not duplicate an existing F E R R IT E

address. See Figure 4.1, INI-VG Series Addresses for the programming address 2 3 CLAM P

switch settings.

4
F E R R IT E
CLAM P
Figure 2.3.1.1 Ribbon Cable Installation

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 5
Section 3: Wiring
Figure 3.1 illustrates the INI-VG Series (Third Generation).

W3 J2 J5 J7 J9 W 4 W 2 J3 TB6

TB2
TB1

TB4
W1

J12 J15
F IB E R M O D U L E # 1
W5
TB5
J13
F IB E R M O D U L E # 2
J4
BAR CODE PRODUCT
LABEL DATE CO DE
S E R IA L N U M B E R LABEL

LED 1 LE D 3 LED 4 LED 5 LED 6 LE D 7 LED 8 LED 9

R EC M RC D UP TX RX 1 R X2 R S T D G

J1 J16
Figure 3.1 INI-VG Series (Third Generation)
INI-VG Series Terminal Designations
Table 3.1 lists the INI-VG Series terminal designation connections.
Designation Description
INI-VG Series (First, Second and Third Generation)
Terminal Block 1-Network connection- using unshielded, twisted-pair
TB1-1 COM 1A connection
TB1-2 COM 1B connection
TB1-3 COM 2A connection
TB1-4 COM 2B connection
Terminal Block 2- External Power Connection
TB2-1 24 VDC (+) Power Input from external power supply or PM-9/PM-9G TB4-1, TB4-3, TB4-5
TB2-2 GND ( - ) Power Input from external power supply or PM-9/PM-9G TB4-2, TB4-4, TB4-6
TB2-3 24 VDC ( + ) Power OUT terminal-wiring terminal only, not a source of power
TB2-4 GND ( - ) Power OUT terminal- wiring terminal only, not a source of power
Terminal Block 5- Fire Fighter Handset or Fire Fighter Phone riser connection (INI-VG Series)
TB5-1 Fire Fighter Phone ( - ):
- Plugs into local Fire Fighter Handset-INI-VGC, INI-VGC
- Phone riser field wiring connection to AOM-TELF Term 3- INI-VGE,INI-VGX (First/Second Generation),
INI-VGE, INI-VGX (Third Generation)
TB5-2 Fire Fighter Phone (+):
- Plugs into local Fire Fighter Handset- INI-VGC
- Phone riser field wiring connection to AOM-TELF Term 4- INI-VGE,INI-VGX (First/Second Generation),
INI-VGE, INI-VGX (Third Generation)
TB5-3 Telephone Plug Supervisory Loop (Connects to TB5-4)
Connect only if INI-VG Series firmware is V2.0-006 or later.
TB5-4 Telephone Plug Supervisory Loop (Connects to TB5-3)
Connect only if INI-VG Series firmware is V2.0-006 or later.
Terminal Block 6- RS485 Remote Connection to ASM-16/ANU-48s in Separate Cabinet
TB6-1 + 24 VDC Supply - connects to remote ASM-16/ANU-48 TB1-3
TB6-2 RS-485 COM B - connects to remote ASM-16/ANU-48 TB1-2
TB6-3 RS-485 COM A - connects to remote ASM-16/ANU-48 TB1-1
TB6-4 System Common ( - ) connects to remote ASM-16/ANU-48 TB1-4

Table 3.1 INI-VG Series Terminal Designation Connections

6 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
INI-VG Series (Third Generation only)
Terminal Block 1-Network connection- using unshielded, twisted-pair, fiber-optic plug-in modules
TB1-5 Earth Ground
Terminal Block 4- Signaling Line Circuit Connections (See Notes 1, 2, 3, 4 and 5)
TB4-1 Local Speaker (INCC or Intelligent Network Transponder) or Connect to ACT-1 (-) Terminal (INI-VGE Only)
(See Note 5).
TB4-2 Local Speaker (INCC or Intelligent Network Transponder) or Connect to ACT-2 (+) Terminal (INI-VGE Only)
(See Note 5).
TB4-3 Signaling Line Circuit ( + ), Style 4
TB4-4 Signaling Line Circuit ( - ), Style 4
NOTES
Note 1: INI-VGC Signaling Line Circuit supports AOM-TEL and AOM-TELF Telephone Modules.
Note 2: INI-VGC Signaling Line Circuit supports AOM-TEL and AOM-TELF Telephone Modules and AOM-2S, AOM-2SF, MMO-6S, MMO-
6SF Speaker Circuit Control Modules.
Note 3: INI-VGE Signaling Line Circuit supports AOM-TEL, AOM-2SF, MMO-6SF Control Modules.
Note 4: Use the Signaling Line Circuit (SLC) devices for Fire applications only.
Note 5: If you use TB4-1 and TB4-2 to connect to a local speaker, you must use a transformer-coupled voice evacuation loudspeaker set
for 25V, 1W or less.
Table 3.1 INI-VG Series Terminal Designation Connections (Continued)
3.1 LED Indicators, Operation and Network Connections
Table 3.1.1 lists the INI-VG Series indicating and diagnostic LEDs.
Designation LED Label Description
LED 1 REC Network is reconfiguring.
LED 3 MRC This node is initiating a network reconfiguration.
LED 4 DUP Duplicate node address or address switch error.
LED 5 TX The sub-assembly is transmitting network data.
LED 6 RX1 The sub-assembly is receiving network data on Channel 1.
LED 7 RX2 The sub-assembly is receiving network data on Channel 2.
LED 8 RST Firmware fault
LED 9 DG Trouble condition
Table 3.1.1 INI-VG Series Indicating and Diagnostic LEDs
You can connect the INI-VG Series to the E3 Series Network in several ways. These connections include the following
options:
• UTP via the terminal TB1
• Fiber-Option Modules (via daughter cards connected to J12 and /or J13)
• Locally using J2, J5 and/or J7
Table 3.1.2 lists the above three options.

UTP UTP and/or Fiber-Option (INI-VG Series Third Generation Only)


Connections Locally using J2, J5 and/or J7
Connections
Connect UTP via TB1 When you use the UTP and/or Fiber- When you use only the local connection
Option connections, the following LEDs
J2, J5 and/or J7, and neither the UTP
are normally activated. nor the Fiber-Option modules are used,
• LED5 (TX) the following LEDs are normally
• LED6 (RX1) activated.
• LED7 (RX2) • LED5 (TX)
(See Notes 1 and 2). • LED9 (DG)
(See Note 3).
Note 1: LED6 and/or LED7 will be activated if the corresponding port is connected to another node.
Note 2: LED9 is normally OFF.
Note 3: Both LED6 and LED7 are normally OFF.
Table 3.1.2 INI-VG Series Connection Options to the E3 Series Network

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 7
3.2 INI-VG Series Power Connections
The INI-VGC and INI-VGE serve as the network interface and control unit of an INCC Command Center. Power connections are
listed as follows:
• INI-VGC connects to its operating power via Terminal Block TB1.
• INI-VGE connects to its operating power via Terminal Block TB1.
The INI-VGX serves as the network interface and control unit of the distributed amplifier assembly that is installed in an Intelligent
Network Transponder cabinet enclosure. It connects to its own dedicated PM-9/PM-9G power supply via the supplied ribbon cable
that connects between J4 of the INI-VGX and J1 of the PM-9/PM-9G. Table 3.2.1 lists the INI-VG Series power connections.

Designation Description
Terminal Block 1
For INI-VGC or INI-VGX (if J4 is not used)
TB2-1 +24 VDC IN - from power supply or TB4-5 of PM-9/PM-9G
TB2-2 GND ( - ) IN – from power supply or TB4-2 of PM-9/PM-9G
TB2-3 +24 VDC OUT
TB2-4 GND ( - ) OUT
Jumper 4
For INI-VGX or INI-VGE (if J4 is used)
J4 SDA/SCL – to PM-9/PM-9G power supply J1. Use for supervision of the PM-9/PM-9G.
Table 3.2.1 INI-VG Series Power Connections
3.3 INI-VG Series Wiring Connections
Table 3.3.1 lists the INI-VG Series jumper, cable and switch connections.

Designation Description Comments


INI-VG Series (First, Second and Third Generation)
J1 "E" FNCTNS/RESET Factory use
J3 RS-485 Local Connects to 1st Local ASM-16/ANU-48 Connector J2
J4 SDA/SCL Connects to PM-9/PM-9G Connector J1 in the INX, INX CAB-B and the INI-VGE only.
Used for the Supervision of the PM-9/PM-9G.
J7 Repeater Network Backplane. Connect to J4 on NGA sub-assembly (optional) or J4 on ILI-E3 Series or
ANX (optional). (See Note).
For optimum ILI95-E3/ILI-E3 Series or ANX network communication, run this cable underneath
the PM-9/PM-9G. (See Note).
NOTE: Use the ANX for Fire applications only.
J15 Microphone Connectors to microphone cable.
If no microphone is installed, jumpers must be installed between pins 3 and 4, and 5 and 6.
J16 Signals In/Out Connects to the first AM-50 Series amplifier connector J1 in the INX or INX CAB-B only
INI-VG Series (Second and Third Generation)
W1 GFI Switch To enable the network ground fault detection, set the switch DOWN.
To disable the network ground fault detection, set the switch UP.
NOTE: When the UTP copper wiring is used for one or both network connections, enable the
network ground fault detection. You can enable ground fault detection of the network wiring
between this INI-VG Series module and any other nodes that are directly connected to this INI-
VG Series module, node.
W2 Termination Switch To enable the RS-485 termination, press the switch LEFT.
To disable the RS-485 termination, press the switch RIGHT.
NOTE: You can enable the RS-485 termination if the last ASM-16 or ANU-48 module is
connected to the RS-485 bus and JMP1 is installed. Otherwise, disable the termination.
W3 EGND Switch To enable the earth ground reference circuit, press the switch LEFT.
To disable the earth ground reference circuit, press the switch RIGHT.
NOTE: You can enable the earth ground reference circuit only if the
INI-VG Series is powered by a power supply that does not supervise ground faults.

Table 3.3.1 INI-VG Series Jumper, Cable and Switch Connections

8 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
INI-VG Series (Second and Third Generation) (Continued)
W5 PHONE Filter Bypass To bypass, set the switch UP.
To enable the filter, set the switch DOWN.
NOTE: Enable the filter if TB5 is connected to a local command center telephone.
INI-VG Series (Third Generation Only)
J2 Local ARCNET Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly. (See Note 1) (Third
Generation only).
J5 Local ARCNET Connects to J2 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly. (See Note 1). (Third
Generation only).
J12 Fiber Module #1 Connection of optional Fiber-Optic modules (FML-E3 or FSL-E3) for Network Port 1. (Third
Generation only).
J13 Fiber Module #2 Connection of optional Fiber-Optic modules (FML-E3 or FSL-E3) for Network Port 2. (Third
Generation only)
W4 ARCNET Termination To enable ARCNET termination, press the switch LEFT.
To disable ARCNET termination, press the switch RIGHT. (Third Generation only).
NOTE: Use OPEN for normal operation.
Use SHORT if the ILI-MB-E3 is located at the end of the ARCNET bus. (These settings are
used for the ILI-MB-E3, First Generation only.)
Note: Use the ANX for fire applications only.
Table 3.3.1 INI-VG Series Jumper, Cable and Switch Connections (Continued)

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 9
3.4 INI-VG Series (Third Generation) Wiring Diagrams
3.4.1 INI-VGC (Third Generation) Wiring Diagram
Figure 3.4.1.1 illustrates the field wiring connections for the INI-VGC circuit board (Third Generation only).
NOTE: To view the INI-VG Series (First/Second Generation) wiring, refer to the INI-VG Series Instructions
(P/N:9000-0549).

TO ASM-16 TB1-3 OR ANU-48 TB1-3 (+) NOTE 2:


TO ASM-16 TB1-2 OR ANU-48 TB1-2 (RS485 COM B) IF NO MICROPHONE
TO ASM-16 TB1-1 OR ANU-48 TB1-1 (RS 485 COM A) IS INSTALLED,
TO ASM-16 TB1-4 OR ANU-48 TB1-4 (-) INSTALL JUMPERS
TO 1ST LOCAL ASM-16 BETWEEN
J2 CONNECTOR PINS 3 & 4 AND 5 & 6.
(IN SAME CABINET)
INCC ONLY NOTE 3:
LOCAL TO NGA J4
INSTALL THE JUMPER
ARCNET
RS485 LOCAL
BETWEEN
W312 91
102
9 1
10 2
11
12
1 9 4 TB5-3 AND TB5-4 ON THE
EGND 1 4
1 J2 J5 J7 TERM
2 10 INI-VG SERIES WHEN THE
FROM NODE COM 2A REPEATERW2 GND (-) IN
COM 1A
E3 SERIES ® NETWORK
J3 RS485 REMOTE 24 VDC + IN FIRMWARE IS
PREVIOUS NODE COM 2B TB1 COM 1B TB6 GND (-) OUT V2.0-006 OR LATER.
TO NODE COM 1A CONNECTIONS USING (SEE NOTE 4)
COM 2A 24 VDC + OUT
NEXT NODE COM 1B COM 2B
WIRE, UNSHIELDED, TB2 1
4 NOTE 4:
EARTH GROUND TWISTED-PAIR SIGNALING LINE CKT (-)
5 EITHER THE RS-485
W1 LOOP SIGNALING LINE CKT (+)
EARTH GROUND GFI LOCAL SPEAKER LOCAL OR RS-485 REMOTE
(SEE SECTION 2.1) FIBER MODULE #1 INI-VGC TB4
1
}CKT. OUTPUT, CONNECTION MAY BE
FML-E3/FSL-E3 J12 25 VOLT, 1 WATT MAX. USED. DO NOT USE BOTH.
ARCNET PORT 1 10 9 6 GRAY

MICROPHONE
(SEE NOTE 7) 2 1 JUMPER NOTE 5:
J15 WHEN THE UTP NETWORK
FIBER MODULE #2 MICROPHONE CABLE WIRING IS USED, JUMPER
FML-E3/FSL-E3 J13 1
(SEE NOTE 2) “GFI” MUST BE

PHONE
O
ARCNET PORT 2 10 9 W5 N
INSTALLED, TO ENABLE
(SEE NOTE 7) 2 1 JUMPER (SEE NOTE 3) THE NETWORK GROUND
4
- 16 AWG (Firefighter FAULT DETECTION.
E3 SERIES ® NETWORK OFF
CONNECTIONS USING J1 + Phone Supervisory)
13 1 GND
FIBER-OPTIC CABLE 2 HK FIREFIGHTER NOTE 6:
(OPTIONAL)
14
“E” FNCTNS\RESET TB5 1 TELEPHONE W1 THRU W5 SWITCHES:
(SEE NOTE 1) J4 9 10 CABLE FOR INFORMATION ON W1
SIGNALS IN/OUT
SDA/SCL

(INCC ONLY) THRU W5 SWITCH


LED LED LED LED LED LED LED LED J16
1 3 4 5 6 7 8 9 19 1 SETTINGS USED TO
REC MRC DUP TX RX1 RX2 RST DG
SW1 20 2 1 2 ENABLE OR DISABLE
SWITCHES, REFER TO
NOTE 1: TABLE 3.2.1.
LED1 = REC (NETWORK CONFIGURATION)
LED3 = MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE NOTE 7:
LED4 = DUP (NODE’S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE) FIBER MODULES #1/#2
LED5 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK) RESTRICTIONS:
LED6 = RX1 (NODE IS RECEIVING DATA FROM THE NETWORK) IF YOU USE TB1-1 AND
LED7 = RX2 (NODE IS RECEIVING DATA FROM THE NETWORK) TB1-2 FOR PORT 1, DO NOT
LED8 = RST (FIRMWARE FAULT) INSTALL FIBER MODULE #1
LED9 = DG (GENERAL NETWORK FAULT) IN CONNECTOR J12.
IF YOU USE TB1-3 AND
TB1-4 FOR PORT 2, DO NOT
INSTALL FIBER MODULE #2
IN CONNECTOR J13.

Figure 3.4.1.1 INI-VGC (Third Generation) Wiring Connections Diagram

10 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
3.4.2 INI-VGE (Third Generation) Wiring Connections Diagram
Figure 3.4.2.1 illustrates the field wiring connections for the INI-VGE sub-assembly.
NOTE: To view the INI-VG Series (First/Second Generation) wiring, refer to the INI-VG Series Instructions (P/N:9000-0549).

TO ASM -16 TB1-3 OR ANU-48 TB1-3 (+) NOTE 2:


TO ASM -16 TB1-2 OR AN U-48 TB1-2 (R S485 C OM B) IF N O M ICRO PHO NE IS
TO ASM -16 TB1-1 OR ANU-48 TB1-1 (RS 485 COM A) INSTALLED ,
TO ASM -16 TB1-4 OR ANU-48 TB1-4 (-) INSTALL JU M PERS
BETW EEN
TO 1 ST LOCAL ASM -16
PINS 3 & 4 AND 5 & 6.
J2 CO NNECTOR
(IN SAM E CABINET)
LOCAL TO NGA J4 INC C ONLY NOTE 3:
ARCNET INSTALL THE JUM PER
BETW EEN
W 3 21 91
102
9 1
10 2
11
12
1
RS485 LOCAL
9 4 TB5-3 AND TB5-4 O N THE
EGND 1
1 J2 J5 J7 TERM
2 10
4
GND (-) INI-VG SERIES W H EN THE
FROM N ODE COM 2A CO M 1A REPEATERW 2
J3 RS485 REMOTE FIRM W AR E IS
24 VDC + OUT
PREVIOUS NODE COM 2B
TB1 COM
®
1B E3 SERIES NETW ORK TB6 V2.0-006 O R LATER.
TO NODE COM 1A (SEE NOTE 4) GND (-)
COM 2A CONNECTION S USIN G 24 VDC + IN
NEXT NODE COM 1B TB2 1
EAR TH GR OUND C OM 2B W IRE, UNSHIELDED, 4 NOTE 4:
TW ISTED-PAIR TO SIGN ALING LIN E CKT (-)
5 EITHER THE RS-485
W1 LOOP TO SIGNALING LINE C KT (+)
EARTH GROUND G FI TO ACT-2 (+) TERM INAL LOC AL OR R S-485 REMO TE
(SEE SECTION 2.1) TB4 TO ACT-1 (-) TERM INA L CO NNECTION M AY BE
FIBER MODULE #1 INI-VGE 1
DISTANCE BETW EEN USED. DO N OT USE BOTH .
FML-E3/FSL-E3 J12 6 INI-VGE AND ACT-1 NOT
ARC NET PORT 1 10 9

MICROPHONE
(SEE NOTE 7) TO EXCEED 20 FEET M AX. N OTE 5:
2 1
W HEN THE U TP NETW O RK
J15
FIBER M ODULE #2 (SEE NO TE 2) W IRING
FML-E3/FSL-E3 J13 1 IS USED, JU MPER “G FI”

PHONE
O
ARCNET POR T 2 10 9
W5 N M UST
(SEE NOTE 7) JUM PER (SEE NOTE 3)
2 1 BE IN STALLED, TO
4 16 AW G (FIREFIGHTER
- EN ABLE TH E NETW OR K
E3 SERIES ® NETW ORK OFF PHONE SUPERVISORY )
CO NNECTIONS USING J1 + G RO UND FA ULT
13 1 G ND TO AOM -TELF(S) TERM 4 DETECTIO N.
FIBER-O PTIC CA BLE 14 2 HK
(OPTIONAL) “E” FNCTNS\RESET TB5 TO AOM -TELF(S) TERM 3
1
J4 9 10 NO TE 6:
TELEPHONE BOX OR W 1 THRU W 5 SW ITCHES:
SIGNALS IN/OUT

SDA/SCL
LED LED LED LED LED LED LED LED J16 FO R INFOR M ATION O N W 1
1 3 4 5 6 7 8 9 19 1 TERM INAL BLOCK

(CLEAR)
REC M RC DUP TX RX1 RX2 RST DG
SW 1 20 2 1 2 THRU W 5 SW ITCH

(BLACK)
SETTIN GS U SED TO
NO TE 1: BLACK ENABLE O R D ISABLE
W HITE
LED 1 = REC (NETW O RK C ONFIG URA TION) RED SW ITCHES, R EFER TO
LED 3 = M RC (NETW OR K RECON FIG UR ATION O RIG INATING FRO M TH IS W HITE TABLE 3.2.1.
NO DE)
CONNECTIONS
LED4 = DUP (NO DE’S N ETW OR K ADD RESS IS D UPLICA TED AT AN OTH ER NO TE 7:
FROM TELEPHONE
N ODE) FIBER MO DU LES #1/#2
LED5 = TX (NOD E IS TRANSMITTING DATA TO THE N ETW O RK) R ESTRICTIO NS:
LED6 = RX1 (NO DE IS R ECEIVING DATA FROM THE N ETW ORK) IF YO U USE TB1-1 A ND
LED7 = RX2 (NO DE IS R ECEIVING DATA FROM THE NETW OR K) TB1-2 FO R PO RT 1, D O NO T
LED 8 = R ST (FIR MW A RE FAULT) INSTALL FIBER MO DULE #1
LED9 = D G (GENERAL NETW OR K FAU LT) IN CO NNEC TOR J12.
IF YOU USE TB1-3 AND
TB1-4 FOR POR T 2, DO NOT
INSTALL FIB ER M OD ULE #2
IN CON NECTO R J13.

Figure 3.4.2.1 INI-VGE (Third Generation) Wiring Connections Diagram

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 11
3.4.3 INI-VGX (Third Generation) Wiring Connections Diagram
Figure 3.4.3.1 illustrates the field wiring connections for the INI-VGX sub-assembly.
NOTE: To view the INI-VG Series (First/Second Generation) wiring, refer to the INI-VG Series Instructions (P/N:9000-0549).

TO ASM-16 TB1-3 OR ANU-48 TB1-3 (+) NOTE 2:


TO ASM-16 TB1-2 OR ANU-48 TB1-2 (RS485 COM B) IF NO MICROPHONE IS
TO ASM-16 TB1-1 OR ANU-48 TB1-1 (RS 485 COM A) INSTALLED,
TO ASM-16 TB1-4 OR ANU-48 TB1-4 (-) INSTALL JUMPERS
TO 1 ST LOCAL ASM-16 BETWEEN
J2 CONNECTOR PINS 3 & 4 AND 5 & 6.
(IN SAME CABINET)
INCC ONLY NOTE 3:
LOCAL TO NGA J4
INSTALL THE JUMPER
ARCNET
BETWEEN
RS485 LOCAL
W312 91
102
9 1
10 2
11
12
1 9 4 TB5-3 AND TB5-4 ON THE
EGND 1 4
1 J2 J5 J7 TERM
2 10
TERMINAL BLOCK TB2 IS INI-VG SERIES WHEN THE
FROM NODE COM 2A COM 1A REPEATERW2
J3 RS485 REMOTE FIRMWARE IS
® TB6 NOT USED WHEN INI-VGX-UTP
PREVIOUS NODE COM2B 1B E3 SERIES NETWORK V2.0-006 OR LATER.
TB1 COM (SEE NOTE 4) IS CONNECTED TO THE
TO NODE COM1A COM 2A CONNECTIONS USING TB2 1 PM-9/PM-9G VIA J4
NEXT NODE COM1B COM 2B WIRE, UNSHIELDED, 4 NOTE 4:
EARTH GROUND TWISTED-PAIR TO SIGNALING LINE CKT (-)
5
TO SIGNALING LINE CKT (+) EITHER THE RS-485
W1 LOOP
EARTH GROUND GFI USED FOR LOCAL OR RS-485 REMOTE
TB4 STYLE 4 CONNECTION MAY BE
(SEE SECTION 2.1) LOCAL SPEAKER
FIBER MODULE #1
FML-E3/FSL-E3 J12
INI-VGX 1 (CLASS “B” ONLY)
25 VOLT, 1 WATT MAX.
USED. DO NOT USE BOTH.
6

MICROPHONE
ARCNET PORT 1 10 9 NOTE 5:
(SEE NOTE 7) 2 1
(SEE NOTE 2) WHEN THE UTP NETWORK
J15
FIBER MODULE #2 WIRING IS USED, JUMPER
FML-E3/FSL-E3 J13
1 “GFI” MUST BE

PHONE
O

ARCNET PORT 2 10 9 W5 JUMPER


N INSTALLED, TO ENABLE
(SEE NOTE 7) 2 1 16 AWG (SEE NOTE 3) 4
THE NETWORK GROUND
(FIREFIGHTER PHONE
- FAULT DETECTION.
E3 SERIES® NETWORK OFF
CONNECTIONS USING
J1 +
SUPERVISORY)
13 1
GND
OFF TO AOM-TELF(S) TERM 4 NOTE 6:
FIBER-OPTIC CABLE 14 2
TB5 HK 1 TO AOM-TELF(S) TERM 3
“E” FNCTNS\RESET W1 THRU W5 SWITCHES:
(OPTIONAL) INI-VGX-UTP PHONE
(SEE NOTE 1) J4 9 10 FOR INFORMATION ON W1
SIGNALS IN/OUT RISER CONNECTION
SDA/SCL
THRU W5 SWITCH
LED LED LED LED LED LED LED LED J16 STYLE 4 (CLASS “B”)
SETTINGS USED TO
1 3 4 5 6 7 8 9 19 1
SW1 USING SHIELDED,
20 2 1 ENABLE OR DISABLE
REC MRC DUP TX RX1 RX2 RST DG 2 TWISTED-PAIR WIRE
SWITCHES, REFER TO
TO PM-9/PM-9G
TABLE 3.2.1.
J1 CONNECTOR
TO 1ST AM-50 SERIES AMPLIFIER (INX, INX CAB-B ONLY)
J1 CONNECTOR (INX OR INX CAB-B ONLY) NOTE 7:
NOTE 1: FIBER MODULES #1/#2
LED1 = REC (NETWORK CONFIGURATION) RESTRICTIONS:
LED3 = MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE IF YOU USE TB1-1 AND
LED4 = DUP (NODE’S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE) TB1-2 FOR PORT 1, DO NOT
LED5 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK) INSTALL FIBER MODULE #1
LED6 = RX1 (NODE IS RECEIVING DATA FROM THE NETWORK) IN CONNECTOR J12.
LED7 = RX2 (NODE IS RECEIVING DATA FROM THE NETWORK) IF YOU USE TB1-3 AND
LED8 = RST (FIRMWARE FAULT) TB1-4 FOR PORT 2, DO NOT
LED9 = DG (GENERAL NETWORK FAULT) INSTALL FIBER MODULE #2
IN CONNECTOR J13.

Figure 3.4.3.1 INI-VGX (Third Generation) Wiring Connections Diagram

12 INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19
Section 4: Programming Address Switch Settings
To set the address, use the Address Switch, SW1. Do not duplicate an existing address. Figure 4.1illustrates the programming
address switch settings for the INI-VG Series modules.
B L A C K = T H E S W IT C H IS U P .
B L A C K = T H E S W IT C H IS D O W N .

IN I-V G S E R IE S A D D R E S S S W IT C H S E T T IN G S
on on on on on on on
=1 =11 =21 =31 =41 =51 =61
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on on on on on on on
=2 =12 =22 =32 =42 =52 =62
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on on on on on on on
=13 =23 =33 =43 =53 =63
1 2 3 4 5 6 7 8 =3 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on on on on on on on
=14 =24 =34 =44 =54 =64
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1o n2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on =4 on on on on
=15 =25 =45 =55
=35
1 2 3 4 5 6 7 8 =5 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on on on on on on
=16 =26 =36 =46 =56
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on =6 on on on on on
=17 =27 =47 =57
=37
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on =7 on on on on on
=18 =28 =38 =48 =58
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on =8 on on on on on
=19 =29 =49 =59
=39
1 2 3 4 5 6 7 8 =9 1 2 3 4 5 6 7 8 1o n2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
on on on on on
=20 =30 =50 =60
=40
1 2 3 4 5 6 7 8 =10 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Figure 4.1 INI-VG Series Address Switch Settings

Section 5: Specifications
The following are the electrical specifications for the INI-VG Series modules.
Operating Voltage: 24 VDC (from the PM-9/PM-9G power supply)
Operating Current: 0.150 amp
Alarm Current: 0.150 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 0 to 93%, non-condensing at 90 F (32° C)
Supervised Class 2 Power-Limited

INI-VG Series (Third Generation) Product Installation Instructions — P/N LS10218-000GF-E:C 05/17/19 13
Section 6: Reference Documentation
Table 6.1 lists the UL-Controlled documentation assigned to the S3 Series and E3 Series Systems. If you require detailed installa-
tion instructions on cabinetry, wiring and specifications, you can download the following UL-Controlled documents from the ESD
site on the Gamewell-FCI Website (www.gamewell-fci-esd.com).
Part Number Title
UL Listing Document
LS10005-051GF-E S3 Series (Small Addressable Fire Alarm Control Panel) UL Listing Document
LS10080-051GF-E E3 Series Fire System (Expandable Emergency Evacuation System) UL Listing Document
Manuals
9000-0575 E3 Series Broadband Installation/Operation Manual
9000-0577 E3 Series Classic Installation/Operation Manual
LS10013-000GF-E E3 Series Combined Fire and MNS Installation/Operation Manual
Installation Instructions
9000-0491 LCD-7100 (Remote Serial Annunciator) Installation Instructions
9000-0544 AM-50 Series (50 Watt Amplifiers) Installation Instructions
9000-0545 INX, INX CAB-B, INX CAB-C and INX CAB-D Installation Instructions
9000-0546 INCC Intelligent Network Interface Installation Instructions
9000-0548 PM-9 (Power Supply) Installation Instructions
9000-0549 INI-VG Series (Intelligent Network Transponder) Installation Instructions
9000-0550 ASM-16 (Addressable Switch Module) Installation Instructions
9000-0564 ANU-48 (Remote LED Driver Annunciator) Installation Instructions
9000-0568 NGA (Network Graphic Annunciator) Installation Instructions
9000-0569 ILI-S-E3 (Intelligent Loop Interface - Expansion Board) Installation Instructions
9000-0579 ILI-MB-E3 (Intelligent Loop Interface - Main Board) Installation Instructions
9000-0580 RPT-E3-UTP (Repeater-E3 Unshielded Twisted-Pair) Installation Instructions
9000-0581 DACT-E3 (Digital Alarm Communicator Transmitter) Installation Instructions
9000-0582 LCD-E3 (Liquid Crystal Display-E3) Installation Instructions
9001-0017 ILI95-MB-E3 (Intelligent Loop Interface-95 - Main Board) Installation Instructions
9001-0018 ILI95-S-E3 (Intelligent Loop Interface-95 - Expansion Board) Installation Instructions
9001-0055 PM-9G (Power Supply) Installation Instructions
9001-0064 ANX (Addressable Node Expander) Installation Instructions
9001-0066 RAN-7100 (Remote Alphanumeric Annunciator) Installation Instructions
LS10044-000GF-E SLC-PM/SLC95-PM (Signaling Line Circuit-Personality Modules Installation Instructions
LS10045-000GF-E LCD-SLP (Liquid Crystal Display-Smart Loop Panel) Installation Instructions
LS10046-000GF-E FML-E3/FSL-E3 (Fiber-Optic Multi-Mode/Fiber-Optic Single-Mode) Installation Instructions
LS10058-000GF-E FLPS-7 (Power Supply) Installation Instructions
LS10082-000GF-E E3 Series Cabinets B, C, D, Retrofit, DR-C4/DR-D4 and EQ Cabinets Installation Instructions
LS10083-000GF-E E3 Series, Remote Annunciator Display and Retrofit Cabinets Installation Instructions
LS10222-000GF-E NGA (Network Graphic Annunciator-Second Generation) Installation Instructions
Addendum
9000-0427-L8 Compatibility Addendum to Gamewell-FCI Installation/Operation Manuals UL File S1869
Supplement
LS10138-151GF-E E3 Series Control Panel, Releasing Applications Supplement
Frame-Posts
9000-0583 E3 Series for the LCD-E3 Operating Instructions
LS10056-000GF-E S3 Series (Small Addressable Fire Alarm Control Panel System), Operating Instructions
LS10121-000GF-E E3 Series for the LCD-SLP Operating Instructions
Table 6.1 Reference Documentation

Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
LS10218-000GF-E | C | 10/19
www.gamewell-fci.com ©2019 Honeywell International Inc.