Section 1: Description
The ILI-MB-E3 (Intelligent Loop Interface-Main Board) is the main circuit board. When the ILI-MB-E3 is connected to
the network, it is compatible with the following systems.
• E3 Series® Fire Alarm and Mass Notification System • E3 Series Broadband System
(Autonomous Control Unit)
• E3 Series (Expandable Emergency Evacuation) System • E3 Series Classic System (for Fire applications only)
NOTE: The E3 Series nodes may be networked with the S3 Series System.
It provides terminals for the connection of all of the sub-assemblies. The ILI-MB-E3 sub-assembly can support the
following modules:
• up to a total of 16 ASM-16 and/or • DACT-E3
• up to a total of 16 ANU-48 Remote LED Driver Modules • LCD-E3 or LCD-SLP
The ILI-MB-E3 supports the System Sensor protocol using Velociti mode. In Velociti mode, each Signaling Line Circuit
(SLC) supports 159 detectors and 159 modules. When the unit is used in conjunction with the RPT-E3-UTP Repeater sub-
assembly, J2, and/or J5 connected, each unit occupies one node on the Broadband network.
NOTE: Use the Signaling Line Circuit (SLC) devices for Fire and/or E3 Series Releasing applications.
Figure 1.1 ILI-MB-E3 (OKI Version) Module Figure 1.2 ILI-MB-E3 (Kinetis Version) Module
1.1 Mass Notification System (MNS)
The Gamewell-FCI, Mass Notification System (MNS) is a Combination In-Building Fire and Mass Notification System.
It comprises the E3 Series Broadband Emergency Voice Evacuation and the E3 Series Broadband Networked Fire Alarm
Systems. This design allows a wide range of configurations to form an integrated, distributed fire alarm system in
combination with the audio evacuation for both Fire and Mass Notification functions as desired. The design also allows
for its use as a dedicated standalone Mass Notification System without the fire alarm service. The network communication
conveys all Fire Alarm and Mass Notification control functions, audio evacuation, voice paging, and fire fighter
communications over a single pair of wires or fiber-optic cable. The modular design offers several configurations to
accommodate the following audio components:
• Autonomous Control Unit (ACU), (Main Command Center)
• Local Operating Console (LOC), (Remote Command Center)
• E3 Series Broadband Voice Evacuation System
Table 1.1.1 lists the E3 Series sub-assemblies that can be used in the Gamewell-FCI, MNS (Mass Notification System).
Autonomous Control Unit (ACU) E3 Broadband System
E3 LOC Remote Command Center
(Main Command Center) (Distributed System)
AM-50 Series Amplifiers AOM-TELF/AOM-2SF AM-50 Series Amplifiers
ANU-48 (Remote Annunciator) ASM-16 (Addressable Switch Module) ANU-48 (Remote Annunciator)
ASM-16 (Addressable Switch Module) INI-VG Series ASM-16 (Addressable Switch Module)
(Intelligent Network Interface Voice
Gateway)
ILI-MB-E3 INCC-MIC (Microphone) ILI-MB-E3
(Intelligent Loop Interface-Main Board) (Intelligent Loop Interface-Main Board)
ILI-S-E3 NGA (Network Graphic Annunciator) ILI-S-E3
(Intelligent Loop Interface-Expansion (Intelligent Loop Interface-Expansion
Board) Board)
ILI95-MB-E3 INCC-TEL (Telephone) ILI95-MB-E3
(Intelligent Loop Interface-Main Board) (Intelligent Loop Interface-Main Board)
ILI95-S-E3 (Intelligent Loop Interface95- ILI95-S-E3 (Intelligent Loop Interface95-
Expansion Board) Expansion Board)
INCC-MIC (Microphone) INCC-MIC (Microphone)
INCC-TEL (Telephone) INCC-TEL (Telephone)
INI-VG Series INI-VGC
(Intelligent Network Interface Voice (Intelligent Network Interface Voice
Gateway) Gateway)
NGA (Network Graphic Annunciator) INI-VGX
(Intelligent Network Interface Voice
Gateway)
PM-9/PM-9G (Power Supply) NGA (Network Graphic Annunciator)
RPT-E3-UTP (Communication Circuit) PM-9/PM-9G (Power Supply)
RPT-E3-UTP (Communication Circuit)
NOTE: In the E3 Series, Mass Notification System, the LCD-E3 and LCD-SLP Display panels are not used.
®
E3 Series is a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories, Inc.
©2016 Copyright by Honeywell International, Inc. All rights reserved.
Compliance - This product has been investigated and found to be in compliance with the following standards.
Underwriters Laboratories
• UL-864 Control Units for Fire Alarm Systems, Ninth Edition
• UL-2017 General Purpose Signaling Devices and Systems, First Edition
• UL-2572 MNS Mass Notification, First Edition
Installation - This product is intended to be installed in accordance with the following standards.
2.3 Specifications
The following list the electrical specifications for the ILI-MB-E3.
Installation Instructions
Cabinet Assembly Options Part Number Cabinet Dimensions (For installation instructions, refer to
the Section listed below).
NOTE: You can use standoffs to mount the DACT-E3/RPT-E3-UTP or the ANX on top of the
ILI-MB-E3.
CABINET B,
BACKBOX
ILI-MB-E3,
8-HOLE MOUNTING
PATTERN
ILI-MB-E3
(NOTE: PCB
ORIENTATION)
1
1
STANDOFF, 1
3/16", (#4-40 x 1.25")
8 PLACES IL I
-M B
-E 3
1
BA
TT
N OTE: THE ANX CAN ER
IE S
MOUNT ON TOP OF THE
ILI-MB-E3.
(IN PLACE OF THE
DACT-E3/RPT-E3-UTP).
Figure 2.5.1.1 ILI-MB-E3 Installed to the Cabinet B Backbox
CABINET C,
E3-INCC-C PLATE
IL I
-M
B- STANDOFF,
E3 3/16" HEX
(#4-40 x 1.25”)
1 8 PLACES
2.5.3.1 ILI-MB-E3 Installed to the B-SLIM-E3 Plate 2.5.3.2 ILI-MB-E3 Installed to the 600XL or 7200
Retrofit Cabinet Mounting Plates
1. Align and mount the ILI-MB-E3 to the pins on the 1. Align and mount the ILI-MB-E3 to the pins on the
B-Slim-E3 Plate. retrofit cabinet, mounting plate.
2. Insert the eight screws (#4-40) into the eight-hole 2. Insert the eight standoffs (3/16” HEX #4-40, x 1.25”)
mounting pattern and secure the screws to the B-SLIM- into the eight-hole mounting pattern and secure the
E3 plate as shown in Location 1 of the figure below. standoffs to the retrofit cabinet, mounting plate as
shown in Location 1 of the figure below.
NOTE: Use standoffs to mount the DACT-E3/RPT-E3-UTP or the ANX on top of the ILI-MB-E3.
Figure 2.5.3.1.1 illustrates the ILI-MB-E3 installed to the Figure 2.5.3.2.1 illustrates the ILI-MB-E3 installed to the
B-SLIM-E3 Plate 7200 Cabinet mounting plates.
7200 CABINET B,
E3-INCC-C PLATE
SCREW, #4-40 B-
8 PLACES SL
IM
-E 1
NOTE: MOUNT ANY OF THE 3P IL I
FOLLOWING OPTIONAL LA -M
MODULES ON TOP OF THE 1 TE B-
E3 STANDOFF,
ILI-MB-E3/ILI95-M,B-E3:
- DACT-E3/RPT-E3-UTP IL I 3/16" HEX
- ILI-S-E3/ILI95-S-E3 -M 1 (#4-40 x 1.25”)
- ANX B- 8 PLACES
E3
Figure 2.5.3.1.1 ILI-MB-E3 Installed to the Figure 2.5.3.2.1 ILI-MB-E3 Installed to the 7200
B-SLIM-E3 Plate Retrofit Cabinet Mounting Plate
Circuit Type Circuit Function Wire Requirements Distance Typical Wire Type*
SLC Connects to intelligent Twisted-unshielded pair, 12 to 10,000 ft. (3,000 m) 12 AWG (3.1 mm2)
(Class 2 and addressable 18 AWG (3.1 to 0.78 mm2) 8,000 ft. (2,400 m)
Power-Limited) modules. 14 AWG (2.00 mm2)
40 Ohms maximum per length 4,875 ft. (1,450 m)
of Style 6 & 7 loops. 16 AWG (1.30 mm2)
40 Ohms combined-branch 3,225 ft. (980 m) 18 AWG (0.78 mm2)
circuits maximum for Style 4
loop.
MC cable with 2 conductor
twisted.
Note: The maximum total
capacitance of all SLC wiring
(both between conductors and
from any conductor to ground)
should not exceed 0.5.
microfarads.
RS-485 Connects to LCD-E3, Twisted-unshielded pair with a 3,000 ft. (.914 m) 16 AWG (1.30 mm2)
(Class 2 LCD-SLP, ASM-16, characteristic impedance of (maximum)
Power-Limited) ANU-48 and LCD- 120 Ohms. 18 AWG
7100/RAN-7100 (0.78 mm2) minimum.
modules.
RS-232 Connects to Printers, Twisted-unshielded pair. 18 50/15.24 16 AWG (1.30 mm2)
(Class 2 CRT, or PC. AWG (0.78 mm2) minimum (without modem)
Power-Limited)
NAC Notification E3 connects to 12-18 AWG (3.1 to 0.78 mm2) To meet 1.2 V drop, 12 to 18 AWG
Appliance Circuit Notification Appliances At alarm current level, no more or sized to provide (3.1 to 0.78 mm2)
(Class 2 than a 1.2 V drop at the end of the minimum rated
Power-Limited) the circuit, or sized to provide operating voltage of
the minimum rated operating the appliances
voltage of the appliances used. used.
24 VDC Power To Transmitter 12-18 AWG (3.1 to 0.78 mm2). To meet 1.2 volt 12 to 18 AWG
Runs Annunciator Size wire so that no more than drop (3.1 to 0.78 mm2)
(Class 2 1.2 V drop across wire run from
Power-Limited) supply source to end of any
branch.
ARCNET Provides interface Twisted-unshielded pair low 3,000 ft. (.914 m) 18 AWG (3.1 mm2)
(Class 2 between network capacitance 18 AWG
Power-Limited) nodes.
ARCNET should be
installed in a separate
conduit.
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL®
Standard 1459.
J5 J2 J4
TB3 TB4
SLC1
J7
PRODUCT
TB3 TB4
SLC2
DATE CODE
PRODUCT
LABEL
TB5
NAC1
TB5
TB2
NAC2
J3
TB1 TB6
RS232
TB1 TB6
SW2 SW1 J1
Figure 3.5.1 ILI-MB-E3 (OKI Version) Module Figure 3.5.2 ILI-MB-E3 (Kinetis Version) Module
NOTE 1: Must be IN when connected via ribbon cable from this ILI-MB-E3 at J1 to a PM-9/PM-9G connector J1.
Requires the removal of the JMP-1 on the PM-9/PM-9G.
Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection is being provided by an INI-VG
Series node that is being powered from a common PM-9/PM-9G.
NOTE 2: Connect J1 to PM-9/PM-9G J1 only when the PM-9/PM-9G is NOT powering an INI-VG Series sub-assembly.
NOTE 3: Use ILI-MB-E3 Auxiliary RS485 Port (TB3-1 COM A & TB3-2 COM B) to connect to the LCD-E3 (E3
annunciator module), LCD-SLP (E3/S3 annunciator module), LCD-7100/RAN-7100 (7100 Remote Annunciator
Module), ASM-16 (Addressable Switch Module), ANU-48 (LED Annunciator Driver Module) or DACT-E3 (E3 Digital
Communicator Transmitter).
NOTE 4: RPT-E3-UTP (E3 Repeater Module) is required when this ILI-MB-E3 is networked via ARCNET to an
INI-VGE, INI-VGC, INI-VGX, or another RPT-E3-UTP equipped node. In addition, when the ILI-MB-E3 is connected to
an NGA (whether the NGA is local or remote), the RPT-E3-UTP is required.
It is not required for LOCAL ARCNET communication within a single enclosure. (J2 or J5).
NOTE 5: For Style 4 use terminals B+ and B- only. For Style 6 use terminals B+ and B- and connect return wires to A+
and A-. For Style 7, wire as for Style 6 and use Isolator Modules and or Isolator Detectors per recommendations as required.
NOTE 6: NAC1 and NAC2 are rated as 2.0 A Special Application and 0.2 A Regulated.
NOTE 7: When used for Releasing, must be configured in CAMWorks™ for Releasing in the General Settings Section.
NOTE 9: The PRN-7 Printer is a dot-matrix printer. It is shipped with a DB-9 Adapter Kit that provides the necessary
hardware and cables for installation. For additional information on the PRN-7 Printer, refer to the Manufacturer’s
Installation Guide.
STANDALONE
8 76 54 3 2 1
=0
on 8 76 54 3 2 1
8 7 6 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1 8 76 54 3 2 1
485A 485B
ARCNET TB4 7 SLC1 CLASS "B", STYLE 4 (-)
9 10 J5 TERM
3 J7 NOTE 4: IF ONLY ONE SLC IS 6 SLC1 CLASS "A", STYLE 6 (+)
LOCAL DISPLAY
RESETTABLE PWR OUT 4 USED STYLE 6 (CLASS “A”), THE 5 SLC1 CLASS "A", STYLE 6 (-)
NOTE 2: USE CABLE P/N: 75645
SYSTEM GROUND 5 TB3 UNUSED SLC TERMINALS MUST 4 SLC2 CLASS "B", STYLE 4 (+)
(20") TO CONNECT TO J5 SOCKET
NON-RESET PWR OUT 6 MB PR
OF NEXT ILI-MB-E3 PCA, ILI-S-E3 BE JUMPERED STYLE 6 TO 3 SLC2 CLASS "B", STYLE 4 (-)
SYSTEM GROUND 7 W7 OR ANX PCA IN SAME CABINET PREVENT LOOP FAULT. 2 SLC2 CLASS "A", STYLE 6 (+)
MUNICIPAL CKT (+) 8 1 SLC2 CLASS "A", STYLE 6 (-)
(UP TO 8 ILI-E3 PCAS OR ANX
NAC2 CLASS B OUT (+) 5 TB2 OUTPUT. RELAYS CONTACTS 4 SUPV NORMALLY CLOSED
MB = MUNICIPAL CKT/RELEASE
NAC2 CLASS B OUT (-) 6 TRANSFER UPON ALARM, 3 ALARM COMMON
(MIDDLE & LEFT PINS OF W7 & W8) FACTORY SUPERVISORY, TROUBLE OR
NAC2 CLASS A RETURN (+) 7 2 ALARM NORMALLY OPEN
PR = REVERSE POLARITY USE
NAC2 CLASS A RETURN (-) 8 SYSTEM POWER LOSS. 1 ALARM NORMALLY CLOSED
(MIDDLE & RIGHT PINS OF W7 & W8) 10 9
UNSHIELDED, TWISTED-PAIR
NO EOL RESISTOR LED4 = TX (NODE IS TRANSMITTING DATA TO THE NETWORK)
LED5 = RX (NODE IS RECEIVING DATA FROM THE NETWORK) 18 AWG MIN. 40 OHMS MAX. WIRE
REQUIRED RESISTANCE PER LOOP
LED6 = RST (NODE IS RESETTING)
NAC RATINGS (EACH): 0.5µF MAX. CAPACITANCE
LED7 = DG (GENERAL NETWORK FAULT)
24VDC (NOMINAL) PER LOOP
LED8 = ALRM (ALARM CONDITION)
MAX. ALARM LOAD LED9 = SUPV (SUPERVISORY OFF-NORMAL) SW2 POS 1 ON = SL1 DISABLED (OFF = SLC1 ENABLED)
2.0 AMPS PER CKT LED10 = TRBL (TROUBLE CONDITION) SW2 POS 2 ON = SL2 DISABLED (OFF = SLC2 ENABLED)
SUPERVISED & LED11 = PWR (DC POWER GOOD) SW2 POS 3 ON = NAC1 & 2 DISABLED (OFF = NAC1 & 2 ENABLED)
CLASS 2 & 3 LED12 = GND FLT (GROUND FAULT) SW2 POS 4 ON = BUZZER DISABLED (OFF = BUZZER ENABLED)
POWER-LIMITED LED13 = CO (CO ALARM) SW2 POS 5 ON = RS232 115.2K BAUD (OFF = DEFINED BY CamWorks™)
18 AWG WIRE MIN. NOTE 7: NAC1 & NAC2 ARE RATED AS 2.0 A SPECIAL APPLICATION AND 0.2 A REGULATED.
15
16
SUPERVISED & NON POWER-LIMITED CONNECT TO EARTH GROUND PER ARTICLE 780 NOTE 1: DISABLE GROUND FAULT DETECTION CIRCUIT:
WHEN SET FOR MUNICIPAL CKT. OF THE NATIONAL ELECTRICAL CODE. FAILURE 1. ON THE PM-9/PM-9G WHEN LOCATED IN THE SAME
UNSUPERVISED WHEN SET FOR TO CONNECT TO A METALLIC GROUND WATER CABINET WITH A SINGLE ILI-MB-E3 PCA.
REVERSE POLARITY PIPE OR GROUND DRIVEN ROD WILL RESULT IN
2.0 AMPS MAX. OUT OF EACH LOSS OF LIGHTNING PROTECTION, REDUCED
EXT PWR OUTPUT. NOTE: PROTECTION AGAINST TRANSIENTS AND COULD
DO NOT EXCEED 2.5 AMPS TOTAL ADVERSELY AFFECT PROPER SYSTEM OPERATION.
BOTH OUTPUTS COMBINED
PANEL NEUTRAL OR CONDUIT GROUND IS NOT
TO: LCD-E3 TB1-4, LCD-SLP TB1-2, ACCEPTABLE. USE 14 AWG WIRE MINIMUM.
ASM-16 TB1-2, ANU-48 TB1-2, TO RPT-E3-UTP GROUND FAULT GROUND FAULT
LCD-7100/RAN-7100 TB1-2, DACT-E3 TB1-2 ARCNET DETECTION ENABLED DETECTION DISABLED
TO: LCD-E3 TB1-3, LCD-SLP TB1-1, ASM-16 TB1-1, LEAVE W1, W4 CONNECTOR (MIDDLE TO RIGHT PIN) (MIDDLE TO LEFT PIN)
ANU-48 TB1-1, LCD-7100/RAN-7100 TB1-1, & W5 OPEN J10
DACT-E3 TB1-1
LOCAL ARCNET LOCAL ARCNET
9 1 9 1
GFLT
W4 ENA
1 W5 J2 15 1 J4 DIS
1 210 2 10 2
ON OFF OFF ON 8 SLC1 CLASS "B", STYLE 4 (+)
16 2
2 AUX TERM W9
485A 485B
ARCNET TB4 7 SLC1 CLASS "B", STYLE 4 (-)
9 10 J5 TERM
3 J7 NOTE 4: IF ONLY ONE SLC IS 6 SLC1 CLASS "A", STYLE 6 (+)
LOCAL DISPLAY
RESETTABLE PWR OUT 4 USED STYLE 6 (CLASS “A”), THE 5 SLC1 CLASS "A", STYLE 6 (-)
NOTE 2: USE CABLE P/N: 75645
SYSTEM GROUND 5 TB3 4 UNUSED SLC TERMINALS MUST SLC2 CLASS "B", STYLE 4 (+)
(20") TO CONNECT TO J5 SOCKET
NON-RESET PWR OUT 6 MB PR
OF NEXT ILI-MB-E3 PCA, ILI-S-E3 3 BE JUMPERED STYLE 6 TO SLC2 CLASS "B", STYLE 4 (-)
SYSTEM GROUND 7 W7 2 PREVENT LOOP FAULT. SLC2 CLASS "A", STYLE 6 (+)
MUNICIPAL CKT (+) 8 OR ANX PCA IN SAME CABINET
(UP TO 8 ILI-E3 PCAS OR ANX 1 SLC2 CLASS "A", STYLE 6 (-)
NAC1 CLASS B OUT (-) 2 NOTE 3: SET FOR MUNICIPAL CKT/ 7 TROUBLE NORMALLY CLOSED
RESISTIVE
NAC1 CLASS A RETURN (+) 3 RELEASE OR REVERSE POLARITY 6 SUPV COMMON
NAC1 CLASS A RETURN (-) 4 NOTE 5: TROUBLE DRY TB5 5 SUPV NORMALLY OPEN
TB2 OUTPUT. W1 RELAYS CONTACTS
NAC2 CLASS B OUT (+) 5 MB = MUNICIPAL CKT/RELEASE 4 SUPV NORMALLY CLOSED
NAC2 CLASS B OUT (-) 6 TRANSFER UPON ALARM, 3 ALARM COMMON
(MIDDLE & LEFT PINS OF W7 & W8)
NAC2 CLASS A RETURN (+) 7 FACTORY SUPERVISORY, TROUBLE OR 2 ALARM NORMALLY OPEN
PR = REVERSE POLARITY USE
NAC2 CLASS A RETURN (-) 8 SYSTEM POWER LOSS. 1 ALARM NORMALLY CLOSED
10 9
NOTE: In a standard E3 Series configuration, install only one ILI-MB-E3 for one PM-9/PM-9G power supply
connected to an FACP cabinet.
NOTE: For information on the latest version of CAMWorks, see the Gamewell-FCI website, www.gamewell-
fci.com.