Data sheet

_________________________________________________________________________________________________________________

SecuriFire
B5-EPI-PCM-GS
Partial Indication and Control Map
The SecuriFire B5-EPI-PCM-GS has 16 red or yellow illuminated
LEDs and 8 keys. The function, colour and actuation behaviour
(static or flashing) of each LED as well as the keys are individually
programmed with SecuriFire Studio. The function of the operation
LED (green) is permanently assigned. Further, the partial indication
and map has an internal audible element and a connection for an
external key switch.

The B5-EPI-PCM-GS is connected via EPI bus to the SecuriFire fire


alarm system.
Fig. 1 B5-EPI-PCM-GS
Domain: SCP 500, SCP 1000, SCP 2000, SCP 3000
_________________________________________________________________________________________________________________

Function/Application Interfaces
The B5-EPI-PCM-GS has 16 two-colour LEDs for state display, a X1 EPI bus connection plug
LED for operation state, 8 function keys, a buzzer, a key for the lamp
X2 Jumper indication and control map audible
test, and a connection for an external key switch.
X4 Key switch connection
The functions of the LEDs, function keys, buzzer and the external S1 Rotary switch EPI bus address
key switch are programmed in SecuriFire Studio.

The connection of the B5-EPI-PCM-GS via patch cable and RJ45


plug to the fire alarm control panel is via an EPI bus basic interface
or via another EPI device.

Another RJ45 plug is for connecting a further EPI device.

The device has a robust ABS plastic housing with protection type IP
42.

Key features
 16 two-colour yellow/red LEDs.
 8 function keys
 Up to 3 devices per EPI interface can be connected.
 Up to 1 m EPI bus total length
 Plug type: 8-pin RJ45
 Cable type: Patch cable (Cat 5e or better)
 ABS plastic map case with IP 42 protection type

Fig. 2 B5-EPI-PCM-GS interfaces

Securiton AG Alpenstrasse 20 3052 Zollikofen Switzerland T 811085 en d 1/4


Data sheet

EPI bus connection plug (X1) Planning


The first EPI participant is connected via the first RJ45 plug (Port A) The country-specific directives apply when planning and installing
to the EPI-BUS. Additional EPI devices can be connected to the sec- automatic fire detector systems.
ond RJ45 plug (Port B).
 The B5-EPI-PPC must be mounted directly next to a control
EPI port A, EPI port B panel MIC11/711 or next to a MMI device providing a MMI-inter-
Terminal Function face (max. 1 m).
1 GNDP  Up to 3 devices per EPI interface can be connected
2 VP-  Up to 1 m EPI bus total length
3 PE+  The bus address set on the rotary switch must correspond to the
4 EXTBUS+ planned address in SecuriFire Studio.
5 EXTBUS-
6 +3V3 When connecting to the EPI interface of a MMI de-
7 +3V3 vice, the system limits for the MMI bus have to be
8 GND taken into account.

Technical data
Information about programming, please refer to the SecuriFire Stu-
Electrical RS485
dio manual T811093.
Coverage max. 1 m
Transmission type Asynchronous serial, 9.6kbit/s The B5-EPI-PCM-GS is supported beginning with SecuriFire Stu-
Direction Bidirectional, half-duplex dio R 1.2.
Mechanical design 8-pin RJ45 plug

Dimensioned drawing
Indication and control map audible (X2) 138 48

Audible switched on

Audible switched off

Key switch connection (X4)

170
136

Terminal Designation
1 Key +
2 Key -

Technical data 5
Electrical potential-free contact
Coverage max. 1 m
Mechanical design Screw terminal, max. 1.0 mm2
87.5
Fig. 3 Dimensioned drawing B5-EPI-PCM-GS
Rotary switch EPI bus address (S1)
Setting the EPI-BUS address (1 to F)

2/4 T 811085 en d B5-EPI-PCM-GS


Data sheet

Mounting Indication and operation elements

Fig. 5 User interface

Fig. 4 Mounting B5-EPI-PCM-GS

 Remove covers (1) on both sides. Insert a screwdriver into the


(1) Operation LED (green)
slit and lightly press to release the lock.
(2) Display test key
 Unlock all four screws (2) and lift the indication and control map
Pressing and holding the key checks all display elements and the
to the front.
internal audible.
 Holes for the required cable entries (3) can be broken out on top,
(3) 16 two-colour red/yellow LEDs
bottom, right, left and on the rear wall of the map case.
The function, colour and actuation behaviour (static or flashing) of
each LED are individually programmed with SecuriFire Studio.
 Cable strain relief is provided by two holders for cable fasteners
in the rear wall of the map case. Plug in the patch cable, set the
(4) LED label
EPI bus address and mount the map case on the rear wall.
Holder for label strips.

(5) 8 function keys


The function of each key is individually programmed with SecuriFire
Studio.

(6) Key label


Holder for label strips.

B5-EPI-PCM-GS T 811085 en d 3/4


Data sheet

Connection
The connection of the B5-EPI-FPC can take place on the EPI bus of a SecuriFire MIC or on the EPI bus of an MMI device.

Fig. 6 Connection

Article numbers / spare parts


Short designation Art. number
B5-EPI-PCM-GS Partial Indication and Control Map 20-1230111-01-xx
Spare parts
COS 701-1 Covering strip (2 pces) 12-4400051-01-xx

Technical data
Power supply The power is supplied to the B5-EPI-PCM-GS by the EPI-BUS
Cable type 0.5 m patch cable cat 5e (included)
Supply voltage +3.3 V ± 5 %
Current consumption 5 mA
Contact protection IP 42
Ambient temperature -5 °C to +50 °C
Relative humidity 5 % to 95 %, without condensation
Air pressure  80 kPa, up to 2’000 m above sea level
Dimensions (H x W x D) 170 x 138 x 48 mm
Housing ABS anthracite grey RAL 7016
Weight xxx g

4/4 T 811085 en d, 31.07.2020 Rd B5-EPI-PCM-GS


First edition: 21.01.2012 Rd
The product specifications contained in this document are subject to change without notice.
© Copyright by Securiton