You are on page 1of 4

Project report: Solaire Elevator ASD

System provider: Customer:


Company: Extinguished Inc Solaire Hotel Resort and Casino
Address: 14 Villa Socorro St Project 8 Tambo Entertainment City, 1 Aseana Ave, Tambo, Parañaque,
Town: Quezon City
Phone:

Comment:
Sky Theater SE 8

EN 54-20 class EN 54-20 compliant possible reasons


C Yes
B Yes
A Yes

Project name: Solaire Elevator ASD


Project build date: 07/10/2020 3:33:47 pm
Fan level: II
Ambient temperature [°C] 20
Ambient pressure [hPa] 950.0

Tube network I Tube network II


Maximum smoke sensor sensitivity according EN 54-20 class C 0.738 --
Maximum smoke sensor sensitivity according EN 54-20 class B 0.128 --
Maximum smoke sensor sensitivity according EN 54-20 class A 0.043 --
Maximum transport time [s] 33 --
Overall sampling tube length [ m ] 37.78 --
Number of sampling points 6 --

SKY THEATER SE 8.report.pdf / 06/01/2021 4:59:50 pm / ASD PipeFlow 2.7.0.7 - Page 1-


Sketch of tube network:

D:\My Desktop\SOLAIRE PIPEFLOW\SKY THEATER SE 8.report.gif

SKY THEATER SE 8.report.pdf / 06/01/2021 4:59:50 pm / ASD PipeFlow 2.7.0.7 - Page 2-


Part Description RL TL S[C] S[B] S[A] P Fl ø t L-cap SP-cap Comment:
(ASD) ASD 535 0.00 0.83 0
A1 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.20 0.20 153 0.83 0
stainless steel)
A2 (AN 25-90 PVC) Angle 90° D=25 mm PVC 0.20
A3 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.30 0.50
stainless steel)
A4 (AN 25-90 PVC) Angle 90° D=25 mm PVC 0.50
A5 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.20 0.70
stainless steel)
A6 (DFU 535L) Dust Filter Unit large D=25 mm 1.20
A7 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 2.22 3.42
stainless steel)
A8 (AN 25-90 PVC) Angle 90° D=25 mm PVC 3.42
A9 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.56 3.98
stainless steel)
A10 (AN 25-90 PVC) Angle 90° D=25 mm PVC 3.98
A11 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.26 4.24
stainless steel)
A12 (AN 25-90 PVC) Angle 90° D=25 mm PVC 4.24
A13 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.30 4.54
stainless steel)
A14 (AN 25-90 PVC) Angle 90° D=25 mm PVC 4.54
A15 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 0.30 4.84
stainless steel)
A16 (AN 25-90 PVC) Angle 90° D=25 mm PVC 4.84
A17 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 1.20 6.04
stainless steel)
A18 (AN 25-90 PVC) Angle 90° D=25 mm PVC 6.04
A19 (TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, 31.74 37.78
stainless steel)
A19 - 1 -1- Sampling point / Clip 0.20 6.24 5.410 0.940 0.320 87 0.16 4.00 3
A19 - 2 -2- Sampling point / Clip 6.27 12.51 6.670 1.160 0.400 57 0.13 4.00 6
A19 - 3 -3- Sampling point / Clip 6.27 18.78 6.560 1.140 0.390 37 0.13 4.50 9
A19 - 4 -4- Sampling point / Clip 6.26 25.04 6.560 1.140 0.390 24 0.13 5.00 14
A19 - 5 -5- Sampling point / Clip 6.27 31.31 6.370 1.110 0.380 18 0.14 5.50 20
A19 - 6 -6- Sampling point / Clip 6.27 37.58 6.600 1.150 0.390 16 0.13 7.00 33
RL: Relative length of this part (distance to previous SP or bend) [m]
TL: Total length of the part end to the ASD [m]
S[C]: Smoke sensitivity [%/m] for this sampling hole, when the smoke sensor alarm level is chosen as proposed in this report.
S[B]: Smoke sensitivity [%/m] for this sampling hole, when the smoke sensor alarm level is chosen as proposed in this report.
S[A]: Smoke sensitivity [%/m] for this sampling hole, when the smoke sensor alarm level is chosen as proposed in this report.
P: Pressure [Pa]
Fl: Airflow [Liter/s] of this sampling point
ø: Diameter [mm]
t: Transport time to the ASD [s]
L-cap: Length of the capillary / stub [ m ]
SP-cap: Samplingpoint of the capillary

SKY THEATER SE 8.report.pdf / 06/01/2021 4:59:50 pm / ASD PipeFlow 2.7.0.7 - Page 3-


Material list:
Part Number Length [ m ] Rod length [ m ] Number of rods Comment:
(ASD) ASD 535 1
(TU ID 19) Sampling tube ID=19 mm (e.g. Cu, aluminium, stainless steel) 10 37.28 5.00 8
(AN 25-90 PVC) Angle 90° D=25 mm PVC 8
(DFU 535L) Dust Filter Unit large D=25 mm 1
(CLIP 4.0 PA) Sampling hole clip d=4.0 mm red PA 2
(CLIP 4.5 PA) Sampling hole clip d=4.5 mm red PA 1
(CLIP 5.0 PA) Sampling hole clip d=5.0 mm red PA 1
(CLIP 5.5 PA) Sampling hole clip d=5.5 mm red PA 1
(CLIP 7.0 PA) Sampling hole clip d=7.0 mm red PA 1
(PC 25 PP) Pipe clamp type Goema halogen-free 38

SKY THEATER SE 8.report.pdf / 06/01/2021 4:59:50 pm / ASD PipeFlow 2.7.0.7 - Page 4-