Non-Conformance Report:

NCR-C&P-001
Name of the Project: BAREQ 132/33KV S/S Date: 12/08/2016
IDENTIFICATION

Contractor/Supplier:

4400005899
Contract No:

Found during what activity:


 Incoming inspection  Other: MATERIAL

 In-process inspection
 Final inspection
As per SEC General instruction Point no.13 VT & CT Wires should be color coded but in actual VT& CT Wires in 132KV
LCC & 13.8KV SWGR & Control-Protection Panels not color coded

VT&CT Wires should be color coded by long Slaves.

R-Phase should be RED Color & Y-Phase should be YELLOW Color & B-Phase should be BLUE Color

Neutral Should be Black Color

DISPOSITION
 Use-as-is  Return to supplier Technical Leader
 Repair  Scrap Name:
 Rework  Missing Signature:

Description of proposed corrective/preventive action (use continuation page if necessary):

Approval of disposition

Site Manager: Signature: ………………………………………………………

QA/QC Engineer: Signature: ………………………………………………………

Rev. 01
CONTINUATION PAGE

Enclosed Pictures:-