ASME ACC Data Reduction:

5-3.1 Air-Side Conditions Data Reduction


(a) Inlet Air Temperature. Inlet air temperature data
shall be averaged for each test run. Variations in inlet
air temperature are normally small enough to allow
arithmetical averaging of the temperatures.
(b) Atmospheric Pressure. The readings taken at the
beginning and end of the test period shall be arithmetically
averaged.
5-3.2 Steam Side Data Reduction
(a) Condenser Pressure. Condenser pressure measurements
will be arithmetically averaged.
(b) Steam Flow Rate. Steam flow rate shall be determined
by a mass and heat balance around the condensate
tank and shall be arithmetically averaged.

Appendix D, mk and n