Professional Documents
Culture Documents
Design Effeciency
Design Effeciency
DG 1301
Design for Energy Efficiency
Any queries or comments on this Guide should be forwarded to Duncan Livingstone - ETCM
Contents
2. Introduction
3. Architectural Consideration
6. De-Humidifiers
2. Introduction
2.1 Energy conservation in general results in reduced running costs, however total operating
costs (including maintenance) are not always minimised. The impact of the energy
conservation techniques considered should be analysed against the defined financial
objectives set by GSK or Local Codes in order to determine those techniques, which are to
be applied.
2.2 Techniques should be evaluated separately and in combination. Simple “pay back”
calculations based on the relevant, agreed, proper, accounting criteria should be undertaken.
If these indicate a “pay back” period acceptable to GSK, then a full “Discounted cash flow”
analysis should be undertaken.
2.3 Selection of fuel depends primarily on availability and the current and future forecast fuel
costs. However, where electrical costs per kWh are significantly higher than that of gas,
lowest energy usage is not necessarily the same as lowest fuel costs.
2.4 Energy efficiency features are traditionally regarded as optional refinements that may or may
not be justified individually on the basis of their cost savings. While this may make sense
from the value-for-money point of view, it is not the correct approach for energy efficiency.
2.5 Most energy efficiency features are more effective when they are integrated into the design
rather than a “bolt-on” refinement. However, determination of the true cost of integrated
features can be imprecise.
2.6 The required scope for the evaluation of energy efficiency features should be carried out on a
system by system basis. The cost of the energy evaluation and the cost of how the system
will operate in practice should be included.
2.7 Within GSKs' facilities, the most expensive source of energy is electricity. Of this, motive
power and lighting consume the largest proportions. Energy saving associated with the
particular forms of motive power is covered in the relevant sections of this Guide. Energy
savings associated with lighting and general electrical installations are covered in Section 10
of this Guide.
2.8 As part of the Concept Design the Contractor should provide estimated energy consumption
figures. These should include for maximum, annual and average daily summer and winter
consumption's.
3. Architectural Consideration
3.1. In order to develop a passive (solar), climate-sensitive design the Contractor shall include
consideration of:
3.2. Heating Strategy.
3.2.1.Solar collection:
transparent elements and total energy transmission
orientation of building and transparent elements
opaque elements and thermal capacities
greenhouse effect
3.2.2.Heat storage:
direct storage
indirect storage
3.2.3 Heat conservation:
reduction of transmission losses
use of opaque elements
reduction of infiltration losses
thermal zoning “heat core” utilisation
3.3. Cooling Strategy
3.3.1.Solar Control:
shading windows and other apertures from unwanted direct sunlight. Shading should
still permit the maximum benefit to be obtained from the sun’s rays in winter
reduction of glazing in direction of the maximum solar gains
application of special glazing, with increased absorption or reflective properties
consideration of “smart” glazing with properties actively responsive to the intensity of
the solar radiation
deliberate use of existing, or created, local shading from buildings and vegetation
3.3.2.External gains - unwanted, external heat gains by transmission through the building
envelope should be reduced by:
insulation
fans should be adjusted by pulley change, speed control or pitch angle adjustment to give
optimum performance during commissioning - closing dampers may be used for volume
adjustment of up 10% of the design flow rate
minimum air change rates that achieve comfort conditions in terms of temperature and
air movement should be used, unless there are specified process requirements such as
fixed-extract or minimum air-change rates that dictate higher air-change rates
equipment such as safety cabinets that are not constantly in use should have the facility
to be switched off , with a corresponding reduction in air-change rates, subject to
acceptable minima
ventilation systems should not be used to offset heat gain from equipment such as large
deep-freezers , heat should be removed by direct exhaust or cooled by means of a water-
based system
ductwork air leakage should be kept to a minimum
where acceptable, air re-circulation should be used
full fresh air ‘free-cooling’ based on temperature or enthalpy control should be
considered
6. De-Humidifiers
6.1 The requirement for Low Relative Humidity (Low RH) requires a high demand for energy.
Minimising this demand can be achieved by the consideration of:
sensible heat recovery from the reactivation exhaust air to the supply before any heating
coils
sub-cooling of the condensate from steam coils
use of the pre-cooler, chilled water (or glycol/water) medium for sensible cooling after
the de-humidifier.
use of heat reclaim from the reactivation air for terminal re-heat/heating
7.2. It follows that selection of chiller type, capacity and refrigerant should be carefully selected
to ensure that the environmental benefits of using non-CFC refrigerants is not negated by the
detrimental effects of increased CO 2 emissions.
7.3. Absorption chillers using steam, gas, or waste heat should be considered. The COP for these
should be >1.0. Energy consumption is significantly greater than for vapour-compression
refrigeration options, but overall fuel costs may be lower due to the type of fuel used.
7.4. For chiller applications in the temperate climates this full load COP for vapour compression
refrigerant water chillers, without ancillaries should not be less than 5.0. This should be
maximised, throughout the range of the machine, by consideration of many factors including
the following:
minimising compression ratio
minimising non-useful superheat
maximising sub-cooling
using high efficiency compressors
using latest fully-developed alternative refrigerants that show most suitable efficiency
characteristics
reviewing rotary compressors that are more efficient than reciprocating machines
minimising evaporator temperature differential.
7.5. Water-cooled condensers generally give the best overall energy-efficient operation.
However due to the perceived problem of legionella and associated water treatment regimes,
their use must be agreed with GSK.
7.6. Condensers should be located to ensure unrestricted air flows and where two or more are
sited adjacent to each other re-circulation or air starvation should not occur regardless of
wind or building effects.
7.7. If air-cooled chillers are used, they should be packaged units or the components closely
grouped. If water-cooled chillers are used the chiller should be located as close as
practicable to the cooling tower to minimise circuit pressure losses, including cooling tower
losses.
7.8. Energy input to cooling tower fans should be optimised by careful selection of cooling tower.
7.9. The most efficient method of capacity control should be used; hot gas injection should be
avoided. The aim is to choose a system which gives a power reduction as close as possible
to the corresponding decrease in capacity.
7.10. Individual systems should be considered where there are loads at significantly different
temperature requirements.
7.11. Where large, centralised, de-coupled systems are required, careful attention should be given
to the loading/unloading control of the chillers to ensure optimum efficiencies are
maintained.
7.12. In the case of air conditioning chilled water systems, flow temperatures <7°C should be
avoided and, where appropriate, scheduled against ambient temperatures such that higher
flow and return temperatures can be used during cooler weather.
7.13. Chillers should be designed to take full advantage of low condenser water temperatures
when ambient conditions permit.
7.14. With chiller installations, opportunities may arise to recover low grade heat from the
condensers. Increasing the temperature of this low grade heat will decrease chiller
efficiencies. Unless there is a need for low grade heat, condenser heat recovery rarely proves
economic, but should be considered.
using inverter drives for pump volume control, most cost effective on motors larger
than1kW
design fluid flow distribution systems such that all extremities are on index runs
if a single index run cannot be avoided then tertiary pumps, or separate systems, should
be provided
operating pressures and flow resistances should be reduced as far as possible; low-loss
commissioning valves should be used
systems and pumps should be located as close to the point of delivery. This implies
regional or even local plant
pipework and fittings should be designed and installed to provide lowest practicable
frictional resistance
pumps should be selected to ensure maximum efficiencies at all operational duties;
normally efficiencies below 75% will be unacceptable
pumps should be adjusted by pulley, speed adjustment or impeller change to give
optimum performance during commissioning; closing valves may be used for volume
adjustment of up 10% of the design flow rate.
Where applicable, heating water temperature should be suitable for economic operation
with condensing boilers.
8.3. Glycol or glycol/water mixtures should be used only where alternative ‘freeze protection’
methods are unsuitable. Where unavoidable the most suitable mix with regards heat transfer,
viscosity, cost and hazards should be reviewed.
8.4. Fluid flow and return temperatures should be as close to ambient as possible, while still
achieving required duty with economically-sized heat transfer equipment.
8.5. In Low Temperature Hot Water (LTHW) systems differential temperatures up to 16C should
be considered.
8.6. Application of ‘out of hours’ adjustment of temperatures should be maximised, e.g. night set-
back.
the use of tungsten lamps for general lighting should not be used
high frequency control equipment for fluorescent luminaires should be used
fluorescent lamps should be T5 tri-phosphor type
diffusers should be clear or prismatic type manufactured from UV stabilised acrylic, opal
type diffusers should not be used
consideration should be given to the use of high efficiency mirrored reflectors
occupancy sensors should be considered for areas of infrequent use
daylight dimming facilities should be considered for luminaries adjacent to windows
manual switches should be installed to ensure that lamps operate according to available
day light and occupation patterns
external lighting should be zoned/designed to ensure it operates efficiently and only as
required, generally for security and safety purposes
10.3. Power Distribution - The following should be considered in the Power Distribution designs;
10.3.1. Energy consumption meters should be located at all relevant distribution points for
monitoring purposes. Where justified, the outputs should be suitable for connection into the
BMS.
10.3.2. Power Consumption Benchmarks.
Manufacturing 65 kWh/m2/year
Offices 72 kWh/m2/year
Storage/Distribution 30 kWh/m2/year