You are on page 1of 2

DESIGN BASIS REPORT FOR SIZING OF RCC COOLING TOWER

SL.NO DESCRIPTION UNITS PARAMETERS Remarks

A DESIGN DATA

1 Type of cooling tower tph Induced Draft, Counter Flow

2 Wet Bulb Temperature (design) °C 28.5

3 Inlet temperature of Cooling tower °C 42

4 Outlet temperature of cooling tower °C 32

5 Design Approach temperature °C 3.5

B CAPACITY OF COOLING TOWER

1 Condenser for one unit m3/hr 2000 Assumed

2 Oil cooler for one unit m3/hr 90 Assumed

3 Alternator for one unit m3/hr 70 Assumed

4 Sample coolers (SWAS) for 3 boilers m3/hr 50 Assumed

5 Boiler feed water pumps (2nos) m3/hr 4 Assumed

6 Ash handling system for 3 boilers m3/hr 60 Assumed

7 Flow required m3/hr 2274

8 Margin % 5

9 Total flow m3/hr 2387.70

10 Say m3/hr 2400

11 No. of cells nos 3

12 Flow per cell m3/hr 800

C MATERIAL OF CONSTRUCTION

1 Cold water basin RCC

2 Frame work / Members / Supporting structure RCC

3 Fills PVC (splash bar)

4 Louvers RCC

5 Sprayers Poly propylene

6 Drift eliminators PVC (Wave type)

7 Drain valves CI

8 Hot water pipe MS Epoxy coated / RCC

9 Fan deck RCC

SL.NO DESCRIPTION UNITS PARAMETERS Remarks

10 Fan stack GRP / FRP


11 Fan blades FRP

12 Fan hub MS Galvanised

13 Fan hub cover FRP

14 Drive shaft SS304

15 Staircase / Cage ladder HDG steel

16 Structural connectors / Fasteners / Washers / Anchor bolts HDG steel

17 Sluice gate CI

18 Pre & post Screen HDG frame with SS304 mesh