TYPE OF OPERATION Bunker hoses

Denominator
SERVICE Diesel
HOSES
DATA SHEET - MECHANICAL Datasheet number DIAMETER (inch) 3"
LENGTH (m) As per material card
SAP or SEDAS number DESIGN PRESSURE 20 BAR
TEMPERATURE RANGE 0 degc to 60 Deg C
TAG NO.
0 For inquiry MANUFACTURER
REV DESCRIPTION PREP CHK APP DATE MODEL NO. / SERIAL NO.

DESCRIPTION MOG SPECIFIED VENDOR REPLY


1 DESIGN
2 RATING (note 1) / Design Pressure N/A
3 HOSE DESIGN STANDARD(s) DS EN 13765
4 DIMENSION AND LENGTH STANDARD DS EN 4671
5 HYDROSTATIC TEST PROCEDURES DS EN 1402
6 APPLICABLE SEDAS AND MOG OFFSHORE PROCEDURES SEDAS - OSP 16 - OSP 56
7 PED CATEGORY Vendor scope
8 PED FLUID GROUP 1
9 HOSE CLASS (see hose class definition on sheet 2) Hose class I
10 MIN. PRESSURE (VACUM) No
11 FITTINGS (Connection between adapter and hose) Vendor scope
12 TYPE OF THREAD (NPT OR BSP - if applicable) N/A
13 HOSE MATERIAL COLOUR (Marking) (note 6) Brown
14 EXTERNAL BRAIDING ( FOR WEAR-PROTECTION ONLY) No
15 GROUNDING WIRE No
16 PRICKLING OF OUTER LAYER No
17
18 MARKING
19 MARKING OF HOSES See sheet 2
20
21
22 FITTING TYPES
23 ADAPTER - END1 - (TYPE AND ANGLING) Platform interface - 150# - B16.5 flange
24 FITTING SIZE - END 1 (Note 7) See note for standard hoses
25 ADAPTER - END2 - (TYPE AND ANGLING) TODO *
26 FITTING SIZE - END 2 (Note 7) See note for standard hoses
27 EXTENSIONS (if required) N/A
28 CLAMPING Vendor scope
29
30 MATERIAL
31 HOSE + (TYPE OR EQUAL) Vendor scope
32 NIPPEL N/A
33 COUPLING Vendor scope
34 CLAMP / FLANGE (TYPE AND MATR.) Vendor scope
35 SEAL / GASKET Vendor scope
36
37 TEST
38 PROOF PRESSURE TEST (DP = Design pressure) 1.5x DP
39 MINIMUM BURST PRESSURE TEST REF ISO 7751 4x DP
40
41 CERTIFICATION / DOCUMENTATION
42 DECLARATION OF CONFORMATY - 97/23/EC (PED) YES
43 DECLARATION OF CONFORMATY - 94/9/EC (ATEX) If applicable
44 NACE MR0175 / ISO 15156-1 (Sour Service) NO
45 MATERIAL CERTIFICATE(s) (DS EN 10204) YES (3.1)
46 BURST TEST (note 2) YES
47 PRESSURE TEST YES
48 FIRE TEST YES
49 NDT Note 3
50 3.RD PARTY INSPECTION DURING FABRICATION Note 4
51 3.RD PARTY INSPECTION RELEASE NOTE Note 5
52 GROUNDING WIRE No
53
54 ADDITIONAL NOTES AND DOCUMENTS
55 Client note 1 Fuel Bunker hose assembly
56 Client note 2 With floating devices and break-away in middle
57 Document 1
58 Document 2
59
See next sheet for notes and information

6/10/2018 12:31 PM Hoses - Revision 2 - 01-NOV-2014 Sheet 1 of 2


Sheet 2/ 2
NOTES

1 Maersk
Deleted Oil to establish this information from the applicable piping spec (MOTS-02) - e.g. 150#
2 Burst and fire test (if applicable) shall be performed and documented by original hose manufactor. If certificate is not available, hose vendor
shall perform burst test. The burst and fire test only applies for the HOSE - not for the assembly.
3 NDT shall be in accordance to the design standard. All weldings shall be provided with documentation for 100% NDT check for external and
internal failures.
4 3rd party inspection release note shall only apply for non-standard hose assemblies and in accordance to the RMR matrix (Maersk Oil scope)
5 3rd party inspection during fabrication shall only apply for non-standard hose assemblies and in accordance to the RMR matrix (Maersk Oil
scope) hoses - Product code color marking of bunkerhoses shall be at least 1 m in each end
6 Bunker
7 Fitting size shall only be stated if the size is differnt to the norminal diameter of the hose

Marking

Example:

HOSE CLASSES

For definition of inspection and documentation level all hoses shall be divided into one of two classes;
Hose class 1;
hoses use for harmfull media according to PED (PED group 1 - see line 10) or
hoses with a diameter > 2" (50 mm) or
hoses containing pressures > 20 BARG or
hoses containing media with temperatures > 65°C or
hoses containing media with temperatures < -20°C or
Hose class 2;
hoses not in class 1

6/10/2018 12:31 PM Hoses - Revision 2 - 01-NOV-2014 Sheet 2 of 2