Comments dated 05-02-2020

Please confirm if there is no SDL required on the water tank floor(special finishes)

Also in water tank Water load is the Live load, why is there a separate 5kN/m2 live load
applied on the water bed

Spring stiffness to
applied for all base
points

Please update wall


thickness appropriately
Please check the
water load on both
these faces
Surcharge load
missing

Water load missing


To be type other

Basic strength design combinations should be 1.35DL+1.5Soil/Water/Sur


Basic strength design combinations should be 1.2DL+1.5LL+1.5Soil/Water/Sur
Comments dated 06-02-2020

Please add a combination without water

Load to be updated

Why is there a load


increment only in this
area
Clear cover to
be 65mm