You are on page 1of 19

Chapter 12

Pump Condition
Monitoring Guidelines

Process pump users often seek a method of de- tory shut-down levels of vibration (Figure 12-1). These
termining the optimum time for overhaul of a pump experience-based values culminated in the bearing life
based on energy savings or other considerations. Once vs. vibration approximations for general-purpose ma-
developed, such a tool should be widely used by mainte- chinery, Figure 12-2 (HPB, 1986).
nance engineers and managers in their role of managing
assets to provide capacity for production, and energy However, machinery vibration and its measure-
efficiency to save operating expense or even to minimize ment are complex issues and require some clarification.
greenhouse impact. This optimization approach can also Typical considerations might include:
be applied to any item in a plant where deterioration
results in loss of efficiency and energy consumption can 1. Bearing cap vibration be measured and/or ana-
be measured or estimated. lyzed by using displacement, velocity or accelera-
tion to evaluate the health of the equipment? The
primary measure of bearing cap vibration used in
VIBRATION BASICS industry today is velocity.

All rotating machines, including pumps, vibrate to 2. Should the “total all-pass” or the “filtered” fre-
some extent due to response from excitation forces, such quency be used? Most industry specifications and
as residual rotor unbalance, turbulent liquid flow, pres- standards use “total all-pass” vibration values to
sure pulsations, cavitation, and/or pump wear. Further, identify problem pumps, with filtered values re-
the magnitude of the vibration will be amplified if the served for analysis of vibration problems.
vibration frequency approaches the resonant frequency
of a major pump, foundation and/or piping component. 3.
Should RMS (root mean square) or peak-to-peak
The issue of interest is not whether or not the pump values be measured or specified? The Hydraulic
vibrates, but: Institute has chosen RMS acceptance limit values,
since most vibration instruments actually measure
• Is the amplitude and/or frequency of the vibration vibration in RMS terms, and calculate peak-to-peak
sufficiently high to cause actual or perceived dam- values if required. API, on the other hand, uses
age to any of the pump components, or peak-to-peak. RMS values are roughly 0.707 times
zero-to-peak values.
• Is the vibration a symptom of some other damag- However, this relationship applies only for
ing phenomenon happening within the pump. vibration consisting of a single sine wave. For more
complex waveforms, this conversion does not yield
Various industry organizations, such as the Hy- correct results.
draulic Institute (ANSI/HI 9.6.4, Ref. 12-1), and Ameri-
can Petroleum Institute (API-610) have set vibration 4. What is the acceptable vibration amplitude (new,
limits to help guide users to avoid excessive levels of or repair levels) for a particular application?
vibration in pumps. But long before industry standards Should acceptance limits change along with overall
were developed, individual reliability professionals pump power and flow-rate regions? The Hydraulic
and multinational pump user companies implemented Institute bases acceptable vibration limits on pump
daily machinery condition logs which guided operating type, power level, operating range, and whether
personnel by listing acceptable, reportable, and manda- measured at the factory or in the field. API gives
343
344 Pump User’s Handbook

Note: API uses peak-to-peak vibra-


tion measurement for shaft vibra-
tion (displacement in mils)
For bearing cap measurements,
API uses peak vibration velocity
(inches per second, or ips)

Figure 12-1: Manual vibration data log format used in the 1970’s
Pump Condition Monitoring Guidelines 345

allows higher test stand values (up to 30% higher


for field values). For vertical turbine pump installa-
tions, it is especially important to know the actual
foundation stiffness to avoid high vibration from
operation at a structural resonant frequency.

6. How much has the vibration amplitude and/or


frequency changed during the life of the machine?
It is helpful to have an as-new vibration signature
taken and kept on file for future use.

7. Location of vibration measurements: The vibration


transducers should be mounted in such a way as to
not adversely affect measurement accuracy. In gen-
Figure 12-2: Approximate bearing life-vibration rela- eral, vibration probes should be located near the
tionship for general purpose machinery center of the bearing housing of between-bearing
pumps, and near the outer bearing of end suction
pumps. Horizontal and vertical dry pit pump vi-
different limits for the “preferred” and “allowable”
bration measurements are normally taken on the
operating regions. A vibration velocity of 0.15 ips
bearing housings (near the outer or uppermost
represents a “rule-of-thumb,” as-new acceptance
bearings). All measurements should be taken in
value. Moreover, this applies to operation in the
the horizontal, vertical and axial planes, with the
preferred operating range and with clear liquids.
maximum value used as the acceptance criterion.
Power levels are limited to 268 hp (200 kW) and
Vertical turbine pump vibration measurements are
low cavitation or suction turbulence.
taken near the top of the motor support. Probes
5. How do factory test stand vibration measurements should not be located on flexible panels or cylinder
compare with field site values? What is the effect walls, such as motor end covers.
of foundation stiffness/grouting? Generally, the
stiffness of a field pump foundation is much higher Not to be overlooked are special vibration moni-
than found on a factory test stand, especially if the toring approaches that are particularly well-suited for
pump base plate is grouted (see Chapter 3). That process pumps. One such approach involves the SKF
is why the Hydraulic Institute vibration standard enveloping process (Figure 12-3). The relevant hand-

1. A typical Velocity Spectrum process does not always reveal


possible bearing defects.

2. The acceleration enveloping process isolates bearing fault


signals by filtering out the machine’s higher amplitude, lower
frequency vibration noise (typically everything under 10-15
times shaft speed), thereby greatly improving the signal-
to-noise ratio of the bearing defect. Then, in the isolated
bearing frequency range, the enveloping process looks for
higher harmonics of repetitive, impulse signals created by
bearing defects.

3. These defect signals are detectable in the defect’s early


stages and typically occur in very high frequency ranges,
anywhere from five to 40 times the fundamental defect
frequency.

4. Once these harmonics are detected, the enveloper sums


the signals together, then folds the enhanced signal back
to the defect’s fundamental frequency range. The result is
a frequency spectrum with a much more obvious, enhanced
Figure 12-3: Acceleration enveloping process of vibration moni- event displayed at the defect’s fundamental fault frequency
toring (Source: SKF Condition Monitoring, San Diego, California) and at evenly spaced harmonics.
346 Pump User’s Handbook

contact produces vastly increased particle acceleration at


the impact point. The severity of these impacts can be
plotted, trended and displayed (see Figure 12-6).
SKF, a bearing manufacturer with manufactur-
ing facilities world-wide, is using several of their data
acquisition and analysis instruments (see top of Figure
12-4) as tools in their “@ptitude” (sic) industrial decision
support system. Making extensive use of data banks
and software, vibration data comprise just one of many
inputs being integrated into one easy to use application.
In essence, the system uses a structured approach to
capturing and applying knowledge—both real-time and
on-demand.
Another major contender is the Vibcode and Vib-
scanner family of German manufacturer Prueftechnik
and its Miami-based U.S. collaborator Ludeca, Figure
12-7. These combination data collectors and analyzers
come with ready-made software packages that start with
vibration and temperature monitoring, but also incor-
porate speed measuring and field balancing capabilities
that are of great value in a conscientiously applied pump
life extension program.
ITT/Goulds has developed a variable frequency
intelligent drive with a monitoring system (called
“PumpSmart®”) that is capable of adjusting the pump
speed to react to fault occurrences, such as a closed suc-
tion valve, cavitation and pump wear.

Figure 12-4: Versatile monitoring devices are part of an


integrated industrial decision support system (Source:
SKF Condition Monitoring, San Diego, California)

held data collection and analysis unit is shown at the


top of Figure 12-4. This data collector, and others like
it, represent versatile bearing distress monitoring tools.
Figure 12-5 shows shock pulse monitoring (SPM)
and manual data collection in progress. In simple terms,
the SPM method detects the development of a mechani-
cal shock wave caused by the impact of two masses.
At the exact instant of impact, molecular contact occurs
and a compression (shock) wave develops in each mass.
The SPM method is based on the events occurring in the
mass during the extremely short time period after the
first particles of the colliding bodies come in contact. Figure 12-5: SPM data collection on a process pump
This time period is so short that no detectable defor- (Source: SPM Instruments, Inc., Marlborough, Con-
mation of the material has yet occurred. The molecular necticut)
Pump Condition Monitoring Guidelines 347

Figure 12-6: Shock pulse monitoring and trend plots of severity


(Source: SPM Instruments, Inc., Marlborough, Connecticut)

PREDICTIVE CONDITION MONITORING even automatically sequence pump impeller rotational


AND FAULT TOLERANT INTELLIGENT direction to unclog debris.
DRIVES/CONTROLS
Condition Monitoring
New intelligent pump solutions have continued to These de-centralized data acquisition devices,
evolve thanks to the rapid advancement of electronic data which are local to the pump sub-system, gather system
processing and communications. What not long ago was data either through the plant network, from directly con-
thought to be too expensive, not reliable, and technically nected sensors and/or from data available on the drive
not possible, is rapidly becoming a reality. Technological (Ref. 12-10). These data acquisition devices have high
advances in devices such as digital signal processors and speed microprocessors capable of sampling data, so that
wireless communication systems are enabling the devel- flow, pressure, speed, torque, vibration spectral analysis
opment of effective intelligent pump solutions. These de- and/or motor current signature analysis can run locally
vices can be decentralized systems, local to the pump and and in conjunction with diagnostic algorithms designed
outside of the main distributive control system, and can specifically for the pump system. The diagnostic results
contain algorithms that have been developed to provide from these de-centralized systems can be fed back into
intelligent solutions, specifically designed for a unique the plant maintenance system, or to any remote location,
class of pumps or application. so that planned maintenance activities can be deployed
Today there are both custom and pre-engineered effectively. In addition, the capability exists on some of
systems available which have this improved function- the newer types of data acquisition devices to implement
ality that can positively impact key life cycle cost ele- local automated control to protect the pump system
ments. In addition to saving energy by varying pump against premature failure and/ or to optimize pump
speed, these new drives/controls can also monitor a system efficiency.
variety of critical pump conditions and either automati-
cally make the required adjustments and/or wirelessly
(or by hard wire) transmit this information for further ROTOR BALANCING
potential action. In addition, they can provide efficient/
reliable control for multi-pump operation, can reduce All impellers, irrespective of their operational
constant on-off cycling in wet well applications, and can speed, should be dynamically (“spin”) balanced before
348 Pump User’s Handbook

Figure 12-7: Pruftechnik’s “Vibcode”


and “Vibscanner” devices collect and
analyze a wide range of data and
are supported by superior software
(Source: Ludeca, Miami, Florida 33172)

installation, either single or two plane. Two-plane bal- one time only as an assembled unit.
ance is required for wide impeller, when the impeller Multistage pump rotors, both horizontal and ver-
width is greater than 1/6th of the impeller diameter. tical, are best not assembled and balanced and then
ISO balancing criteria are illustrated in Figure 12-8. disassembled for re-assembly. Often, more problems
There is no doubt that dynamic balancing of the are caused by the disassembly than are caused by the
three major rotating pump components, shaft, impeller component balance. The static (single plane) force in
and coupling, will increase mechanical seal and bear- the balance is always the more important of the two
ing life. All couplings of any weight or size should forces, static and dynamic (couple force). If balancing
be balanced, if they are part of a conscientious and of individual rotor components is chosen, it is best to
reliability-focused pump failure reduction program. use a tighter tolerance for the static (single plane) force.
Couplings that cannot be balanced have no place in In theory, if all the static force is removed from each
industrial process pumps. part, there should be very little dynamic (couple) force
The preferred procedure of balancing a rotating remaining in the rotor itself.
unit is to balance the impeller and coupling indepen- For impellers operating at 1,800 rpm or less, the
dently, and then the impeller and coupling on the shaft ISO 1940 G6.3 tolerance is acceptable. For 3,600 to 1,800
as a single unit. Another method is to balance the rotor rpm, the ISO G2.5 is a better tolerance. Both are dis-
Pump Condition Monitoring Guidelines 349

played on the balance tolerance nomo-


grams for small (Figure 12-9) and large
machinery rotors (Figure 12-10). Gener-
ally tighter balance tolerances (G1.0)
are not warranted unless the balancing
facility has modern, automated balanc-
ing equipment that will achieve these
results without adding much time and
effort. Using older balancing equipment
may make the G1.0 quality difficult and
unnecessarily costly to obtain and dupli-
cate. Also, factory vibration tests have,
at best, shown insignificant reductions
in pump vibration with this tighter bal-
ance grade.
Balancing machine sensitivity must
be adequate for the part to be balanced.
This means that the machine is to be
capable of measuring unbalance levels
to one-tenth of the maximum residual
unbalance allowed by the balance qual-
ity grade selected for the component
being balanced.
Rotating assembly balance is rec-
ommended when practical and if the
tighter quality grades, G2.5 or G1.0, are
desired. Special care must be taken to
ensure that keys and keyways in balanc-
ing arbors are dimensionally identical to
those in the assembled rotor. Impellers
must have an interference fit with the
shaft, when G1.0 balance is desired. Al-
though looseness between impeller hub
and shaft (or balance machine arbor) is
allowed for the lesser balance grades, it NOTE: The light area is the generally used area, based on common experience.
should not exceed the values given in
Table 12-1 for grades G2.5 or G6.3: Figure 12-8: Permissible residual specific unbalance based on balance
quality grade G and service speed n. (Source: ISO Standard 1940)

VIBRATION ACCEPTANCE LIMITS


suction pumps, depending on the power level. HI also
Hydraulic Institute Standard ANSI/HI 9.6.4 includes the API-610 values for end suction refinery
(www.Pumps.org) presents the generally accepted pumps (in RMS terms), although the API document
allowable pump “field” vibration values for various requires that these acceptance values be demonstrated
pump types (see Table 12-2). The standard is based on on the factory test stand.
RMS total, or all-pass vibration values (Ref. 12-1). The The HI standard also states that these values only
standard states that factory or laboratory values can apply to pumps operating under good field conditions,
be as much as 30% above these field limits, depend- which are defined as:
ing on the rigidity of the test stand. The ANSI/ASME
B73 standard accepts 27% and 17% above the HI 9.6.4 1. Adequate NPSH margin (see Chapter 5).
values for factory tests performed on chemical end 2. Operation within the pump’s preferred operating
350 Pump User’s Handbook

Figure 12-9: Balance tolerance


nomogram for G2.5 and G6.3,
small rotors (Source: Bloch,
Heinz P., and F.K. Geitner, “Ma-
chinery Component Mainte-
nance and Repair,” 2nd Edition,
1990, Gulf Publishing Com-
pany, Houston, Texas, ISBN
0-87201-781-8)

region (between 70% and 120% of BEP)—see also recommended if vibration levels increase to twice the
Chapter 5. “field” acceptance limits (or initial actual readings).
3. Proper pump/motor coupling alignment (Ch. 3).
4. Pump intake must conform to ANSI/HI 9.8 (pump
intake design). CAUSES OF EXCESSIVE VIBRATION

The HI standard further bases the allowable vibra- Once a pump has been determined to have a
tion levels on pump power, Table 12-2. high “total/all-pass” vibration level, the next step is to
It should also be noted that the acceptable vibra- identify the cause. This is the time to obtain a filtered
tion values for slurry and solids handling pumps are vibration analysis (see Figure 12-11A).
about double the values given for horizontal clean liquid You cannot just assume that the rotor is out of bal-
pumps. ance (which could be the case). There are many other
Once a pump is accepted and commissioned, potential culprits. Machinery vibration problems often
somewhat higher total (all-pass) vibration values are result from the interaction between an exciting force
usually accepted before further follow-up and analysis (hydraulic or mechanical) and the associated structural
are deemed appropriate. As a general rule, follow-up is and/or hydraulic resonance frequency response. The
Pump Condition Monitoring Guidelines 351

Figure 12-10: Balance tolerance


nomogram for G2.5 and G6.3,
large rotors (Source: Bloch,
Heinz P., and F.K. Geitner,
“Machinery Component Main-
tenance and Repair,” 2nd Edi-
tion, 1990, Gulf Publishing
Company, Houston, Texas,
ISBN 0-87201-781-8)

Table 12-1: Maximum Diametral Hub Looseness


————————————————————————————————
Impeller Hub Maximum Diametral Looseness
Bore < 1,800 rpm 1,800-3,600 rpm
————————————————————————————————
0 — 1.499 in. . 0015 in. . 0015 in.
1.5 — 1.999 in. . 0020 in. . 0015 in.
2.0 in. and larger . 0025 in. . 0015 in.
————————————————————————————————

stronger the exciting force, and/or the closer these Rotor lateral vibration (x,y or z axis), and torsional vi-
exciting force(s) are to a component natural frequency, bration (commonly occurring with reciprocating engine
the greater the vibration amplitude. The object for any drives). Structural lateral vibration is quite common
pump vibration analysis should be to find the root cause with long-shafted vertical pumps, although not limited
of the excessive vibration, and then determine how to to these structures.
correct it. Basic vibration types to evaluate include:
352
Table 12-2: Allowable pump field-installed vibration values

Pump User’s Handbook


Pump Condition Monitoring Guidelines 353

Table 12-3: Sources of Specific Vibration Excitations


———————————————————————————————————
FREQUENCY SOURCE
———————————————————————————————————
0.1 × Running Speed Diffuser Stall
0.8 × Running Speed Impeller Stall (Recirculation)
1 × Running Speed Unbalance or Bent Shaft
1 × or 2 × Running Speed Misalignment
Number of Vanes × Running Speed Vane/Volute Gap & Cavitation
———————————————————————————————————

Figure 12-11A:
Frequency
spectrum
showing (top)
time-velocity
plot and, (bot-
tom) frequency
vs. vibration
amplitude plot

Figure 12-11B: Acoustical Pipe Resonance Half Wave Length, based on


Pump Speed and Number of Impeller Vanes
354 Pump User’s Handbook

CAUSES OF EXCESSIVE VIBRATION EXCITATION: cause increased vibration, normally by increased


local velocities, which in turn, increases cavitation,
There are many potential vibration excitation and/or causes turbulence within the pump.
sources, which can often be identified through a filtered 7. Bearing wear: Rolling element bearings have dis-
vibration analysis. Figure 12-11A shows some of these tinct vibration signatures based on the number of
filtered vibration peaks, as multiples of the pump run- bearing balls or rollers.
ning speed and number of impeller vanes. A further 8. Opening up of impeller wearing ring clearances,
breakdown of potential excitation sources, with their which can reduce the NPSH margin by shifting the
specific frequency signatures (as multiples of the pump pump operating flow point to higher levels.
running speed), is shown in Table 12-3. It should be noted 9. Broken rotor bars on electric motors, which will
that the “diffuser stall,” “recirculation” and “cavitation” generate specific frequencies.
sources, listed in Table 12-3, are hydraulic in nature,
with the remaining being mechanical. The most common Hydraulic Pump Vibration Excitation—Amplitude
causes of excessive pump vibration excitation are: The amplitude of hydraulic pump excitations,
especially those at blade pass frequencies, is typically
1. Rotor unbalance, caused by new residual impeller/ a function of one of two pump energy factors: “High
rotor unbalance, or unbalance caused by impeller Suction Energy” and/or “High (discharge) Energy.” Ac-
metal removal (wear). cording to the Hydraulic Institute, pumps with heads
2. Shaft (or coupling) misalignment. greater than 650 ft/stage that require more than 300
3. Liquid turbulence due to operation too far away hp/stage, have high (discharge) energy, while high
from the pump best efficiency flow rate, and/or (and very high) suction energy (suction specific speed
operation in the low flow pump suction recircula- x inlet tip speed x specific gravity) has been defined in
tion region (see Figure 12-12). Chapter 5. It should be noted that the excitation levels
4. Cavitation due to insufficient NPSH margin, es- related to high suction energy are also a function of the
pecially with “High Suction Energy” pumps (see pump NPSH margin (NPSHA/NPSHR), see Chapter
chapter 5). 5. The pressure pulsation excitations generated from
5. Pressure pulsations from impeller vane/casing either high (discharge) energy, or high (or very high)
tongue (cutwater) interaction, in high discharge suction energy pumps, both occur at impeller vane-pass
energy pumps. frequency, and each can also cause destructive acoustic
6. Poor pump suction or discharge piping (having pipe resonant vibration under the right conditions. Gen-
turns or fittings too close to the pump), can also erally speaking, the higher the suction and/or discharge
energy level the greater the vibration amplitude.
The most common pump suction hydraulic exit-
ing forces come from turbulence or cavitation within
the pump suction, which can become a problem when
the suction energy at the pump impeller inlet is high
enough. One of the ways to reduce pump suction
energy is to reduce the pump speed with a VFD, to
achieve low suction energy. However, a VFD can also
make it much more likely that a pipe, foundation or
pump resonance will be excited, so it can be a double-
edged sword.
Discharge pressure pulsations are typically caused
by the interaction between the different pressures (and
velocities) on the leading and trailing surfaces of the
impeller vanes, at the impeller O.D. and the casing cut-
water (volute tongue). The higher the pump head and
Figure 12-12: Hydraulic Institute vibration values ap- the smaller the gap between the impeller O.D. and the
ply only within preferred operating region of pump, volute tongue, the greater the discharge pressure pulsa-
i.e. vibration due to recirculation may greatly exceed tions. These discharge pressure pulsations also occur at
anticipated vibration amplitudes vane pass frequency.
Pump Condition Monitoring Guidelines 355

RESONANCE RESPONSE: full wavelengths and multiples thereof. Normally only


the first and second harmonics need to be considered.
Amplified resonant vibration response root causes Typical reflection points include orifice plates, reducers
are generally more complex to analyze. They typically or increasers (with a 50% or more velocity change), tees
result from pump operation at speeds (running or vane and partially closed gate or check valves. Long radius
pass) close to a mechanical or hydraulic resonant fre- elbows do not reflect waves, while short radius elbows
quency of a major pump, foundation or pipe component. and vaned elbows may reflect waves.
This is of special concern with variable speed, large mul-
tistage horizontal and/or vertical pumps. A margin of
safety should be provided between the pump/vane-pass SOME CORRECTIVE MEASURES:
speed/frequencies, and any major structural (and/or
hydraulic) natural frequencies. Typical acceptable mar- Effective corrective measures that address reso-
gins are in the range of 15-25%. The magnitude of the nance caused high vibration problems, are ones that
vibration response can be amplified 2.5 times or higher detune the resonance conditions, by providing a mini-
at or near a component natural (critical), or resonant mum 15 to 25 percent separation margin between the
frequency. pump excitation and piping acoustic and/or structural
In addition to structural resonant frequencies found resonance frequencies. The following detuning actions
in pump suction and/or discharge piping, pump and should be considered:
motor foundations, and in vertical turbine pump instal-
lations, structural resonances are also quite common in • Change the vane count of the impeller (if the
large multistage horizontal pumps. pump manufacturer offers this option) feeding the
offending channel (pipe length). This changes the
Acoustic Resonance Response: excitation frequency and therefore the wavelength
Acoustical pipe resonances (Ref. 12-11), which can (see Figure 12-11B).
be excited by pressure pulsation from the pump (see • When a VFD is controlling the pump speed, it
Figure 12-11A), can also cause excessive pump and/ may be possible to “lock out” the offending speed
or pipe vibration. This occurs when a high (suction or ranges from continuous operation.
discharge) energy frequency excitation (typically vane- • If feasible, change the physical length of the offend-
pass), corresponds with the frequency that will generate ing (resonance) pipe.
a standing acoustic wave inside a fluid filled channel. • Install an acoustic filter (when the issue is an
Although acoustic pulsations are not a frequent acoustic resonance), but filters typically must be
or common source of excessive vibration in pumping matched to the system and resonant frequency.
systems, their occurrence is increasing with the growing
popularity of variable speed pump drives. When reso- If detuning is not feasible (or is the issue), the ap-
nant pulsations do develop in a liquid pumping system, plicable excitation levels can also be reduced by imple-
they tend to be high in amplitude and can cause severe menting one or more of the measures listed below:
vibration problems. Pre-installation analyses and field
testing may need to be performed to avoid an acoustic • If the excessive vibration is at running speed, bal-
resonance problem. ance the rotor, as discussed in the prior section of
Acoustic resonance can occur in the suction and/ this chapter.
or discharge piping, in the long crossover of multistage • If the excess vibration is at vane-pass frequency
pumps, and in other fluid filled channels, in response and the pump has high suction energy, reduce the
to a pump hydraulic excitation frequency. The phenom- pump suction energy level by reducing the pump
enon takes place when the return of a reflected pressure speed, and/or increasing the impeller vane over-
wave, generated by a periodic excitation, coincides with lap, if it is less than 15 degrees. Pressure pulsation
the generation of the next pressure pulse. In that case, a levels are proportional to the square of the speed.
standing wave forms inside the fluid filled channel. • Also if the vibration is at vane-pass, and the pump
The channel length, for acoustic resonance, is has high suction energy, increase the NPSH Avail-
determined by a reflective condition at the end of the able (or reduce the pump NPSHR) to reduce cavi-
channel opposite to the induction of the pressure wave. tation (see chapter 5 for desired minimum NPSH
The channel length may be equal to quarter, half, or Margin Ratios).
356 Pump User’s Handbook

• Cut back on the volute cutwater tips (preferably For critical machines, more than one method of
with an angle cut) to increase the B-gap (see page condition monitoring may be justified. This segment will
411), which should reduce the discharge excitation demonstrate use of vibration and performance analysis
levels, if the pump has high discharge energy and as inter-related and practical examples of condition
the excessive vibration is at vane pass. monitoring.
• Minimizing the impeller vane outlet thicknesses
by means of overfilling, again for high discharge The Head-flow Method of
energy pumps with vane-pass vibration. Pump Condition Monitoring
The most useful condition monitoring method
is by head-flow measurement, because in addition to
USING PREDICTIVE MAINTENANCE pump deterioration, it detects any changes in system
AS YOUR DECISION MAKING TOOL* resistance. The head-flow measurement method can be
used for all pumps where flow, or a repeatable indicator
Pump Condition of it, can be quantified.
Monitoring Examined Throttling the pump to obtain points over the full
The extent and effects of internal wear in centrifu- flow range is not necessary. Some points near the normal
gal pumps vary with the nature of the liquid pumped, operating duty point are sufficient to reveal the effects
the pump type and its operating duty. Some pumps last of wear, usually shown by the head-flow curve moving
for years, others for only months. towards the zero flow axis by an amount roughly equal
Overhauling of pumps on a fixed time or sched- to the internal leakage flow. This is demonstrated by
ule basis is rarely the most cost-effective policy. Use of “test points-worn pump” on Figure 12-13.
condition monitoring ensures that pump overhauls or A series of test readings at steady conditions at
performance restoration efforts are done when really about 15 second intervals is sufficient; the average
necessary. However, despite the many excellent pump values are being plotted. Speed must be measured for
textbooks, there is little information available on how variable speed pumps, and the head-flow data corrected
to apply condition-based maintenance to pumps. to a standard speed (Ref. 12-2).
Monitoring methods should be chosen that would
detect each of the various failure modes that can be
foreseen to occur:

• Vibration monitoring and analysis (probably the


most widely applied method of condition monitor-
ing for rotating machines in general, and suited
to detect such faults as unbalance, misalignment,
looseness)

• On large pumps, sampling and analysis of lubri-


cants for deterioration and wear debris (relevant
for bearings/lubrication system faults)

• Electrical plant tests (relevant for motor condition)

• Visual inspection and Non-Destructive Testing


(particularly relevant for casing wear)

• Performance monitoring and analysis (relevant for


pump internal condition).

*This major segment was contributed by Ray Beebe, Senior Lecturer


at Monash University, Gippsland School of Engineering, Churchill,
Victoria 3842, Australia. It is based on testing and analytical work Figure 12-13: Head-flow of new pump and head-flow
performed under his guidance. points from worn pump
Pump Condition Monitoring Guidelines 357

Field tests sometimes give results slightly different


from the manufacturer’s shop tests because actual site
conditions for flow and pressure measurement are rarely
as required by the various standards for pump testing.
However, for monitoring, we are seeking relative changes
rather than absolute accuracy. Non-intrusive ultrasonic
flowmeters are applicable in most cases. A permanent
flowmeter installed as part of a pump’s minimum flow
protection or process measurement can be used, provided
its long-term condition is considered to be constant, or it
can be inspected regularly.
Such performance information shows the extent to
which a pump has deteriorated, and pumps can be pri-
oritized for overhaul on the basis of their relative wear.

Shut-off Head Method


Measuring head at zero flow is a simple test. It is
only possible where it can be tolerated; it thus excludes
high-energy or high-specific-speed pumps, where power
at shut-off is greater than that at duty point. Figure 12-14: Measured degradation of a 230 kW pump
With the discharge valve closed fully for no longer by head-flow testing
than 30 seconds, suction and discharge pressures are
read when steady. The liquid temperature is also needed temperature is very small, great care is required to mea-
to find the density, which is used to convert the pressure sure it. Any recirculation effects at pump inlet and outlet
readings into head values. must be eliminated, and tests are not possible at very
Wear of vane outer diameters will show readily, as low or zero flows. Efficiency can be calculated from the
the head-flow curve of a worn pump moves towards the inlet temperature, differential temperature and head. If
zero flow axis. To show sealing wear ring degradation, efficiency changes with time, comparisons can be made
the pump head/flow curve needs to be relatively steep. on efficiency vs. head plots. For high head pumps, an al-
(Note that if the pump has a rising curve, internal leak- lowance must be made for the isentropic temperature rise
age will initially give an increase in shut-off head). that occurs as a result of pressure increase (Ref. 12-3).
Figure 12-14 shows the trend in degradation of a A commercially available device is widely used in
230 kW pump over three years. Wear amplitude is ex- the UK water industry (Ref. 12-4). Pressure taps at suc-
pressed at duty point flow, as the percentage reduction tion and discharge are required to be two diameters away
in total head compared with the new datum condition. from pump flanges. These taps allow for the installation
This is usually derived from head-flow tests near duty of pressure/temperature probes. Clamp-on type detectors
point, but can also be obtained using the shut-off head are placed to measure motor power. Pump efficiency is
test where this is allowable. then found from precise head and temperature rise mea-
Please note that such testing requires that two surements through the pump. From assessment of motor
frequently ignored conditions be met: losses, power absorbed by the pump is computed. From
all these data, the pump flow can be found.
1. Pressure gauge connections must be provided on For condition monitoring, tests at around normal
the pump suction and discharge sides operating point are usually sufficient. The thermody-
2. All pressure gauges must be tested and calibrated namic method would be more attractive economically
before data taking. Using a brand new gauge is no if no special tapping points were required. Research
guarantee that readings will be correct. at Monash University on high head pumps using spe-
cial semi-conductor temperature probes on the piping
Thermodynamic Method outside surface, covered with insulation, gave usable
Another pump monitoring method is to measure results, provided the pump is being operated at steady
the temperature rise of the liquid through the pump, conditions for 30 minutes to allow the piping tempera-
which reflects pump inefficiency. Since the differential ture to stabilize (Ref. 12-5).
358 Pump User’s Handbook

Percent efficiency for pumps in water service up On yet another 11-stage pump, the head-flow
to 54°C is given by the empirical formula given below, performance was tested as being well below the da-
which includes a correction for the isentropic tempera- tum curve. As the pump was dismantled, measure-
ture rise (total head is in kPa, temperatures in °C). See ments showed that interstage clearances were not
Ref. 12-6 for discussion. worn. A condition monitoring credibility crisis was
averted when the balance seat area was reached and
100
Pump efficiency = ————————————— found to be severely eroded. Balance flow had obvi-
[1–0.003(inlet T–2) + 4,160 ously been very high. For the best monitoring, both
(Temp. Rise/Total Head]) head flow and balance flow should be measured,
particularly if the balance area can be separately dis-
Balance Flow Measurement mantled in the field.
Multistage pumps with the impellers facing in the
same direction usually have a balance disc or drum Optimum Time for Overhaul
arranged such that final stage discharge pressure coun- The most economic time to restore lost perfor-
teracts the axial thrust on the shaft line. This makes it mance by overhaul will vary with the circumstances.
possible to monitor pump condition by measuring the If the deterioration is constant over time, then a cash flow
leak-off from the balance device (Ref. 12-7). The basis analysis can be done to ensure that the investment in
is that if increased wear in the annular space to the overhaul will give the required rate of return. This is the
balance device is evident from increased leak-off flow, same process as used in deciding on any investment in
then the interstage clearances are also worn. plant improvement.
As the leak-off line is quite small compared to If the deterioration rate is increasing with time, then
the pump main flow piping, a permanent flowmeter is the optimum time for overhaul will be when the cumu-
relatively inexpensive. For some years, overhauls have lative cost of increased electricity consumption equals
been scheduled on this basis on a number of boiler feed the overhaul cost.
pumps. Flows are read manually, and trends plotted The method is now described for some plausible
using a database program (Figure 12-15). Note that here scenarios and actual situations.
the balance flow of 15 l/s corresponds to about 10% of
the duty flow, and about 250 kW of extra power. When Pump Deterioration Results in
added to the likely internal recirculation, this would Reduced Plant Production
mean that an even larger proportion of the power Where the cost of overhaul is insignificant in
absorbed is being wasted. These pumps are variable proportion to the cost of lost production cost, prompt
speed, and tests show that the measured flows must overhaul is usually simply justified at a convenient
be corrected in direct proportion to the speed. “window.”
On a set of pumps of another design elsewhere,
both head-flow and balance flow were measured for Pump Which Runs Intermittently to
some years, but no correlation was found. Meet a Demand
In a pumping installation such as topping up a
water supply tank or pumping out, deterioration will
cause the pump to take more time to do its duty. The
extra service time required therefore results in increased
power consumption that can be related to the overhaul
cost.

Pump Deterioration Does Not Affect


Plant Production, at Least Initially:
Constant Speed, Throttle Valve Controlled Pump
The internal wear does not cause any loss in
Figure 12-15: Condition monitoring of a high energy production from the plant, as the control valve opens
multi-stage pump by measurement of balance device more fully to ensure that pump output is maintained.
leak-off flow (flows are corrected to a standard pump Eventually, as wear progresses, pump output may be
speed) insufficient to avoid loss of production, or the power
Pump Condition Monitoring Guidelines 359

taken will exceed the motor rating. Since the time now is 24 months, $3,240 ÷ 24 gives
Earlier, Figure 12-13 showed the head-power-flow the average deterioration cost rate as $135 per month.
site test characteristics of such a pump. Its output is The optimum time for overhaul can be calculated
controlled using a throttle control valve. The duty flow (Ref. 12-9), from
is 825 m3/h, and the duty point in the new condition
is “A.” The power absorbed by the pump is read off T = [(2)(O)/C]1/2
the power-flow curve as 2,150 kW, “B.” The power-flow where:
curve should ideally be found on site, but factory test O = cost of overhaul
data may have to suffice. C = cost rate of deterioration
After some service, the plotted “test points-worn
The result here is T = 27.2 months.
pump” indicate internal wear. When worn to this extent,
the operating point moves to “C,” as the system resistance But it is better to calculate and plot the average to-
curve lowers when the throttle valve is opened further. tal cost/month values for a range of times. Seen clearly
The increased power required in the worn condi- will be the cost impact of doing the repairs at some other
tion can be estimated by extending from the head-flow time, such as at a scheduled plant shutdown.
curve at constant head from the operating point to “D,”
and then intersecting the power-flow curve for new con- Calculating Average Cost Per Month:
dition at constant flow, “E.” Follow the arrowed line in In this example, take the time at 22 months.
Figure 12-13. This assumes that the original curve still
represents the flow through the impellers (of which less Average monthly cost to cover overhaul:
is leaving the pump to the system). Of course, the power $50,000/22 = $2,273/month
could be measured on test at extra expense if the pump
was motor-driven. Average extra energy cost:
In our example, power required for this duty in the $135 × 1/2 × 22 = $1,485/month
worn condition is shown in Figure 12-13 by the projec-
tion from the duty flow of 825 m3/h to the test curve to Total average cost/month is
find 640 m head, then across to the “site test-new pump” the sum of these two figures =
curve, then down to the power curve, to find 2,300 kW. $3,758/month
The extra electric power consumption is therefore
2,300 – 2,150 = 150 kW which, divided by the motor Repeat this calculation for several months, perhaps
efficiency (here it is 90%), will yield 167 kW. using a spreadsheet, and look for the minimum total
If the wear ring clearances are known by previous cost, which is at 27.2 months. If plotted as cost/month
experience of correlation with measured performance, or against time, the resulting curves will show the overhaul
if the pump is opened up already, the extra power con- cost per month dropping with time, with the lost energy
sumed likely to be saved by overhaul can be estimated cost increasing with time. (The time value of money
(Ref. 12-8). could also be taken into account, if required). Usually
Using this method, a number of pumps of varying the total cost curve is fairly flat for +/- 20% or so.
wear conditions could be prioritized for maintenance, If the overhaul were delayed until, say, 30 months,
based on their increased power consumption and their then the accumulated cost of lost energy would have
relative costs of overhaul, i.e. the cost/benefit ratio. reached $135 × 1/2 × (30)2 = $60,750. At 27.2 months,
the cost is $135 × 1/2 × (27.2)2 = $49,939. The cost of
Finding the Optimum Time for delaying overhaul is thus the difference, $10,811.
Overhaul from Head-flow Data Note that this calculation is only correct if the wear
For this example, the test points were obtained fol- progresses at a uniformly increasing rate with time, but, as
lowing 24 months of service since the pump was known Figure 12-14 shows, this is not always so. Information
to be in new condition; an overhaul would cost $50,000; may not be available to make any other assumption,
electricity costs 10¢/kWh, and the pump is in service but decision makers have to start somewhere! There are
approximately 27% of the time. other formulas for nonlinear rates of change (Ref. 12-9).
Tests showed that the cost of deterioration had Note that some relatively small pumps may never
reached 167 kW × 0.10 × 720 × 0.27 = $3,240/month justify overhaul on savings in energy use alone, but may
(taking an average month as 720 hours). be justified on reduced plant production rate.
360 Pump User’s Handbook

When Pump Deterioration Does Not Affect Production


For a pump where the speed is varied to meet its
desired duty, the effect of wear on power required is
much more dramatic than for the case of a constant-
speed, throttle-controlled pump. This is because the
power increases in proportion to the speed ratio cubed.
Unless pump output is limited by the pump
reaching its maximum speed, or by its driver reaching
its highest allowable power output, no production will
be lost. However, power consumed will increase more
dramatically for a given wear state than for a constant-
speed pump.
To estimate power required in the worn state, the
head-flow curve must be drawn for the current higher
speed in the new condition. Select a head-flow point on the
original new condition curve, and correct it to the higher
speed. Multiply the flow by the speed ratio and multiply
the head by the square of the speed ratio. Repeat this Figure 12-16: Head-flow-power characteristics of new
for some other points at flows above duty flow to draw variable speed pump, and head-flow points from worn
the new condition head-flow curve. pump
Follow the same method and calculations as be-
fore to find the time for overhaul at minimum total Head-power-flow characteristics in the “new” state
cost. The operating point is projected from the worn are needed as before, and the operating point must be
curve to the new curve at the same speed as the known. Note power required at operating point as be-
worn curve. Figure 12-16 shows the performance of a fore. Make an overlay trace of the head-flow curve in the
variable speed pump. When new, operation at 1,490 new condition. Place it over the “new” curve and move
rpm meets the desired duty flow at operating point to the left horizontally until the curve cuts the head axis
“A,” requiring 325 kW power, point “B.” After some at the shut-off head value obtained on the test. The trace
time in service, internal leakage and “roughness” has is now in the position of the “worn” head-flow curve
increased such that the pump must run at 1,660 rpm that is being experienced. Exactly the same process can
to meet the required duty—still point “A.” be followed as explained previously.
To estimate the power required now, the head-
flow curve must be drawn for the higher speed in the Worn Vertical Multistage Pump
new condition. Several head-flow points are selected Both vibration and performance analysis were
and corrected for the higher speed: multiply each flow used to help solve a case where a pump experienced
by the speed ratio, and multiply each matching head excessive vibration. This involved a 9-stage mixed flow
by the speed ratio squared. This will result in the pump, rated at 70 l/s with a head at 155m, operating
head-flow curve at 1,660 rpm in the new condition. at 1,480 rpm. Only the motor and the pump discharge
The head at the duty flow -point “A”- is pro- piping were visible above the plant floor, with the base
jected across to meet the head-flow curve at 1,660 r/ flange bolted to the floor.
min (new condition, line “C” in Figure 12-16). Projec- For condition monitoring by performance analy-
tion downward at constant flow leads to the increased sis, a permanently installed orifice plate flowmeter was
power required at 425 kW. The extra power demand used. An ultrasonic flowmeter showed close agreement.
is 31%! Vibration measurements were taken in the horizontal
The same calculations as before are followed to and axial directions on the motor flange.
find the time for overhaul for minimum total cost. The pump had not yet been added to the routine
vibration program. High vibration was reported and
Optimization Using Shut-off Head Test Results vibration measurements showed 14 mm/s (0.55 ips)
The shut-off head test information can also be used horizontal vibration, all at 7.5 Hz. This level is not ac-
to estimate power used in the worn state, and do the ceptable for reliable service. (See page 344.)
optimization calculations explained previously. Lower down the casing, the vibration was half
Pump Condition Monitoring Guidelines 361

this level, but mostly at 50 Hz, with some at 7.5 Hz. No


vibration was evident at the running speed frequency
of 25 Hz. More frequent monitoring commenced, and
a week later, the vibration had increased to 22 mm/s
(0.87 ips), all at 6.5 Hz. The performance at the usual
operating point had also decreased by 18%.
Since an alternative flow path was available with-
out reducing production, albeit reducing plant efficiency,
the pump was removed for overhaul. All impellers and
wear rings were found damaged beyond repair, and the
shaft was bent.
After repairs, the highest vibration level was below
1 mm/s (0.04 ips) at 25 Hz and 50 Hz frequencies, and
tested performance had also returned to the datum level.
Routine measurements were commenced at three-month
intervals.
It was suspected that the base mounting bolts had
worked loose sufficiently to allow the pump to vibrate at
its natural frequency of about 7.5 Hz. This was thought
to have resulted in internal damage.
Figure. 12-17: Modern light-weight data collector and
Understand Your Measurement Options
vibration analyzer (Source: Prueftechnik, Germany,
The authors believe that Ray Beebe’s work at
and Ludeca, Inc., www.ludeca.com)
Monash University shows what can be accomplished
by careful measurements on a variety of pump types.
The rapid expansion of plant-wide distributive control in the DCS software. There is no need to wait for the
systems (DCS) has opened another opportunity. detection of a fire or excessive vibration levels to initiate
It is true that few process pumps (if any) are troubleshooting.
equipped with calibrated flowmeters, temperature sen- New data collectors and vibration analyzers enter
sors and pressure gauges. However, a process unit can the market every year and the user/owner of process
be modeled to an extent where inlet and discharge pumps should keep informed on available models, con-
pressures as well as power consumption of each pump figurations and options. Figure 12-17 represents just one
for a given set of operating conditions can be predicted. of these, a lightweight, two-channel FFT data collector/
Only a few selected parameters need to be continuously vibration analyzer for monitoring and analyzing machine
monitored in order to detect unusual events that might condition. As a data collector, this instrument records all
indicate the need for further troubleshooting. Data from forms of machine vibrations, bearing conditions, process
pressure transmitters, thermocouples and electric motor data and visual inspection information. Collected ma-
current transmitters can now be added to plant control chinery data are stored on mass storage cards and then
computer networks. Calculation of the cost of through- transferred to suitable maintenance software for further
put reduction, or power waste, can readily be integrated evaluation, report generation and archiving.

You might also like