Partitions
This section contains a full range of lightweight partition and wall
systems for use in new and existing buildings. They cover all applications,
from simple space division to high performance walls
Partitions
C04
Introduction
Partitions
British Gypsum offers a full range of lightweight
partition and wall systems. Our systems are
non-loadbearing and constructed using modern,
drylining techniques. British Gypsum metal
framed partitions and walls can be used in all
types of new and existing buildings, including
private and social housing, apartments,
Partitions
healthcare, educational facilities, recreational
and industrial properties.
C04
They cover all applications, from simple space
division, through to high performance walls
designed to meet the most demanding fire
resistance, sound insulation, impact and height
requirements.
When specifying partitions, a number of performance characteristics are normally used to determine the required solution.
Depending on the project or construction type, these performance parameters could be set by minimum regulatory
standards, or a client or customer requirement for buildings that offer the highest standards of performance and comfort.
Our quick-reference partition system guide, below, allows you to simply select the performance categories of interest and
identify the British Gypsum partitions systems that best satisfy your project requirements.
Duty Maximum
Fire rating height1
Partition
Acoustic performance
performance thickness System Page
Partitions
Medium -
30 - 120 75 - 211 34 - 63 47 - 57 8100 GypWall classic C04.S02.P02
Severe
C04
Heavy -
30 - 90 102 - 208 49 - 63 48 - 55 5700 GypWall staggered C04.S06.P02
Severe
Non-loadbearing timber
30 - 120 88 - 196 34 - 52 - - - C04.S11.P02
stud (internal partitions)
Non-loadbearing timber
60 - 90 141 - 293 56 - 63 48 - 53 - - C04.S11.P05
stud (separating walls)
1
Based on studs at 600mm centres
Additional information
Try out The White Book System Selector, an online tool designed to help find the ideal solutions for your
project needs. Additional information such as BIM data (Revit), NBS clauses, CAD drawings and other
associated items can be downloaded. Visit british-gypsum.com
Introduction
Acoustic performance
Table 1 — Sound insulation performance for residential specification
On-site Laboratory2
Approved Document E (England and Wales) Minimum solution Recommended solution
DnT,w + Ctr dB
(Rw + Ctr ) dB (Rw + Ctr ) dB
On-site Laboratory2
Partitions
Technical Standards Section 5 (Scotland) Minimum solution Recommended solution
DnT,w + Ctr dB
Rw dB Rw dB
C04
or conversion (traditional buildings1)
1
Definition of traditional buildings - A building or part of a building of a type constructed before or around 1919:
a) using construction techniques that were commonly in use before 1919; and
b) with permeable components, in a way that promotes the dissipation of moisture from the building fabric.
2
Minimum solutions provide little or no margin of safety to allow for reduction in performance due to flanking transmission. Recommended solutions have
greater potential to satisfy the requirements of Building regulations.
Table 2 – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting deflection of L/240 at
200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
48 S 50 1 x 12.5mm 2500 2800 2900 3200 3100 3500
1 x 15mm 2800 3000 3100 3300 3300 3600
2 x 12.5mm 3400 3600 3600 3800 3800 4000
2 x 15mm 3700 3800 3900 4000 4000 4200
48 I 50 1 x 12.5mm 2900 - 3400 - 3700 -
1 x 15mm 3100 - 3500 - 3800 -
Partitions
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
Introduction
Table 2 (continued) – GypWall classic metal stud partition recommended maximum heights (mm) - based on a limiting
deflection of L/240 at 200Pa. Applicable to non fire-rated or BS 476: Part 22 fire-rated constructions only (not applicable to
EN 1364-1)
Stud Boarding 600mm 600mm 400mm 400mm 300mm 300mm
each side centres boxed centres boxed centres boxed
92 S 60 1 x 12.5mm 4700 5000 5200 5600 5600 6100
1 x 15mm 4900 5300 5400 5800 5800 6300
2 x 12.5mm 5800 6000 6100 6500 6500 6900
2 x 15mm 6000 6200 6300 6700 6600 7000
92 AS 50 1 x 12.5mm 4700 5100 5200 5700 5700 6200
Partitions
1 x 15mm 4900 5300 5400 5700 5800 6400
2 x 12.5mm 5800 6100 6200 6500 6500 6900
2 x 15mm 6000 6300 6400 6700 6700 7000
92 S 10 1 x 12.5mm 5300 5800 6000 6600 6500 7200
1 x 15mm 5500 6000 6100 6700 6600 7300
C04
2 x 12.5mm 6200 6600 6700 7200 7200 7700
2 x 15mm 6400 6800 6900 7400 7300 7800
92 I 90 1 x 12.5mm 6000 - 6800 - 7400 -
1 x 15mm 6200 - 6900 - 7500 -
2 x 12.5mm 6800 - 7400 - 7900 -
2 x 15mm 6900 - 7500 - 8000 -
146 S 50 1 x 12.5mm 6200 6800 6900 7600 7500 8300
1 x 15mm 6500 7000 7200 7800 7700 8400
2 x 12.5mm 7600 8000 8100 8600 8500 9100
2 x 15mm 7900 8200 8300 8800 8700 9300
146 AS 50 1 x 12.5mm 6600 7100 7300 8000 8000 8800
1 x 15mm 6800 7400 7600 8200 8200 8900
2 x 12.5mm 7800 8200 8400 8900 8900 9500
2 x 15mm 8100 8500 8600 9100 9100 9700
146 I 80 1 x 12.5mm 7900 - 8900 - 9700 -
1 x 15mm 8100 - 9000 - 9800 -
2 x 12.5mm 8800 - 9600 - 10400 -
2 x 15mm 9000 - 9800 - 10500 -
146 TI 90 1 x 12.5mm 8300 - 9400 - 10300 -
1 x 15mm 8400 - 9500 - 10400 -
2 x 12.5mm 9200 - 10100 - 10900 -
2 x 15mm 9400 - 10300 - 11100 -
In all GypWall classic systems, it is recommended that for heights between 4200mm and 8000mm, the Gypframe Deep Flange Floor & Ceiling Channel is
used. Gypframe Extra Deep Flange Floor & Ceiling Channel is used for heights above 8000mm. Additional consideration needs to be given if there is a deflection
head requirement.
To be read in conjunction with system specific details. Refer to relevant system sections
1 1a
1
3
5
5
Partitions
300mm
2
600mm
600mm
600mm
C04
2
300mm
6
7
2 2a
Centres
at 600mm
Centres
at
thereafter
600mm
thereafter
1479mm
1479mm
50mm
50mm
50mm
38mm
30mm
38mm
879mm
879mm
279mm
279mm
Service cut-outs - Gypframe ‘C’ and Gypframe ‘I’ Studs Service cut-outs - Gypframe AcouStuds
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
3 3a
Partitions
11
4
3 6
3
1
C04
2 7
6
4
10
Head and base Junction with masonry and stop end detail
To be read in conjunction with system specific details. Refer to relevant system sections
5 6
2 1
3
Partitions
7a 7b
2 2
1
1
4
3
3
‘T’ junction to optimise acoustic performance and reduce ‘T’ junction to optimise acoustic performance and reduce
flanking transmission flanking transmission
8 9
2 1
1
5
2
3
1 Gyproc plasterboard or Glasroc F specialist board 4 Gypframe GA5 Internal Fixing Angle
2 Gypframe 'C' Stud 5 Gypframe GA6 Splayed Angle
3 Isover insulation
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
10 11
1
1
2
2
Partitions
Corner detail - single layer Corner detail - double layer
C04
12 13
16
mm
12 12
mm mm
2
3
1
1
4
14
Installing the screw into the side of the Gypframe Service Support Plate and the web of the Gypframe 'C' Stud will avoid creating excessive distortion to
the lining board.
To be read in conjunction with system specific details. Refer to relevant system sections
15
15mm 7 16 15mm 7
15mm 6 15mm 6
4 4
20mm 15mm 10
3
11
2
1 2
1
Partitions
Deflection head for 15mm downward movement Deflection head for 15mm downward movement
and 60 minutes fire resistance and up to 120 minutes fire resistance
Not suitable for 60 minutes single layer systems on 48mm studs to Not suitable for 48mm studs to BS EN 1364-1
C04
BS EN 1364-1
17 7 18
7
25mm 50mm
8 8
7
25mm 7 50mm
5 5
55mm
30mm
3
3
2
2
1
1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance and 60 minutes fire resistance
19 20 7
7
25mm 9
50mm
9
7
25mm 7
50mm
5 5
30mm
3 55mm
3
2 2
1 1
Deflection head for plus or minus 25mm movement Deflection head for 50mm downward movement
and 60 minutes fire resistance and 60 minutes fire resistance
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap (or stud nogging in construction detail 16). Continuous Gyproc FireStrip must be installed as shown to
maintain fire performance. Where there is a need for a deflection head in a 90 minute wall, the 120 minute solution can be used (refer to construction detail 16)
or alternatively, please contact the British Gypsum Technical Advice Centre for further guidance.
To minimise loss in acoustic performance refer to C02 S01 P10 Acoustic performance of head details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
21 2 22
5 7
2
9
5
8
15mm 6 15mm 6
15mm 15mm
3 3
15mm 10
15mm
Partitions
10
4
4
C04
1
1
Deflection head parallel to floor profile for 15mm downward Deflection head perpendicular to floor profile for 15mm downward
movement and up to 60 minutes fire resistance 1 movement and up to 60 minutes fire resistance
Not suitable for 60 minutes single layer systems on 48mm studs to Not suitable for 60 minutes single layer systems on 48mm studs to
BS EN 1364-1 BS EN 1364-1
23 24
12 12
13 13
1
1
4
4
11 11
14
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board fixing,
which should be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown to maintain fire performance.
1
To minimise acoustic downgrade, install Isover insulation within the hollow rib void.
To be read in conjunction with system specific details. Refer to relevant system sections
25
Partitions
150mm
4
C04
1200mm 1200mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Light and Medium Duty (up to 35kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel 7 Timber sub-frame
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
26
150mm
Partitions
4
C04
3
2
300mm
1200mm 1200mm
150mm
Door frame (maximum 1200mm width) to satisfy BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 5 Timber door frame and architrave
2 Gypframe 'C' Stud 6 Gypframe 'C' Stud to maintain stud module
3 Gypframe Floor & Ceiling Channel to sleeve studs 7 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws. The
studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
To be read in conjunction with system specific details. Refer to relevant system sections
27
8
7
Partitions
150mm
4
C04
2
300mm
150mm
Alternative door frame for fixed partition heads only (maximum 1200mm width) to satisfy
BS 5234: Parts 1 & 2: 1992 - Heavy and Severe Duty (up to 60kg door)
1 Gyproc plasterboard or Glasroc F specialist board 6 Gypframe 'C' Stud to maintain stud module
2 Gypframe 'C' Stud 7 Gypframe 'C' Studs fixed back to back with
British Gypsum Drywall Screws at 300mm centres staggered
3 Gypframe Floor & Ceiling Channel to sleeve studs
8 Plasterboard infill (same type as lining) cut to fit between studs
4 Gypframe Floor & Ceiling Channel cut and bent to form door head
9 Gypframe Floor & Ceiling Channel cut and bent to extend up studs
5 Timber door frame and architrave
Advice should be sought from the door manufacturer prior to the construction of these details.
At the base, the channel is cut and bent to extend 300mm up the studs and fixed each side with two British Gypsum Wafer Head Drywall Screws.
The studs each side of the opening are sleeved full height of opening with Gypframe Floor & Ceiling Channel.
The principle of this alternative detail is only suitable for GypWall classic, GypWall robust and GypWall extreme for fixed head situations only.
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
28
3
1
Partitions
150mm
4
C04
5
150mm
Openings 1201 - 3300mm wide, for example double doors or large windows
1 Gypframe 'C' Stud 6 Centre stud required for margin up to 600mm between openings
2 Stud sleeved to full opening height with Gypframe Floor & Ceiling Channel 7 Partition between openings, minimum 600mm for Gypframe 'C' Studs
3 Gypframe studs (appropriate to system) (minimum 300mm for Gypframe 'I' Studs)
4 Gypframe Extra Deep Flange Floor & Ceiling Channel 8 Maximum distance 2400mm (if exceeds 2400mm contact British Gypsum
Technical Advice Centre)
5 Gypframe stud insert
To be read in conjunction with system specific details. Refer to relevant system sections
29 30
Elevation
4
X
Y
Partitions
2
C04
2
Section X - X
1
Fire tested construction in which the damper is supported
3 by the partition (isometric view)
4 31
150mm
6
Section Y - Y
Opening for service penetrations in fire-rated partitions Opening up to 600mm wide for services
1 Gyproc plasterboard or Glasroc F specialist board 5 Damper (by others). Weight of damper should not exceed 57kg.
2 Gypframe 'C' Stud Size of damper should not exceed 1400 x 1200mm
3 Gypframe Floor & Ceiling Channel 6 Gypframe Folded Edge Standard Floor & Ceiling Channel cut and bent
to form opening head and cill
4 Penetration seal if required (refer to damper manufacturer for details)
Introduction
To be read in conjunction with system specific details. Refer to relevant system sections
32
Partitions
5
C04
2
33 34
2 6
7 7
Horizontal board joint - double layer Horizontal board joint - single layer
1 Inner layer of Gyproc plasterboard or Glasroc F specialist board 5 British Gypsum Drywall Screws
2 Outer layer of Gyproc plasterboard or Glasroc F specialist board 6 Gyproc plasterboard or Glasroc F specialist board
3 Gypframe GFS1 Fixing Strap 7 Gypframe 'C' Stud
4 Gypframe metal framing 8 Gypframe GFT1 Fixing T (alternatively use Gypframe GSF1 Fixing Strap)
GypWall quiet sf
Single frame acoustic separating wall system
Partitions
This makes it the ideal solution for a wide
range of buildings where it is important System can be skim
finished with
ThistlePro PureFinish.
to provide occupants with a comfortable
C04
Refer to C02. S01. P49
Key benefits
— Very efficient use of floor space due to a high
level of acoustic performance being achieved
with a minimal partition width
— Reduced sound transmission is achieved
through the use of Gypframe RB1 Resilient Bar
to provide a high degree of isolation between
the Gypframe 'C' Studs and the high
performance Gyproc plasterboard lining
— Additional acoustic performance can be
achieved with the application of
Thistle MultiFinish plaster skim on selected
specifications
1 2 3
Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’
Studs at 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1
Partitions
Resilient Bar at 600mm centres to one side. 50mm Resilient Bar at 600mm centres to both sides. Resilient Bar at 600mm centres to one side. 50mm
Isover Acoustic Partition Roll (APR 1200) 50mm Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board type1 Lining Stud Max. Sound insulation Duty Approx. System reference
thickness thickness size partition Rw (Rw + Ctr) dB5 rating weight
mm mm mm height2 kg/m²
mm Any3 Skim4 Any3 Skim4
finish only finish only
1 223 Gyproc SoundBloc 2 x 15 146 5000 62 (57) 63 (57) Severe 51 A316017 A316017S
Gyproc FireLine + 1 x 15 +
1 147 70 4000 61 (53) 62 (53) Severe 53 Q606040 Q606040S
Gyproc DuraLine 1 x 15
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer can be replaced with a layer of 15mm Gyproc DuraLine.
3
The maximum heights quoted are limited by the fire state field of application or by limiting deflection of L/240 at 200 Pa, whichever is the more onerous.
3
Sound insulation performance for partitions finished using jointing or plaster skim.
4
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
5
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
GypWall quiet sf
For details of when
to specify fire
70mm, 92mm and 146mm Gypframe ‘C’ Stud resistance using BS
Refer to C02. S01. P05
Table 1b — Solutions to satisfy requirements of BS 476: Part 22: 1987
1 2 3
Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’ Two layers of board each side of Gypframe ‘C’
Studs at 600mm centres with Gypframe RB1 Studsat 600mm centres with Gypframe RB1 Studs at 600mm centres with Gypframe RB1
Partitions
Resilient Bar at 600mm centres to one side. 50mm Resilient Bar at 600mm centres to both sides. Resilient Bar at 600mm centres to one side. 50mm
Isover Acoustic Partition Roll (APR 1200) 50mm Isover Acoustic Partition Roll (APR 1200) Isover Acoustic Partition Roll (APR 1200)
in the cavity. Linings as in table. in the cavity. Linings as in table. in the cavity. Linings as in table.
C04
Detail Partition Board type1 Lining Stud Max. Sound insulation Duty Approx. System reference
thickness thickness size partition Rw (Rw + Ctr) dB5 rating weight
mm mm mm height2 kg/m²
mm Any3 Skim4 Any3 Skim4
finish only finish only
1 223 Gyproc SoundBloc 2 x 15 146 6900 62 (57) 63 (57) Severe 51 A316017 A316017S
Gyproc FireLine + 1 x 15 +
1 147 70 4200 61 (53) 62 (53) Severe 53 Q606040 Q606040S
Gyproc DuraLine 1 x 15
For further assistance in choosing the right solution for your project, try the White Book System Selector; an online tool that enables quick and
easy filtering by performance criteria. It provides system specific information downloads including BIM (Revit) objects. Go to british-gypsum.com
1
For improved durability and impact resistance, the outer layer can be replaced with a layer of 15mm Gyproc DuraLine.
2
Based on a limiting deflection of L/240 at 200 Pa. For increased heights Gypframe 'I' Studs could be used (Refer to table 2 within this section)
3
Sound insulation performance for partitions finished using jointing or plaster skim.
4
Sound insulation performance for partitions finished with a 2mm skim finish of Thistle MultiFinish.
5
These British Gypsum Approved Systems are designed to achieve minimum DnT,w + Ctr 45dB, subject to Pre-Completion Testing
(Refer to Partitions introduction C04. S01. P04 – table 1)
For heights above 4200mm Gypframe Deep Flange Floor & Ceiling Channel should be used at base and at head (subject to deflection criteria).
The fire resistance and sound insulation performances are for imperforate partitions, walls and ceilings incorporating boards with all joints taped and
filled, or skimmed according to British Gypsum’s recommendations. The quoted performances are achieved only if British Gypsum and Saint-Gobain Isover
components are used throughout, and the Company’s fixing recommendations are strictly observed. Any variation in the specifications should be checked with
British Gypsum.
Studs at 600mm 2 x 12.5mm board, 2 x 15mm board, 19mm + 12.5mm board, Gypframe RB1 Resilient Bar
centres Gypframe RB1 Resilient Bar Gypframe RB1 Resilient Bar Gypframe RB1 Resilient Bar both sides
to one side to one side to one side
1
The above have not been subjected to acoustic tests and therefore any sound insulation performances are opinion only.
For heights between 4200mm and 8000mm Gypframe Deep Flange Floor & Ceiling Channel should be used.
Partitions
C04
GypWall quiet sf
Building design Door openings
GypWall quiet sf comprises Gypframe 'C' Studs installed at Any openings will require very careful detailing to minimise the
600mm centres within Gypframe Floor & Ceiling Channels and loss of acoustic performance of the partition. Consult with an
Gypframe RB1 Resilient Bars horizontally fixed to one or both sides. Acoustic Consultant. Specialist heavy acoustic doorsets may require
additional support.
Planning – key factors
Refer to construction detail 8 within this section.
The position of services and heavy fixtures should be
pre-determined and their installation planned into the frame Framing surround for openings
erection stage. Timber sole plates should be considered where
Where services such as horizontal ducts, fire dampers and access
the floor is uneven. All penetrations will need to be adequately
panels are required to penetrate the wall, their position should be
fire-stopped.
pre-determined in order that a framed opening can be provided.
Partitions
The openings should be constructed using established metal stud
procedures.
Handy hint
Refer to Partitions introduction C04. S01. P16 – construction
details 28-31.
Be aware that if working to centre lines on a
C04
plan, GypWall quiet sf systems incorporating
Cavity barriers
Gypframe RB1 Resilient Bar to one side only
are not symmetrical. Stone mineral wool (by others) cut neatly to fit across the cavity
forms a suitable closure.
If the concrete or screeded floor is new, consideration should be For optimum performance all air paths should be sealed.
given to the installation of a damp-proof membrane between the Gyproc Sealant should be applied to the perimeter of the inner layer
floor surface and the channel or sole plate. immediately prior to fitting the face layer board on the side(s) of the
partition where resilient bars are located.
Penetrations
Partition to structural steelwork junctions
Penetrations of fire-resistant or sound-insulating constructions
When designing the layout of rooms requiring separation by sound
for services need careful consideration to ensure that the
insulating walls abutting structural steelwork, consideration should
performance of the element is not downgraded. Consideration also
be given to the potential loss of sound insulation performance
needs to be given to the services themselves so they do not act as
through the steelwork.
the mechanism of fire spread or sound transmission.
If you require a wider partition to fully encompass structural steel, Refer to C02. S01. P32 – Service installations.
refer to GypWall quiet or GypWall quiet iwl.
Electrical Fixtures
The installation of electrical services should be carried out in
Lightweight fixtures can be made directly to the partitions.
accordance with BS 7671. The cut-outs in the studs can be used
Medium weight fixtures can be made to Gypframe 99 FC 50 Fixing
for routing electrical and other small services (refer to Partitions
Channel. Heavyweight fixtures (to BS 5234), such as wash basins
introduction C04. S01. P07 – construction detail 2). Switch boxes
and wall cupboards, can be fixed using plywood secured with a
and socket outlets can be supported from Gypframe 99 FC 50 Fixing
Gypframe Service Support Plates. In all instances the
Channel fixed horizontally between studs, or a high performance
Gypframe Service Support Plates are fixed to the side without a
socket box detail used where higher acoustic performance is
Gypframe RB1 Resilient Bar.
required.
Medium and heavy weight fixtures can only be made when the
Where Gypframe AcouStuds are used, services are routed through
lining boards are fixed directly to the stud framing. The installation
50mm x 28mm ‘H’ shaped push-outs, at the same centres as shown
of fixings may downgrade the acoustic performance of the wall,
Partitions
the same end of each stud to ensure cut-out alignment. of a partition, consider using GypWall quiet or GypWall quiet iwl.
SpecSure®
All our systems are covered by SpecSure® when
using genuine British Gypsum and Saint-Gobain
Isover products.
GypWall quiet sf
1 2
5
6
6
2
Partitions
3
10
11
C04
15
1
3
Junction with masonry
4 3
17
2
14
12
6
15mm
13
15mm
9 20mm
8 16
4
7 1
6 2
3
5
No fixings should be made through the boards into the flanges of the head channel. The arrow ( ) denotes the position of the uppermost board
fixing, which should be made into Gypframe GFS1 Fixing Strap. Continuous Gyproc FireStrip must be installed as shown to maintain fire performance.
4 5
3
3
2 2
1
1
Partitions
5
4
C04
5 4
Corner - resilient bar to external corner Corner - resilient bar to internal corner
6 7
3 3
2 2
1 1
6 6
4 4
5 5
‘T’ junction (resilient bar on opposite side) ‘T’ junction (resilient bar on abutment side)
Guidance must be sought from the relevant approval authority e.g. Building Control to establish if a cavity barrier is required (Approved Document B)
150mm
Partitions
4
C04
8
7
2
300mm
10
1200mm 1200mm
11
150mm
Door frame to satisfy BS 5234: Parts 1 and 2: 1992 - Heavy and Severe Duty (up to 60kg door)
Advice should be sought from the door manufacturer prior to the construction of these details.
Gypframe ‘C’ Studs (70 S 50, 92 S 50, 146 S 50) Gypframe 99 FC 50 Fixing Channel
Vertical stud providing acoustic and structural A versatile metal fixing channel used to support
performances designed to receive fixing of board medium weight fixtures on walls.
after installation of Gypframe RB1 Resilient Bars.
Gypframe Folded Edge Standard Floor & Ceiling Gypframe GFS1 Fixing Strap
Channels (72 FEC 50, 94 FEC 50, 148 FEC 50) Used to support horizontal board joints and within
Standard floor and ceiling channels for retaining the deflection head.
Gypframe studs at floor and ceiling junctions and
Partitions
Gypframe Deep Flange Floor & Ceiling Channels Gypframe GFT1 Fixing T
(72 DC 60, 94 DC 60, 148 DC 60) Used to support horizontal board joints.
C04
Gypframe Extra Deep Flange Floor & Ceiling Gypframe RB1 Resilient Bar
Channels (72 EDC 80, 94 EDC 70, 148 EDC 80) Acoustically engineered channel to separate board
Floor and ceiling channels with extra deep flanges fixing from the primary frame. Fixed horizontally to
for retaining the Gypframe studs at floor and ceiling face of studs.
junctions for partitions over 8000mm high. Also used
around openings and in deflection heads (maximum
50mm deflection).
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
Glasroc F firecase
Non-combustible glass-reinforced gypsum board.
Used to form deflection head.
Partitions
1
Also available in a Moisture Resistant (mr) version. mr boards are specified in intermittent wet use areas.
C04
British Gypsum Drywall Screws British Gypsum Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws
for fixing board to metal framing less than for fixing board to metal framing 0.8mm thick and
0.8mm thick ('I' studs less than 0.6mm thick). greater (‘I’ studs 0.6mm thick and greater).
British Gypsum Collated Drywall Screws British Gypsum Wafer Head Jack-Point Screws
Corrosion resistant self-tapping steel screws Corrosion resistant self-tapping steel screws for
for fixing board to metal framing less than fixing metal to metal framing 0.8mm thick and
0.8mm thick ('I' studs less than 0.6mm thick). greater ('I' studs 0.6mm thick and greater).
GypWall quiet sf
This is intended to be a basic description of how the system is built.
For detailed installation guidance refer to the British Gypsum Site Book.
Partitions
Gypframe Floor & Ceiling channels are Gypframe 'C' Studs are suitably fixed to The perimeter of the partition is then
suitably fixed to the floor and soffit. abutments and door openings. sealed with Gyproc Sealant except where
Gypframe RB1 Resilent Bars are to be
If you are using Gypframe RB1 Resilient Bars Ensure Gyproc CoreBoard to the deflection installed on that side. Where Gypframe RB1
C04
on one side of the partition only, the dimensions head takes into account the width of the
Resilient Bars are to be installed, the
will be offset by 16mm. This needs to be Gypframe RB1 Resilent Bars.
Gyproc Sealant is applied to the perimeter
considered when detailing to show locations of
partition layouts. of the first layer of board.
Gypframe 'C' Studs are fitted vertically to a Gypframe RB1 Resilient Bars are fixed Gypframe RB1 Resilient Bars are installed
friction-fit within the channel sections, to transverse to the stud framing. vertically to abutment and door studs to
form the framework. Studs are fitted to all Gypframe RB1 Resilient Bars are joined by accept perimeter fixings for the Gyproc
face the same way. nesting them together over a Gypframe plasterboard linings.
‘C’ Stud using British Gypsum Wafer Head
Drywall Screws. Gypframe RB1 Resilient
Bars are normally fixed with the base flange
on the top side, with the exception of the
uppermost bar, which is fixed base flange
down to provide board fixing at the head.
Isover Acoustic Partition Roll (APR 1200) Gyproc plasterboards are fixed with To maintain acoustic performance care
insulation is added to the partition cavity British Gypsum Drywall Screws to the must be taken to select the correct length
for optimal acoustic performance. Gypframe RB1 Resilient Bars with all joints screws to avoid them contacting or penetrating
the Gypframe 'C' Studs when fixing Gyproc
staggered. Where Gyproc Plank is required plasterboards to Gypframe RB1 Resilient Bar.
as an inner layer, it is fixed horizontally to
the Gypframe RB1 Resilient Bars at each
bar position.