TO FIND DUCT DIAMETER AND TO FIND DUCT DIAMETER TO FIND DUCT VELOCITY AND

FRICTION LOSS AND DUCT VELOCITY FRICTION LOSS

Enter Velocity, Air Flow & Length Enter Friction Loss, Airflow & Length Enter Friction Loss, Airflow & Length
Available Pressure - (Inches
Duct Velocity (FPM) 3,544 W.C.) 0.23 Duct Diameter Round (inches) 12

Duct Airflow (CFM) 1,129 Duct Airflow (CFM) 1,000 Duct Airflow (CFM) 1,000

Duct Length (Feet) 53 Duct Length (Feet) 100 Duct Length (Feet) 100

Enter Number of Bends Enter Number of Bends Enter Number of Bends


45º Bends (QTY) 0 45º Bends (QTY) 0 45º Bends (QTY) 0

90º Bends (QTY) 0 90º Bends (QTY) 0 90º Bends (QTY) 0

180º Offset (QTY) 0 180º Offset (QTY) 0 180º Offset (QTY) 0

Results Results Results


Duct Diameter (in) 7.6 Duct Diameter (in) 11.8 Duct Velocity (FPM) 1,274

Friction Loss - (Inches W.C.) 1.62 Duct Velocity (FPM) 1,317 Friction Loss - (Inches W.C.) 0.22

TO FIND AIR MIXTURE TO FIND EQUIVALENT TO FIND EQUIVALENT


RECTANGULAR DUCT ROUND DUCT

Enter Diameter Enter Height


First Airstream Round Duct Diameter (in) 12 Rectangular Duct Height (in) 8
0 CFM 0
0.0 Temp, deg. F 0.0 Enter Desired Height Enter Width
0.0 Humidity, Gr/Lb 0.0 Rectangular Duct Height (in) 8 Rectangular Duct Width (in) 16

Second Airstream Results rounded to nearest inch Results rounded to nearest inch
0 CFM 0 Rectangular Duct Width (in) 14 Round Duct Diameter (in) 13
0.0 Temp, deg. F 0.0
0.0 Humidity, Gr/Lb 0.0 APPROXIMATE DYNAMIC MAXIMUM RECOMMENDED
LOSS COEFFICIENTS SUPPLY VELOCITY
Mixture Results Main Duct Branch
0 CFM 0
0.0 Temp, deg. F 0.0 Residential 900 fpm 600 fpm
0.0 Humidity, Gr/Lb 0.0
Commericial 1,300 fpm 900 fpm

Industrial 1,800 fpm 1,000 fpm

® and ™ Trademarks of Bry-Air (Asia) Pvt. Ltd.

ALL INFORMATION ON THIS PAGE SHOULD BE VERIFIED BY A PROFESSIONAL


ENGINEER AND IS PROVIDED FOR INFORMATIONAL USE ONLY
Creat By: Suraj D. Shinde

Duct Velocity from hood to BF 18 m/sec


Duct velocity in BF 17
Duct velocity from BF to fan 16

TO FIND DUCT DIAMETER AND


FRICTION LOSS
Enter Velocity, Air Flow & Length

Duct Velocity (FPM) 3,543

Duct Airflow (CFM) 11,176

Duct Length (Feet) 82

Enter Number of Bends


45º Bends (QTY) 1

90º Bends (QTY) 1

180º Offset (QTY) 0

Results
Duct Diameter (in) 24.1

Duct Diameter ( mm) 612.14

Friction Loss - (mm W.C.) 17.88


TO FIND AIR MIXTURE

First Airstream
0 CFM 0
0.0 Temp, deg. F 0.0
0.0 Humidity, Gr/Lb 0.0

Second Airstream
0 CFM 0
0.0 Temp, deg. F 0.0
0.0 Humidity, Gr/Lb 0.0

Mixture Results
0 CFM 0
0.0 Temp, deg. F 0.0
0.0 Humidity, Gr/Lb 0.0
Volume Flow Rate 19000 m/hr
Duct Length 25 m

TO FIND DUCT DIAMETER


AND DUCT VELOCITY
Enter Friction Loss, Airflow & Length Enter Friction Loss, Airflow &

Available Pressure - (Inches W.C.) 1.61

Duct Airflow (CFM) 1,129

Duct Length (Feet) 53

Enter Number of Bends Enter Number of Bends


45º Bends (QTY) 0

90º Bends (QTY) 0

180º Offset (QTY) 0

Results Results
Duct Diameter (in) 7.6

Duct Velocity (FPM) 3,586


TO FIND EQUIVALENT
RECTANGULAR DUCT
Enter Diameter Enter Height
Round Duct Diameter (in) 12

Enter Desired Height Enter Width


Rectangular Duct Height (in) 8

Results rounded to nearest inch Results


Rectangular Duct Width (in) 14
TO FIND DUCT VELOCITY AND
FRICTION LOSS
Enter Friction Loss, Airflow & Length

Duct Diameter Round (inches) 12

Duct Airflow (CFM) 1,000

Duct Length (Feet) 100

Enter Number of Bends


45º Bends (QTY) 0

90º Bends (QTY) 0

180º Offset (QTY) 0

Duct Velocity (FPM) 1,274

Friction Loss - (Inches W.C.) 0.22


TO FIND EQUIVALENT
ROUND DUCT
Enter Height
Rectangular Duct Height (in) 8

Enter Width
Rectangular Duct Width (in) 16

rounded to nearest inch


Round Duct Diameter (in) 13
Dyanamic Loss Coeff.