AFAM – RIVERS STATE GOVERNMENT

OCGT POWER PLANT


Job Number UNIT
032083 95

SPEC N. 95-PA-E-98615
INSTRUMENT LIST
Sh. 1 of 2 Rev. 00

EMERGENCY DIESEL GENERATOR


ITEM: 95-EDG-007

INSTRUMENT LIST

ORDER N.: 515956 DATE 21.05.2010

00 Issued for construction C.Brambilla C.Zamproni C.Zamproni 11.10..2010


OB Added water presence alarm inside fuel C.Brambilla C.Zamproni C.Zamproni 30.09.2010
0A First issue C.Brambilla C.Zamproni C.Zamproni 26.07.2010
Rev. Description Prepared Checked Approved Date
Description TAG Mfr Model Range Alarm Trip
Set point set point
Cooling water temperature transmitter, engine outlet TT101 PERKINS EMC-ADEM4 0-200°C - -
Cooling water temperature indicator TI101 SICES DST4601 0-999°C
Cooling water temperature high switch TSH100 PERKINS EMC-ADEM4 Fixed point 99°C -
Cooling water temperature high alarm TAH100 SICES DST4601 0-999°C 99°C
Cooling water temperature high high switch TSHH100 PERKINS EMC-ADEM4 Fixed point - 107°C
Cooling water temperature high high alarm TAHH100 SICES DST4601 0-999°C - 107°C
Cooling water level switch low TSL102 PERKINS EMC-ADEM4 Fixed point 80% -
Lube oil pressure transmitter PT100 PERKINS EMC-ADEM4 0-10bar - -
Lube oil pressure indicator PI100 SICES DST4601 0-999bar - -
Lube oil pressure low switch PSL100 PERKINS EMC-ADEM4 Fixed point - 2,6
Lube oil pressure low alarm PAL100 SICES DST4601 0-999bar - 2,6
Fuel oil level low switch LSL101 VALCO M2B2021850 Fixed point 30% -
Fuel oil level low alarm LAL101 SICES DST4601 - 30% -
Fuel oil level high switch LSH101 VALCO M2B2021850 Fixed point 102% -
Fuel oil level high alarma LAH101 SICES DST4601 Fixed point 102% -
Lube oil level low switch LSL200 Murphy L129CK1 0-100% 80% -
Lube oil level low alarm LAL200 SICES DST4601 - 80% -
Engine overspeed - PERKINS EMC-ADEM4 Fixed point - 110%
Water presence in the fuel LSH102 RACOR 751000FHVP30 Fixed point ON