You are on page 1of 1

CHECK LIST: PIKO INVERTERS

Customer: Installer:
Address: Address:
Postal code: Postal code:
Town: Town:
Phone: Phone:

PIKO INVERTER
Serial No: Model:
Installation date: Country settings or Standard:
CHECK LIST RANGE/UNIT READING COMMENTS
Ambient temperature °C
Wall mount stability OK /not OK
Free space for air circulation on the sides and top of the inverter see handbook
Installation place ventilated and protected from sun and rain see handbook
Polarity of the strings [Black=(-), Red=(+)] yes / no
Residual current circuit breaker installed in AC side mA
Magnetic circuit breaker (AC automatic fuse) see handbook
Lightning protection (DC side) yes / no
Lightning protection (AC side) yes / no
Check of documentation availability (handbook...) yes / no
CONNECTIONS
Earth continuity between main grounded terminal and the body of the inverter (Ohmmeter) Ohms

Supply AC voltage: □230 - 1N - 50Hz; □400-3N-50Hz; □Other voltage _________


Supply DC voltage: □String 1 _______ □String 2 _______ □String 3 _______ 180V - 950V

String 1 panels (Brand_____________ Model____________ pcs________ ) orientation / inclination


String 2 panels (Brand_____________ Model____________ pcs________ ) orientation / inclination
String 3 panels (Brand_____________ Model____________ pcs________ ) orientation / inclination
Parallel connection between DC1 and DC2? yes / no

Communication status ( □DLS router; □GSM modem; □other_________; □No connection) yes / no
TESTING
Screws threads are clean (optical inspection / easy screwing and unscrewing) OK /not OK
Cover sealed normaly (optical inspection) OK /not OK
DC switch test (switching status and robustness) OK /not OK
All DC voltages between 180V - 950V (consider temperature - measure on inverter's DC terminals) OK /not OK
All external cable connection screws are tightened (Check AC/DC external connection boards) OK /not OK
AC voltage test: L1-N:_____; L2-N:_____; L3-N:_____; (inverter's AC terminal) OK /not OK
AC voltage test: L1-L2:_____; L1-L3:_____; L2-L3:_____; (inverter's DC terminal) OK /not OK
Insulation Resistance (Riso) in AC/DC harness is >1,5Mohms OK /not OK
Display lits by pressing any button OK /not OK
Feed in status achieved (Green LED is on, after country setting's mandatory "stand by" time) OK /not OK
Error codes on display Error code number
Correct functioning of the fans (fan test) OK /not OK
Communication connection test OK /not OK
Portal connection test OK /not OK
Training to end user OK /not OK
Comments (Non conformity/Suggestions):

Service Partner: Tel: Customer's name:


Tech. name: Tel: Customer's signature:
Tech. signature: Date: Position: