Type
6518
standard
• High flow-rate capacity
• Reduced power consumption
• Single or manifold mounting
Type 6519
standard • Standard-, Ex m and Ex i versions
• Threaded port G 1/4” or NAMUR flange
Type 6518/6519 can be combined with...
Type 2508 Type 1078 Type 2511/12 Type 8600 Type 2012 Type 2030
Cable plug Timer unit ASI cable plug Dosing control Single-seat Diaphragm valve
globe valve
I &URTHERôVERSIONSôONôREQUEST
Approvals
FM-Ex
EC Gas Appliances Directive www.burkert.com p. 1/18
6518/6519
Type 6518/6519 standard (with tag connector acc. to DIN EN 175301-803 Form A, without cable plug)
Technical data
Orifice DN 8.0 and 9.0 mm
Body materials
Type 6518
Pilot valve and main Polyamide, reinforced
valve Type 6519
Pilot valve Polyamide
Main valve 5/2-way; polyamide, 5/3-way; aluminium
Type 6518 Thread insert material Brass (stainless steel on request)
standard Type 6519 Seal materials NBR, NBR and PUR
standard
Pneumatic connection
Supply ports 1,3,5 Threaded port G 1/4, can also be flanged
Service ports 2 and 4 Threaded port G 1/4 (on request NPT 1/4)
Electrical connection Tag connector acc. to DIN EN 175301-803 Form A
Type 6518 and the Type 6519 together form a product
(previously DIN 43650)
line. Both types can be mounted on a pneumatic module.
Protection class IP65 with cable plug
The valve width of 32 mm allows high flow rates. Operating voltage 24 V/DC, 24/110/230 V, 50-60 Hz
A solenoid valve Type 6014 is used as a pilot.
Voltage tolerance ±10%
The valves can be used individually or in blocks. Power consumption coil 2 W (100% continuous rating)
Power consumption
Ambient temperature -25 to +55°C
Inrush Hold (hot coil) Media Lubricated or non-lubricated compressed air, neutral gases
AC [VA] AC [VA/W] DC [W] on request Technical vacuum
11 6/2 2 Environmental Open air, chemical atmosphere
conditions
1)
Response times
1)
Measured at valve outlet at 6 bar and +20°C acc. to ISO 12238.
Opening 20 [ms] Opening: Pressure rise 0 to 90%
Closing 40 [ms] Closing: Pressure drop 100 to 10%
Ordering chart valves with manual override (without manual override on request)
connection
air1) [l/min]
Weight [g]
power [W]
frequency
QNn value
threaded
Pressure
Voltage/
Nominal
function
material
Item no.
range2)
Orifice
Circuit
[V/Hz]
[mm]
body
[bar]
Seal
Port
port
Type 6518 standard – thread insert material brass, threaded port 1 and 3 can also be flanged; without cable plug (see Accessories p. 10)
C 2 8.0 NBR and G 1/4 1300 2-8 370 2 024/DC 132 457
12 10 PUR 024/50-60 132 458
1 3 (polyamide)
3/2-way valve, servo-assisted, in 110/50-60 132 459
de-energized position port 2 exhausted 230/50-60 132 460
D 2 8.0 NBR and G 1/4 1300 2-8 370 2 024/DC 132 461
12
10 PUR 024/50-60 132 462
1 3 (polyamide)
3/2-way valve, servo-assisted, in de- 110/50-60 132 463
energized position port 2 pressurized 230/50-60 132 464
Type 6519 standard – thread insert material brass, threaded port 1, 3 and 5 can also be flanged; without cable plug (see Accessories p. 10)
H 4(B) 2(A) 8.0 NBR and G 1/4 1300 2-8 450 2 024/DC 132 465
14
12 PUR
5(S) 3(R) 024/50-60 132 466
1(P)
(polyamide)
5/2-way valve, servo-assisted, in de- 110/50-60 132 467
energized position port 2 pressurized, 230/50-60 132 468
port 4 exhausted
L 4 2 9.0 NBR G 1/4 1300 3-10 720 2 024/DC 132 469
14 12 (aluminium) 024/50-60 132 470
5 3
1 110/50-60 132 471
5/3-way valve, servo-assisted, in middle
position all ports locked 230/50-60 132 472
N 4 2 9.0 NBR G 1/4 1300 3-10 720 2 024/DC 132 473
14 12 (aluminium) 024/50-60 132 474
5 3
1 110/50-60 132 475
5/3-way valve, servo-assisted, in middle
position ports 2 and 4 exhausted 230/50-60 132 476
1) Flow rate: QNn value air [l/min]: Measured at +20°C, 6 bar pressure at valve inlet, 1 bar pressure difference
2) Pressure values [bar]: Gauge pressures with respect to the prevailing atmospheric pressure
Manifold assembly see page 8 Accessories see page 10 Dimensions see page 11
p. 2/18
6518/6519
Technical data
Orifice DN 8.0 and 9.0 mm
Body materials
Type 6518
Pilot valve and main Polyamide, reinforced
valve Type 6519
Pilot valve Polyamide
Main valve 5/2-way; polyamide, 5/3-way; aluminium
Thread insert material Brass (stainless steel on request)
Seal materials NBR, NBR and PUR
Pneumatic connection
Supply ports 1,3,5 Threaded port G 1/4, can also be flanged
Type 6519 Ex m Service ports 2 and 4 Threaded port G 1/4 (on request NPT 1/4)
Type 6518 Ex m Electrical connection Moulded cable, 3 m (non-detachable),
Terminal box on request
Protection class IP65
The approval Ex m is achieved by the mounting of an Approval II 2G Ex m II T 5 PTB 00 ATEX 2129X
approved push-over coil. The cable connection and the II 2DIP 65T 100°C
cable are non-detachable and sealed together with the Operating voltage 24/110/230 V/UC
valve. The valves can be used individually or in blocks. Voltage tolerance ±10%
Power consumption coil 3 W (100% continuous rating)
1)
Response times
Opening 20 [ms] Ambient temperature -25 to +50°C
Closing 50 [ms] Media Lubricated or non-lubricated compressed air, neutral gases
on request technical vacuum
1)
Measured at valve outlet at 6 bar and +20°C acc. to ISO 12238.
Environmental conditions Open air, chemical atmosphere
Opening: Pressure rise 0 to 90%,
Closing: Pressure drop 100 to 10% For use in zone 1, 2, 21 and 22
Ordering chart valves with manual override (without manual override on request)
connection
Weight [g]
port [inch]
power [W]
frequency
QNn value
threaded
Pressure
Voltage/
Nominal
function
material
Item no.
air 1) [l/
range2)
Orifice
Circuit
[V/Hz]
[mm]
body
[bar]
Seal
min]
Port
Type 6518 Ex m – thread insert material brass, threaded port 1 and 3 can also be flanged; with moulded cable, 3 m long 3)
C 2 8.0 NBR G 1/4 1300 2-8 600 3 024/UC 134 716
12 10 and 110/UC 134 717
1 3 PUR
230/UC 134 718
3/2-way valve, servo-assisted, in (polyamide)
de-energized position port 2 exhausted
D 2 8.0 NBR G 1/4 1300 2-8 600 3 024/UC 134 719
12
10 and 110/UC 134 720
1 3 PUR
230/UC 134 721
3/2-way valve, servo-assisted, in de- (polyamide)
energized position port 2 pressurized
Type 6519 Ex m – thread insert material brass, threaded port 1, 3 and 5 can also be flanged; with moulded cable, 3 m long 4)
H 4(B) 2(A) 8.0 NBR G 1/4 1300 2-8 700 3 024/UC 134 722
14
12 and 110/UC 134 723
5(S) 3(R)
1(P) PUR
230/UC 134 724
5/2-way valve, servo-assisted, in de- (polyamide)
energized position port 2 pressurized,
port 4 exhausted
L 4 2 9.0 NBR G 1/4 1300 3-10 1,100 3 024/UC 134 725
14 12 (aluminium) 110/UC 134 726
5 3
1 230/UC 134 727
5/3-way valve, servo-assisted, in middle
position all ports locked
N 4 2 9.0 NBR G 1/4 1300 3-10 1,100 3 024/UC 134 728
14 12 (aluminium) 110/UC 134 729
5 3
1 230/UC 134 730
5/3-way valve, servo-assisted, in middle
position ports 2 and 4 exhausted
1) Flow rate: QNn value air [l/min]: Measured at +20°C, 6 bar pressure at valve inlet, 1 bar pressure difference 2) Pressure values [bar]: Gauge pressures with respect to the prevailing atmospheric pressure
3) Versions with terminal box on request 4) Circuit function H (5/2-way) as impulse version on request
Manifold assembly see page 8 Accessories see page 10 Dimensions see page 13
p. 3/18
6518/6519
Type 6518/6519 Ex i (with tag connector acc. to DIN EN 175301-803 Form A, without cable plug)
Technical data
Orifice DN 8.0 mm
Body materials
Pilot valve Stainless steel 1.4305 or brass
Main valve Polyamide, glass-fibre reinforced
Thread insert material Stainless steel or brass, nickel-plated
Seal materials FPM, NBR and PUR
Pneumatic connection
Supply ports 1,3,5 Threaded port G 1/4”
Service ports 2 and 4 Threaded port G 1/4”
Electrical connection Tag connector acc. to DIN EN 175301-803 Form A
Type 6518 Ex i (previously DIN 43650) for cable plug Type 2508 (not
Type 6519 Ex i included, see accessories). Ensure correct polarity!
Protection class IP65 with cable plug
Ambient temperature -25 to +55°C
The intrinsically-safe Type 6518 Ex i and 6519 Ex i valves Media Lubricated or non-lubricated compressed air,
consist of an intrinsically-safe pilot control and a pneumatic instrument air, nitrogen
amplifier. The diaphragm-controlled valve seats work with Environmental conditions Open air, chemical atmosphere
very low friction, ensuring reliable switching of the valve,
For use in zone 1, 2, 21 and 22
even after long shutdown periods.
1)
Response times
1)
Measured at valve outlet at 6 bar and +20°C acc. to ISO 12238.
Opening 75 [ms]
Opening: Pressure rise 0 to 90%,
Closing 115 [ms] Closing: Pressure drop 100 to 10%
Ordering chart valves without manual override (with manual override and high-impedance coil on request)
connection
QNn value
pilot valve
Weight [g]
port [inch]
threaded
Pressure
function
material
material
material
Item no.
Pilot air
range 2)
Orifice
Circuit
[l/min]
thread
insert
Body
[mm]
body
[bar]
Seal
air 1)
Port
WW C
ohne Handnotbetätigung
Type 6518 Ex i without cable plug (see accessories page10)
C 2 St. st. 145 111
NBR St. st.
12 10 brass, nickel
and 1.4305 144 486
1 3 8.0 G 1/4 1300 2-8 580 plated
PUR
3/2-way valve, servo-assisted, in de- (polyamide) brass, nickel
brass 147 253
energized position port 2 exhausted plated
Type 6519 Ex i without cable plug (see accessories page10)
H 4(B) 2(A)
14 St. st. 144 484
12 NBR St. st.
5(S) 3(R) 1.4305
1(P)
and brass, nickel
8.0 G 1/4 1300 2-8 670 144 485
5/2-way valve, servo-assisted, PUR plated
in de-energized position port 2 (polyamide) brass, nickel
pressurized, port 4 exhausted brass 147 252
plated
1) Flow rate: QNn value air [l/min]: Measured at +20°C, 6 bar pressure at valve inlet, 1 bar pressure difference
2) Pressure values [bar]: Gauge pressures with respect to the prevailing atmospheric pressure
p. 4/18
6518/6519
Type 6519 NAMUR standard (with tag connector acc. to DIN EN 175301-803 Form A, without cable plug)
Technical data
Orifice DN 6.0 mm
Body materials
Pilot valve and main valve Polyamide (PA)
Thread insert material Brass, nickel-plated or stainless steel
Seal material NBR and PUR
Pneumatic connection
Supply ports 1,3,5 Threaded port G 1/4”
Service ports 2 and 4 NAMUR flange
Electrical connection Tag connector acc. to DIN EN 175301-803 Form A
(previously DIN 43650)
Type 6519 NAMUR
Protection class IP65 with cable plug
Standard
Operating voltage 24/110/230 V/UC (direct or universal current)
Voltage tolerance ±10%
Duty cycle 100 % continuous rating
The valve bodies of Type 6519 NAMUR are identical
with the Ex m variants. The difference is in the coils, Ambient temperature -25 to +55°C
which are laid out and approved in different ways. By Media Compressed air, nitrogen, instrument air
changing the coil on the valve body, it is possible to Environmental conditions Slightly aggressive, also open air
easily convert from Non-Ex operation to Ex operation
(or vice versa). The coils are designed to be push-over Power consumption Response times 1)
Ordering chart valves with manual override (without manual override on request)
without cable plug (see accessories page10)
consumption
connection
Weight [g]
port [inch]
1)
frequency
QNn value
threaded
Pressure
Voltage/
function
material
material
Item no.
Thread
range3)
Orifice
Circuit
[l/min]
Power
[V/Hz]
insert
[mm]
body
[bar]
Seal
air 2)
Port
[W]
1) If the connectors are from stainless steel, the mounting screws will also be from stainless steel
2) Flow rate: QNn value air [l/min]: Measured at +20°C, 6 bar pressure at valve inlet, 1 bar pressure difference
3) Pressure values [bar]: Gauge pressures with respect to the prevailing atmospheric pressure
All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter
plate that comes with the valves, the change between the two circuit functions can be set up.
p. 5/18
6518/6519
Ordering chart valves with manual override (without manual override on request)
Thread insert
consumption
range 3) [bar]
Orifice [mm]
connection
QNn value
Weight [g]
port [inch]
material 1)
frequency
threaded
Pressure
Voltage/
function
material
Item no.
Circuit
[l/min]
Power
[V/Hz]
body
Seal
air 2)
Port
[W]
All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter plate that comes with the valves, the change between the
two circuit functions can be set up.
Type 6519 NAMUR Ex i (with tag connector acc. to DIN EN 175301-803 Form A, without cable plug)
Technical data
Orifice DN 6.0 mm
Body materials
Pilot valve Stainless steel 1.4305 or brass
Main valve Polyamide, glass-fibre reinforced
Thread insert material Stainless steel or brass, nickel-plated
Seal materials FPM, NBR and PUR
Pneumatic connection
Supply ports 1,3,5 Threaded port G 1/4”
Service ports 2 and 4 NAMUR flange acc. to VDI/VDE 3845
Electrical connection Tag connector acc. to DIN EN 175301-803 Form A
(previously DIN 43650) for cable plug Type 2508 (see
Type 6519 NAMUR Ex i Accessories). Ensure correct polarity!
Protection class IP65 with cable plug
Ambient temperature -25 to +55°C
The Type 6519 NAMUR Ex i valve is used for the pneumatic Media Lubricated or non-lubricated compressed air,
control of double or single-acting actuators with a NAMUR instrument air, nitrogen
adapter plate flange. The circuit function can easily be
Environmental conditions Open air, chemical atmosphere
changed using an adapter plate. In the 3/2-way function,
feedback of the exhaust air takes place in the spring area 1)
1)
Measured at valve outlet at 6 bar and +20°C acc. to ISO 12238.
Response times [ms]
of the armature drive. The diaphragm-controlled valve seats Opening: Pressure rise 0 to 90%,
work with very low friction, ensuring reliable switching of the Opening 75 Closing: Pressure drop 100 to 10%
valve even after long shutdown periods and at ambient tem- Closing 115
peratures below 0 °C. The valves work without a continuous
air consumption. Electrical data
Approval II 2G Ex ia IIC T6 PTB 01 ATEX 2101
Note
II 2D Ex ia D21 T 80°C
The units may only be used in explosive atmospheres in the
manner approved by the Federal Institute of Physics and Functional values for valve
Technology (PTB), i.e., the permissible maximum electrical switching function 1) at +20°C at +55°C
values must be complied with. Suitable barriers and isolat- Minimum switching current 29 mA 29 mA
ing modules are available for this. Nominal resistance of the coil 310 Ω 360 Ω
Barrier/ Minimum terminal voltage 9.0 V 10.4 V
PLC isolating Permissible maximum
component
values acc. to certificate
of conformity
The valve is intended for operation on 24 VDC outputs via Ui 35 V
the intermediate switching of a corresponding intrinsically- Ii 0.9 A
safe operating resource (isolating module or barrier). Pi 1.1 W
If required, request the “Recommended Barrier and Isolating 1)
With high-impedance coil on request
Module” data sheet.
Ordering chart valves without manual override (with manual override and high-impedance coil on request)
without cable plug (see accessories page10)
connection
air1) [l/min]
for control
pilot valve
Weight [g]
port [inch]
QNn value
threaded
Pressure
Material
function
material
material
Item no.
air bush
range2)
Orifice
Circuit
Body
[mm]
body
[bar]
Seal
Port
42
C
12 St. st. 144 482
315 St. st.
1.4305
3/2-way valve, with exhaust air return, in de- brass,
NBR 144 483
energized position port 2 exhausted internally nickel-plated
and
or 4(B) 2(A) 6.0 G 1/4 900 2-8 670
14
PUR
H 12 (polyamide)
5(S) 3(R)
1(P)
brass,
brass 147 244
5/2-way valve, servo-assisted, in de-ener- nickel-plated
gized position pressure port 1 connected to
port 2, port 4 exhausted
1) Flow rate: QNn value air [l/min]: Measured at +20°C, 6 bar pressure at valve inlet, 1 bar pressure difference
2) Pressure values [bar]: Gauge pressures with respect to the prevailing atmospheric pressure.
All valves can be operated in circuit function C as well as in circuit function H. By replacing the adapter plate that comes with the valves, the change
between the two circuit functions can be set up. All valves have mounting plates and tag connectors acc. to DIN EN 175301-803 Form A
(previously DIN 43650) and are supplied without cable plug (see Accessories p. 10)
Connector module,
Pneumatic basic Pneumatic intermediate supply module: supply channel pushed
left
module, 3 valves through for additional pressure supply
or
Connector module, right: supply channel closed off, thereby several
operational pressures possible in a single block
Pneumatic
basic module,
2 valves
Connector module,
right
Supply ports
3(R)
1(P)
p. 8/18
6518/6519
101.5
59 + (n x 33) 65
ø 5.5
35
15
3 3
182
1
102.5
115
124.8
120
249
108
24
58
100
92
82
57.5
48
5 5
G 1/2
10
G 1/8 6
33 NPT 1/2
NPT 1/8 8
G 1/4 55
NPT 1/4
46
n x 33 52
87 + (n x 33) 90
110 + (n x 33)
Valve assembly on pneumatic modules Type MP05 using the supplied M4 screws
p. 9/18
6518/6519
Accessories
Cable plug Type 2508 acc. to DIN EN 175301-803 Form A Fixing screw
The delivery of a cable plug includes the flat seal and the fixing screw. For other cable plug
versions acc. to DIN EN 175301-803 Form A (previously DIN 43650) with
integrated circuitry, see datasheet Type 2508. Flat seal
18 46
27,5
18
18
1,5
M3
28
p. 10/18
6518/6519
Dimensions [mm]
Standard versions
Type 6518
3/2-way valve, circuit function C and D
32
SW 14 45
G1/8 20.5
11.2
G1/4 / NPT1/4
8 - 4.3 deep
G1/4 / NPT1/4
138.7
4.3
69.6
4.3
13.5
12
28.5
25.5
25.5
8
3 43 24
3 - 3 tief
24 53
32
Type 6519
5/2-way valve, circuit function H
32
SW 14 45
G1/8 20.5
11.2
G1/4 / NPT1/4
G1/4 / NPT1/4
4.3
28.5
8 - 4.3 deep
4.3
107.7
36
24
48
26.5
39.6
3 - 3 deep
3 43 24
24 53
32
p. 11/18
6518/6519
Dimensions [mm]
Standard versions
Type 6519
5/3-way valve, circuit function L and N
32
SW 14 45
G1/8 20.5
11.2
G1/4 / NPT1/4
3 - 3 deep
G1/4 / NPT1/4
26 24
4.3
28.5
11 - 3 deep
43
36
250.2
112
24
70
4.5
26.5
50
44
32
p. 12/18
138.7
Type 6518
191.9
25.5 25.5
G1/4 / NPT 1/4 11.2
G1/4 / NPT1/4
Ex m/me versions
Dimensions [mm]
32
24
32
32
24
with terminal box (Ex me)
3
3
4.3
6518/6519
4.3
G1/8
7.9 - 4.2 deep
SW 14
13.5
with moulded cable, 3 m long (Ex m)
13.5
119.8
69.6
69.6 25.5
25.5 12
12
76
101.3
G1/8
53
43
53
43
4.3 10
8 - 4.3 deep 4.3
138.6 8 - 4.3 deep
28.5
8
28.5
8
24
24
60
3 - 3 deep G1/4 / NPT1/4
3 - 3 deep 67
G1/4 / NPT 1/4
p. 13/18
6518/6519
Dimensions [mm]
Ex m/me versions
Type 6519
5/2-way valve, circuit function H
32
SW 14 moulded cable
(Standard 3 m long)
G1/8 76
11.2
G1/4 / NPT1/4
G1/4 / NPT1/4
4.3
28.5
8 - 4.3 deep
107.7
4.3
36
24
48
26.5
39.6
3 - 3 deep
3 43 24
24 53
32
32
moulded cable
SW14 (Standard 3 m long)
G1/8 76
G1/4 / NPT 1/4 11.2
26 24
4.3
11 - 3 deep
28.5
43
250.2
36
112
24
70
48
26.5
4.5
50
44
32
p. 14/18
183.8
Type 6519
Type 6518
145,7
Ex i versions
24
G1/4 / NPT1/4 11.2 25,5
G1/4 / NPT1/4 11,2
Dimensions [mm]
40
32
24
32
24
40
3
3
3/2-way valve, circuit function C
4.3 4,3
G1/8
G1/8
SW 14
7,9 - 4,2 tief
SW 14
13,5
39.6 36
69,6
25,5
12
pp
51
53
43
23.5
51
53
43
4.3
23,5
8 - 4.3 deep
107.7 4,3
8 - 4,3 tief
26.5 28.5
28,5
8
24
24
p. 15/18
6518/6519
Dimensions [mm]
NAMUR standard version
Type 6519
3/2-way valve, circuit function C or 5/2-way valve, circuit function H
32
45
SW 14
20.5
G1/8
11.2
G1/4 / NPT1/4
176.8
5.3
107.7
48
24
51.6
51.6
32 3.95
37 32
53
p. 16/18
6518/6519
Dimensions [mm]
NAMUR Ex m/me-Ausführung
Type 6519
3/2-way valve, circuit function C or 5/2-way valve, circuit function H
32
Integrated cable
SW 14 (Standard 3 m long)
G1/8 76
11.2
G1/4 / NPT1/4
176.8
5.3
107.7
48
24
51.6
51.6
32 3.95
37 32
53
60 101.3
G1/8
119.8
10
67
G1/4 / NPT1/4
230
176.7
5.3
24
48
51.6
51.6
32 3.95
37 32
53
p. 17/18
6518/6519
Dimensions [mm]
NAMUR Ex i version
Type 6519
3/2-way valve, circuit function C or 5/2-way valve, circuit function H
40
SW 14 51
G1/8 23.5
11.2
G1/4 / NPT1/4
183.6
5.3
107.7
48
24
51.6
51.6
32 3.95
37 32
53
To find your nearest Bürkert facility, click on the orange box www.burkert.com
In case of special application conditions, We reserve the right to make technical changes without notice.
please consult for advice. © Christian Bürkert GmbH & Co. KG 1412/7_EU-en_00891764
p. 18/18