Professional Documents
Culture Documents
Part 5 - Two Approaches To Capacity Control - A7545
Part 5 - Two Approaches To Capacity Control - A7545
Energy efficiency
Two approaches to
capacity control
Pump capacity is mainly controlled by means of throttle valves
or by varying the rotational speed. In this fifth article in a
series on energy savings, Hans Vogelesang of PumpSupport
considers the advantages and disadvantages of both methods
and whether it is always useful to use speed regulation.
I
n the last article1 we saw that the 254 mm. With this pump, the design Throttle control
operational point is determined by the capacity at design speed lies exactly
With this method a control valve is placed in
intersection of the pump and piping at the optimal operational point with
the discharge line of the centrifugal pump,
(system) characteristic curves. During the the highest efficiency rate (BEP; best
which is opened to a greater or lesser degree
process the operational conditions vary and efficiency point). In pump performance
depending on the desired pump output.
the piping characteristic also changes (Q–H) graphs, such as those discussed in
accordingly. In practice the output of the later sections, the pump efficiency rate is Note that this is only applicable for centrif-
pump will change continuously during a always represented by means of lines of ugal pumps. Throttle control cannot be used
process without capacity control. equal efficiency. In this way the optimal with a positive-displacement pump!
efficiency rate within a given Q–H graph is
In many cases this is undesirable and with With a closed circuit, for instance a cooling
immediately recognizable.
many processes the capacity of the pump water system as shown in Figure 1, the
has to be controlled very accurately. Think It is important to note that when control- necessary differential head consists solely of
for instance of heating or cooling systems ling the capacity of pumps the output of friction losses. Because there is no stationary
where the required heat transfer has to be the pump should never be less than the differential head, the piping characteristic
adjusted depending on the need. Besides minimal flow as indicated by the manu- has its origin at 0 m3/h and 0 m and will
varying the temperature of the medium, facturer. The rule of thumb is 25% of the increase quadratically as capacity increases.
the amount of water passing through the optimal capacity (= Q at ηmax). If the throttle valve is fully open then,
system is often increased or decreased.
Expansion vessel
Capacity control
The capacity of centrifugal pumps is mainly
regulated in two different ways. Tradition-
ally, the best-known method is throttle
control, which is still often applied. With
this method a control valve is placed in the
discharge line. Circulation pump Throttle valve Cooler
The second method involves regulating
the pump speed, which is employed
increasingly since the introduction of
frequency converters. But this method
cannot be applied indiscriminately in
all cases. The examples discussed below
will illustrate this. In all cases the exam-
ples are based on a design capacity of
100%, and in all cases the same pump Return cooler
is used with an impeller diameter of Figure 1. Example of a closed circuit with only dynamic losses.
Head - m
will shift to the left, corresponding to a lower 12.5
flow rate. The amount of water circulating
10
through the system will decrease more and
more as the throttle valve is throttled more 7.5
and more. In this way the output of the Additional pressure drop
in control valve
centrifugal pump is always simply continu- 5
ously variable.
2.5
Figure 3. Example of an open system with both static differential head and dynamic losses.
Speed control
In the case of speed (frequency) regulation
22.5
254 mm 50 60
there is no throttle valve and the delivery 65
70 73
75
77 77.5
valves are always fully open. The pump’s 20
77 1450 rpm
speed is variable. Various speed-regulated 17.5
75
73
pump drives are available but in most cases
70
15
a frequency converter in the power supply
Head - m
www.worldpumps.com
28 Feature
WORLD PUMPS April 2009
7.5
With a control valve, satisfactory and easily
800 rpm
variable control of the output of a centrifugal
5
600 rpm
pump is obtained but a major disadvan-
2.5
tage of throttle control is the high energy
consumption. Because throttle control moves
0 20 40 60 80 100 120 140 the intersection and/or operational point to
m3/hr
Q = 50% Q = 100% the left along the pump characteristic when
Figure 5. Speed control: the capacity decreases as the rotational speed of the pump is reduced.
throttling, the efficiency of the pump at the
new operational point will always be lower
than at the optimal operational point (BEP).
This means that the internal losses increase at
the cost of extra energy loss; when throt-
6
tling the control valve, extra friction losses
254 mm 50 60 65
70 73 75 are deliberately generated within the system
5 77 77.5
77 720 rpm and extra friction loss also means extra loss
75
73 of energy.
4
70
Head - m
7.5 kW
12 times slightly adapted three-phase motor it is
65 also necessary to buy a frequency converter.
10 5.5 kW
Fortunately, frequency converters have
8 4 kW become cheaper in the past few years.
60
3 kW
6 152 mm The great advantage of frequency control
4
2.2 kW
is generally the energy saving. This is at
50 1.5 kW its highest with closed systems, as shown
2 20 40 60 80 100 120 140 in Figure 1. In this system, 50% capacity is
m3/hr
Q = 50% Q = 100% reached at a rotational speed of 720 rpm
(Figure 6). The power consumption at that
Figure 7. Speed regulation in an open system with a mainly stationary differential head results in only a small energy saving
point is about 0.9 kW. Compared to the
and often carries the risk of pump problems and unstable control.
power consumption of approximately 5.5 kW
for the same closed circuit with throttle
In a similar way, the open system shown output is already reached at a speed control it is clear that there is a substantial
in Figure 3 can also be controlled by of 1360 rpm. The applicable system energy saving. The higher investment costs
decreasing the speed but, because the and pump characteristics are shown in are earned back quickly, especially with
system characteristic curve is flatter, 50% Figure 7. continuously operating systems.
www.worldpumps.com
Feature 29
WORLD PUMPS April 2009
22.5
254 mm 50 60 65
70 73
75
20 77 77.5
77 1450 rpm
75
17.5
73
70
15
Head - m
12.5 7.5 kW
65
10 5.5 kW
60 4 kW
7.5
152 mm
3 kW
5
2.2 kW
50
2.5 1.5 kW
Figure 8. With throttle control the operational point of the pump shifts away from the BEP.
However, it is important to be very careful selected pump should never be too flat
when using speed control for an open because then undesired pump problems
system. Because the intersection and/or and/or unstable control will occur. ■
operational point with speed control in
an open system (Figure 3) shifts along the
References
system characteristic, this operational point
will shift continuously further left on the [1] H. Vogelesang, ‘Choosing the pump to
subject pump characteristic as rotational optimize energy use’, World Pumps, No. 507,
speed drops. Figure 7 shows this shift very pp. 20–24, (2008).
clearly. This will result in a decline in effi- [2] System Efficiency – A guide for energy
ciency with accompanying higher internal efficient rotodynamic pumping systems, Euro-
losses. In spite of this, the power consump- pump, (2006).
tion of ca. 4.5 kW at a flow rate of 50% will
[3] Pump Life Cycle Cost – A guide to LCC
always be lower than the 5.5 kW required
Analysis for Pumping Systems, Europump/
with throttle control, but clearly the saving is
Hydraulic Institute, (2001).
lower and because of this the payback will
be longer than with the closed circuit. [4] Europump/Hydraulic Institute, Variable
Speed Pumping – A guide to successful applica-
With the combination of a flat system
tions, Elsevier Science, (2004).
characteristic and a flat pump characteristic
(Figure 7) there is not only a loss of saving
but also a significant risk. Only a small
Contact
change in rotational speed will result in a
Hans Vogelesang
large capacity change, making it difficult PumpSupport (NL)
to maintain stable control. There is also the Charley Tooropstraat 38
3343 RE Hendrik Ido Ambacht
danger that the operational point will fall
The Netherlands
below the permitted minimal flow for the Tel: +31 78 682 0602
pump. This is very bad for the life span of Fax: +31 78 682 1833
the pump. In such circumstances you can E-mail: info@pumpsupport.nl
www.pumpsupport.nl
limit the risk by choosing a pump with a
steeper pump characteristic.
www.worldpumps.com