Dated: 12/14/2018
Page: 1 / 11
Eurovent classification
Cooling (EER) : A
SELECTED MOUNTING
I = Standard supply
I0 = On-site supply
R = Standard return
R0 =On-site supply return
E =Air extraction
N = Fresh air
No.
Dated: 12/14/2018
Page: 2 / 11
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 3 / 11
OPERATING CONDITIONS
SUMMER OPERATION
Outdoor Air: 35.0 0C / 40 %(RH) / 23.9 0C(WB) / 14.5 g/kg Dry air
Return air: 26.0 0C / 50 %(RH) / 18.7 0C(WB) / 10.7 g/kg Dry air
Mixed air : 28.2 0C / 48 %(RH) / 20.0 0C(WB) / 11.7 g/kg Dry air
Evaporator outlet air : 15.8 0C / 92 %(RH) / 15.1 0C(WB) / 10.6 g/kg Dry air
Supply air : 16.6 0C / 88 %(RH) / 15.3 0C(WB) / 10.6 g/kg Dry air
WINTER OPERATION
Outdoor Air: 6.00 0C / 90 %(RH) / 5.26 0C(WB) / 5.3 g/kg Dry air
Return air: 20.0 0C / 50 %(RH) / 13.7 0C(WB) / 7.4 g/kg Dry air
Mixed air : 16.4 0C / 58 %(RH) / 11.7 0C(WB) / 6.9 g/kg Dry air
Condenser outlet air : 16.4 0C / 58 %(RH) / 11.7 0C(WB) / 6.9 g/kg Dry air
Supply air : 17.2 0C / 55 %(RH) / 12.1 0C(WB) / 6.9 g/kg Dry air
COMPLETE PERFORMANCE
SUMMER OPERATION
Gross cooling capacity: 76.6 kW
Gross sensible cooling capacity: 63.4 kW
Total cooling capacity output : 72.4 kW
Sensible cooling capacity output : 59.2 kW
Compressor power input: 18.2 kW
Total input power : 29.0 kW
EER (EN 14511-2018) : 2.82
SEER* (EN14825-2016) : 4.49
WINTER OPERATION
Gross heating capacity : 0.0 kW
Heating capacity provided: 0.0 kW
Compressor power input: 0.0 kW
Total maximum power input: 10.8 kW
COP (EN 14511-2018) :
SCOP* (EN14825-2016) : NU
*SEER/SCOP values valid for EC axial external fan and supply EC plug fan
EXTERNAL SECTION
Number of fan(s) : 2
Air flow : 33,000 m3/h
Total motor(s) power : 2.80 kW
Rotation speed : 1020 rpm
Machines EN 60-204-1
Refrigerating systems and heat pumps EN 378-2
Refrigerant information :
CE N°2037/2000 (JO CE 29/09/2000) European Norm does not allowed HCFC use anymore for all EEC
countries from : 01/01/2004
The output of the heat pump depends on the weather conditions and drops as the temperature lowers.
The waste heat output at the lowest operating temperature must be checked.
Installing an auxiliary heating device (optional electric heater, gas burner or hot water coil) is recommended.
Dimension drawings
Chimney NOT SUPPLIED. Please, check dimensions in technical documentation.
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 6 / 11
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 7 / 11
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 8 / 11
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 9 / 11
TECHNICAL DESCRIPTION
ROOF TOP
Error: Reference source not found Error: Reference source not found
No.
Dated: 12/14/2018
Page: 11 / 11
- Unit ON / OFF.
- Selection of the operating mode.
- Selection of the setpoints.
- On-screen display of controlled variables and sensor values measured.
- On-screen display of current alarms and historical record of alarms.
Error: Reference source not found Error: Reference source not found