You are on page 1of 5

Summary Performance Report For 1

Project: 18-00655_Ch 01/11/2019


Prepared By: 10:38AM

Non contractual photo

PackagedChillerReport:DoNotEdit

30RB-033CH------A Air Cooled Scroll Chiller


Seasonal Energy Efficiency Unit Information
SEER 23/18°C Comfort medium temp: 4.05 kWh/kWh Manufacturing Source: European Union
SEPR -2°/-8°C Process medium temp*:3.02 kWh/kWh Refrigerant: R-410A
SEPR 12/7°C Process high temp: 5.16 kWh/kWh Capacity Control Steps: 1
ESEER(Data not certified): 3.62 kW/kW Minimum Capacity: 100 %
All data related to seasonal efficiency are given for standard units. Number of Refrigerant Circuit: 1
Operating/Shipping Weight without packaging option: 280/285 kg
* ECODESIGN Compliance value as per ( EU) 2015/1095 Unit Dimensions (LxWxH) without packaging option:1002/824/1790 m

Electrical Information
Unit Voltage: 400(+/-15%)-3-50 V-Ph-Hz
Cooling Mode Standby Power: 0.07 kW
Performance Information Power Factor: 0.81
Seasonal Efficiency (ESEER): 3.58 kW/kW
Cooling Capacity: 32.0 kW Electrical Electrical
Cooling Efficiency (EER): 3.23 kW/kW Amps (Un) Circuit 1 Circuit 2
Unit Power Input: 9.91 kW Maximum Current In (A): 27 None
Evaporator Information Start Up Current (A) 121 None
Fluid Type: Ethylene Glycol Current at Eurovent 20 None
Brine Concentration: 30.0 % Conditions (A)
Fouling Factor: 0.0000 (sqm-K)/kW
Leaving Temperature: 7.0 °C Accessories and Installed Options
Entering Temperature: 12.0 °C Hydraulic Module
Evaporator Hydraulic Module Information Expansion tank
External Static Pressure: 130.7 kPa With Neutral Cable on Power Supply
Pump Power Input: 1.18 kW
Fluid Flow: 1.69 l/s
Condenser Information
Altitude: 600 m
Number of Fans: 1
Entering Air Temperature: 32.8 °C

Acoustic Information (cooling mode)


Sound Power Level (LwA): 78 dB(A)
Sound Pressure Level at 10.0m (LpA): 46 dB(A)

All performances are compliant with EN14511 – 3 : 2013. Sound power level according to ISO9614 – 1.

CARRIER participates in the ECP program for Liquid Chilling Packages and Hydronic Heat Pumps. Check ongoing validity of
certificate:www.eurovent-certification.com.

Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI).

Packaged Chiller Builder EMEA 3.39g Page 1 of 5


Acoustic Summary For 1
Project: 18-00655_Ch 01/11/2019
Prepared By: 10:38AM

PackagedChillerReport:DoNotEdit

Unit Parameters
Tag Name: 1
Model Number: 30RB-033CH------A
Condenser Type: Air Cooled
Compressor Type: Scroll
Chiller Nameplate Voltage: 400-3-50 V-Ph-
Hz
Quantity: 1
Manufacturing Source: European Union
Refrigerant: R-410A
Shipping Weight: 285 kg
Operating Weight: 280 kg
Unit Length: 1002 mm d - Distance From Unit To Receiver
Unit Width: 824 mm
Unit Height: 1790 mm

Accessories and Installed Options


Hydraulic Module
Expansion tank
With Neutral Cable on Power Supply

Acoustic Information (Full Load)

Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k Total


Sound Power at Chiller Acoustic Center, dB 79 76 76 74 67 60 83
A-Weighted Sound Power, dBA 63 67 73 74 68 61 78
Sound pressure at specified distance in a free field, dB 47 44 44 42 35 28 51
A-Weighted Sound Pressure Level, dBA 31 36 41 42 37 29 46

Notes
d - Horizontal Distance From Chiller to Receiver = 10.0 m
Estimated Sound Power levels - dB re: 1 picowatt
Estimated Sound Pressure levels - dB re: 20 micropascal
Estimated sound levels given above are assumed to originate at the acoustic center of the chiller.

Sound Power level Lw in accordance with ISO 9614-1. Only the Total Sound Power level Lw is certified by Eurovent, at Full Load
in cooling mode, with all fans and pumps running at nominal speed, and for inlet air temperature at the condenser between 30°C
and 35°C. The sound levels by octave band are guideline values only and not contractually binding.

Estimated average sound pressure Lp at a given distance on a reflective surface in a free field environment.

Packaged Chiller Builder EMEA 3.39g Page 2 of 5


Detailed Performance Summary For 1
Project: 18-00655_Ch 01/11/2019
Prepared By: 10:38AM

Non contractual photo

PackagedChillerReport:DoNotEdit

30RB-033CH------A Air Cooled Scroll Chiller


Seasonal Energy Efficiency Unit Information
SEER 23/18°C Comfort medium temp: 4.05 kWh/kWh Manufacturing Source: European Union
SEPR -2°/-8°C Process medium temp*:3.02 kWh/kWh Refrigerant: R-410A
SEPR 12/7°C Process high temp: 5.16 kWh/kWh Capacity Control Steps: 1
ESEER(Data not certified): 3.62 kW/kW Minimum Capacity: 100 %
All data related to seasonal efficiency are given for standard units Number of Refrigerant Circuit: 1
Operating/Shipping Weight without packaging option: 280/285 kg
* ECODESIGN Compliance value as per ( EU) 2015/1095 Unit Dimensions (LxWxH) without packaging option:1002/824/1790 m

Electrical Information
Unit Voltage: 400(+/-15%)-3-50 V-Ph-Hz
Cooling Mode Standby Power: 0.07 kW
Performance Information Power Factor: 0.81
Cooling Capacity: 32.0 kW
Cooling Efficiency (EER): 3.23 kW/kW Electrical Electrical
Seasonal Efficiency (ESEER): 3.58 kW/kW Amps (Un) Circuit 1 Circuit 2
Unit Power Input: 9.91 kW Maximum Current In (A): 27 None
Evaporator Information Start Up Current (A) 121 None
Fluid Type: Ethylene Glycol Current at Eurovent 20 None
Brine Concentration: 30.0 % Conditions (A)
Fouling Factor: 0.0000 (sqm-K)/kW
Leaving Temperature: 7.0 °C Accessories and Installed Options
Entering Temperature: 12.0 °C Hydraulic Module
Evaporator Hydraulic Module Information Expansion tank
External Static Pressure: 130.7 kPa With Neutral Cable on Power Supply
Pump Power Input: 1.18 kW
Fluid Flow: 1.69 l/s
Condenser Information
Altitude: 600 m
Number of Fans: 1
Entering Air Temperature: 32.8 °C

Acoustic Information (cooling mode)


Sound Power Level (LwA): 78 dB(A)
Sound Pressure Level at 10.0m (LpA): 46 dB(A)

All performances are compliant with EN14511 – 3 : 2013. Sound power level according to ISO9614 – 1.

CARRIER participates in the ECP program for Liquid Chilling Packages and Hydronic Heat Pumps. Check ongoing validity of
certificate:www.eurovent-certification.com.

Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI).

Packaged Chiller Builder EMEA 3.39g Page 3 of 5


Detailed Performance Summary For 1
Project: 18-00655_Ch 01/11/2019
Prepared By: 10:38AM

European Seasonal Energy Efficiency Ratio


ESEER(Data not certified): 3.58 kW/kW

Unit Performance (1) (1) (1)


Percent Full Load Capacity, % 100 75 50 25
Percent of Full Load Power, % 100 68 44 24
Cooling Capacity, kW 33.2 24.9 16.6 8.3
Unit Power Input, kW 10.2 7.0 4.5 2.4
Efficiency, kW/kW 3.24 3.55 3.70 3.44
Evaporator Data
Fluid Entering Temperature, °C 12.0 12.2 12.4 12.6
Fluid Leaving Temperature, °C 7.0 7.0 7.0 7.0
Fluid Flow Rate, l/s 1.60 1.60 1.60 1.60
Fouling Factor, (sqm-K)/kW 0.000 0.000 0.000 0.000
Condenser Data
Entering Air Temperature, °C 35.0 30.0 25.0 20.0

Values given are interpolated and are not directly measurable under laboratory conditions.

(1) Compressor cycling is expected. Stated performances are average.

Evaporator Hydraulic Module Information


External Static Pressure: 131 kPa
Pump Power Input: 1.180 kW
Fluid Flow: 1.692 l/s

Packaged Chiller Builder EMEA 3.39g Page 4 of 5


Detailed Performance Summary For 1
Project: 18-00655_Ch 01/11/2019
Prepared By: 10:38AM

Seasonal Energy Efficiency Ratio


Tdesign: 35 °C
Temperature Application: Cooling Floor
Climate Reference: Average
Capacity Control: Fixed
Indoor Outlet Temperature: Fixed
Indoor Water Flow Rate: Fixed
Indoor Fluid Type: FW
Indoor Fluid Concentration: 0 %

Seasonal Space Cooling Energy 159


Efficiency, %
Pdesignh, kW 45.76
SEER, kWh/kWh 4.05

Conditions A B C D
External Air Temperature, °C 35.0 30.0 25.0 20.0
Part Load Ratio, % 100 74 47 21
Cool Demand, kW 46 34 22 10
Unit Performance
Cooling Capacity, kW 46 48 49 51

Values given are interpolated and are not directly measurable under laboratory conditions.

All performances are compliant with EN14511 – 3 : 2013. Sound power level according to ISO9614 – 1.

CARRIER participates in the ECP program for Liquid Chilling Packages and Hydronic Heat Pumps. Check ongoing validity of
certificate:www.eurovent-certification.com.

Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P)
and AHRI Standard 551/591 (SI).

Packaged Chiller Builder EMEA 3.39g Page 5 of 5

You might also like