PackagedChillerReport:DoNotEdit;
Condenser Information
Altitude: 0,000 m
Number of Fans: 12
Total Condenser Fan Air Flow: 52.670 L/s
Entering Air Temperature: 35,0 °C
Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 60,93 33,51 16,13
Unloading Sequence B B B B
Cooling Capacity, kW 680,2 510,1 340,1 170,0
Total Unit Power, kW 218,7 133,3 73,30 35,27
Efficiency (COPR), kW/kW 3,110 3,828 4,640 4,821
Evaporator Data
Fluid Entering Temperature, °C 12,22 10,83 9,44 8,05
Fluid Leaving Temperature, °C 6,67 6,67 6,67 6,67
Fluid Flow Rate, L/s 29,18 29,18 29,18 29,18
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Condenser Data
Entering Air Temperature, °C 35,0 26,7 18,3 12,8
Unit Performance
Percent of Full Load Capacity, % 100,00 75,00 50,00 25,00
Percent of Full Load Power, % 100,00 60,72 33,65 16,08
Unloading Sequence B B B B
Capacity, kW 688,1 516,1 344,0 172,0
Total Unit Power, kW 219,9 133,5 73,99 35,37
Efficiency (COPR), kW/kW 3,129 3,865 4,650 4,863
Evaporator Data
Fluid Entering Temperature, °C 14,00 12,24 10,49 8,75
Fluid Leaving Temperature, °C 7,00 7,00 7,00 7,00
Fluid Flow Rate, L/s 23,44 23,44 23,44 23,44
Fouling Factor, (sqm-K)/kW 0,0176 0,0176 0,0176 0,0176
Condenser Data
Entering Air Temperature, °C 35,0 26,7 18,4 12,8
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which
is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org.
The NPLV is not an AHRI 550/590 metric and is not certified. It is based on ambient temperature varying linearly from the full
load ambient to 55 F at 0% load.
Unit Parameters
Tag Name: DS - 30XA200
Model Number: 30XA200
Condenser Type: Air Cooled
Compressor Type: Screw
Chiller Nameplate Voltage: 380-3-60 V-Ph-
Hz
Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R-134a
Shipping Weight: 6135 kg
Operating Weight: 6220 kg
Unit Length: 7188 mm 1 - Chiller Height Above Ground
Unit Width: 2253 mm 2 - Horizontal Distance From Chiller to Receiver
Unit Height: 2297 mm 3 - Receiver Height Above Ground
(See Note 3)
Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input
for dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Notes: (1) Measurements performed in accordance with AHRI Standard 370-2015 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0,0 m
2 - Horizontal Distance From Chiller to Receiver = 9,1 m
3 - Receiver Height Above Ground = 0,9 m