Air Cooled Screw Chiller Performance

Datasheet
Net Cooling Nominal Power
Unit Tag Qty Model No Refrigerant Type
Capacity (ton.R) Volts-Ph-Hz
CH-350TR 1 YVAA0500JCF46BAVDXX 218.9 460-3-60.0 R134a

PIN:
YVAA0500JC F46BAVDXXX SAXLXXXX60 16XOSXXS21 0X1DXGA3BC XFXX1XXXXX XGXEXX
....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 29.00 Fluid Volume (USGAL) 146.9 EER (Btu/W∙h) 4.904
LWT (°F) 16.00 Min. Flow Rate (USGPM) 423.0 NPLV.IP (Btu/W∙h) 9.180
Design Flow Rate (USGPM) 457.3 Max. Flow Rate (USGPM) 1440
Total Press. Drop (ft H2O) 8.18 Condenser Data Physical Data
Ethylene
Fluid 35 Ambient Temp. Design (°F) 105.0 Rigging Wt. (lb) 32304
Glycol (%)
Fouling Factor (h.ft².F/Btu) 0.000100 Altitude (ft) 1600 Operating Wt. (lb) 33660
VSD Screw - Semi
Number Passes 3 Compressor Type Refrigerant Charge (lb) 987.6
Hermetic

Electrical Data
Circuit 1 2 3 4
Compressor kW 253.2 251.9
Compressor RLA 368 368
Fan QTY/FLA (each) 10 / 3.3 10 / 3.3

Multi Point
Min. Circuit Ampacity 498 493
Max. Fuse / CB Rating (A) 600 600
Unit Short Circuit Withstand (STD) 30 [kA]
Wires Per Phase 2 2
Wire Range (Lug Size) #2 - 600 kcmil #2 - 600 kcmil
Displacement Power Factor 0.95 Operating Condition Electrical Data
Control kVA 3 Compressor kW 505.1
Total kW 535.7

Notes:
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle
Certification Program, but is rated in accordance with AHRI Standard 550/590 (I-P) and AHRI
Standard 551/591 (SI). Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
Min DSD (Factory Purpose/Use only): 80 psig
Use Copper Conductors only
Displacement Power Factor refers to compressor only. Unit Power Factor depends on fan option
selected. Calculated value is available by request.

Minimum and maximum evaporator flow information are for full load ratings with Ethylene Glycol.
Evaporator Passes: 3, Condenser Type: C, Fan Type: F
Actuated suction service valves ARE NOT selected
Exclusion of actuated suction service valves will require incorporation of additional freeze protection including use of glycol, pump control or draining the
evaporator.

MLP Effective Date:3/1/2020 SURA INDUSTRIALES MED


Generated on2020-03-31 E.20.1.21625.0-D.84.0011(REV. v8_17.idd) Datasheet Spec
Unit Folder: CU-CU Software Version: YW20.01 Page_1_of_2
Air Cooled Screw Chiller Performance
Datasheet

Part Load Rating Data


Unit Efficiency
Load % Ambient (°F) Capacity (ton.R) Total kW
(Btu/W∙h)
100 105.0 218.9 535.7 4.904
75 80.0 164.2 232.2 8.486
50 65.0 109.5 136.5 9.623
25 55.0 54.73 63.79 10.30

Sound Power Levels (In Accordance with AHRI 370)


Ambient 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Load % LWA
(°F) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB)
100 105.0 99 100 100 109 107 103 98 93 111
75 80.0 99 99 100 101 98 92 90 85 102
50 65.0 99 99 100 100 96 90 87 85 101
25 55.0 96 96 97 98 94 88 84 82 99

Note: Unit is equipped with Low Sound Fans.

Performance at AHRI Conditions


Evaporator Data Condenser Data Performance Data
EWT (°F) 54.00 Ambient Temp. (°F) 95.0 EER (Btu/W∙h) 8.064
LWT (°F) 44.00 Altitude (ft) 0.000 IPLV.IP (Btu/W∙h) 14.97
Net Cooling Capacity
Flow Rate (USGPM) 1115 465.9
(ton.R)
Pressure Drop (ft H2O) 45.2
Fluid Water
Fouling Factor (h.ft².F/Btu) 0.000100
Fluid Volume (USGAL) 146.9

Note: Unit rated at design condition compressor frequency.

Part Load Rating Data at AHRI Conditions


Unit Efficiency
Load % Ambient (°F) Capacity (ton.R) Total kW
(Btu/W∙h)
100 95.0 465.9 693.3 8.064
75 80.0 349.4 326.4 12.85
50 65.0 233.0 170.8 16.37
25 55.0 116.5 78.92 17.71

MLP Effective Date:3/1/2020 SURA INDUSTRIALES MED


Generated on2020-03-31 E.20.1.21625.0-D.84.0011(REV. v8_17.idd) Datasheet Spec
Unit Folder: CU-CU Software Version: YW20.01 Page_2_of_2