You are on page 1of 3

Project: Rating Program: XEngine 1.0.

7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:30:16
Customer:

SALES REPORT

Unit Specifications
Model YMC2-S1934AB Refrigerant R-134a
Specified Net Capacity (Tons) 550.0 Refrigerant Charge (lb) 1477
Rated Net Capacity (Tons) 550.0 Variable Orifice V2
Heat Rejection Capacity (MBtu/h) 7.740
Full Load (kW/Ton.R) 0.5887 Isolation Valve Y
NPLV.IP (kW/Ton.R) 0.3080 OptiSound Control Y
Input Power (kW) 323.8 Voltage / Hz 415 / 50.0
Starter Type HYP0730XHC***-68A FLA (Amps) 476
Compressor M2C-246FAC A-Weighted SPL (dBA) 76
Evaporator EB3314-321-CS*-2*** Min Circuit Ampacity 595
Condenser CB3314-260-BS*-2*** Max Circuit Breaker Amps 1000
Sales Model YMC3314C3314B246M2B

Evaporator Condenser
Fluid Water* Water*
Tube MTI No. 321 260 / 260
Passes 2* 2*
Fouling Factor (hr-ft²-°F/Btu) 0.000100* 0.000250*
Entering Fluid Temp (°F) 53.60* 89.60*
Leaving Fluid Temp (°F) 44.60* 98.60*
Fluid Flow (gpm) 1462 1731
Fluid Pressure Drop (ft H2O) 18.6 22.2
(*) Designates User Specified Input

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 1 of 3
Project: Rating Program: XEngine 1.0.7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:30:16
Customer:

Partload Data (CEFT constant)


Net Capacity Input Power EEFT ELFT CEFT CLFT
% Load % Power kW/Ton.R
(Tons) (kW) (°F) (°F) (°F) (°F)
100 550.0 100 323.8 53.60 44.60 89.60 98.60 0.5888
90 495.0 87 281.0 52.70 44.60 89.60 97.66 0.5678
80 440.0 75 241.4 51.80 44.60 89.60 96.74 0.5486
70 385.0 64 208.2 50.90 44.60 89.60 95.84 0.5409
60 330.0 56 179.6 50.00 44.60 89.60 94.96 0.5442
50 275.0 47 153.3 49.10 44.60 89.60 94.09 0.5576
40 220.0 40 129.1 48.20 44.60 89.60 93.22 0.5870
30 165.0 33 107.1 47.30 44.60 89.60 92.37 0.6491
20 110.0 28 91.32 46.40 44.60 89.60 91.55 0.8302
14 75.86 27 86.25 45.84 44.60 89.60 91.06 1.137

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 2 of 3
Project: Rating Program: XEngine 1.0.7053
Unit Tag: Software Version: YW 19.02
Engineer: Date: 05/06/2019 18:30:16
Customer:

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-Heating Packages Using
Vapor Compressor Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI 551/591
(SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in
total kW: Chiller Controls.
Compliant with ASHRAE 90.1-2004.
Compliant with ASHRAE 90.1-2007.
Compliant with ASHRAE 90.1-2010.
Compliant with ASHRAE 90.1-2013.
Compliant with ASHRAE 90.1-2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant Management Credit
(EAc4).
Materials and construction per mechanical specifications - Form 160.84-EG1.
Auxiliary components included in total kW - Chiller controls.

Page 3 of 3