Date: 12/12/2018

Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

GENERAL DATA Eurovent energy classification


Customer reference CTA01
Number off 1
Location External (flat roof)
Delivery In sections
AHU finish Outside in standard colour
(RAL 7035)
Product Air handling unit
AHU configuration Double deck (opposite)
Pallet option Excluded
Lifting Beam Excluded
Total weight (each) kg 5590
(Radiated casework SWL) dB(A) 67
ErP identification code NRVU / BVU

SFPe kJ/m³ 2.26 SFPv kJ/m³ 2.08


Calculations conform to the Regulation for bidirectional ventilation unit (BVU) for delivery after 01.01.2018
Remarks are needed to be solved to comply with the Regulation.

Ecodesign 1253/2014 2018 BVU after 01.01.2018


Intermediate calculations Supply air unit data Extract air unit data
E (HR Bonus) (Pa) 291 Airflow (m³/s) 8.15 Airflow (m³/s) 6.92
F (Filter correction) (Pa) 0 System effect (Pa) 25 System effect (Pa) 21
SFP int_limit (W/(m³/s)) 1091.0 Static pressure (Pa) 868 Static pressure (Pa) 724
SFP int supply air (W/(m³/s)) 395.6 p fan (kW) 10.78 p fan (kW) 7.64
SFP int extract air (W/(m³/s)) 264.1 n fan (%) 65.6 n fan (%) 65.6
SFP int (W/(m³/s)) 659.6 Fine Filter Yes Medium Filter Yes
dp Fine filter (Pa) 73 dp Medium filter (Pa) 15
nt nrvu (%) 83 nt nrvu (%) 83
dp HRS (Pa) 161 dp HRS (Pa) 137
Check
Fan is selected with VSD Warning
Heat recovery Passed
Thermal by-pass facility Passed
SFP int Passed
Filters equipped with pressure Warning
gauge
Total check Passed
Remark
To comply with Regulation EU No 1253 you need to equip the fan with a Variable Speed Drive.
To comply with Regulation EU No 1253 you need to equip the filter with a pressure gauge.

ACCESS DATA
Handle type L-Handle Internal handles Included
All locks with handles Yes Pressure guard at positive Included
pressure doors

EXHAUST DATA
Type 39HQ 18.10 Air volume m³/s 6.92
Casing construction GP080 Internal sheet Galvanised 0.80mm
60 mm
Insulation Glassfibre 20-30 kg/m³ External sheet PUR-PA painted galvanized
steel 0.80mm
Unit velocity m/s 1.56
SFPe kJ/m³ 1.10 SFPv kJ/m³ 1.03

Mechanical performance according EN1886 Model box D1 L1 (-400Pa) L1 (+400Pa) L1 (+700Pa) F9 T2 TB2
Real Unit L1 (-400Pa) L1 (+400Pa) L1 (+700Pa)

Page 1 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

(Sound data exhaust SWL) Hz 125 250 500 1k 2k 4k 8k dB(A)


dB 70 48 37 28 22 24 32 54
dB 82 78 77 76 72 69 64 80

SUPPLY DATA
Type 39HQ 18.10 Air volume m³/s 8.15
Casing construction GP080 Internal sheet Galvanised 0.80mm
60 mm
Design outdoor °C -15.0 External sheet PUR-PA painted galvanized
temperature steel 0.80mm
Unit velocity m/s 1.84 Insulation Glassfibre 20-30 kg/m³
SFPe kJ/m³ 1.32 SFPv kJ/m³ 1.20

Mechanical performance according EN1886 Model box D1 L1 (-400Pa) L1 (+400Pa) L1 (+700Pa) F9 T2 TB2
Real Unit L1 (-400Pa) L1 (+400Pa) L1 (+700Pa)

(Sound data supply SWL) Hz 125 250 500 1k 2k 4k 8k dB(A)


dB 80 77 72 65 61 55 50 73
dB 77 54 44 39 34 42 50 61

In direction of airflow, the unit comprises:

DELIVERY SECTION(S)
Section Width (mm) Height (mm) Length (mm) Baseframe (mm) Weight (kg)
1 2978 1698 1969 62 794
2 2978 1698 1649 62 729
3 2978 1698 418 62 333
4 2978 1698 1218 62 479
5 3458 3458 1538 62 1915
6 2978 1698 689 62 302
7 2978 1698 1600 62 590
8 2978 1698 1329 62 448

EXHAUST COMPONENTS

INLET
Opening, width x height mm 2818 x 1538 Provided with:
Pressure drop Pa 0 Opening product Flexible connection single
skin

FILTER
Filter type Bag (Synthetic) Withdrawal method Side
Filter class F8 Test method 0.4 µm acc. EN779
Initial pressure drop Pa 90
Design pressure drop Pa 137
Final pressure drop Pa 184
Filter length mm 500
Filter frame material Galvanised

Filters
592x592 Qty 8 287x592 Qty 2
592x287 Qty 4

ACCESS
Access type Door Access side Left

EXTRAS
2 x Measuring nipple, 6mm

Page 2 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

ATTENUATOR
Length mm 1280
Pressure drop Pa 19 Sound data according ISO 7235
Insertion loss Hz 63 125 250 500 1k 2k 4k 8k
dB 8 10 29 46 50 58 36 25

INLET PLENUM
Diffuser Type Withdrawable Air pressure drop Pa 0

ACCESS
Access type Hatch Access side Right

FAN
Fan type RLM E6-5663
Fan arrangement Dual Installed motor power kW 2 x 4.00
Air volume m³/s 2 x 3.46 Motor Run
External static pressure Pa 400 Motor efficiency class IE3
Internal static pressure Pa 303 Motor nominal speed rpm 1440
Static pressure ISP+ESP Pa 703 Voltage V 400
System effect Pa 21 Current A 2 x 8.1
Extra static pressure Pa 0 Abs. motor power incl. F.I. kW 2 x 3.82
Total static pressure Pa 724 Operating frequency Hz 49
Dynamic pressure Pa 44 Max. operating frequency Hz 51
Total pressure Pa 768
Fan speed rpm 1417
Max fan speed rpm 1480
Efficiency (total) % 81
Fan shaft power kW 2 x 3.29

(Fan sound data SWL) Hz 63 125 250 500 1k 2k 4k 8k


Total Inlet dB 76 82 79 76 74 72 70 67
Outlet dB 79 84 80 80 80 77 75 72

FAN EXTRAS
Flexible connection single skin

ACCESS
Access type Door Access side Left

EXTRAS
2 x Measuring nipple, 6mm

HEAT WHEEL
Rotor situation Build-in with inspection
Winter conditions
Exhaust air on °C/%RH 22.0 / 40 Exhaust pressure drop Pa 137
Exhaust air off °C/%RH -11.0 / 93
Summer conditions
Exhaust air on °C/%RH 25.0 / 50 Exhaust pressure drop Pa 137
Exhaust air off °C/%RH 32.5 / 35

OUTLET
Opening, width x height mm 2880 x 1600 Provided with:
Pressure drop Pa 10 Opening product Louvre
Damper Internal, Opposed blades,
1 x 25 Nm, max 0 Pa Suitable for actuator,
Aluminium

SUPPLY COMPONENTS

Page 3 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

INLET
Opening, width x height mm 2880 x 1600 Provided with:
Pressure drop Pa 13 Opening product Louvre
Damper Internal, Opposed blades,
1 x 25 Nm, max 0 Pa Suitable for actuator,
Aluminium

COMBINED FILTER
Primary filter type Panel (Synthetic) Secondary filter type Bag (Synthetic)
Filter class G4 Filter class F8
Initial pressure drop Pa 60 Initial pressure drop Pa 110
Design pressure drop Pa 98 Design pressure drop Pa 163
Final pressure drop Pa 136 Final pressure drop Pa 216
Filter length mm 48 Filter length mm 500
Withdrawal method Side
Filter frame material Galvanised Measuring section Included

Filters Filters
592x592 Qty 8 592x592 Qty 8
287x592 Qty 2 287x592 Qty 2
287x592 Qty 4 592x287 Qty 4
287x287 Qty 1

ACCESS
Access type Door Access side Right

EXTRAS
4 x Measuring nipple, 6mm

HEAT WHEEL
Rotor Model SE3-XL-SV-3110-DS-K2-A1-0,W3315,H3315,IB
Rotor type Enthalpy Rotor frame material Galvanised
Rotor material Aluminium Rotor purging sector Excluded
Rotor situation Build-in with inspection Delivery requirement Single section
Component mountings Galvanised
Winter conditions
Supply air on °C/%RH -15.0 / 90 Supply pressure drop Pa 161
Supply air off °C/%RH 13.1 / 50
Supply dry efficiency % 76 Supply latent efficiency % 66
Supply dry effectiveness % 90 Supply latent effectiveness % 78
Total duty kW 370.60
Summer conditions
Supply air on °C/%RH 33.5 / 36 Supply pressure drop Pa 161
Supply air off °C/%RH 27.1 / 50
Supply dry efficiency % 75 Supply latent efficiency % 31
Supply dry effectiveness % 88 Supply latent effectiveness % 36
Total duty kW 78.20 Dry efficiency at equal % 83
airflow

ACCESS
Access type (x 4) Door Access side Right

EXTRAS
1 x Basic heat-wheel control, 370W, IP54

INDIRECT GAS HEATER


Pressure drop Pa 80 3 x RHC 8100.12 _ Nortek

Page 4 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

INLET PLENUM
Diffuser Type Withdrawable Air pressure drop Pa 0

ACCESS
Access type Hatch Access side Right

FAN
Fan type RLM E6-5663
Fan arrangement Dual Installed motor power kW 2 x 5.50
Air volume m³/s 2 x 4.07 Motor Run
External static pressure Pa 300 Motor efficiency class IE3
Internal static pressure Pa 543 Motor nominal speed rpm 1460
Static pressure ISP+ESP Pa 843 Voltage V 400
System effect Pa 25 Current A 2 x 11.1
Extra static pressure Pa 0 Abs. motor power incl. F.I. kW 2 x 5.39
Total static pressure Pa 868 Operating frequency Hz 54
Dynamic pressure Pa 60 Max. operating frequency Hz 56
Total pressure Pa 928
Fan speed rpm 1602
Max fan speed rpm 1650
Efficiency (total) % 81
Fan shaft power kW 2 x 4.69

(Fan sound data SWL) Hz 63 125 250 500 1k 2k 4k 8k


Total Inlet dB 79 85 82 79 77 75 73 70
Outlet dB 82 87 83 83 83 80 78 75

FAN EXTRAS
Flexible connection single skin

ACCESS
Access type Door Access side Right

EXTRAS
2 x Measuring nipple, 6mm

ATTENUATOR
Length mm 1280
Pressure drop Pa 27 Sound data according ISO 7235
Insertion loss Hz 63 125 250 500 1k 2k 4k 8k
dB 8 10 29 46 50 58 36 25

OUTLET
Opening, width x height mm 2818 x 1538 Provided with:
Pressure drop Pa 0 Opening product Flexible connection single
skin

Page 5 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

Supply fan - RLM E6-5663

Page 6 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

Exhaust fan - RLM E6-5663

Page 7 of 8
Date: 12/12/2018
Technical Specification

Project name : Airovision Builder version: E1.07 (11-1-2018)(R061)/A


Quotation no. : 18-00347_R2F / 001 Eurovent identification number: 08.02.251

Psychrometric charts
Heatwheel

115

0.032
110

105
0.030

100

ON OFF
95 0.028
°C RH MC °C RH MC 30

90
Winter (Sup0-1)
-15.0 89 0.001 13.1 49 0.005
0.026
Winter (Exh2-3)
22.0 39 0.007 -11.0 93 0.001 85

Summer (Sup4-5)
33.5 36 0.012 27.1 49 0.011 80 0.024
Summer (Exh6-7)
25.0 49 0.010 32.5 34 0.011
75

0.022
70

MOISTURE CONTENT kg/kg DRY AIR


65 25
0.020

60

g 55 0.018
/k
kJ
N
O 50
TI
RA
0.016

TU 45
SA 20

AT 40 0.014
PY
AL35
TH
EN 0.012
30 ON(4)
15 OFF(5)
25 OFF(7)
0.010
ON(6)
20

0.008
15 10

10
ON(2) 0.006
5 5

OFF(1)
0 0.004
0

-5
0.002
-10
OFF(3)
ON(0)
0.000
-10 -5 0 5 10 15 20 25 30 35 40 45 50 55
0.75 VOLUME m3/kg DRY AIR 0.80 DRY BULB TEMPERATURE0.85
°C

ENTHALPY DEVIATION kJ/kg -0.05 -0.10 -0.20 -0.40 -0.60 -0.80 -1.00

Page 8 of 8