Summary Performance Report For CH-1-CU-AL

Project: Jaco Zate 02/17/2021


Prepared By: 12:00PM

PackagedChillerReport:DoNotEdit;

AquaForce TM Air-Cooled Screw Chiller

Unit Information Accessories and Installed Options


Tag Name: CH-1-CU-AL Control Transformer
Model Number: 30XA501 High Ambient Fan Motor Option
Quantity: 1 High Ambient Valve Configuration (Middle East Only)
Manufacturing Source: Charlotte, NC USA Al Fin/Cu Tube
ASHRAE 90.1: 2010, 2007 Wye-Delta Starter
Refrigerant: R-134a Dual Point
Independent Refrigerant Circuits: 2 BACnet Communications
Shipping Weight: 13382 kg Export Packaging (Skid + Bag)
Operating Weight: 13691 kg Coil Trim Panels (Header side only)
Unit Length: 15570 mm Touch Pilot Display
Unit Width: 2253 mm Std SCCR 5 k Current Rating (All Voltages)
Unit Height: 2297 mm
Extended Leadtime Options
Evaporator Information
Fluid Type: Fresh Water Blanket Control # Description Quantity
Fouling Factor: 0.0176 (sqm-K)/kW ACPRT20-0004 SASO Label 1
Number of Passes: 2
Leaving Temperature: 5.50 °C Electrical Information
Entering Temperature: 11.10 °C Unit Voltage: 380-3-60 V-Ph-Hz
Fluid Flow: 66.53 L/s Connection Type: Dual Point
Pressure Drop: 62.2 kPa Minimum Voltage: 342 Volts
Maximum Voltage: 418 Volts
Condenser Information
Altitude: 7.00 m Electrical Electrical
Number of Fans: 26 Amps Circuit 1 Circuit 2
Total Condenser Fan Air Flow: 152,200 L/s MCA 647.6 602.5
Entering Air Temperature: 43.0 °C MOCP 1000.0 1000.0
ICF 849.5 836.4
Integrated Pump Information Rec Fuse Size 800.0 800.0
No Pump Selected

Performance Information
Cooling Capacity: 1,564 kW
Total Compressor Power: 578.1 kW
Total Fan Motor Power: 67.75 kW
Total Unit Power (without pump): 645.8 kW
Efficiency (without pump) (COPR): 2.422 kW/kW
IPLV:.IP: 4.058 kW/kW

Sound power measured in accordance with ANSI/AHRI Standard 370-2015.

Packaged Chiller Builder NACO 3.59n Page 1 of 6


Summary Performance Report For CH-1-CU-AL
Project: Jaco Zate 02/17/2021
Prepared By: 12:00PM

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI
Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.59n Page 2 of 6


Summary Performance Report For CH-1-CU-AL
Project: Jaco Zate 02/17/2021
Prepared By: 12:00PM

Unit Parameters
Tag Name: CH-1-CU-AL
Model Number: 30XA501
Condenser Type: Air Cooled
Compressor Type: Screw
Chiller Nameplate Voltage: 380-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R-134a
Shipping Weight: 13382 kg
Operating Weight: 13691 kg
Unit Length: 15570 mm
Unit Width: 2253 mm 1 - Chiller Height Above Ground
Unit Height: 2297 mm 2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Control Transformer BACnet Communications
High Ambient Fan Motor Option Export Packaging (Skid + Bag)
High Ambient Valve Configuration (Middle East Only) Coil Trim Panels (Header side only)
Al Fin/Cu Tube Touch Pilot Display
Wye-Delta Starter Std SCCR 5 k Current Rating (All Voltages)
Dual Point

Extended Leadtime Options

Blanket Control # Description Quantity Master Price


ACPRT20-0004 SASO Label 1 $1,700

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load --- 72 88 101 101 105 100 94 85 108
75% Load --- 71 87 100 100 104 99 94 85 108
50% Load --- 69 85 97 97 101 96 91 82 105
25% Load --- 66 83 97 96 100 95 89 82 104

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load --- 44 60 72 73 77 72 66 57 80
75% Load --- 43 59 72 72 76 71 65 57 80
50% Load --- 41 57 69 69 73 68 63 53 77
25% Load --- 38 55 69 68 72 67 61 53 76

Notes: (1) Measurements performed in accordance with AHRI Standard 370-2015 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 m
2 - Horizontal Distance From Chiller to Receiver = 9.1 m
3 - Receiver Height Above Ground = 0.9 m

Packaged Chiller Builder NACO 3.59n Page 3 of 6


Summary Performance Report For CH-1-Micro Channel
Project: Jaco Zate 02/17/2021
Prepared By: 12:00PM

PackagedChillerReport:DoNotEdit;

AquaForce TM Air-Cooled Screw Chiller

Unit Information Accessories and Installed Options


Tag Name: CH-1-Micro Channel Control Transformer
Model Number: 30XA501 High Ambient Fan Motor Option
Quantity: 1 High Ambient Valve Configuration (Middle East Only)
Manufacturing Source: Charlotte, NC USA Micro Channel
ASHRAE 90.1: 2010, 2007 Wye-Delta Starter
Refrigerant: R-134a Dual Point
Independent Refrigerant Circuits: 2 BACnet Communications
Shipping Weight: 12257 kg Export Packaging (Skid + Bag)
Operating Weight: 12566 kg Coil Trim Panels (Header side only)
Unit Length: 15570 mm Touch Pilot Display
Unit Width: 2253 mm Std SCCR 5 k Current Rating (All Voltages)
Unit Height: 2297 mm
Extended Leadtime Options
Evaporator Information
Fluid Type: Fresh Water Blanket Control # Description Quantity
Fouling Factor: 0.0176 (sqm-K)/kW ACPRT20-0004 SASO Label 1
Number of Passes: 2
Leaving Temperature: 5.50 °C Electrical Information
Entering Temperature: 11.10 °C Unit Voltage: 380-3-60 V-Ph-Hz
Fluid Flow: 66.65 L/s Connection Type: Dual Point
Pressure Drop: 62.5 kPa Minimum Voltage: 342 Volts
Maximum Voltage: 418 Volts
Condenser Information
Altitude: 7.00 m Electrical Electrical
Number of Fans: 26 Amps Circuit 1 Circuit 2
Total Condenser Fan Air Flow: 152,200 L/s MCA 647.6 602.5
Entering Air Temperature: 43.0 °C MOCP 1000.0 1000.0
ICF 849.5 836.4
Integrated Pump Information
Rec Fuse Size 800.0 800.0
No Pump Selected

Performance Information
Cooling Capacity: 1,567 kW
Total Compressor Power: 574.8 kW
Total Fan Motor Power: 67.75 kW
Total Unit Power (without pump): 642.5 kW
Efficiency (without pump) (COPR): 2.439 kW/kW
IPLV:.IP: 4.091 kW/kW

Sound power measured in accordance with ANSI/AHRI Standard 370-2015.

Packaged Chiller Builder NACO 3.59n Page 4 of 6


Summary Performance Report For CH-1-Micro Channel
Project: Jaco Zate 02/17/2021
Prepared By: 12:00PM

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI
Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org.

Packaged Chiller Builder NACO 3.59n Page 5 of 6


Summary Performance Report For CH-1-Micro Channel
Project: Jaco Zate 02/17/2021
Prepared By: 12:00PM

Unit Parameters
Tag Name: CH-1-Micro Channel
Model Number: 30XA501
Condenser Type: Air Cooled
Compressor Type: Screw
Chiller Nameplate Voltage: 380-3-60 V-Ph-Hz
Quantity: 1
Manufacturing Source: Charlotte, NC USA
Refrigerant: R-134a
Shipping Weight: 12257 kg
Operating Weight: 12566 kg
Unit Length: 15570 mm
Unit Width: 2253 mm 1 - Chiller Height Above Ground
Unit Height: 2297 mm 2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)

Accessories and Installed Options


Control Transformer BACnet Communications
High Ambient Fan Motor Option Export Packaging (Skid + Bag)
High Ambient Valve Configuration (Middle East Only) Coil Trim Panels (Header side only)
Micro Channel Touch Pilot Display
Wye-Delta Starter Std SCCR 5 k Current Rating (All Voltages)
Dual Point

Extended Leadtime Options

Blanket Control # Description Quantity Master Price


ACPRT20-0004 SASO Label 1 $1,700

Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load --- 72 88 101 101 105 100 94 85 108
75% Load --- 71 87 100 100 104 99 94 85 108
50% Load --- 69 85 97 97 101 96 91 82 105
25% Load --- 66 83 97 96 100 95 89 82 104

Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.

Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall


100% Load --- 44 60 72 73 77 72 66 57 80
75% Load --- 43 59 72 72 76 71 65 57 80
50% Load --- 41 57 69 69 73 68 63 53 77
25% Load --- 38 55 69 68 72 67 61 53 76

Notes: (1) Measurements performed in accordance with AHRI Standard 370-2015 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 m
2 - Horizontal Distance From Chiller to Receiver = 9.1 m
3 - Receiver Height Above Ground = 0.9 m

Packaged Chiller Builder NACO 3.59n Page 6 of 6