Detailed performance summary

Project Name:q
Saler:q
Version:1.0 13-10-2020 12:31:24
Input data:
Selection mode: Auto Total capacity: 610 kW
Chiller quantity: 5 Capacity bias: 5,0 %
Power supply: 50 Ambient dry bulb: 32 °C
Conditions: T1 Outlet fluid temp.: 6,0 °C
Series: All Altitude: 600 m
Refrigerant: R410A Fouling factor: 0,08600
Fluid: Water Work mode: Cooling

Unit Information
Unit Name: ···································· MC-SS130/RN1
Unit Quantity: ··················································· 5
Packing Weight: ·········································· 950 kg
Operating Weight: ······································ 1020 kg
Unit Depth: ············································ 2200 mm
Unit Width: ············································ 1120 mm
Unit Height: ············································ 2060 mm
Sound Power Level: ·································· 68 dB(A)
Performance Information
Cooling Capacity: ···································· 128,0 kW
Heating Capacity: ····································· *138 kW
Cooling Efficiency (E.E.R.): ····················· 3,1 kW/kW
Heating Efficiency (C.O.P.): ····················· *3,2 kW/kW
Compressor Information
Quantity: ················································ 2 Pieces
Type: ······································· Scroll(Fixed speed)
Refrigerant Type: ········································· R410A
Refrigerant Charge: ·································· 10.5*2 kg
Evaporator Information
Fluid Type: ················································· Water
Concentration: ······················································
Fouling Factor: ········································· 0,08600
Leaving Temperature: ··································· 6,0 °C
Entering Temperature: ···································· 11 °C
Water Flow: ··········································· 22,0 m3/h
Total Pressure Drop: ··································· 39,0 kPa
Condenser Information
Type: ······················································ Fin-coil
Air Flow: ············································ 50000 m3/h
Fan Motor Rated Current: ····························· 4.8*2 A
Fan Motor Input: ···································· 2.59*2 kW
Electrical Information
Unit Voltage: ·························· 380~415/3/50 V/Ph/Hz
Max Unit Current(RLA): ································ 109 A
Max Start Up Current: ···································· 308 A

Note: * The specification is based on standard condition: chilled water inlet/outlet: 53.6¡ãF / 44.6¡ãF, and outdoor
ambient temp. of 95¡ãF DB.

1 / 3
Detailed performance summary
Project Name:q
Saler:q
Version:1.0 13-10-2020 12:31:24

IPLV
Unit performance:
Percent of full load capacity % 100 75 50 25
Entering air temperature °C 34,00 26,00 17,00 12,00
Fluid entering temperature °C 12,0 9,0 9,0 9,0
Fluid leaving temperature °C 6,0 6,0 6,0 6,0
Fluid flow rate m3/h 21,00 21,00 21,00 21,00
Capacity kW 130,0 73,0 78,0 78,0
Input kW 42,0 22,0 17,0 16,2
EER1 kW/kW 3,0 3,0 4,0 4,0
EER2 Btu/W.h 10,0 10,0 14,0 15,0
IPLV Btu/W.h 13,00
THE IPLV DATA IS BASED ON AHRI STANDARD 550/590-2011
The above data may be changed without notice for future improvement on quality and
performance.

Pressure Drop Curve:

2 / 3
Detailed performance summary
Project Name:q
Saler:q
Version:1.0 13-10-2020 12:31:24
Dimension Chart:

Water inlet Water outlet


Flange DN65 Flange DN65

3 / 3