You are on page 1of 5

Project Name: 21HEDS021 P Cogeneracion Coopervision PR JCI Contract No: Contract #

Location: Coil Version: 7.05b


Consultant/Engineer: Printed Date: 11/5/2020 6:17:56 AM
Contractor: Selection Date: 11/3/2020 7:24:16 AM
Sold To: Last Revision Date: 11/5/2020 5:32:30 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FHP06, FHP06 2 FHP-D06 242.1 L/s 6.22 kW 4.57 kW
Unit Data
Model Size : 06 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [mm] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/10 Filter (Qty) Size : 31x10.5x1 Coil Face Area [m²] 0.2
Motor FLA : 1.6 Filter Face Area [m²] 0.2 Weight* [kg] 33.1
Motor Type : PSC
Capacity : High Capacity
Output Data Options
Altitude [m] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [L/s] 242.1 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [Pa] 59.72 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°C] 26.99/ 19.00 Galvanized Drain pan
LAT DB/WB [°C] 11.61/ 11.22 Return Air Options- Return: Rear No Duct Collar
Total Capacity [kW] 6.22 Thermostat Location- Remote Mounted Thermostat
Sensible Capacity [kW] 4.57 Thermostat- D03C Digital - 2 Pipe Cool - 3/SS
EWT/LWT [°C] 7.01/ 12.01 Chilled Water Coil: Piping Package Size - 1/2"
Fluid Flow [L/s] 0.303 Chilled Water Coil:2 Position Close-Off (24v Only)
Fluid P.D [kPa] 14.54 Chilled Water Coil:3-Way Control Valve
Fluid Velocity [m/s] 0.88 Chilled Water Coil:Actuator Position- Normally Closed - 2 Pos Close-Off
Rows / FPI / Circuits : 5 Row / 10 FPI / 5 Ckt Chilled Water Coil:Factory Mounted Piping Package
Coil Connection Size: [mm] 22.23 Chilled Water Coil:Galvanized Casing
Heating Data Chilled Water Coil:Left Hand Connection
EAT DB [°C] -17.78 Chilled Water Coil:Manual Air Vent
LAT DB [°C] -17.78 Chilled Water Coil:Package Code- Code: 36 (Manual Ball Valve with Memory
Sensible Capacity [kW] - Stop)
Rows / FPI / Circuits : -/-/- Chilled Water Coil:Unions

Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 • * Unit weight includes unit with wet coil(s) as selected.
◦ Does not include accessories
Total Full Load Amps : 1.60 • Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.00 / 15.00 440.
Fan Power Input [Watts@CFM] 142.03 • Sound data tested in accordance with AHRI-260-2012
• Sound Data Calculated at 242.1 L/s and 1345.05 RPM
Sound Data Calculated at 242.1 L/s and 1345.05 RPM • Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz • For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 73 60 54 54 52 45 39
Casing Radiated Free Inlet 64 63 59 57 52 47 43
Project Name: 21HEDS021 P Cogeneracion Coopervision PR JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 11/5/2020 6:17:56 AM
Contractor: Selection Date: 11/3/2020 7:53:08 AM
Sold To: Last Revision Date: 11/5/2020 5:33:01 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FHP09 1 FHP-D09 328.0 L/s 7.31 kW 5.57 kW
Unit Data
Model Size : 09 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [mm] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/6 Filter (Qty) Size : (1)20x10.5x1 Coil Face Area [m²] 0.2
Motor FLA : 2.1 (1)22.25x10.5x1 Weight* [kg] 42.2
Motor Type : PSC Filter Face Area [m²] 0.3
Capacity : High Capacity
Output Data Options
Altitude [m] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [L/s] 328.0 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [Pa] 59.72 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°C] 26.99/ 19.00 Galvanized Drain pan
LAT DB/WB [°C] 13.14/ 12.41 Return Air Options- Return: Rear No Duct Collar
Total Capacity [kW] 7.31 Thermostat Location- Remote Mounted Thermostat
Sensible Capacity [kW] 5.57 Thermostat- D03C Digital - 2 Pipe Cool - 3/SS
EWT/LWT [°C] 7.01/ 11.97 Chilled Water Coil: Piping Package Size - 1/2"
Fluid Flow [L/s] 0.353 Chilled Water Coil:2 Position Close-Off (24v Only)
Fluid P.D [kPa] 17.44 Chilled Water Coil:3-Way Control Valve
Fluid Velocity [m/s] 1.04 Chilled Water Coil:Actuator Position- Normally Closed - 2 Pos Close-Off
Rows / FPI / Circuits : 4 Row / 10 FPI / 5 Ckt Chilled Water Coil:Factory Mounted Piping Package
Coil Connection Size: [mm] 22.23 Chilled Water Coil:Galvanized Casing
Heating Data Chilled Water Coil:Left Hand Connection
EAT DB [°C] -17.78 Chilled Water Coil:Manual Air Vent
LAT DB [°C] -17.78 Chilled Water Coil:Package Code- Code: 36 (Manual Ball Valve with Memory
Sensible Capacity [kW] - Stop)
Rows / FPI / Circuits : -/-/- Chilled Water Coil:Unions

Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 • * Unit weight includes unit with wet coil(s) as selected.
◦ Does not include accessories
Total Full Load Amps : 2.10 • Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.63 / 15.00 440.
Fan Power Input [Watts@CFM] 206.85 • Sound data tested in accordance with AHRI-260-2012
• Sound Data Calculated at 328.0 L/s and 1330.09 RPM
Sound Data Calculated at 328.0 L/s and 1330.09 RPM • Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz • For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 67 61 56 56 53 47 41
Casing Radiated Free Inlet 63 64 59 57 52 47 43
Project Name: 21HEDS021 P Cogeneracion Coopervision PR JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 11/5/2020 6:17:56 AM
Contractor: Selection Date: 11/3/2020 8:03:04 AM
Sold To: Last Revision Date: 11/5/2020 6:15:18 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FNP12, FNP12 2 FNP12 503.2 L/s 13.85 kW 9.93 kW
Unit Data
Model Size : 12 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [mm] 3/8
Type : Horizontal High Performance (Motors) HP : (2) 1/6 Filter (Qty) Size : (2) 16x16 Coil Face Area [m²] 0.3
Motor FLA : 5.2 Filter Face Area [m²] 0.3 Weight* [kg] 88.9
Motor Type : PSC Inlet Direction : Rear
Capacity : Std. Capacity
Output Data Options
Altitude [m] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [L/s] 503.2 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [Pa] 59.72 Coil Casing- Galvanized Casing
Chilled Water Coil Data Control Enclosure Handing- Opposite of Coil 1
EAT DB/WB [°C] 26.99/ 19.00 Enclosure Mount- Unit Mounted
LAT DB/WB [°C] 10.90/ 10.54 Filter Bottom Access
Total Capacity [kW] 13.85 Galvanized Drain pan
Sensible Capacity [kW] 9.93 Standard Fiberglass
EWT/LWT [°C] 7.01/ 12.01 Thermostat Location- Remote Mounted Thermostat
Fluid Flow [L/s] 0.681 Thermostat- D03C Digital - 2 Pipe Cool - 3/SS
Fluid P.D [kPa] 51.48 Chilled Water Coil: Piping Package Size - 3/4"
Fluid Velocity [m/s] 1.40 Chilled Water Coil:2 Position Close-Off (24v Only)
Rows / FPI / Circuits : 6 Row / 10 FPI / 7 Ckt Chilled Water Coil:3-Way Control Valve
Coil Connection Size: [mm] 22.23 Chilled Water Coil:Actuator Position- Normally Closed - 2 Pos Close-Off
Heating Data Chilled Water Coil:Factory Mounted Piping Package
EAT DB [°C] -17.78 Chilled Water Coil:Manual Air Vent
LAT DB [°C] -17.78 Chilled Water Coil:Package Code- Code: 36 (Manual Ball Valve with Memory
Sensible Capacity [kW] - Stop)
Rows / FPI / Circuits : -/-/- Chilled Water Coil:Right Hand
Chilled Water Coil:Unions
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 • * Unit weight includes unit with wet coil(s) as selected.
◦ Does not include accessories
Total Full Load Amps : 5.20 • Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 5.85 / 15.00 440.
Fan Power Input [Watts@CFM] 396.28 • Sound data tested in accordance with AHRI-260-2012
• Sound Data Calculated at 503.2 L/s and 1111.81 RPM
Sound Data Calculated at 503.2 L/s and 1111.81 RPM • Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz • For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 72 68 66 65 62 60 51
Casing Radiated Free Inlet 76 69 67 67 62 58 53
Project Name: 21HEDS021 P Cogeneracion Coopervision PR JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 11/5/2020 6:17:56 AM
Contractor: Selection Date: 11/3/2020 8:27:49 AM
Sold To: Last Revision Date: 11/5/2020 5:34:59 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FNP14 1 FNP14 622.6 L/s 15.93 kW 11.71 kW
Unit Data
Model Size : 14 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [mm] 3/8
Type : Horizontal High Performance (Motors) HP : (2) 1/4 Filter (Qty) Size : (1) 16x16, & (1) 16x20 Coil Face Area [m²] 0.3
Motor FLA : 8.8 Filter Face Area [m²] 0.3 Weight* [kg] 96.6
Motor Type : PSC Inlet Direction : Rear
Capacity : Std. Capacity
Output Data Options
Altitude [m] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [L/s] 622.6 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [Pa] 59.72 Coil Casing- Galvanized Casing
Chilled Water Coil Data Control Enclosure Handing- Opposite of Coil 1
EAT DB/WB [°C] 26.99/ 19.00 Enclosure Mount- Unit Mounted
LAT DB/WB [°C] 11.66/ 11.22 Filter Bottom Access
Total Capacity [kW] 15.93 Galvanized Drain pan
Sensible Capacity [kW] 11.71 Standard Fiberglass
EWT/LWT [°C] 7.01/ 12.02 Thermostat Location- Remote Mounted Thermostat
Fluid Flow [L/s] 0.795 Thermostat- D03C Digital - 2 Pipe Cool - 3/SS
Fluid P.D [kPa] 27.47 Chilled Water Coil: Piping Package Size - 1"
Fluid Velocity [m/s] 1.16 Chilled Water Coil:2 Position Close-Off (24v Only)
Rows / FPI / Circuits : 6 Row / 10 FPI / 10 Ckt Chilled Water Coil:3-Way Control Valve
Coil Connection Size: [mm] 28.58 Chilled Water Coil:Actuator Position- Normally Closed - 2 Pos Close-Off
Heating Data Chilled Water Coil:Factory Mounted Piping Package
EAT DB [°C] -17.78 Chilled Water Coil:Manual Air Vent
LAT DB [°C] -17.78 Chilled Water Coil:Package Code- Code: 36 (Manual Ball Valve with Memory
Sensible Capacity [kW] - Stop)
Rows / FPI / Circuits : -/-/- Chilled Water Coil:Right Hand
Chilled Water Coil:Unions
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 • * Unit weight includes unit with wet coil(s) as selected.
◦ Does not include accessories
Total Full Load Amps : 8.80 • Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 9.90 / 15.00 440.
Fan Power Input [Watts@CFM] 519.23 • Sound data tested in accordance with AHRI-260-2012
• Sound Data Calculated at 622.6 L/s and 1109.91 RPM
Sound Data Calculated at 622.6 L/s and 1109.91 RPM • Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz • For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 70 68 67 66 63 61 52
Casing Radiated Free Inlet 70 68 65 63 61 60 55
Project Name: 21HEDS021 P Cogeneracion Coopervision PR JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 11/5/2020 6:17:56 AM
Contractor: Selection Date: 11/3/2020 8:33:00 AM
Sold To: Last Revision Date: 11/5/2020 5:36:51 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FNP12, FNP12 2 FNP12 599.0 L/s 12.44 kW 9.71 kW
Unit Data
Model Size : 12 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [mm] 3/8
Type : Horizontal High Performance (Motors) HP : (2) 1/6 Filter (Qty) Size : (2) 16x16 Coil Face Area [m²] 0.3
Motor FLA : 5.2 Filter Face Area [m²] 0.3 Weight* [kg] 80.7
Motor Type : PSC Inlet Direction : Rear
Capacity : Std. Capacity
Output Data Options
Altitude [m] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [L/s] 599.0 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [Pa] 59.72 Coil Casing- Galvanized Casing
Chilled Water Coil Data Control Enclosure Handing- Opposite of Coil 1
EAT DB/WB [°C] 26.99/ 19.00 Enclosure Mount- Unit Mounted
LAT DB/WB [°C] 13.77/ 12.86 Filter Bottom Access
Total Capacity [kW] 12.44 Galvanized Drain pan
Sensible Capacity [kW] 9.71 Standard Fiberglass
EWT/LWT [°C] 7.01/ 12.06 Thermostat Location- Remote Mounted Thermostat
Fluid Flow [L/s] 0.612 Thermostat- D03C Digital - 2 Pipe Cool - 3/SS
Fluid P.D [kPa] 28.46 Chilled Water Coil: Piping Package Size - 3/4"
Fluid Velocity [m/s] 1.25 Chilled Water Coil:2 Position Close-Off (24v Only)
Rows / FPI / Circuits : 4 Row / 10 FPI / 7 Ckt Chilled Water Coil:3-Way Control Valve
Coil Connection Size: [mm] 22.23 Chilled Water Coil:Actuator Position- Normally Closed - 2 Pos Close-Off
Heating Data Chilled Water Coil:Factory Mounted Piping Package
EAT DB [°C] -17.78 Chilled Water Coil:Manual Air Vent
LAT DB [°C] -17.78 Chilled Water Coil:Package Code- Code: 36 (Manual Ball Valve with Memory
Sensible Capacity [kW] - Stop)
Rows / FPI / Circuits : -/-/- Chilled Water Coil:Right Hand
Chilled Water Coil:Unions
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 • * Unit weight includes unit with wet coil(s) as selected.
◦ Does not include accessories
Total Full Load Amps : 5.20 • Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 5.85 / 15.00 440.
Fan Power Input [Watts@CFM] 449.23 • Sound data tested in accordance with AHRI-260-2012
• Sound Data Calculated at 599.0 L/s and 1085.52 RPM
Sound Data Calculated at 599.0 L/s and 1085.52 RPM • Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz • For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 70 67 66 65 62 60 52
Casing Radiated Free Inlet 73 68 67 67 62 58 53