You are on page 1of 1

Project Name: TBHD_11132023 Titus Contract No: Contract #

Location: Coil Version: 4.28a


Consultant/Engineer: Printed Date: 11/13/2023 9:54:18 AM
Contractor: Selection Date: 11/13/2023 9:50:19 AM
Sold To: Last Revision Date: 11/13/2023 9:50:51 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty Weight
FCU-02 1 TBH-D 1250 CFM 63.4 MBH 38.6 MBH 280 lb
Unit Data
Model Size : 16 Motor Qty :1 Filter : 2" 30% Pleated (MERV 8) Coil Tube Dia. [in.] 0.52
Type : Direct Drive Blower Coils Motor FLA : 6.90 Filter (Qty) Size : (2) 16x20x2 Tube Wall [in.] 0.016
Motor Type : Direct Drive ECM Fan Amps@CFM : 2.71 Filter Face Area [ft²] 4.4 Coil Face Area [ft²] 3.5
Motor HP : 1 Fan RPM@CFM : 1212

Output Data Options


Altitude [Ft.] 0 Access Door- Standard
Air Flow Rate [CFM] 1250 Control Enclosure Location- Standard
ESP [in.wg] 1.11 Drain Pan Handing- Right Hand
TSP [in.wg] 1.46 Drain Pan Material- IAQ Galvanized
Filter Type- 2" 30% Pleated (MERV 8)
Chilled Water Coil Data Inlet Option- None
EAT DB/WB [°F] 86.0/ 71.8 Insulation Type- Standard Fiberglass
LAT DB/WB [°F] 58.4/ 56.7 Motor Control- Select (3 Speed Adjustable)
Total Capacity [MBH] 63.4 Motor Handing- Right Hand
Sensible Capacity [MBH] 38.6 Motor Type- Direct Drive ECM
EWT/LWT [°F] 44.0/ 54.0 Speed Switch- Field Provided
Fluid Flow [gpm] 12.60 Unit Arrangement- Fan Arr. 3 (Horiz. Top Front)
Fluid P.D [ft.wg] 16.22 Chilled Water Coil:Coil Casing Material- Galvanized
Fluid Velocity [fps] 5.40 Chilled Water Coil:Coil Handing- Right Hand
Rows / FPI / Circuits : 4 Row/ 8 FPI / 4 Ckt Chilled Water Coil:Tube Wall- 0.016 in.
Coil Connection Size: [in.] 0.875
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [MBH] 0
Rows / FPI / Circuits : -/-/-

Special Quote (SQ)# 50517 Special Quote (SQ)# Special Quote (SQ)#
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data Unit weight includes unit wet coil(s) as selected.
V/P/HZ : 277/1/60 ECM Coils are manufactured in accordance with AHRI-410.
Total Full Load Amps : 6.90
MCA / MSCP : 8.63 / 15.00
Fan Power Input [Watts@CFM] 461

Sound Data Calculated at 1250 CFM, 1.46 in.wg, and 1212 RPM
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Ducted Discharge 83 85 74 70 70 66 66 60
Casing Rad. Free Inlet 71 69 64 56 55 51 46 38