Air System Sizing Summary for FCU-1101-A

Project Name: B-241 04/20/2023


Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-A Number of zones 1
Equipment Class CW AHU Floor Area 22.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.7 kW Load occurs at Jul 1400
Sensible coil load 3.3 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1400 296 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 296 L/s Leaving DB / WB 15.6 / 15.1 °C
Sum of peak zone L/s 296 L/s Coil ADP 14.6 °C
Sensible heat ratio 0.886 Bypass Factor 0.100
L/(s kW) 80.6 Resulting RH 56 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 160.5 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 296 L/s Fan motor BHP 0.02 BHP
Standard L/s 296 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 12.94 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 1 of 340


Zone Sizing Summary for FCU-1101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-A Number of zones 1
Equipment Class CW AHU Floor Area 22.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 296 296 12.94 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.4 Jul 1400 0.3 22.9

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1101-A 1 3.4 Jul 1400 296 0.3 22.9 12.94

Hourly Analysis Program 5.10 Page 2 of 340


Air System Design Load Summary for FCU-1101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 719 - 12 m² - -
Wall Transmission 0 m² 2 - 0 m² 1 -
Roof Transmission 23 m² 128 - 23 m² 44 -
Window Transmission 12 m² 448 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 940 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 229 W 229 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 344 W 343 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 307 20 0% 0 0
>> Total Zone Loads - 3376 420 - 252 0
Zone Conditioning - 3241 420 - 8 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 296 L/s 0 - 296 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 296 L/s 14 - 296 L/s -14 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3255 420 - -5 0
Central Cooling Coil - 3255 420 - 0 0
>> Total Conditioning - 3255 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 3 of 340


Zone Design Load Summary for FCU-1101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 719 - 12 m² - -
Wall Transmission 0 m² 2 - 0 m² 1 -
Roof Transmission 23 m² 128 - 23 m² 44 -
Window Transmission 12 m² 448 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 940 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 229 W 229 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 344 W 343 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 307 20 0% 0 0
>> Total Zone Loads - 3376 420 - 252 0

Hourly Analysis Program 5.10 Page 4 of 340


Air System Sizing Summary for FCU-1101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-B Number of zones 1
Equipment Class CW AHU Floor Area 29.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.1 kW Load occurs at Aug 1700
Sensible coil load 4.6 kW OA DB / WB 44.6 / 28.7 °C
Coil L/s at Aug 1700 412 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 412 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 412 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.891 Bypass Factor 0.100
L/(s kW) 80.0 Resulting RH 55 %
m²/kW 5.8 Design supply temp. 14.4 °C
W/m² 172.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.14 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 412 L/s Fan motor BHP 0.02 BHP
Standard L/s 411 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 13.81 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 5 of 340


Zone Sizing Summary for FCU-1101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-B Number of zones 1
Equipment Class CW AHU Floor Area 29.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 412 412 13.81 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.7 Jul 1700 0.3 29.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1101-B 1 4.7 Jul 1700 412 0.3 29.8 13.81

Hourly Analysis Program 5.10 Page 6 of 340


Air System Design Load Summary for FCU-1101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1379 - 16 m² - -
Wall Transmission 2 m² 31 - 2 m² 6 -
Roof Transmission 30 m² 167 - 30 m² 58 -
Window Transmission 16 m² 563 - 16 m² 263 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 34 m² 993 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 298 W 298 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 447 W 447 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 422 27 0% 0 0
>> Total Zone Loads - 4647 560 - 327 0
Zone Conditioning - 4563 560 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 412 L/s 0 - 412 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 412 L/s 19 - 412 L/s -19 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4582 560 - -13 0
Central Cooling Coil - 4582 561 - 0 0
>> Total Conditioning - 4582 561 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 7 of 340


Zone Design Load Summary for FCU-1101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1413 - 16 m² - -
Wall Transmission 2 m² 31 - 2 m² 6 -
Roof Transmission 30 m² 173 - 30 m² 58 -
Window Transmission 16 m² 563 - 16 m² 263 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 34 m² 993 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 298 W 298 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 447 W 447 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 426 27 0% 0 0
>> Total Zone Loads - 4690 560 - 327 0

Hourly Analysis Program 5.10 Page 8 of 340


Air System Sizing Summary for FCU-1101-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-C Number of zones 1
Equipment Class CW AHU Floor Area 56.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.9 kW Load occurs at Jul 1600
Sensible coil load 6.4 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 575 L/s Entering DB / WB 24.6 / 18.3 °C
Max block L/s 575 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 575 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.919 Bypass Factor 0.100
L/(s kW) 82.8 Resulting RH 55 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.19 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 575 L/s Fan motor BHP 0.03 BHP
Standard L/s 575 L/s Fan motor kW 0.03 kW
Actual max L/(s·m²) 10.21 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 9 of 340


Zone Sizing Summary for FCU-1101-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1101-C Number of zones 1
Equipment Class CW AHU Floor Area 56.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 575 575 10.21 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.6 Aug 1600 0.4 56.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1101-C 1 6.6 Aug 1600 575 0.4 56.3 10.21

Hourly Analysis Program 5.10 Page 10 of 340


Air System Design Load Summary for FCU-1101-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1371 - 16 m² - -
Wall Transmission 2 m² 28 - 2 m² 6 -
Roof Transmission 56 m² 319 - 56 m² 109 -
Window Transmission 16 m² 579 - 16 m² 263 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 56 m² 0 - 56 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 563 W 563 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 845 W 844 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 595 27 0% 0 0
>> Total Zone Loads - 6547 560 - 378 0
Zone Conditioning - 6359 560 - 17 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 575 L/s 0 - 575 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 575 L/s 27 - 575 L/s -27 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6386 560 - -10 0
Central Cooling Coil - 6386 560 - 0 0
>> Total Conditioning - 6386 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 11 of 340


Zone Design Load Summary for FCU-1101-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 16 m² 1385 - 16 m² - -
Wall Transmission 2 m² 29 - 2 m² 6 -
Roof Transmission 56 m² 309 - 56 m² 109 -
Window Transmission 16 m² 579 - 16 m² 263 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 56 m² 0 - 56 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 563 W 563 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 845 W 844 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 596 27 0% 0 0
>> Total Zone Loads - 6552 560 - 378 0

Hourly Analysis Program 5.10 Page 12 of 340


Air System Sizing Summary for FCU-1102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-A Number of zones 1
Equipment Class CW AHU Floor Area 26.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.2 kW Load occurs at Jun 1700
Sensible coil load 3.8 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 343 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 343 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 343 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.900 Bypass Factor 0.100
L/(s kW) 80.8 Resulting RH 55 %
m²/kW 6.1 Design supply temp. 14.4 °C
W/m² 163.2 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 343 L/s Fan motor BHP 0.02 BHP
Standard L/s 343 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 13.19 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 13 of 340


Zone Sizing Summary for FCU-1102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-A Number of zones 1
Equipment Class CW AHU Floor Area 26.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 343 343 13.19 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.9 Jul 1700 0.3 26.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1102-A 1 3.9 Jul 1700 343 0.3 26.0 13.19

Hourly Analysis Program 5.10 Page 14 of 340


Air System Design Load Summary for FCU-1102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 26 m² 150 - 26 m² 50 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 32 m² 917 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 390 W 390 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 352 20 0% 0 0
>> Total Zone Loads - 3876 420 - 258 0
Zone Conditioning - 3803 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 343 L/s 0 - 343 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 343 L/s 16 - 343 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3819 420 - -11 0
Central Cooling Coil - 3819 423 - 0 0
>> Total Conditioning - 3819 423 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 15 of 340


Zone Design Load Summary for FCU-1102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1112 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 26 m² 151 - 26 m² 50 -
Window Transmission 12 m² 443 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 32 m² 935 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 260 W 260 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 390 W 390 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 355 20 0% 0 0
>> Total Zone Loads - 3908 420 - 258 0

Hourly Analysis Program 5.10 Page 16 of 340


Air System Sizing Summary for FCU-1102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-B Number of zones 1
Equipment Class CW AHU Floor Area 23.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.7 kW Load occurs at Aug 1600
Sensible coil load 4.2 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 372 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 372 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 372 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.881 Bypass Factor 0.100
L/(s kW) 78.4 Resulting RH 55 %
m²/kW 4.9 Design supply temp. 14.4 °C
W/m² 202.7 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.13 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 372 L/s Fan motor BHP 0.02 BHP
Standard L/s 372 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 15.90 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 17 of 340


Zone Sizing Summary for FCU-1102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-B Number of zones 1
Equipment Class CW AHU Floor Area 23.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 372 372 15.90 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.2 Jul 1700 0.3 23.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1102-B 1 4.2 Jul 1700 372 0.3 23.4 15.90

Hourly Analysis Program 5.10 Page 18 of 340


Air System Design Load Summary for FCU-1102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1147 - 13 m² - -
Wall Transmission 3 m² 37 - 3 m² 8 -
Roof Transmission 23 m² 129 - 23 m² 45 -
Window Transmission 13 m² 479 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 38 m² 1129 - 38 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 234 W 234 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 351 W 351 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 385 27 0% 0 0
>> Total Zone Loads - 4237 560 - 271 0
Zone Conditioning - 4163 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 372 L/s 0 - 372 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 372 L/s 17 - 372 L/s -17 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4181 560 - -7 0
Central Cooling Coil - 4181 563 - 0 0
>> Total Conditioning - 4181 563 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 19 of 340


Zone Design Load Summary for FCU-1102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1170 - 13 m² - -
Wall Transmission 3 m² 40 - 3 m² 8 -
Roof Transmission 23 m² 136 - 23 m² 45 -
Window Transmission 13 m² 467 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 38 m² 1110 - 38 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 234 W 234 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 351 W 351 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 385 27 0% 0 0
>> Total Zone Loads - 4238 560 - 271 0

Hourly Analysis Program 5.10 Page 20 of 340


Air System Sizing Summary for FCU-1102-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-C Number of zones 1
Equipment Class CW AHU Floor Area 42.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.7 kW Load occurs at Jul 1700
Sensible coil load 5.1 kW OA DB / WB 44.6 / 28.7 °C
Coil L/s at Jul 1700 465 L/s Entering DB / WB 24.7 / 18.6 °C
Max block L/s 465 L/s Leaving DB / WB 15.6 / 15.1 °C
Sum of peak zone L/s 465 L/s Coil ADP 14.6 °C
Sensible heat ratio 0.901 Bypass Factor 0.100
L/(s kW) 82.2 Resulting RH 56 %
m²/kW 7.4 Design supply temp. 14.4 °C
W/m² 134.7 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.15 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 465 L/s Fan motor BHP 0.03 BHP
Standard L/s 465 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.08 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 21 of 340


Zone Sizing Summary for FCU-1102-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1102-C Number of zones 1
Equipment Class CW AHU Floor Area 42.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 465 465 11.08 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.3 Aug 1600 0.3 42.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1102-C 1 5.3 Aug 1600 465 0.3 42.0 11.08

Hourly Analysis Program 5.10 Page 22 of 340


Air System Design Load Summary for FCU-1102-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1112 - 12 m² - -
Wall Transmission 4 m² 48 - 4 m² 9 -
Roof Transmission 42 m² 244 - 42 m² 81 -
Window Transmission 12 m² 443 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 42 m² 0 - 42 m² 0 -
Partitions 54 m² 1577 - 54 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 420 W 420 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 630 W 630 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 482 27 0% 0 0
>> Total Zone Loads - 5301 560 - 298 0
Zone Conditioning - 5077 560 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 465 L/s 0 - 465 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 465 L/s 22 - 465 L/s -22 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5098 560 - -15 0
Central Cooling Coil - 5098 560 - 0 0
>> Total Conditioning - 5098 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 23 of 340


Zone Design Load Summary for FCU-1102-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 4 m² 45 - 4 m² 9 -
Roof Transmission 42 m² 231 - 42 m² 81 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 42 m² 0 - 42 m² 0 -
Partitions 54 m² 1604 - 54 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 420 W 420 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 630 W 630 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 482 27 0% 0 0
>> Total Zone Loads - 5303 560 - 298 0

Hourly Analysis Program 5.10 Page 24 of 340


Air System Sizing Summary for FCU-1103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-A Number of zones 1
Equipment Class CW AHU Floor Area 32.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.5 kW Load occurs at Sep 1500
Sensible coil load 6.1 kW OA DB / WB 44.9 / 28.5 °C
Coil L/s at Sep 1500 556 L/s Entering DB / WB 24.4 / 18.1 °C
Max block L/s 556 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 556 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.936 Bypass Factor 0.100
L/(s kW) 85.1 Resulting RH 55 %
m²/kW 5.0 Design supply temp. 14.4 °C
W/m² 201.8 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.18 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 556 L/s Fan motor BHP 0.03 BHP
Standard L/s 556 L/s Fan motor kW 0.03 kW
Actual max L/(s·m²) 17.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 25 of 340


Zone Sizing Summary for FCU-1103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-A Number of zones 1
Equipment Class CW AHU Floor Area 32.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 556 556 17.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.3 Oct 1500 0.6 32.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1103-A 1 6.3 Oct 1500 556 0.6 32.4 17.16

Hourly Analysis Program 5.10 Page 26 of 340


Air System Design Load Summary for FCU-1103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.9 °C / 28.5 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 29 m² 2020 - 29 m² - -
Wall Transmission 3 m² 31 - 3 m² 7 -
Roof Transmission 32 m² 157 - 32 m² 63 -
Window Transmission 29 m² 1004 - 29 m² 482 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 32 m² 0 - 32 m² 0 -
Partitions 46 m² 1322 - 46 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 486 W 486 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 560 20 0% 0 0
>> Total Zone Loads - 6164 420 - 552 0
Zone Conditioning - 6092 420 - 15 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 556 L/s 0 - 556 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 556 L/s 26 - 556 L/s -26 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6117 420 - -11 0
Central Cooling Coil - 6117 420 - 0 0
>> Total Conditioning - 6117 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 27 of 340


Zone Design Load Summary for FCU-1103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 27.3 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 29 m² 2374 - 29 m² - -
Wall Transmission 3 m² 32 - 3 m² 7 -
Roof Transmission 32 m² 132 - 32 m² 63 -
Window Transmission 29 m² 909 - 29 m² 482 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 32 m² 0 - 32 m² 0 -
Partitions 46 m² 1244 - 46 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 324 W 324 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 486 W 486 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 576 20 0% 0 0
>> Total Zone Loads - 6336 420 - 552 0

Hourly Analysis Program 5.10 Page 28 of 340


Air System Sizing Summary for FCU-1103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-B Number of zones 1
Equipment Class CW AHU Floor Area 24.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.3 kW Load occurs at Nov 1400
Sensible coil load 3.9 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 349 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 349 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 349 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.902 Bypass Factor 0.100
L/(s kW) 81.4 Resulting RH 55 %
m²/kW 5.8 Design supply temp. 14.4 °C
W/m² 173.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 349 L/s Fan motor BHP 0.02 BHP
Standard L/s 348 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 14.12 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 29 of 340


Zone Sizing Summary for FCU-1103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-B Number of zones 1
Equipment Class CW AHU Floor Area 24.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 349 349 14.12 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.0 Nov 1400 0.3 24.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1103-B 1 4.0 Nov 1400 349 0.3 24.7 14.12

Hourly Analysis Program 5.10 Page 30 of 340


Air System Design Load Summary for FCU-1103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1483 - 13 m² - -
Wall Transmission 1 m² 13 - 1 m² 3 -
Roof Transmission 25 m² 74 - 25 m² 48 -
Window Transmission 13 m² 330 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 35 m² 834 - 35 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 247 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 371 W 370 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 361 20 0% 0 0
>> Total Zone Loads - 3973 420 - 269 0
Zone Conditioning - 3843 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 349 L/s 0 - 349 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 349 L/s 16 - 349 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3859 420 - -7 0
Central Cooling Coil - 3859 421 - 0 0
>> Total Conditioning - 3859 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 31 of 340


Zone Design Load Summary for FCU-1103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1483 - 13 m² - -
Wall Transmission 1 m² 13 - 1 m² 3 -
Roof Transmission 25 m² 74 - 25 m² 48 -
Window Transmission 13 m² 330 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 25 m² 0 - 25 m² 0 -
Partitions 35 m² 834 - 35 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 247 W 247 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 371 W 370 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 361 20 0% 0 0
>> Total Zone Loads - 3973 420 - 269 0

Hourly Analysis Program 5.10 Page 32 of 340


Air System Sizing Summary for FCU-1103-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-C Number of zones 1
Equipment Class CW AHU Floor Area 47.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.8 kW Load occurs at Oct 1400
Sensible coil load 5.4 kW OA DB / WB 42.7 / 27.2 °C
Coil L/s at Oct 1400 484 L/s Entering DB / WB 24.6 / 18.2 °C
Max block L/s 484 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 484 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.928 Bypass Factor 0.100
L/(s kW) 83.4 Resulting RH 55 %
m²/kW 8.2 Design supply temp. 14.4 °C
W/m² 121.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.16 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 484 L/s Fan motor BHP 0.03 BHP
Standard L/s 484 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 10.12 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 33 of 340


Zone Sizing Summary for FCU-1103-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1103-C Number of zones 1
Equipment Class CW AHU Floor Area 47.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 484 484 10.12 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.5 Oct 1400 0.3 47.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1103-C 1 5.5 Oct 1400 484 0.3 47.8 10.12

Hourly Analysis Program 5.10 Page 34 of 340


Air System Design Load Summary for FCU-1103-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1222 - 13 m² - -
Wall Transmission 1 m² 13 - 1 m² 3 -
Roof Transmission 48 m² 194 - 48 m² 93 -
Window Transmission 13 m² 401 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 48 m² 0 - 48 m² 0 -
Partitions 65 m² 1729 - 65 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 478 W 478 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 717 W 717 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 501 20 0% 0 0
>> Total Zone Loads - 5514 420 - 314 0
Zone Conditioning - 5363 420 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 484 L/s 0 - 484 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 484 L/s 22 - 484 L/s -22 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5385 420 - -16 0
Central Cooling Coil - 5385 420 - 0 0
>> Total Conditioning - 5385 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 35 of 340


Zone Design Load Summary for FCU-1103-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 13 m² 1222 - 13 m² - -
Wall Transmission 1 m² 13 - 1 m² 3 -
Roof Transmission 48 m² 194 - 48 m² 93 -
Window Transmission 13 m² 401 - 13 m² 218 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 48 m² 0 - 48 m² 0 -
Partitions 65 m² 1729 - 65 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 478 W 478 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 717 W 717 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 501 20 0% 0 0
>> Total Zone Loads - 5514 420 - 314 0

Hourly Analysis Program 5.10 Page 36 of 340


Air System Sizing Summary for FCU-1104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-A Number of zones 1
Equipment Class CW AHU Floor Area 24.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1300
Sensible coil load 3.6 kW OA DB / WB 38.7 / 25.8 °C
Coil L/s at Nov 1300 332 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 332 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 332 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.895 Bypass Factor 0.100
L/(s kW) 82.2 Resulting RH 56 %
m²/kW 6.1 Design supply temp. 14.4 °C
W/m² 163.0 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 332 L/s Fan motor BHP 0.02 BHP
Standard L/s 332 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 13.40 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 37 of 340


Zone Sizing Summary for FCU-1104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-A Number of zones 1
Equipment Class CW AHU Floor Area 24.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 332 332 13.40 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.3 24.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1104-A 1 3.8 Nov 1400 332 0.3 24.8 13.40

Hourly Analysis Program 5.10 Page 38 of 340


Air System Design Load Summary for FCU-1104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.7 °C / 25.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1395 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 25 m² 75 - 25 m² 48 -
Window Transmission 12 m² 293 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 734 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 248 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 372 W 372 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 338 20 0% 0 0
>> Total Zone Loads - 3718 420 - 256 0
Zone Conditioning - 3605 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 332 L/s 0 - 332 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 332 L/s 15 - 332 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3620 420 - -6 0
Central Cooling Coil - 3620 423 - 0 0
>> Total Conditioning - 3620 423 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 39 of 340


Zone Design Load Summary for FCU-1104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 25 m² 75 - 25 m² 48 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 248 W 248 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 372 W 372 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 344 20 0% 0 0
>> Total Zone Loads - 3787 420 - 256 0

Hourly Analysis Program 5.10 Page 40 of 340


Air System Sizing Summary for FCU-1104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-B Number of zones 1
Equipment Class CW AHU Floor Area 23.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1400
Sensible coil load 3.6 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 328 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 328 L/s Leaving DB / WB 15.8 / 15.2 °C
Sum of peak zone L/s 328 L/s Coil ADP 14.8 °C
Sensible heat ratio 0.895 Bypass Factor 0.100
L/(s kW) 82.1 Resulting RH 56 %
m²/kW 5.8 Design supply temp. 14.4 °C
W/m² 172.2 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 328 L/s Fan motor BHP 0.02 BHP
Standard L/s 328 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 14.14 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 41 of 340


Zone Sizing Summary for FCU-1104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-B Number of zones 1
Equipment Class CW AHU Floor Area 23.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 328 328 14.14 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.3 23.2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1104-B 1 3.7 Nov 1400 328 0.3 23.2 14.14

Hourly Analysis Program 5.10 Page 42 of 340


Air System Design Load Summary for FCU-1104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 23 m² 70 - 23 m² 45 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 232 W 232 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 348 W 348 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 340 20 0% 0 0
>> Total Zone Loads - 3738 420 - 253 0
Zone Conditioning - 3559 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 328 L/s 0 - 328 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 328 L/s 15 - 328 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3574 420 - -10 0
Central Cooling Coil - 3574 421 - 0 0
>> Total Conditioning - 3574 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 43 of 340


Zone Design Load Summary for FCU-1104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 23 m² 70 - 23 m² 45 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 232 W 232 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 348 W 348 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 340 20 0% 0 0
>> Total Zone Loads - 3738 420 - 253 0

Hourly Analysis Program 5.10 Page 44 of 340


Air System Sizing Summary for FCU-1104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-C Number of zones 1
Equipment Class CW AHU Floor Area 43.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.6 kW Load occurs at Nov 1400
Sensible coil load 5.2 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 466 L/s Entering DB / WB 24.4 / 18.2 °C
Max block L/s 466 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 466 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.924 Bypass Factor 0.100
L/(s kW) 83.4 Resulting RH 55 %
m²/kW 7.8 Design supply temp. 14.4 °C
W/m² 128.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.15 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 466 L/s Fan motor BHP 0.03 BHP
Standard L/s 465 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 10.71 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 45 of 340


Zone Sizing Summary for FCU-1104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1104-C Number of zones 1
Equipment Class CW AHU Floor Area 43.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 466 466 10.71 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.3 Oct 1400 0.3 43.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1104-C 1 5.3 Oct 1400 466 0.3 43.5 10.71

Hourly Analysis Program 5.10 Page 46 of 340


Air System Design Load Summary for FCU-1104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 44 m² 131 - 44 m² 84 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 44 m² 0 - 44 m² 0 -
Partitions 66 m² 1573 - 66 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 435 W 435 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 653 W 652 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 478 20 0% 0 0
>> Total Zone Loads - 5255 420 - 292 0
Zone Conditioning - 5140 420 - 6 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 466 L/s 0 - 466 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 466 L/s 22 - 466 L/s -22 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5161 420 - -15 0
Central Cooling Coil - 5161 422 - 0 0
>> Total Conditioning - 5161 422 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 47 of 340


Zone Design Load Summary for FCU-1104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1160 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 44 m² 176 - 44 m² 84 -
Window Transmission 12 m² 381 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 44 m² 0 - 44 m² 0 -
Partitions 66 m² 1756 - 66 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 435 W 435 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 653 W 652 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 482 20 0% 0 0
>> Total Zone Loads - 5307 420 - 292 0

Hourly Analysis Program 5.10 Page 48 of 340


Air System Sizing Summary for FCU-1105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1105-A Number of zones 1
Equipment Class CW AHU Floor Area 19.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.8 kW Load occurs at Nov 1400
Sensible coil load 3.4 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 312 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 312 L/s Leaving DB / WB 15.7 / 15.2 °C
Sum of peak zone L/s 312 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.890 Bypass Factor 0.100
L/(s kW) 81.5 Resulting RH 56 %
m²/kW 5.1 Design supply temp. 14.4 °C
W/m² 196.1 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 312 L/s Fan motor BHP 0.02 BHP
Standard L/s 311 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 15.98 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 49 of 340


Zone Sizing Summary for FCU-1105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1105-A Number of zones 1
Equipment Class CW AHU Floor Area 19.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 312 312 15.98 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.6 Nov 1400 0.2 19.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1105-A 1 3.6 Nov 1400 312 0.2 19.5 15.98

Hourly Analysis Program 5.10 Page 50 of 340


Air System Design Load Summary for FCU-1105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1316 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 20 m² 59 - 20 m² 38 -
Window Transmission 11 m² 293 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 20 m² 0 - 20 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 195 W 195 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 293 W 292 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 323 20 0% 0 0
>> Total Zone Loads - 3551 420 - 232 0
Zone Conditioning - 3387 420 - 8 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 312 L/s 0 - 312 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 312 L/s 14 - 312 L/s -14 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3402 420 - -6 0
Central Cooling Coil - 3402 421 - 0 0
>> Total Conditioning - 3402 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 51 of 340


Zone Design Load Summary for FCU-1105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1316 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 20 m² 59 - 20 m² 38 -
Window Transmission 11 m² 293 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 20 m² 0 - 20 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 195 W 195 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 293 W 292 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 323 20 0% 0 0
>> Total Zone Loads - 3551 420 - 232 0

Hourly Analysis Program 5.10 Page 52 of 340


Air System Sizing Summary for FCU-1105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1105-B Number of zones 1
Equipment Class CW AHU Floor Area 25.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 328 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 328 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 328 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 80.4 Resulting RH 55 %
m²/kW 6.3 Design supply temp. 14.4 °C
W/m² 159.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 328 L/s Fan motor BHP 0.02 BHP
Standard L/s 328 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.82 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 53 of 340


Zone Sizing Summary for FCU-1105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1105-B Number of zones 1
Equipment Class CW AHU Floor Area 25.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 328 328 12.82 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.2 25.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1105-B 1 3.7 Nov 1400 328 0.2 25.6 12.82

Hourly Analysis Program 5.10 Page 54 of 340


Air System Design Load Summary for FCU-1105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1316 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 26 m² 77 - 26 m² 50 -
Window Transmission 11 m² 293 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 256 W 256 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 384 W 384 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 340 20 0% 0 0
>> Total Zone Loads - 3738 420 - 244 0
Zone Conditioning - 3647 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 328 L/s 0 - 328 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 328 L/s 15 - 328 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3662 420 - -6 0
Central Cooling Coil - 3662 420 - 0 0
>> Total Conditioning - 3662 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 55 of 340


Zone Design Load Summary for FCU-1105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1316 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 26 m² 77 - 26 m² 50 -
Window Transmission 11 m² 293 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 26 m² 0 - 26 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 256 W 256 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 384 W 384 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 340 20 0% 0 0
>> Total Zone Loads - 3738 420 - 244 0

Hourly Analysis Program 5.10 Page 56 of 340


Air System Sizing Summary for FCU-1106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-A Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1600
Sensible coil load 2.9 kW OA DB / WB 45.0 / 28.9 °C
Coil L/s at Jun 1600 260 L/s Entering DB / WB 24.5 / 18.4 °C
Max block L/s 260 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 260 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.872 Bypass Factor 0.100
L/(s kW) 77.9 Resulting RH 56 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 260 L/s Fan motor BHP 0.02 BHP
Standard L/s 259 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.61 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 57 of 340


Zone Sizing Summary for FCU-1106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-A Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 260 260 9.61 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.0 Jun 1600 0.2 27.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1106-A 1 3.0 Jun 1600 260 0.2 27.0 9.61

Hourly Analysis Program 5.10 Page 58 of 340


Air System Design Load Summary for FCU-1106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 241 - 7 m² - -
Wall Transmission 6 m² 49 - 6 m² 16 -
Roof Transmission 27 m² 152 - 27 m² 52 -
Window Transmission 7 m² 262 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 1050 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 270 W 270 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 405 W 405 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 269 20 0% 0 0
>> Total Zone Loads - 2957 420 - 191 0
Zone Conditioning - 2893 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 260 L/s 0 - 260 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 260 L/s 12 - 260 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2905 420 - -8 0
Central Cooling Coil - 2905 425 - 0 0
>> Total Conditioning - 2905 425 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 59 of 340


Zone Design Load Summary for FCU-1106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 241 - 7 m² - -
Wall Transmission 6 m² 49 - 6 m² 16 -
Roof Transmission 27 m² 152 - 27 m² 52 -
Window Transmission 7 m² 262 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 1050 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 270 W 270 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 405 W 405 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 269 20 0% 0 0
>> Total Zone Loads - 2957 420 - 191 0

Hourly Analysis Program 5.10 Page 60 of 340


Air System Sizing Summary for FCU-1106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-B Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Jun 1600
Sensible coil load 3.2 kW OA DB / WB 45.0 / 28.9 °C
Coil L/s at Jun 1600 284 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 284 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 284 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.883 Bypass Factor 0.100
L/(s kW) 79.2 Resulting RH 56 %
m²/kW 8.8 Design supply temp. 14.4 °C
W/m² 114.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 284 L/s Fan motor BHP 0.02 BHP
Standard L/s 284 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.04 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 61 of 340


Zone Sizing Summary for FCU-1106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-B Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 284 284 9.04 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.2 Jun 1600 0.2 31.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1106-B 1 3.2 Jun 1600 284 0.2 31.4 9.04

Hourly Analysis Program 5.10 Page 62 of 340


Air System Design Load Summary for FCU-1106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 241 - 7 m² - -
Wall Transmission 6 m² 49 - 6 m² 16 -
Roof Transmission 31 m² 177 - 31 m² 61 -
Window Transmission 7 m² 262 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 40 m² 1167 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 294 20 0% 0 0
>> Total Zone Loads - 3234 420 - 200 0
Zone Conditioning - 3150 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 284 L/s 0 - 284 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 284 L/s 13 - 284 L/s -13 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3163 420 - -9 0
Central Cooling Coil - 3163 420 - 0 0
>> Total Conditioning - 3163 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 63 of 340


Zone Design Load Summary for FCU-1106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 241 - 7 m² - -
Wall Transmission 6 m² 49 - 6 m² 16 -
Roof Transmission 31 m² 177 - 31 m² 61 -
Window Transmission 7 m² 262 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 40 m² 1167 - 40 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 294 20 0% 0 0
>> Total Zone Loads - 3234 420 - 200 0

Hourly Analysis Program 5.10 Page 64 of 340


Air System Sizing Summary for FCU-1106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 337 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 337 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.3 Resulting RH 56 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 147.8 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 65 of 340


Zone Sizing Summary for FCU-1106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1106-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-106-C 1 3.8 Nov 1400 337 0.2 27.7 12.16

Hourly Analysis Program 5.10 Page 66 of 340


Air System Design Load Summary for FCU-1106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0
Zone Conditioning - 3656 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3672 420 - -6 0
Central Cooling Coil - 3672 421 - 0 0
>> Total Conditioning - 3672 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 67 of 340


Zone Design Load Summary for FCU-1106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0

Hourly Analysis Program 5.10 Page 68 of 340


Air System Sizing Summary for FCU-1107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1107-A Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.6 kW Load occurs at Jul 1700
Sensible coil load 4.2 kW OA DB / WB 44.6 / 28.7 °C
Coil L/s at Jul 1700 381 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 381 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 381 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.909 Bypass Factor 0.100
L/(s kW) 82.4 Resulting RH 55 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 147.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 381 L/s Fan motor BHP 0.02 BHP
Standard L/s 381 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.14 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 69 of 340


Zone Sizing Summary for FCU-1107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1107-A Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 381 381 12.14 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.3 Jun 1600 0.3 31.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1107-A 1 4.3 Jun 1600 381 0.3 31.4 12.14

Hourly Analysis Program 5.10 Page 70 of 340


Air System Design Load Summary for FCU-1107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 375 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 31 m² 182 - 31 m² 61 -
Window Transmission 12 m² 443 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 64 m² 1869 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 392 20 0% 0 0
>> Total Zone Loads - 4317 420 - 272 0
Zone Conditioning - 4189 420 - 11 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 381 L/s 0 - 381 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 381 L/s 18 - 381 L/s -18 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4207 420 - -7 0
Central Cooling Coil - 4207 420 - 0 0
>> Total Conditioning - 4207 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 71 of 340


Zone Design Load Summary for FCU-1107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 31 m² 177 - 31 m² 61 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 64 m² 1867 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 395 20 0% 0 0
>> Total Zone Loads - 4343 420 - 272 0

Hourly Analysis Program 5.10 Page 72 of 340


Air System Sizing Summary for FCU-1107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1107-B Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1500
Sensible coil load 2.9 kW OA DB / WB 45.4 / 29.0 °C
Coil L/s at Jun 1500 265 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 265 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 265 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 6.9 Design supply temp. 14.4 °C
W/m² 145.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 265 L/s Fan motor BHP 0.02 BHP
Standard L/s 265 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 11.54 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 73 of 340


Zone Sizing Summary for FCU-1107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-1107-B Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 265 265 11.54 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.0 Jun 1700 0.3 23.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1107-B 1 3.0 Jun 1700 265 0.3 23.0 11.54

Hourly Analysis Program 5.10 Page 74 of 340


Air System Design Load Summary for FCU-1107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 378 - 12 m² - -
Wall Transmission 0 m² 2 - 0 m² 1 -
Roof Transmission 23 m² 128 - 23 m² 45 -
Window Transmission 12 m² 445 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 937 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 273 20 0% 0 0
>> Total Zone Loads - 2998 420 - 253 0
Zone Conditioning - 2917 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 265 L/s 0 - 265 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 265 L/s 12 - 265 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2929 420 - -8 0
Central Cooling Coil - 2929 420 - 0 0
>> Total Conditioning - 2929 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 75 of 340


Zone Design Load Summary for FCU-1107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 433 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 23 m² 133 - 23 m² 45 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 917 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 275 20 0% 0 0
>> Total Zone Loads - 3025 420 - 253 0

Hourly Analysis Program 5.10 Page 76 of 340


Air System Sizing Summary for FCU-11F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-11F-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 7.7 kW Load occurs at Jul 1700
Sensible coil load 6.5 kW OA DB / WB 44.6 / 28.7 °C
Coil L/s at Jul 1700 579 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 579 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 579 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.851 Bypass Factor 0.100
L/(s kW) 75.7 Resulting RH 56 %
m²/kW 14.3 Design supply temp. 14.4 °C
W/m² 69.9 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.21 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 579 L/s Fan motor BHP 0.03 BHP
Standard L/s 579 L/s Fan motor kW 0.03 kW
Actual max L/(s·m²) 5.29 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 77 of 340


Zone Sizing Summary for FCU-11F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:49PM

Air System Information


Air System Name FCU-11F-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 579 579 5.29 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 6.6 Jul 1600 0.2 109.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-11F-CORR 1 6.6 Jul 1600 579 0.2 109.5 5.29

Hourly Analysis Program 5.10 Page 78 of 340


Air System Design Load Summary for FCU-11F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 110 m² 635 - 110 m² 212 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1957 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 598 54 0% 0 0
>> Total Zone Loads - 6577 1136 - 212 0
Zone Conditioning - 6488 1136 - 8 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 579 L/s 0 - 579 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 579 L/s 27 - 579 L/s -27 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 6514 1136 - -19 0
Central Cooling Coil - 6514 1137 - 0 0
>> Total Conditioning - 6514 1137 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 79 of 340


Zone Design Load Summary for FCU-11F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 110 m² 622 - 110 m² 212 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1990 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 600 54 0% 0 0
>> Total Zone Loads - 6600 1136 - 212 0

Hourly Analysis Program 5.10 Page 80 of 340


Air System Sizing Summary for FCU-1F-101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-101-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 174.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 320 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.25 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 81 of 340


Zone Sizing Summary for FCU-1F-101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-101-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.25 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-101-A 1 3.7 Aug 1600 321 0.2 22.5 14.25

Hourly Analysis Program 5.10 Page 82 of 340


Air System Design Load Summary for FCU-1F-101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0
Zone Conditioning - 3490 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3504 420 - -6 0
Central Cooling Coil - 3504 420 - 0 0
>> Total Conditioning - 3504 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 83 of 340


Zone Design Load Summary for FCU-1F-101-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0

Hourly Analysis Program 5.10 Page 84 of 340


Air System Sizing Summary for FCU-1F-101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-101-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 85 of 340


Zone Sizing Summary for FCU-1F-101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-101-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-101-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 86 of 340


Air System Design Load Summary for FCU-1F-101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 87 of 340


Zone Design Load Summary for FCU-1F-101-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 88 of 340


Air System Sizing Summary for FCU-1F-102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-102-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 174.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 320 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.25 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 89 of 340


Zone Sizing Summary for FCU-1F-102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-102-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.25 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-102-A 1 3.7 Aug 1600 321 0.2 22.5 14.25

Hourly Analysis Program 5.10 Page 90 of 340


Air System Design Load Summary for FCU-1F-102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0
Zone Conditioning - 3490 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3504 420 - -6 0
Central Cooling Coil - 3504 420 - 0 0
>> Total Conditioning - 3504 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 91 of 340


Zone Design Load Summary for FCU-1F-102-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0

Hourly Analysis Program 5.10 Page 92 of 340


Air System Sizing Summary for FCU-1F-102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-102-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 93 of 340


Zone Sizing Summary for FCU-1F-102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-102-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-102-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 94 of 340


Air System Design Load Summary for FCU-1F-102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 95 of 340


Zone Design Load Summary for FCU-1F-102-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 96 of 340


Air System Sizing Summary for FCU-1F-103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-103-A Number of zones 1
Equipment Class CW AHU Floor Area 22.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.8 Design supply temp. 14.4 °C
W/m² 172.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 321 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.09 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 97 of 340


Zone Sizing Summary for FCU-1F-103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-103-A Number of zones 1
Equipment Class CW AHU Floor Area 22.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.09 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-103-A 1 3.7 Aug 1600 321 0.2 22.8 14.09

Hourly Analysis Program 5.10 Page 98 of 340


Air System Design Load Summary for FCU-1F-103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 228 W 228 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 342 W 342 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 333 20 0% 0 0
>> Total Zone Loads - 3660 420 - 208 0
Zone Conditioning - 3496 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3511 420 - -6 0
Central Cooling Coil - 3511 420 - 0 0
>> Total Conditioning - 3511 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 99 of 340


Zone Design Load Summary for FCU-1F-103-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 228 W 228 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 342 W 342 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 333 20 0% 0 0
>> Total Zone Loads - 3660 420 - 208 0

Hourly Analysis Program 5.10 Page 100 of 340


Air System Sizing Summary for FCU-1F-103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-103-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 101 of 340


Zone Sizing Summary for FCU-1F-103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-103-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-103-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 102 of 340


Air System Design Load Summary for FCU-1F-103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 103 of 340


Zone Design Load Summary for FCU-1F-103-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 104 of 340


Air System Sizing Summary for FCU-1F-104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-A Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.2 kW Load occurs at Oct 1500
Sensible coil load 4.8 kW OA DB / WB 43.1 / 27.3 °C
Coil L/s at Oct 1500 435 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 435 L/s Leaving DB / WB 15.8 / 15.2 °C
Sum of peak zone L/s 435 L/s Coil ADP 14.8 °C
Sensible heat ratio 0.919 Bypass Factor 0.100
L/(s kW) 83.9 Resulting RH 55 %
m²/kW 4.4 Design supply temp. 14.4 °C
W/m² 225.3 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.14 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 435 L/s Fan motor BHP 0.03 BHP
Standard L/s 435 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 18.91 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 105 of 340


Zone Sizing Summary for FCU-1F-104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-A Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 435 435 18.91 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.0 Oct 1500 0.4 23.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-104-A 1 5.0 Oct 1500 435 0.4 23.0 18.91

Hourly Analysis Program 5.10 Page 106 of 340


Air System Design Load Summary for FCU-1F-104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 27.3 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 2022 - 24 m² - -
Wall Transmission 1 m² 6 - 1 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 777 - 24 m² 412 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 865 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 450 20 0% 0 0
>> Total Zone Loads - 4955 420 - 413 0
Zone Conditioning - 4741 420 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 435 L/s 0 - 435 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 435 L/s 20 - 435 L/s -20 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4761 420 - -13 0
Central Cooling Coil - 4761 420 - 0 0
>> Total Conditioning - 4761 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 107 of 340


Zone Design Load Summary for FCU-1F-104-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 27.3 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 2022 - 24 m² - -
Wall Transmission 1 m² 6 - 1 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 777 - 24 m² 412 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 865 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 450 20 0% 0 0
>> Total Zone Loads - 4955 420 - 413 0

Hourly Analysis Program 5.10 Page 108 of 340


Air System Sizing Summary for FCU-1F-104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-B Number of zones 1
Equipment Class CW AHU Floor Area 28.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1300
Sensible coil load 3.6 kW OA DB / WB 38.7 / 25.8 °C
Coil L/s at Nov 1300 326 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 326 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 326 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.894 Bypass Factor 0.100
L/(s kW) 81.9 Resulting RH 56 %
m²/kW 7.2 Design supply temp. 14.4 °C
W/m² 138.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 326 L/s Fan motor BHP 0.02 BHP
Standard L/s 326 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.32 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 109 of 340


Zone Sizing Summary for FCU-1F-104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-B Number of zones 1
Equipment Class CW AHU Floor Area 28.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 326 326 11.32 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.2 28.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-104-B 1 3.7 Nov 1400 326 0.2 28.8 11.32

Hourly Analysis Program 5.10 Page 110 of 340


Air System Design Load Summary for FCU-1F-104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.7 °C / 25.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1321 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 277 - 12 m² 196 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 734 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 432 W 432 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3647 420 - 197 0
Zone Conditioning - 3547 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 326 L/s 0 - 326 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 326 L/s 15 - 326 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3562 420 - -10 0
Central Cooling Coil - 3562 420 - 0 0
>> Total Conditioning - 3562 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 111 of 340


Zone Design Load Summary for FCU-1F-104-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1334 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 297 - 12 m² 196 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 432 W 432 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 338 20 0% 0 0
>> Total Zone Loads - 3715 420 - 197 0

Hourly Analysis Program 5.10 Page 112 of 340


Air System Sizing Summary for FCU-1F-104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-C Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 337 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 337 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.899 Bypass Factor 0.100
L/(s kW) 81.6 Resulting RH 56 %
m²/kW 6.6 Design supply temp. 14.4 °C
W/m² 150.9 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.32 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 113 of 340


Zone Sizing Summary for FCU-1F-104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-104-C Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.32 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-104-C 1 3.8 Nov 1400 337 0.2 27.4 12.32

Hourly Analysis Program 5.10 Page 114 of 340


Air System Design Load Summary for FCU-1F-104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 858 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 204 0
Zone Conditioning - 3701 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3716 420 - -6 0
Central Cooling Coil - 3716 420 - 0 0
>> Total Conditioning - 3716 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 115 of 340


Zone Design Load Summary for FCU-1F-104-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 858 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 204 0

Hourly Analysis Program 5.10 Page 116 of 340


Air System Sizing Summary for FCU-1F-105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-105-A Number of zones 1
Equipment Class CW AHU Floor Area 22.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Dec 1500
Sensible coil load 3.5 kW OA DB / WB 38.0 / 24.8 °C
Coil L/s at Dec 1500 319 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 319 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 319 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.891 Bypass Factor 0.100
L/(s kW) 81.6 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 176.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 319 L/s Fan motor BHP 0.02 BHP
Standard L/s 318 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.41 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 117 of 340


Zone Sizing Summary for FCU-1F-105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-105-A Number of zones 1
Equipment Class CW AHU Floor Area 22.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 319 319 14.41 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.6 Nov 1400 0.2 22.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-105-A 1 3.6 Nov 1400 319 0.2 22.1 14.41

Hourly Analysis Program 5.10 Page 118 of 340


Air System Design Load Summary for FCU-1F-105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 24.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1448 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 270 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 32 m² 705 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 332 W 331 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 324 20 0% 0 0
>> Total Zone Loads - 3562 420 - 208 0
Zone Conditioning - 3464 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 319 L/s 0 - 319 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 319 L/s 15 - 319 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3479 420 - -6 0
Central Cooling Coil - 3479 425 - 0 0
>> Total Conditioning - 3479 425 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 119 of 340


Zone Design Load Summary for FCU-1F-105-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 332 W 331 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 330 20 0% 0 0
>> Total Zone Loads - 3630 420 - 208 0

Hourly Analysis Program 5.10 Page 120 of 340


Air System Sizing Summary for FCU-1F-105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-105-B Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 333 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 333 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 333 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.898 Bypass Factor 0.100
L/(s kW) 81.0 Resulting RH 55 %
m²/kW 6.7 Design supply temp. 14.4 °C
W/m² 150.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 333 L/s Fan motor BHP 0.02 BHP
Standard L/s 333 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 121 of 340


Zone Sizing Summary for FCU-1F-105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-105-B Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 333 333 12.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-105-B 1 3.8 Nov 1400 333 0.2 27.4 12.16

Hourly Analysis Program 5.10 Page 122 of 340


Air System Design Load Summary for FCU-1F-105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 6 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 345 20 0% 0 0
>> Total Zone Loads - 3796 420 - 205 0
Zone Conditioning - 3678 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 333 L/s 0 - 333 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 333 L/s 15 - 333 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3694 420 - -6 0
Central Cooling Coil - 3694 420 - 0 0
>> Total Conditioning - 3694 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 123 of 340


Zone Design Load Summary for FCU-1F-105-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 6 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 345 20 0% 0 0
>> Total Zone Loads - 3796 420 - 205 0

Hourly Analysis Program 5.10 Page 124 of 340


Air System Sizing Summary for FCU-1F-106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-A Number of zones 1
Equipment Class CW AHU Floor Area 24.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1400
Sensible coil load 3.5 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 324 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 324 L/s Leaving DB / WB 15.7 / 15.2 °C
Sum of peak zone L/s 324 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.894 Bypass Factor 0.100
L/(s kW) 82.0 Resulting RH 56 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 162.6 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 324 L/s Fan motor BHP 0.02 BHP
Standard L/s 324 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 13.33 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 125 of 340


Zone Sizing Summary for FCU-1F-106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-A Number of zones 1
Equipment Class CW AHU Floor Area 24.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 324 324 13.33 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.2 24.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-106-A 1 3.7 Nov 1400 324 0.2 24.3 13.33

Hourly Analysis Program 5.10 Page 126 of 340


Air System Design Load Summary for FCU-1F-106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 243 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 365 W 364 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3691 420 - 208 0
Zone Conditioning - 3516 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 324 L/s 0 - 324 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 324 L/s 15 - 324 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3531 420 - -10 0
Central Cooling Coil - 3531 420 - 0 0
>> Total Conditioning - 3531 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 127 of 340


Zone Design Load Summary for FCU-1F-106-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 243 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 365 W 364 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3691 420 - 208 0

Hourly Analysis Program 5.10 Page 128 of 340


Air System Sizing Summary for FCU-1F-106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-B Number of zones 1
Equipment Class CW AHU Floor Area 29.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 336 L/s Entering DB / WB 24.7 / 18.6 °C
Max block L/s 336 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 336 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.2 Resulting RH 56 %
m²/kW 7.1 Design supply temp. 14.4 °C
W/m² 140.2 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 336 L/s Fan motor BHP 0.02 BHP
Standard L/s 335 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.53 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 129 of 340


Zone Sizing Summary for FCU-1F-106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-B Number of zones 1
Equipment Class CW AHU Floor Area 29.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 336 336 11.53 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 29.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-106-B 1 3.8 Nov 1400 336 0.2 29.1 11.53

Hourly Analysis Program 5.10 Page 130 of 340


Air System Design Load Summary for FCU-1F-106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 291 W 291 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 437 W 436 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 348 20 0% 0 0
>> Total Zone Loads - 3823 420 - 208 0
Zone Conditioning - 3646 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 336 L/s 0 - 336 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 336 L/s 16 - 336 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3661 420 - -10 0
Central Cooling Coil - 3661 420 - 0 0
>> Total Conditioning - 3661 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 131 of 340


Zone Design Load Summary for FCU-1F-106-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 291 W 291 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 437 W 436 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 348 20 0% 0 0
>> Total Zone Loads - 3823 420 - 208 0

Hourly Analysis Program 5.10 Page 132 of 340


Air System Sizing Summary for FCU-1F-106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 337 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 337 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.3 Resulting RH 56 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 147.8 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 133 of 340


Zone Sizing Summary for FCU-1F-106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-106-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-106-C 1 3.8 Nov 1400 337 0.2 27.7 12.16

Hourly Analysis Program 5.10 Page 134 of 340


Air System Design Load Summary for FCU-1F-106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0
Zone Conditioning - 3656 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3672 420 - -6 0
Central Cooling Coil - 3672 421 - 0 0
>> Total Conditioning - 3672 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 135 of 340


Zone Design Load Summary for FCU-1F-106-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0

Hourly Analysis Program 5.10 Page 136 of 340


Air System Sizing Summary for FCU-1F-107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-A Number of zones 1
Equipment Class CW AHU Floor Area 22.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.7 kW Load occurs at Oct 1400
Sensible coil load 4.2 kW OA DB / WB 42.7 / 27.2 °C
Coil L/s at Oct 1400 383 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 383 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 383 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.910 Bypass Factor 0.100
L/(s kW) 82.4 Resulting RH 55 %
m²/kW 4.9 Design supply temp. 14.4 °C
W/m² 205.8 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.13 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 383 L/s Fan motor BHP 0.02 BHP
Standard L/s 383 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 16.96 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 137 of 340


Zone Sizing Summary for FCU-1F-107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-A Number of zones 1
Equipment Class CW AHU Floor Area 22.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 383 383 16.96 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.4 Oct 1400 0.2 22.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-107-A 1 4.4 Oct 1400 383 0.2 22.6 16.96

Hourly Analysis Program 5.10 Page 138 of 340


Air System Design Load Summary for FCU-1F-107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1084 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 11 m² 356 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 64 m² 1703 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 339 W 339 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 397 20 0% 0 0
>> Total Zone Loads - 4367 420 - 194 0
Zone Conditioning - 4214 420 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 383 L/s 0 - 383 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 383 L/s 18 - 383 L/s -18 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4232 420 - -8 0
Central Cooling Coil - 4232 420 - 0 0
>> Total Conditioning - 4232 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 139 of 340


Zone Design Load Summary for FCU-1F-107-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1084 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 11 m² 356 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 64 m² 1703 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 339 W 339 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 397 20 0% 0 0
>> Total Zone Loads - 4367 420 - 194 0

Hourly Analysis Program 5.10 Page 140 of 340


Air System Sizing Summary for FCU-1F-107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-B Number of zones 1
Equipment Class CW AHU Floor Area 28.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.6 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 334 L/s Entering DB / WB 24.7 / 18.6 °C
Max block L/s 334 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 334 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.1 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 142.8 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 334 L/s Fan motor BHP 0.02 BHP
Standard L/s 334 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.72 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 141 of 340


Zone Sizing Summary for FCU-1F-107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-B Number of zones 1
Equipment Class CW AHU Floor Area 28.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 334 334 11.72 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 28.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-107-B 1 3.8 Nov 1400 334 0.2 28.5 11.72

Hourly Analysis Program 5.10 Page 142 of 340


Air System Design Load Summary for FCU-1F-107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 428 W 427 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 346 20 0% 0 0
>> Total Zone Loads - 3807 420 - 208 0
Zone Conditioning - 3633 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 334 L/s 0 - 334 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 334 L/s 15 - 334 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3649 420 - -6 0
Central Cooling Coil - 3649 421 - 0 0
>> Total Conditioning - 3649 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 143 of 340


Zone Design Load Summary for FCU-1F-107-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 428 W 427 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 346 20 0% 0 0
>> Total Zone Loads - 3807 420 - 208 0

Hourly Analysis Program 5.10 Page 144 of 340


Air System Sizing Summary for FCU-1F-107-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-C Number of zones 1
Equipment Class CW AHU Floor Area 28.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Dec 1400
Sensible coil load 3.7 kW OA DB / WB 37.5 / 24.7 °C
Coil L/s at Dec 1400 337 L/s Entering DB / WB 24.4 / 18.3 °C
Max block L/s 337 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.898 Bypass Factor 0.100
L/(s kW) 81.4 Resulting RH 56 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 148.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.05 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 145 of 340


Zone Sizing Summary for FCU-1F-107-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-107-C Number of zones 1
Equipment Class CW AHU Floor Area 28.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.05 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 28.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-107-C 1 3.8 Nov 1400 337 0.2 28.0 12.05

Hourly Analysis Program 5.10 Page 146 of 340


Air System Design Load Summary for FCU-1F-107-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.5 °C / 24.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1482 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 260 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 734 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 280 W 280 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 420 W 420 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 344 20 0% 0 0
>> Total Zone Loads - 3783 420 - 208 0
Zone Conditioning - 3710 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3726 420 - -6 0
Central Cooling Coil - 3726 422 - 0 0
>> Total Conditioning - 3726 422 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 147 of 340


Zone Design Load Summary for FCU-1F-107-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 280 W 280 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 420 W 420 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 208 0

Hourly Analysis Program 5.10 Page 148 of 340


Air System Sizing Summary for FCU-1F-108-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-108-A Number of zones 1
Equipment Class CW AHU Floor Area 21.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.2 kW Load occurs at Jul 1600
Sensible coil load 3.8 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 341 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 341 L/s Leaving DB / WB 15.3 / 14.8 °C
Sum of peak zone L/s 341 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.900 Bypass Factor 0.100
L/(s kW) 81.4 Resulting RH 55 %
m²/kW 5.2 Design supply temp. 14.4 °C
W/m² 191.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 341 L/s Fan motor BHP 0.02 BHP
Standard L/s 341 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 15.57 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 149 of 340


Zone Sizing Summary for FCU-1F-108-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-108-A Number of zones 1
Equipment Class CW AHU Floor Area 21.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 341 341 15.57 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.9 Jun 1600 0.2 21.9

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-108-A 1 3.9 Jun 1600 341 0.2 21.9 15.57

Hourly Analysis Program 5.10 Page 150 of 340


Air System Design Load Summary for FCU-1F-108-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 354 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 219 W 219 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 329 W 328 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 353 20 0% 0 0
>> Total Zone Loads - 3880 420 - 211 0
Zone Conditioning - 3755 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 341 L/s 0 - 341 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 341 L/s 16 - 341 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3771 420 - -11 0
Central Cooling Coil - 3771 420 - 0 0
>> Total Conditioning - 3771 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 151 of 340


Zone Design Load Summary for FCU-1F-108-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 64 m² 1867 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 219 W 219 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 329 W 328 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 353 20 0% 0 0
>> Total Zone Loads - 3886 420 - 211 0

Hourly Analysis Program 5.10 Page 152 of 340


Air System Sizing Summary for FCU-1F-108-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-108-B Number of zones 1
Equipment Class CW AHU Floor Area 23.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1700
Sensible coil load 2.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 261 L/s Entering DB / WB 24.7 / 18.7 °C
Max block L/s 261 L/s Leaving DB / WB 15.6 / 15.0 °C
Sum of peak zone L/s 261 L/s Coil ADP 14.6 °C
Sensible heat ratio 0.872 Bypass Factor 0.100
L/(s kW) 79.6 Resulting RH 57 %
m²/kW 7.2 Design supply temp. 14.4 °C
W/m² 138.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 261 L/s Fan motor BHP 0.02 BHP
Standard L/s 261 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 11.01 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 153 of 340


Zone Sizing Summary for FCU-1F-108-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-108-B Number of zones 1
Equipment Class CW AHU Floor Area 23.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 261 261 11.01 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.0 Jun 1600 0.2 23.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-108-B 1 3.0 Jun 1600 261 0.2 23.7 11.01

Hourly Analysis Program 5.10 Page 154 of 340


Air System Design Load Summary for FCU-1F-108-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 433 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 237 W 237 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 356 W 355 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 270 20 0% 0 0
>> Total Zone Loads - 2971 420 - 211 0
Zone Conditioning - 2847 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 261 L/s 0 - 261 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 261 L/s 12 - 261 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2859 420 - -8 0
Central Cooling Coil - 2859 421 - 0 0
>> Total Conditioning - 2859 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 155 of 340


Zone Design Load Summary for FCU-1F-108-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 34 m² 992 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 237 W 237 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 356 W 355 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 270 20 0% 0 0
>> Total Zone Loads - 2973 420 - 211 0

Hourly Analysis Program 5.10 Page 156 of 340


Air System Sizing Summary for FCU-1F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.9 kW Load occurs at Jun 1500
Sensible coil load 5.8 kW OA DB / WB 45.4 / 29.0 °C
Coil L/s at Jun 1500 520 L/s Entering DB / WB 24.5 / 18.6 °C
Max block L/s 520 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 520 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.836 Bypass Factor 0.100
L/(s kW) 74.9 Resulting RH 57 %
m²/kW 15.8 Design supply temp. 14.4 °C
W/m² 63.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.19 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 520 L/s Fan motor BHP 0.03 BHP
Standard L/s 520 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 4.75 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 157 of 340


Zone Sizing Summary for FCU-1F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 520 520 4.75 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.9 Jul 1500 0.0 109.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-CORR 1 5.9 Jul 1500 520 0.0 109.5 4.75

Hourly Analysis Program 5.10 Page 158 of 340


Air System Design Load Summary for FCU-1F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1962 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 535 54 0% 0 0
>> Total Zone Loads - 5884 1136 - 0 0
Zone Conditioning - 5783 1136 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 520 L/s 0 - 520 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 520 L/s 24 - 520 L/s -24 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5807 1136 - -24 0
Central Cooling Coil - 5807 1137 - 0 0
>> Total Conditioning - 5807 1137 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 159 of 340


Zone Design Load Summary for FCU-1F-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1998 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 539 54 0% 0 0
>> Total Zone Loads - 5924 1136 - 0 0

Hourly Analysis Program 5.10 Page 160 of 340


Air System Sizing Summary for FCU-1F-GYM
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-GYM Number of zones 1
Equipment Class CW AHU Floor Area 91.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.2 kW Load occurs at Jun 1600
Sensible coil load 5.3 kW OA DB / WB 45.0 / 28.9 °C
Coil L/s at Jun 1600 469 L/s Entering DB / WB 24.5 / 18.4 °C
Max block L/s 469 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 469 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.857 Bypass Factor 0.100
L/(s kW) 76.1 Resulting RH 56 %
m²/kW 14.9 Design supply temp. 14.4 °C
W/m² 67.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.17 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 469 L/s Fan motor BHP 0.03 BHP
Standard L/s 469 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 5.13 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 161 of 340


Zone Sizing Summary for FCU-1F-GYM
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

Air System Information


Air System Name FCU-1F-GYM Number of zones 1
Equipment Class CW AHU Floor Area 91.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 469 469 5.13 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.3 Jul 1500 0.0 91.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-GYM 1 5.3 Jul 1500 469 0.0 91.5 5.13

Hourly Analysis Program 5.10 Page 162 of 340


Air System Design Load Summary for FCU-1F-GYM
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:50PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 92 m² 0 - 92 m² 0 -
Partitions 65 m² 1896 - 65 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 915 W 915 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 482 42 0% 0 0
>> Total Zone Loads - 5297 883 - 0 0
Zone Conditioning - 5255 883 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 469 L/s 0 - 469 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 469 L/s 22 - 469 L/s -22 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5277 883 - -22 0
Central Cooling Coil - 5277 884 - 0 0
>> Total Conditioning - 5277 884 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 163 of 340


Zone Design Load Summary for FCU-1F-GYM
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 92 m² 0 - 92 m² 0 -
Partitions 65 m² 1938 - 65 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 915 W 915 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 14 1005 841 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 486 42 0% 0 0
>> Total Zone Loads - 5344 883 - 0 0

Hourly Analysis Program 5.10 Page 164 of 340


Air System Sizing Summary for FCU-1F-MP HALL
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-1F-MP HALL Number of zones 1
Equipment Class CW AHU Floor Area 55.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.8 kW Load occurs at Jul 1400
Sensible coil load 4.0 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1400 357 L/s Entering DB / WB 24.5 / 18.6 °C
Max block L/s 357 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 357 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.841 Bypass Factor 0.100
L/(s kW) 75.0 Resulting RH 57 %
m²/kW 11.7 Design supply temp. 14.4 °C
W/m² 85.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.13 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 357 L/s Fan motor BHP 0.02 BHP
Standard L/s 357 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 6.41 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 165 of 340


Zone Sizing Summary for FCU-1F-MP HALL
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-1F-MP HALL Number of zones 1
Equipment Class CW AHU Floor Area 55.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 357 357 6.41 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Jul 1500 0.0 55.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-1F-MP HALL 1 4.1 Jul 1500 357 0.0 55.7 6.41

Hourly Analysis Program 5.10 Page 166 of 340


Air System Design Load Summary for FCU-1F-MP HALL
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 56 m² 0 - 56 m² 0 -
Partitions 43 m² 1264 - 43 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 557 W 557 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 368 36 0% 0 0
>> Total Zone Loads - 4050 757 - 0 0
Zone Conditioning - 3989 757 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 357 L/s 0 - 357 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 357 L/s 17 - 357 L/s -17 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4006 757 - -17 0
Central Cooling Coil - 4006 757 - 0 0
>> Total Conditioning - 4006 757 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 167 of 340


Zone Design Load Summary for FCU-1F-MP HALL
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 56 m² 0 - 56 m² 0 -
Partitions 43 m² 1282 - 43 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 557 W 557 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 12 862 721 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 370 36 0% 0 0
>> Total Zone Loads - 4071 757 - 0 0

Hourly Analysis Program 5.10 Page 168 of 340


Air System Sizing Summary for FCU-201-1001-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-201-1001-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 174.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 320 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.25 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 169 of 340


Zone Sizing Summary for FCU-201-1001-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-201-1001-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.25 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-201-1001-A 1 3.7 Aug 1600 321 0.2 22.5 14.25

Hourly Analysis Program 5.10 Page 170 of 340


Air System Design Load Summary for FCU-201-1001-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0
Zone Conditioning - 3490 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3504 420 - -6 0
Central Cooling Coil - 3504 420 - 0 0
>> Total Conditioning - 3504 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 171 of 340


Zone Design Load Summary for FCU-201-1001-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0

Hourly Analysis Program 5.10 Page 172 of 340


Air System Sizing Summary for FCU-201-1001-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-201-1001-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 173 of 340


Zone Sizing Summary for FCU-201-1001-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-201-1001-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-201-1001-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 174 of 340


Air System Design Load Summary for FCU-201-1001-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 175 of 340


Zone Design Load Summary for FCU-201-1001-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 176 of 340


Air System Sizing Summary for FCU-202-1002-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-202-1002-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 174.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 320 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.25 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 177 of 340


Zone Sizing Summary for FCU-202-1002-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-202-1002-A Number of zones 1
Equipment Class CW AHU Floor Area 22.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.25 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-202-1002-A 1 3.7 Aug 1600 321 0.2 22.5 14.25

Hourly Analysis Program 5.10 Page 178 of 340


Air System Design Load Summary for FCU-202-1002-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0
Zone Conditioning - 3490 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3504 420 - -6 0
Central Cooling Coil - 3504 420 - 0 0
>> Total Conditioning - 3504 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 179 of 340


Zone Design Load Summary for FCU-202-1002-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 225 W 225 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 338 W 337 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3652 420 - 208 0

Hourly Analysis Program 5.10 Page 180 of 340


Air System Sizing Summary for FCU-202-1002-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-202-1002-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 181 of 340


Zone Sizing Summary for FCU-202-1002-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-202-1002-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-202-1002-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 182 of 340


Air System Design Load Summary for FCU-202-1002-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 183 of 340


Zone Design Load Summary for FCU-202-1002-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 184 of 340


Air System Sizing Summary for FCU-203-1003-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-203-1003-A Number of zones 1
Equipment Class CW AHU Floor Area 22.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Aug 1600
Sensible coil load 3.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Aug 1600 321 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 321 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 321 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.893 Bypass Factor 0.100
L/(s kW) 81.7 Resulting RH 56 %
m²/kW 5.8 Design supply temp. 14.4 °C
W/m² 172.4 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 321 L/s Fan motor BHP 0.02 BHP
Standard L/s 321 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.09 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 185 of 340


Zone Sizing Summary for FCU-203-1003-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-203-1003-A Number of zones 1
Equipment Class CW AHU Floor Area 22.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 321 321 14.09 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Aug 1600 0.2 22.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-203-1003-A 1 3.7 Aug 1600 321 0.2 22.8 14.09

Hourly Analysis Program 5.10 Page 186 of 340


Air System Design Load Summary for FCU-203-1003-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 228 W 228 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 342 W 342 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 333 20 0% 0 0
>> Total Zone Loads - 3660 420 - 208 0
Zone Conditioning - 3496 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 321 L/s 0 - 321 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 321 L/s 15 - 321 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3511 420 - -6 0
Central Cooling Coil - 3511 420 - 0 0
>> Total Conditioning - 3511 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 187 of 340


Zone Design Load Summary for FCU-203-1003-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 228 W 228 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 342 W 342 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 333 20 0% 0 0
>> Total Zone Loads - 3660 420 - 208 0

Hourly Analysis Program 5.10 Page 188 of 340


Air System Sizing Summary for FCU-203-1003-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-203-1003-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1700
Sensible coil load 3.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 356 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 356 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 356 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.875 Bypass Factor 0.100
L/(s kW) 79.3 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 143.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 356 L/s Fan motor BHP 0.02 BHP
Standard L/s 356 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.37 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 189 of 340


Zone Sizing Summary for FCU-203-1003-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-203-1003-B Number of zones 1
Equipment Class CW AHU Floor Area 31.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 356 356 11.37 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Aug 1600 0.2 31.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-203-1003-B 1 4.1 Aug 1600 356 0.2 31.3 11.37

Hourly Analysis Program 5.10 Page 190 of 340


Air System Design Load Summary for FCU-203-1003-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1114 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 365 27 0% 0 0
>> Total Zone Loads - 4016 560 - 208 0
Zone Conditioning - 3913 560 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 356 L/s 0 - 356 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 356 L/s 16 - 356 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3930 560 - -6 0
Central Cooling Coil - 3930 560 - 0 0
>> Total Conditioning - 3930 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 191 of 340


Zone Design Load Summary for FCU-203-1003-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1090 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 313 W 313 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 470 W 469 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 369 27 0% 0 0
>> Total Zone Loads - 4056 560 - 208 0

Hourly Analysis Program 5.10 Page 192 of 340


Air System Sizing Summary for FCU-204-1004-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-A Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.2 kW Load occurs at Oct 1500
Sensible coil load 4.8 kW OA DB / WB 43.1 / 27.3 °C
Coil L/s at Oct 1500 435 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 435 L/s Leaving DB / WB 15.8 / 15.2 °C
Sum of peak zone L/s 435 L/s Coil ADP 14.8 °C
Sensible heat ratio 0.919 Bypass Factor 0.100
L/(s kW) 83.9 Resulting RH 55 %
m²/kW 4.4 Design supply temp. 14.4 °C
W/m² 225.3 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.14 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 435 L/s Fan motor BHP 0.03 BHP
Standard L/s 435 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 18.91 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 193 of 340


Zone Sizing Summary for FCU-204-1004-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-A Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 435 435 18.91 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.0 Oct 1500 0.4 23.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-204-1004-A 1 5.0 Oct 1500 435 0.4 23.0 18.91

Hourly Analysis Program 5.10 Page 194 of 340


Air System Design Load Summary for FCU-204-1004-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 27.3 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 2022 - 24 m² - -
Wall Transmission 1 m² 6 - 1 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 777 - 24 m² 412 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 865 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 450 20 0% 0 0
>> Total Zone Loads - 4955 420 - 413 0
Zone Conditioning - 4741 420 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 435 L/s 0 - 435 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 435 L/s 20 - 435 L/s -20 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4761 420 - -13 0
Central Cooling Coil - 4761 420 - 0 0
>> Total Conditioning - 4761 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 195 of 340


Zone Design Load Summary for FCU-204-1004-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.1 °C / 27.3 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 24 m² 2022 - 24 m² - -
Wall Transmission 1 m² 6 - 1 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 24 m² 777 - 24 m² 412 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 865 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 450 20 0% 0 0
>> Total Zone Loads - 4955 420 - 413 0

Hourly Analysis Program 5.10 Page 196 of 340


Air System Sizing Summary for FCU-204-1004-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-B Number of zones 1
Equipment Class CW AHU Floor Area 28.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1300
Sensible coil load 3.6 kW OA DB / WB 38.7 / 25.8 °C
Coil L/s at Nov 1300 326 L/s Entering DB / WB 24.6 / 18.5 °C
Max block L/s 326 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 326 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.894 Bypass Factor 0.100
L/(s kW) 81.9 Resulting RH 56 %
m²/kW 7.2 Design supply temp. 14.4 °C
W/m² 138.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 326 L/s Fan motor BHP 0.02 BHP
Standard L/s 326 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.32 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 197 of 340


Zone Sizing Summary for FCU-204-1004-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-B Number of zones 1
Equipment Class CW AHU Floor Area 28.8 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 326 326 11.32 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.2 28.8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-204-1004-B 1 3.7 Nov 1400 326 0.2 28.8 11.32

Hourly Analysis Program 5.10 Page 198 of 340


Air System Design Load Summary for FCU-204-1004-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.7 °C / 25.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1321 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 277 - 12 m² 196 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 734 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 432 W 432 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 332 20 0% 0 0
>> Total Zone Loads - 3647 420 - 197 0
Zone Conditioning - 3547 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 326 L/s 0 - 326 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 326 L/s 15 - 326 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3562 420 - -10 0
Central Cooling Coil - 3562 420 - 0 0
>> Total Conditioning - 3562 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 199 of 340


Zone Design Load Summary for FCU-204-1004-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1334 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 297 - 12 m² 196 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 432 W 432 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 338 20 0% 0 0
>> Total Zone Loads - 3715 420 - 197 0

Hourly Analysis Program 5.10 Page 200 of 340


Air System Sizing Summary for FCU-204-1004-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-C Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 337 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 337 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.899 Bypass Factor 0.100
L/(s kW) 81.6 Resulting RH 56 %
m²/kW 6.6 Design supply temp. 14.4 °C
W/m² 150.9 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.32 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 201 of 340


Zone Sizing Summary for FCU-204-1004-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-204-1004-C Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.32 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-204-1004-C 1 3.8 Nov 1400 337 0.2 27.4 12.32

Hourly Analysis Program 5.10 Page 202 of 340


Air System Design Load Summary for FCU-204-1004-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 858 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 204 0
Zone Conditioning - 3701 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3716 420 - -6 0
Central Cooling Coil - 3716 420 - 0 0
>> Total Conditioning - 3716 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 203 of 340


Zone Design Load Summary for FCU-204-1004-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 36 m² 858 - 36 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 204 0

Hourly Analysis Program 5.10 Page 204 of 340


Air System Sizing Summary for FCU-205-1005-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-205-1005-A Number of zones 1
Equipment Class CW AHU Floor Area 22.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Dec 1500
Sensible coil load 3.5 kW OA DB / WB 38.0 / 24.8 °C
Coil L/s at Dec 1500 319 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 319 L/s Leaving DB / WB 15.5 / 14.9 °C
Sum of peak zone L/s 319 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.891 Bypass Factor 0.100
L/(s kW) 81.6 Resulting RH 56 %
m²/kW 5.7 Design supply temp. 14.4 °C
W/m² 176.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 319 L/s Fan motor BHP 0.02 BHP
Standard L/s 318 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 14.41 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 205 of 340


Zone Sizing Summary for FCU-205-1005-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-205-1005-A Number of zones 1
Equipment Class CW AHU Floor Area 22.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 319 319 14.41 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.6 Nov 1400 0.2 22.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-205-1005-A 1 3.6 Nov 1400 319 0.2 22.1 14.41

Hourly Analysis Program 5.10 Page 206 of 340


Air System Design Load Summary for FCU-205-1005-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 38.0 °C / 24.8 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1448 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 270 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 32 m² 705 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 332 W 331 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 324 20 0% 0 0
>> Total Zone Loads - 3562 420 - 208 0
Zone Conditioning - 3464 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 319 L/s 0 - 319 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 319 L/s 15 - 319 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3479 420 - -6 0
Central Cooling Coil - 3479 425 - 0 0
>> Total Conditioning - 3479 425 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 207 of 340


Zone Design Load Summary for FCU-205-1005-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 221 W 221 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 332 W 331 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 330 20 0% 0 0
>> Total Zone Loads - 3630 420 - 208 0

Hourly Analysis Program 5.10 Page 208 of 340


Air System Sizing Summary for FCU-205-1005-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-205-1005-B Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 333 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 333 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 333 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.898 Bypass Factor 0.100
L/(s kW) 81.0 Resulting RH 55 %
m²/kW 6.7 Design supply temp. 14.4 °C
W/m² 150.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 333 L/s Fan motor BHP 0.02 BHP
Standard L/s 333 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 209 of 340


Zone Sizing Summary for FCU-205-1005-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:51PM

Air System Information


Air System Name FCU-205-1005-B Number of zones 1
Equipment Class CW AHU Floor Area 27.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 333 333 12.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-205-1005-B 1 3.8 Nov 1400 333 0.2 27.4 12.16

Hourly Analysis Program 5.10 Page 210 of 340


Air System Design Load Summary for FCU-205-1005-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 6 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 345 20 0% 0 0
>> Total Zone Loads - 3796 420 - 205 0
Zone Conditioning - 3678 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 333 L/s 0 - 333 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 333 L/s 15 - 333 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3694 420 - -6 0
Central Cooling Coil - 3694 420 - 0 0
>> Total Conditioning - 3694 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 211 of 340


Zone Design Load Summary for FCU-205-1005-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1383 - 12 m² - -
Wall Transmission 0 m² 6 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 308 - 12 m² 203 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 274 W 274 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 411 W 411 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 345 20 0% 0 0
>> Total Zone Loads - 3796 420 - 205 0

Hourly Analysis Program 5.10 Page 212 of 340


Air System Sizing Summary for FCU-206-1006-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-A Number of zones 1
Equipment Class CW AHU Floor Area 24.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Nov 1400
Sensible coil load 3.5 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 324 L/s Entering DB / WB 24.8 / 18.7 °C
Max block L/s 324 L/s Leaving DB / WB 15.7 / 15.2 °C
Sum of peak zone L/s 324 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.894 Bypass Factor 0.100
L/(s kW) 82.0 Resulting RH 56 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 162.6 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.1 K

Supply Fan Sizing Data


Actual max L/s 324 L/s Fan motor BHP 0.02 BHP
Standard L/s 324 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 13.33 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 213 of 340


Zone Sizing Summary for FCU-206-1006-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-A Number of zones 1
Equipment Class CW AHU Floor Area 24.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 324 324 13.33 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Nov 1400 0.2 24.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-206-1006-A 1 3.7 Nov 1400 324 0.2 24.3 13.33

Hourly Analysis Program 5.10 Page 214 of 340


Air System Design Load Summary for FCU-206-1006-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 243 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 365 W 364 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3691 420 - 208 0
Zone Conditioning - 3516 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 324 L/s 0 - 324 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 324 L/s 15 - 324 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3531 420 - -10 0
Central Cooling Coil - 3531 420 - 0 0
>> Total Conditioning - 3531 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 215 of 340


Zone Design Load Summary for FCU-206-1006-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 243 W 243 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 365 W 364 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3691 420 - 208 0

Hourly Analysis Program 5.10 Page 216 of 340


Air System Sizing Summary for FCU-206-1006-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-B Number of zones 1
Equipment Class CW AHU Floor Area 29.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 336 L/s Entering DB / WB 24.7 / 18.6 °C
Max block L/s 336 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 336 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.2 Resulting RH 56 %
m²/kW 7.1 Design supply temp. 14.4 °C
W/m² 140.2 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 336 L/s Fan motor BHP 0.02 BHP
Standard L/s 335 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.53 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 217 of 340


Zone Sizing Summary for FCU-206-1006-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-B Number of zones 1
Equipment Class CW AHU Floor Area 29.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 336 336 11.53 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 29.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-206-1006-B 1 3.8 Nov 1400 336 0.2 29.1 11.53

Hourly Analysis Program 5.10 Page 218 of 340


Air System Design Load Summary for FCU-206-1006-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 291 W 291 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 437 W 436 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 348 20 0% 0 0
>> Total Zone Loads - 3823 420 - 208 0
Zone Conditioning - 3646 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 336 L/s 0 - 336 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 336 L/s 16 - 336 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3661 420 - -10 0
Central Cooling Coil - 3661 420 - 0 0
>> Total Conditioning - 3661 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 219 of 340


Zone Design Load Summary for FCU-206-1006-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 291 W 291 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 437 W 436 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 348 20 0% 0 0
>> Total Zone Loads - 3823 420 - 208 0

Hourly Analysis Program 5.10 Page 220 of 340


Air System Sizing Summary for FCU-206-1006-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.7 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 337 L/s Entering DB / WB 24.8 / 18.6 °C
Max block L/s 337 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.3 Resulting RH 56 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 147.8 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.16 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 221 of 340


Zone Sizing Summary for FCU-206-1006-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-206-1006-C Number of zones 1
Equipment Class CW AHU Floor Area 27.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.16 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 27.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-206-1006-C 1 3.8 Nov 1400 337 0.2 27.7 12.16

Hourly Analysis Program 5.10 Page 222 of 340


Air System Design Load Summary for FCU-206-1006-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0
Zone Conditioning - 3656 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3672 420 - -6 0
Central Cooling Coil - 3672 421 - 0 0
>> Total Conditioning - 3672 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 223 of 340


Zone Design Load Summary for FCU-206-1006-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 277 W 277 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 416 W 415 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 349 20 0% 0 0
>> Total Zone Loads - 3837 420 - 208 0

Hourly Analysis Program 5.10 Page 224 of 340


Air System Sizing Summary for FCU-207-1007-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-207-1007-A Number of zones 1
Equipment Class CW AHU Floor Area 22.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.7 kW Load occurs at Oct 1400
Sensible coil load 4.2 kW OA DB / WB 42.7 / 27.2 °C
Coil L/s at Oct 1400 383 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 383 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 383 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.910 Bypass Factor 0.100
L/(s kW) 82.4 Resulting RH 55 %
m²/kW 4.9 Design supply temp. 14.4 °C
W/m² 205.8 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.13 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 383 L/s Fan motor BHP 0.02 BHP
Standard L/s 383 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 16.96 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 225 of 340


Zone Sizing Summary for FCU-207-1007-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-207-1007-A Number of zones 1
Equipment Class CW AHU Floor Area 22.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 383 383 16.96 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.4 Oct 1400 0.2 22.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-207-1007-A 1 4.4 Oct 1400 383 0.2 22.6 16.96

Hourly Analysis Program 5.10 Page 226 of 340


Air System Design Load Summary for FCU-207-1007-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1084 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 11 m² 356 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 64 m² 1703 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 339 W 339 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 397 20 0% 0 0
>> Total Zone Loads - 4367 420 - 194 0
Zone Conditioning - 4214 420 - 10 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 383 L/s 0 - 383 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 383 L/s 18 - 383 L/s -18 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4232 420 - -8 0
Central Cooling Coil - 4232 420 - 0 0
>> Total Conditioning - 4232 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 227 of 340


Zone Design Load Summary for FCU-207-1007-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 42.7 °C / 27.2 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 11 m² 1084 - 11 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 11 m² 356 - 11 m² 194 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 64 m² 1703 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 226 W 226 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 339 W 339 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 397 20 0% 0 0
>> Total Zone Loads - 4367 420 - 194 0

Hourly Analysis Program 5.10 Page 228 of 340


Air System Sizing Summary for FCU-207-1007-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-207-1007-B Number of zones 1
Equipment Class CW AHU Floor Area 28.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Nov 1400
Sensible coil load 3.6 kW OA DB / WB 39.9 / 26.0 °C
Coil L/s at Nov 1400 334 L/s Entering DB / WB 24.7 / 18.6 °C
Max block L/s 334 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 334 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.897 Bypass Factor 0.100
L/(s kW) 82.1 Resulting RH 56 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 142.8 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 334 L/s Fan motor BHP 0.02 BHP
Standard L/s 334 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.72 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 229 of 340


Zone Sizing Summary for FCU-207-1007-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

Air System Information


Air System Name FCU-207-1007-B Number of zones 1
Equipment Class CW AHU Floor Area 28.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 334 334 11.72 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 28.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-207-1007-B 1 3.8 Nov 1400 334 0.2 28.5 11.72

Hourly Analysis Program 5.10 Page 230 of 340


Air System Design Load Summary for FCU-207-1007-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:52PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 428 W 427 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 346 20 0% 0 0
>> Total Zone Loads - 3807 420 - 208 0
Zone Conditioning - 3633 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 334 L/s 0 - 334 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 334 L/s 15 - 334 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3649 420 - -6 0
Central Cooling Coil - 3649 421 - 0 0
>> Total Conditioning - 3649 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 231 of 340


Zone Design Load Summary for FCU-207-1007-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 29 m² 0 - 29 m² 0 -
Partitions 32 m² 762 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 285 W 285 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 428 W 427 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 346 20 0% 0 0
>> Total Zone Loads - 3807 420 - 208 0

Hourly Analysis Program 5.10 Page 232 of 340


Air System Sizing Summary for FCU-207-1007-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-207-1007-C Number of zones 1
Equipment Class CW AHU Floor Area 28.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.1 kW Load occurs at Dec 1400
Sensible coil load 3.7 kW OA DB / WB 37.5 / 24.7 °C
Coil L/s at Dec 1400 337 L/s Entering DB / WB 24.4 / 18.3 °C
Max block L/s 337 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 337 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.898 Bypass Factor 0.100
L/(s kW) 81.4 Resulting RH 56 %
m²/kW 6.8 Design supply temp. 14.4 °C
W/m² 148.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 337 L/s Fan motor BHP 0.02 BHP
Standard L/s 337 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.05 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 233 of 340


Zone Sizing Summary for FCU-207-1007-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-207-1007-C Number of zones 1
Equipment Class CW AHU Floor Area 28.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 337 337 12.05 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.8 Nov 1400 0.2 28.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-207-1007-C 1 3.8 Nov 1400 337 0.2 28.0 12.05

Hourly Analysis Program 5.10 Page 234 of 340


Air System Design Load Summary for FCU-207-1007-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 37.5 °C / 24.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1482 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 260 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 734 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 280 W 280 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 420 W 420 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 344 20 0% 0 0
>> Total Zone Loads - 3783 420 - 208 0
Zone Conditioning - 3710 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 337 L/s 0 - 337 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 337 L/s 16 - 337 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3726 420 - -6 0
Central Cooling Coil - 3726 422 - 0 0
>> Total Conditioning - 3726 422 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 235 of 340


Zone Design Load Summary for FCU-207-1007-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 39.9 °C / 26.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 1409 - 12 m² - -
Wall Transmission 0 m² 4 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 314 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 810 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 280 W 280 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 420 W 420 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 350 20 0% 0 0
>> Total Zone Loads - 3846 420 - 208 0

Hourly Analysis Program 5.10 Page 236 of 340


Air System Sizing Summary for FCU-208-1008-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-208-1008-A Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.0 kW Load occurs at Jul 1600
Sensible coil load 3.6 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 325 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 325 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 325 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.895 Bypass Factor 0.100
L/(s kW) 81.1 Resulting RH 56 %
m²/kW 6.7 Design supply temp. 14.4 °C
W/m² 148.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 325 L/s Fan motor BHP 0.02 BHP
Standard L/s 324 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 12.02 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 237 of 340


Zone Sizing Summary for FCU-208-1008-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-208-1008-A Number of zones 1
Equipment Class CW AHU Floor Area 27.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 325 325 12.02 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.7 Jul 1600 0.1 27.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-208-1008-A 1 3.7 Jul 1600 325 0.1 27.0 12.02

Hourly Analysis Program 5.10 Page 238 of 340


Air System Design Load Summary for FCU-208-1008-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 210 - 7 m² - -
Wall Transmission 6 m² 48 - 6 m² 16 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 270 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 270 W 270 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 405 W 405 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3698 420 - 139 0
Zone Conditioning - 3568 420 - 9 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 325 L/s 0 - 325 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 325 L/s 15 - 325 L/s -15 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3583 420 - -6 0
Central Cooling Coil - 3583 420 - 0 0
>> Total Conditioning - 3583 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 239 of 340


Zone Design Load Summary for FCU-208-1008-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 7 m² 210 - 7 m² - -
Wall Transmission 6 m² 48 - 6 m² 16 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 7 m² 270 - 7 m² 123 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 27 m² 0 - 27 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 270 W 270 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 405 W 405 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 336 20 0% 0 0
>> Total Zone Loads - 3698 420 - 139 0

Hourly Analysis Program 5.10 Page 240 of 340


Air System Sizing Summary for FCU-208-1008-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-208-1008-B Number of zones 1
Equipment Class CW AHU Floor Area 18.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.9 kW Load occurs at Jun 1700
Sensible coil load 2.5 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 229 L/s Entering DB / WB 24.7 / 18.8 °C
Max block L/s 229 L/s Leaving DB / WB 15.7 / 15.1 °C
Sum of peak zone L/s 229 L/s Coil ADP 14.7 °C
Sensible heat ratio 0.856 Bypass Factor 0.100
L/(s kW) 78.6 Resulting RH 57 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 161.3 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.08 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 229 L/s Fan motor BHP 0.01 BHP
Standard L/s 229 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 12.68 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 241 of 340


Zone Sizing Summary for FCU-208-1008-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-208-1008-B Number of zones 1
Equipment Class CW AHU Floor Area 18.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 229 229 12.68 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.6 Jun 1600 0.2 18.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-208-1008-B 1 2.6 Jun 1600 229 0.2 18.1 12.68

Hourly Analysis Program 5.10 Page 242 of 340


Air System Design Load Summary for FCU-208-1008-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 365 - 10 m² - -
Wall Transmission 2 m² 18 - 2 m² 6 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 362 - 10 m² 175 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 0 - 18 m² 0 -
Partitions 32 m² 917 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 181 W 181 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 272 W 271 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 237 20 0% 0 0
>> Total Zone Loads - 2612 420 - 180 0
Zone Conditioning - 2489 420 - 3 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 229 L/s 0 - 229 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 229 L/s 11 - 229 L/s -11 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2500 420 - -7 0
Central Cooling Coil - 2500 420 - 0 0
>> Total Conditioning - 2500 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 243 of 340


Zone Design Load Summary for FCU-208-1008-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 342 - 10 m² - -
Wall Transmission 2 m² 17 - 2 m² 6 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 372 - 10 m² 175 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 0 - 18 m² 0 -
Partitions 32 m² 933 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 181 W 181 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 272 W 271 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 238 20 0% 0 0
>> Total Zone Loads - 2615 420 - 180 0

Hourly Analysis Program 5.10 Page 244 of 340


Air System Sizing Summary for FCU-208-1008-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:53PM

Air System Information


Air System Name FCU-208-1008-C Number of zones 1
Equipment Class CW AHU Floor Area 28.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1500
Sensible coil load 2.9 kW OA DB / WB 45.4 / 29.0 °C
Coil L/s at Jun 1500 260 L/s Entering DB / WB 24.5 / 18.4 °C
Max block L/s 260 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 260 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.873 Bypass Factor 0.100
L/(s kW) 78.4 Resulting RH 56 %
m²/kW 8.5 Design supply temp. 14.4 °C
W/m² 117.0 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 260 L/s Fan motor BHP 0.02 BHP
Standard L/s 260 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.18 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 245 of 340


Zone Sizing Summary for FCU-208-1008-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-208-1008-C Number of zones 1
Equipment Class CW AHU Floor Area 28.3 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 260 260 9.18 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.0 Jun 1600 0.2 28.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-208-1008-C 1 3.0 Jun 1600 260 0.2 28.3 9.18

Hourly Analysis Program 5.10 Page 246 of 340


Air System Design Load Summary for FCU-208-1008-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 319 - 10 m² - -
Wall Transmission 2 m² 16 - 2 m² 6 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 375 - 10 m² 175 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 996 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 283 W 283 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 425 W 424 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 267 20 0% 0 0
>> Total Zone Loads - 2939 420 - 180 0
Zone Conditioning - 2879 420 - 8 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 260 L/s 0 - 260 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 260 L/s 12 - 260 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2891 420 - -4 0
Central Cooling Coil - 2891 420 - 0 0
>> Total Conditioning - 2891 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 247 of 340


Zone Design Load Summary for FCU-208-1008-C
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 10 m² 342 - 10 m² - -
Wall Transmission 2 m² 17 - 2 m² 6 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 10 m² 372 - 10 m² 175 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 0 - 28 m² 0 -
Partitions 34 m² 992 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 283 W 283 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 425 W 424 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 269 20 0% 0 0
>> Total Zone Loads - 2959 420 - 180 0

Hourly Analysis Program 5.10 Page 248 of 340


Air System Sizing Summary for FCU-209-1009-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-209-1009-A Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.4 kW Load occurs at Jun 1700
Sensible coil load 4.0 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 364 L/s Entering DB / WB 24.6 / 18.4 °C
Max block L/s 364 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 364 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.905 Bypass Factor 0.100
L/(s kW) 82.0 Resulting RH 55 %
m²/kW 7.1 Design supply temp. 14.4 °C
W/m² 141.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 364 L/s Fan motor BHP 0.02 BHP
Standard L/s 364 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 11.59 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 249 of 340


Zone Sizing Summary for FCU-209-1009-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-209-1009-A Number of zones 1
Equipment Class CW AHU Floor Area 31.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 364 364 11.59 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.1 Jun 1600 0.2 31.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-209-1009-A 1 4.1 Jun 1600 364 0.2 31.4 11.59

Hourly Analysis Program 5.10 Page 250 of 340


Air System Design Load Summary for FCU-209-1009-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 433 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 64 m² 1835 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 375 20 0% 0 0
>> Total Zone Loads - 4129 420 - 211 0
Zone Conditioning - 4001 420 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 364 L/s 0 - 364 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 364 L/s 17 - 364 L/s -17 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4018 420 - -12 0
Central Cooling Coil - 4018 420 - 0 0
>> Total Conditioning - 4018 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 251 of 340


Zone Design Load Summary for FCU-209-1009-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 31 m² 0 - 31 m² 0 -
Partitions 64 m² 1867 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 314 W 314 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 471 W 471 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 377 20 0% 0 0
>> Total Zone Loads - 4148 420 - 211 0

Hourly Analysis Program 5.10 Page 252 of 340


Air System Sizing Summary for FCU-209-1009-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-209-1009-B Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.2 kW Load occurs at Jul 1700
Sensible coil load 2.8 kW OA DB / WB 44.6 / 28.7 °C
Coil L/s at Jul 1700 253 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 253 L/s Leaving DB / WB 15.4 / 14.8 °C
Sum of peak zone L/s 253 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.869 Bypass Factor 0.100
L/(s kW) 78.8 Resulting RH 56 %
m²/kW 7.2 Design supply temp. 14.4 °C
W/m² 139.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 253 L/s Fan motor BHP 0.01 BHP
Standard L/s 253 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 10.99 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 253 of 340


Zone Sizing Summary for FCU-209-1009-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-209-1009-B Number of zones 1
Equipment Class CW AHU Floor Area 23.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 253 253 10.99 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.9 Jun 1600 0.2 23.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-209-1009-B 1 2.9 Jun 1600 253 0.2 23.0 10.99

Hourly Analysis Program 5.10 Page 254 of 340


Air System Design Load Summary for FCU-209-1009-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.6 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 375 - 12 m² - -
Wall Transmission 0 m² 3 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 443 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 935 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 259 20 0% 0 0
>> Total Zone Loads - 2849 420 - 208 0
Zone Conditioning - 2777 420 - 7 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 253 L/s 0 - 253 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 253 L/s 12 - 253 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2789 420 - -4 0
Central Cooling Coil - 2789 420 - 0 0
>> Total Conditioning - 2789 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 255 of 340


Zone Design Load Summary for FCU-209-1009-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 0 m² 2 - 0 m² 1 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 23 m² 0 - 23 m² 0 -
Partitions 32 m² 933 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 230 W 230 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 345 W 345 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 262 20 0% 0 0
>> Total Zone Loads - 2881 420 - 208 0

Hourly Analysis Program 5.10 Page 256 of 340


Air System Sizing Summary for FCU-210-1010-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-210-1010-A Number of zones 1
Equipment Class CW AHU Floor Area 21.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.2 kW Load occurs at Jul 1600
Sensible coil load 3.8 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 341 L/s Entering DB / WB 24.5 / 18.3 °C
Max block L/s 341 L/s Leaving DB / WB 15.3 / 14.8 °C
Sum of peak zone L/s 341 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.900 Bypass Factor 0.100
L/(s kW) 81.4 Resulting RH 55 %
m²/kW 5.2 Design supply temp. 14.4 °C
W/m² 191.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.11 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 341 L/s Fan motor BHP 0.02 BHP
Standard L/s 341 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 15.57 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 257 of 340


Zone Sizing Summary for FCU-210-1010-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:54PM

Air System Information


Air System Name FCU-210-1010-A Number of zones 1
Equipment Class CW AHU Floor Area 21.9 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 341 341 15.57 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.9 Jun 1600 0.2 21.9

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-210-1010-A 1 3.9 Jun 1600 341 0.2 21.9 15.57

Hourly Analysis Program 5.10 Page 258 of 340


Air System Design Load Summary for FCU-210-1010-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 354 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 455 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 64 m² 1901 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 219 W 219 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 329 W 328 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 353 20 0% 0 0
>> Total Zone Loads - 3880 420 - 211 0
Zone Conditioning - 3755 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 341 L/s 0 - 341 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 341 L/s 16 - 341 L/s -16 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3771 420 - -11 0
Central Cooling Coil - 3771 420 - 0 0
>> Total Conditioning - 3771 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 259 of 340


Zone Design Load Summary for FCU-210-1010-A
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 22 m² 0 - 22 m² 0 -
Partitions 64 m² 1867 - 64 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 219 W 219 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 329 W 328 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 353 20 0% 0 0
>> Total Zone Loads - 3886 420 - 211 0

Hourly Analysis Program 5.10 Page 260 of 340


Air System Sizing Summary for FCU-210-1010-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-210-1010-B Number of zones 1
Equipment Class CW AHU Floor Area 23.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.3 kW Load occurs at Jun 1700
Sensible coil load 2.9 kW OA DB / WB 44.1 / 28.7 °C
Coil L/s at Jun 1700 261 L/s Entering DB / WB 24.7 / 18.7 °C
Max block L/s 261 L/s Leaving DB / WB 15.6 / 15.0 °C
Sum of peak zone L/s 261 L/s Coil ADP 14.6 °C
Sensible heat ratio 0.872 Bypass Factor 0.100
L/(s kW) 79.6 Resulting RH 57 %
m²/kW 7.2 Design supply temp. 14.4 °C
W/m² 138.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.09 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 261 L/s Fan motor BHP 0.02 BHP
Standard L/s 261 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 11.01 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 261 of 340


Zone Sizing Summary for FCU-210-1010-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-210-1010-B Number of zones 1
Equipment Class CW AHU Floor Area 23.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 261 261 11.01 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.0 Jun 1600 0.2 23.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-210-1010-B 1 3.0 Jun 1600 261 0.2 23.7 11.01

Hourly Analysis Program 5.10 Page 262 of 340


Air System Design Load Summary for FCU-210-1010-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.1 °C / 28.7 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 433 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 430 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 34 m² 975 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 237 W 237 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 356 W 355 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 270 20 0% 0 0
>> Total Zone Loads - 2971 420 - 211 0
Zone Conditioning - 2847 420 - 4 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 261 L/s 0 - 261 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 261 L/s 12 - 261 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2859 420 - -8 0
Central Cooling Coil - 2859 421 - 0 0
>> Total Conditioning - 2859 421 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 263 of 340


Zone Design Load Summary for FCU-210-1010-B
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.0 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 12 m² 406 - 12 m² - -
Wall Transmission 1 m² 11 - 1 m² 4 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 12 m² 442 - 12 m² 207 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 24 m² 0 - 24 m² 0 -
Partitions 34 m² 992 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 237 W 237 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 356 W 355 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 270 20 0% 0 0
>> Total Zone Loads - 2973 420 - 211 0

Hourly Analysis Program 5.10 Page 264 of 340


Air System Sizing Summary for FCU-210-1010-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-210-1010-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 6.9 kW Load occurs at Jun 1500
Sensible coil load 5.8 kW OA DB / WB 45.4 / 29.0 °C
Coil L/s at Jun 1500 520 L/s Entering DB / WB 24.5 / 18.6 °C
Max block L/s 520 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 520 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.836 Bypass Factor 0.100
L/(s kW) 74.9 Resulting RH 57 %
m²/kW 15.8 Design supply temp. 14.4 °C
W/m² 63.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.19 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 520 L/s Fan motor BHP 0.03 BHP
Standard L/s 520 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 4.75 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 265 of 340


Zone Sizing Summary for FCU-210-1010-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-210-1010-CORR Number of zones 1
Equipment Class CW AHU Floor Area 109.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 520 520 4.75 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.9 Jul 1500 0.0 109.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-2F-10F-CORR 1 5.9 Jul 1500 520 0.0 109.5 4.75

Hourly Analysis Program 5.10 Page 266 of 340


Air System Design Load Summary for FCU-210-1010-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1962 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 535 54 0% 0 0
>> Total Zone Loads - 5884 1136 - 0 0
Zone Conditioning - 5783 1136 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 520 L/s 0 - 520 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 520 L/s 24 - 520 L/s -24 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 5807 1136 - -24 0
Central Cooling Coil - 5807 1137 - 0 0
>> Total Conditioning - 5807 1137 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 267 of 340


Zone Design Load Summary for FCU-210-1010-CORR
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 110 m² 0 - 110 m² 0 -
Partitions 67 m² 1998 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1095 W 1095 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 18 1292 1082 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 539 54 0% 0 0
>> Total Zone Loads - 5924 1136 - 0 0

Hourly Analysis Program 5.10 Page 268 of 340


Air System Sizing Summary for FCU-GF-00
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-GF-00 Number of zones 1
Equipment Class CW AHU Floor Area 41.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.9 kW Load occurs at Jul 1600
Sensible coil load 2.9 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 256 L/s Entering DB / WB 24.5 / 19.0 °C
Max block L/s 256 L/s Leaving DB / WB 15.1 / 14.6 °C
Sum of peak zone L/s 256 L/s Coil ADP 14.0 °C
Sensible heat ratio 0.747 Bypass Factor 0.100
L/(s kW) 65.9 Resulting RH 60 %
m²/kW 10.6 Design supply temp. 14.4 °C
W/m² 94.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 256 L/s Fan motor BHP 0.01 BHP
Standard L/s 255 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 6.22 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 269 of 340


Zone Sizing Summary for FCU-GF-00
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

Air System Information


Air System Name FCU-GF-00 Number of zones 1
Equipment Class CW AHU Floor Area 41.1 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 256 256 6.22 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.9 Jul 1500 0.0 41.1

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-00 1 2.9 Jul 1500 256 0.0 41.1 6.22

Hourly Analysis Program 5.10 Page 270 of 340


Air System Design Load Summary for FCU-GF-00
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:55PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1010 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 411 W 411 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 617 W 616 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 264 47 0% 0 0
>> Total Zone Loads - 2907 980 - 0 0
Zone Conditioning - 2884 980 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 256 L/s 0 - 256 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 256 L/s 12 - 256 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2895 980 - -12 0
Central Cooling Coil - 2895 983 - 0 0
>> Total Conditioning - 2895 983 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 271 of 340


Zone Design Load Summary for FCU-GF-00
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 411 W 411 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 617 W 616 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 265 47 0% 0 0
>> Total Zone Loads - 2911 980 - 0 0

Hourly Analysis Program 5.10 Page 272 of 340


Air System Sizing Summary for FCU-GF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-01 Number of zones 1
Equipment Class CW AHU Floor Area 40.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.8 kW Load occurs at Sep 1500
Sensible coil load 2.9 kW OA DB / WB 44.9 / 28.5 °C
Coil L/s at Sep 1500 254 L/s Entering DB / WB 24.5 / 19.0 °C
Max block L/s 254 L/s Leaving DB / WB 15.1 / 14.6 °C
Sum of peak zone L/s 254 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.745 Bypass Factor 0.100
L/(s kW) 66.1 Resulting RH 60 %
m²/kW 10.5 Design supply temp. 14.4 °C
W/m² 94.9 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 254 L/s Fan motor BHP 0.01 BHP
Standard L/s 254 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 6.27 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 273 of 340


Zone Sizing Summary for FCU-GF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-01 Number of zones 1
Equipment Class CW AHU Floor Area 40.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 254 254 6.27 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.9 Jul 1500 0.0 40.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-01 1 2.9 Jul 1500 254 0.0 40.5 6.27

Hourly Analysis Program 5.10 Page 274 of 340


Air System Design Load Summary for FCU-GF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Sep 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.9 °C / 28.5 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 977 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 405 W 405 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 608 W 607 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 260 47 0% 0 0
>> Total Zone Loads - 2855 980 - 0 0
Zone Conditioning - 2853 980 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 254 L/s 0 - 254 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 254 L/s 12 - 254 L/s -12 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2865 980 - -12 0
Central Cooling Coil - 2865 980 - 0 0
>> Total Conditioning - 2865 980 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 275 of 340


Zone Design Load Summary for FCU-GF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 405 W 405 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 608 W 607 - 0 0 -
People 7 605 933 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 263 47 0% 0 0
>> Total Zone Loads - 2895 980 - 0 0

Hourly Analysis Program 5.10 Page 276 of 340


Air System Sizing Summary for FCU-GF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-02 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1500
Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 168 L/s Entering DB / WB 24.5 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 168 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.816 Bypass Factor 0.100
L/(s kW) 73.4 Resulting RH 58 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.06 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.01 BHP
Standard L/s 167 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.06 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 277 of 340


Zone Sizing Summary for FCU-GF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-02 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 168 168 9.06 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.9 Jul 1500 0.0 18.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-PF-02 1 1.9 Jul 1500 168 0.0 18.5 9.06

Hourly Analysis Program 5.10 Page 278 of 340


Air System Design Load Summary for FCU-GF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0
Zone Conditioning - 1856 420 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 168 L/s 0 - 168 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 168 L/s 8 - 168 L/s -8 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1864 420 - -8 0
Central Cooling Coil - 1864 420 - 0 0
>> Total Conditioning - 1864 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 279 of 340


Zone Design Load Summary for FCU-GF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0

Hourly Analysis Program 5.10 Page 280 of 340


Air System Sizing Summary for FCU-GF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-03 Number of zones 1
Equipment Class CW AHU Floor Area 13.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.3 kW Load occurs at Jul 1600
Sensible coil load 1.0 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 91 L/s Entering DB / WB 24.5 / 18.8 °C
Max block L/s 91 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 91 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.786 Bypass Factor 0.100
L/(s kW) 69.8 Resulting RH 58 %
m²/kW 9.9 Design supply temp. 14.4 °C
W/m² 100.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.04 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 91 L/s Fan motor BHP 0.01 BHP
Standard L/s 91 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 7.02 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 281 of 340


Zone Sizing Summary for FCU-GF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:56PM

Air System Information


Air System Name FCU-GF-03 Number of zones 1
Equipment Class CW AHU Floor Area 13.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 91 91 7.02 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.0 Jul 1500 0.0 13.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-03 1 1.0 Jul 1500 91 0.0 13.0 7.02

Hourly Analysis Program 5.10 Page 282 of 340


Air System Design Load Summary for FCU-GF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 13 m² 0 - 13 m² 0 -
Partitions 15 m² 446 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 130 W 130 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 195 W 195 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 94 13 0% 0 0
>> Total Zone Loads - 1038 280 - 0 0
Zone Conditioning - 1024 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 91 L/s 0 - 91 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 91 L/s 4 - 91 L/s -4 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1028 280 - -4 0
Central Cooling Coil - 1028 280 - 0 0
>> Total Conditioning - 1028 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 283 of 340


Zone Design Load Summary for FCU-GF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 13 m² 0 - 13 m² 0 -
Partitions 15 m² 447 - 15 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 130 W 130 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 195 W 195 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 95 13 0% 0 0
>> Total Zone Loads - 1040 280 - 0 0

Hourly Analysis Program 5.10 Page 284 of 340


Air System Sizing Summary for FCU-GF-04
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Air System Information


Air System Name FCU-GF-04 Number of zones 1
Equipment Class CW AHU Floor Area 124.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 13.2 kW Load occurs at Jul 1500
Sensible coil load 10.4 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 947 L/s Entering DB / WB 24.6 / 19.0 °C
Max block L/s 947 L/s Leaving DB / WB 15.5 / 15.0 °C
Sum of peak zone L/s 947 L/s Coil ADP 14.5 °C
Sensible heat ratio 0.788 Bypass Factor 0.100
L/(s kW) 71.7 Resulting RH 59 %
m²/kW 9.4 Design supply temp. 14.4 °C
W/m² 106.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.35 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 947 L/s Fan motor BHP 0.06 BHP
Standard L/s 946 L/s Fan motor kW 0.04 kW
Actual max L/(s·m²) 7.64 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 285 of 340


Zone Sizing Summary for FCU-GF-04
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Air System Information


Air System Name FCU-GF-04 Number of zones 1
Equipment Class CW AHU Floor Area 124.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 947 947 7.64 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 10.8 Jul 1500 0.0 124.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-04 1 10.8 Jul 1500 947 0.0 124.0 7.64

Hourly Analysis Program 5.10 Page 286 of 340


Air System Design Load Summary for FCU-GF-04
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 124 m² 0 - 124 m² 0 -
Partitions 167 m² 4980 - 167 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1240 W 1240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1860 W 1860 - 0 0 -
People 20 1730 2666 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 981 133 0% 0 0
>> Total Zone Loads - 10790 2799 - 0 0
Zone Conditioning - 10357 2799 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 947 L/s 0 - 947 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 947 L/s 44 - 947 L/s -44 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 10401 2799 - -44 0
Central Cooling Coil - 10401 2800 - 0 0
>> Total Conditioning - 10401 2800 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 287 of 340


Zone Design Load Summary for FCU-GF-04
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 124 m² 0 - 124 m² 0 -
Partitions 167 m² 4980 - 167 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1240 W 1240 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1860 W 1860 - 0 0 -
People 20 1730 2666 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 981 133 0% 0 0
>> Total Zone Loads - 10790 2799 - 0 0

Hourly Analysis Program 5.10 Page 288 of 340


Air System Sizing Summary for FCU-GF-05
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Air System Information


Air System Name FCU-GF-05 Number of zones 1
Equipment Class CW AHU Floor Area 29.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1600
Sensible coil load 2.0 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 180 L/s Entering DB / WB 24.5 / 18.4 °C
Max block L/s 180 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 180 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.878 Bypass Factor 0.100
L/(s kW) 78.2 Resulting RH 56 %
m²/kW 12.8 Design supply temp. 14.4 °C
W/m² 78.0 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.06 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 180 L/s Fan motor BHP 0.01 BHP
Standard L/s 180 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 6.10 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 289 of 340


Zone Sizing Summary for FCU-GF-05
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

Air System Information


Air System Name FCU-GF-05 Number of zones 1
Equipment Class CW AHU Floor Area 29.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 180 180 6.10 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.1 Jul 1500 0.0 29.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-05 1 2.1 Jul 1500 180 0.0 29.5 6.10

Hourly Analysis Program 5.10 Page 290 of 340


Air System Design Load Summary for FCU-GF-05
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:57PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 32 m² 950 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 295 W 295 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 443 W 442 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 186 13 0% 0 0
>> Total Zone Loads - 2047 280 - 0 0
Zone Conditioning - 2013 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 180 L/s 0 - 180 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 180 L/s 8 - 180 L/s -8 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2022 280 - -8 0
Central Cooling Coil - 2022 280 - 0 0
>> Total Conditioning - 2022 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 291 of 340


Zone Design Load Summary for FCU-GF-05
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 30 m² 0 - 30 m² 0 -
Partitions 32 m² 954 - 32 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 295 W 295 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 443 W 442 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 186 13 0% 0 0
>> Total Zone Loads - 2051 280 - 0 0

Hourly Analysis Program 5.10 Page 292 of 340


Air System Sizing Summary for FCU-GF-06
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-06 Number of zones 1
Equipment Class CW AHU Floor Area 61.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.6 kW Load occurs at Jul 1600
Sensible coil load 3.4 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 299 L/s Entering DB / WB 24.6 / 18.2 °C
Max block L/s 299 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 299 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.923 Bypass Factor 0.100
L/(s kW) 82.2 Resulting RH 54 %
m²/kW 16.8 Design supply temp. 14.4 °C
W/m² 59.7 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.10 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 299 L/s Fan motor BHP 0.02 BHP
Standard L/s 299 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 4.91 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 293 of 340


Zone Sizing Summary for FCU-GF-06
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-06 Number of zones 1
Equipment Class CW AHU Floor Area 61.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 299 299 4.91 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 3.4 Jul 1500 0.0 61.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-06 1 3.4 Jul 1500 299 0.0 61.0 4.91

Hourly Analysis Program 5.10 Page 294 of 340


Air System Design Load Summary for FCU-GF-06
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 61 m² 0 - 61 m² 0 -
Partitions 47 m² 1396 - 47 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 610 W 610 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 915 W 915 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 309 13 0% 0 0
>> Total Zone Loads - 3403 280 - 0 0
Zone Conditioning - 3345 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 299 L/s 0 - 299 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 299 L/s 14 - 299 L/s -14 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 3359 280 - -14 0
Central Cooling Coil - 3359 280 - 0 0
>> Total Conditioning - 3359 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 295 of 340


Zone Design Load Summary for FCU-GF-06
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 61 m² 0 - 61 m² 0 -
Partitions 47 m² 1401 - 47 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 610 W 610 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 915 W 915 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 310 13 0% 0 0
>> Total Zone Loads - 3409 280 - 0 0

Hourly Analysis Program 5.10 Page 296 of 340


Air System Sizing Summary for FCU-GF-07
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-07 Number of zones 1
Equipment Class CW AHU Floor Area 57.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.7 kW Load occurs at Jul 1500
Sensible coil load 4.1 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 365 L/s Entering DB / WB 24.5 / 18.4 °C
Max block L/s 365 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 365 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.880 Bypass Factor 0.100
L/(s kW) 78.4 Resulting RH 56 %
m²/kW 12.4 Design supply temp. 14.4 °C
W/m² 80.9 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.13 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 365 L/s Fan motor BHP 0.02 BHP
Standard L/s 365 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 6.34 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 297 of 340


Zone Sizing Summary for FCU-GF-07
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-07 Number of zones 1
Equipment Class CW AHU Floor Area 57.6 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 365 365 6.34 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.2 Jul 1500 0.0 57.6

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-07 1 4.2 Jul 1500 365 0.0 57.6 6.34

Hourly Analysis Program 5.10 Page 298 of 340


Air System Design Load Summary for FCU-GF-07
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 58 m² 0 - 58 m² 0 -
Partitions 67 m² 1998 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 576 W 576 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 864 W 864 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 378 27 0% 0 0
>> Total Zone Loads - 4162 560 - 0 0
Zone Conditioning - 4081 560 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 365 L/s 0 - 365 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 365 L/s 17 - 365 L/s -17 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4098 560 - -17 0
Central Cooling Coil - 4098 560 - 0 0
>> Total Conditioning - 4098 560 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 299 of 340


Zone Design Load Summary for FCU-GF-07
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 58 m² 0 - 58 m² 0 -
Partitions 67 m² 1998 - 67 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 576 W 576 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 864 W 864 - 0 0 -
People 4 346 533 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 378 27 0% 0 0
>> Total Zone Loads - 4162 560 - 0 0

Hourly Analysis Program 5.10 Page 300 of 340


Air System Sizing Summary for FCU-GF-08
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-08 Number of zones 1
Equipment Class CW AHU Floor Area 18.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.8 kW Load occurs at Jul 1400
Sensible coil load 1.5 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1400 132 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 132 L/s Leaving DB / WB 15.2 / 14.7 °C
Sum of peak zone L/s 132 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.841 Bypass Factor 0.100
L/(s kW) 75.2 Resulting RH 57 %
m²/kW 10.2 Design supply temp. 14.4 °C
W/m² 97.6 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.05 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 132 L/s Fan motor BHP 0.01 BHP
Standard L/s 132 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 7.34 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 301 of 340


Zone Sizing Summary for FCU-GF-08
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:58PM

Air System Information


Air System Name FCU-GF-08 Number of zones 1
Equipment Class CW AHU Floor Area 18.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 132 132 7.34 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.5 Jul 1500 0.0 18.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-08 1 1.5 Jul 1500 132 0.0 18.0 7.34

Hourly Analysis Program 5.10 Page 302 of 340


Air System Design Load Summary for FCU-GF-08
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 0 - 18 m² 0 -
Partitions 25 m² 735 - 25 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 270 W 270 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 136 13 0% 0 0
>> Total Zone Loads - 1493 280 - 0 0
Zone Conditioning - 1471 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 132 L/s 0 - 132 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 132 L/s 6 - 132 L/s -6 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1477 280 - -6 0
Central Cooling Coil - 1477 280 - 0 0
>> Total Conditioning - 1477 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 303 of 340


Zone Design Load Summary for FCU-GF-08
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 18 m² 0 - 18 m² 0 -
Partitions 25 m² 745 - 25 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 180 W 180 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 270 W 270 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 137 13 0% 0 0
>> Total Zone Loads - 1505 280 - 0 0

Hourly Analysis Program 5.10 Page 304 of 340


Air System Sizing Summary for FCU-GF-09
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Air System Information


Air System Name FCU-GF-09 Number of zones 1
Equipment Class CW AHU Floor Area 7.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.2 kW Load occurs at Jul 1600
Sensible coil load 0.9 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 80 L/s Entering DB / WB 24.6 / 19.0 °C
Max block L/s 80 L/s Leaving DB / WB 15.4 / 14.9 °C
Sum of peak zone L/s 80 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.760 Bypass Factor 0.100
L/(s kW) 68.6 Resulting RH 60 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 162.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.03 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 80 L/s Fan motor BHP 0.00 BHP
Standard L/s 80 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 11.13 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 305 of 340


Zone Sizing Summary for FCU-GF-09
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Air System Information


Air System Name FCU-GF-09 Number of zones 1
Equipment Class CW AHU Floor Area 7.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 80 80 11.13 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.9 Jul 1500 0.0 7.2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-09 1 0.9 Jul 1500 80 0.0 7.2 11.13

Hourly Analysis Program 5.10 Page 306 of 340


Air System Design Load Summary for FCU-GF-09
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 16 m² 475 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 108 W 108 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 83 13 0% 0 0
>> Total Zone Loads - 911 280 - 0 0
Zone Conditioning - 885 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 80 L/s 0 - 80 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 80 L/s 4 - 80 L/s -4 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 889 280 - -4 0
Central Cooling Coil - 889 280 - 0 0
>> Total Conditioning - 889 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 307 of 340


Zone Design Load Summary for FCU-GF-09
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 16 m² 477 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 108 W 108 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 83 13 0% 0 0
>> Total Zone Loads - 913 280 - 0 0

Hourly Analysis Program 5.10 Page 308 of 340


Air System Sizing Summary for FCU-GF-10
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Air System Information


Air System Name FCU-GF-10 Number of zones 1
Equipment Class CW AHU Floor Area 7.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.2 kW Load occurs at Jul 1600
Sensible coil load 0.9 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 80 L/s Entering DB / WB 24.6 / 19.0 °C
Max block L/s 80 L/s Leaving DB / WB 15.4 / 14.9 °C
Sum of peak zone L/s 80 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.760 Bypass Factor 0.100
L/(s kW) 68.6 Resulting RH 60 %
m²/kW 6.2 Design supply temp. 14.4 °C
W/m² 162.3 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.03 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 80 L/s Fan motor BHP 0.00 BHP
Standard L/s 80 L/s Fan motor kW 0.00 kW
Actual max L/(s·m²) 11.13 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 309 of 340


Zone Sizing Summary for FCU-GF-10
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Air System Information


Air System Name FCU-GF-10 Number of zones 1
Equipment Class CW AHU Floor Area 7.2 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 80 80 11.13 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 0.9 Jul 1500 0.0 7.2

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-10 1 0.9 Jul 1500 80 0.0 7.2 11.13

Hourly Analysis Program 5.10 Page 310 of 340


Air System Design Load Summary for FCU-GF-10
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 16 m² 475 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 108 W 108 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 83 13 0% 0 0
>> Total Zone Loads - 911 280 - 0 0
Zone Conditioning - 885 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 80 L/s 0 - 80 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 80 L/s 4 - 80 L/s -4 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 889 280 - -4 0
Central Cooling Coil - 889 280 - 0 0
>> Total Conditioning - 889 280 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 311 of 340


Zone Design Load Summary for FCU-GF-10
Project Name: B-241 04/20/2023
Prepared by: EDMAC 04:59PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 7 m² 0 - 7 m² 0 -
Partitions 16 m² 477 - 16 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 108 W 108 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 83 13 0% 0 0
>> Total Zone Loads - 913 280 - 0 0

Hourly Analysis Program 5.10 Page 312 of 340


Air System Sizing Summary for FCU-GF-11
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-11 Number of zones 1
Equipment Class CW AHU Floor Area 15.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 1.5 kW Load occurs at Jul 1500
Sensible coil load 1.3 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 113 L/s Entering DB / WB 24.6 / 18.8 °C
Max block L/s 113 L/s Leaving DB / WB 15.4 / 14.9 °C
Sum of peak zone L/s 113 L/s Coil ADP 14.4 °C
Sensible heat ratio 0.816 Bypass Factor 0.100
L/(s kW) 73.7 Resulting RH 58 %
m²/kW 9.8 Design supply temp. 14.4 °C
W/m² 102.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.04 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 113 L/s Fan motor BHP 0.01 BHP
Standard L/s 113 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 7.56 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 313 of 340


Zone Sizing Summary for FCU-GF-11
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-11 Number of zones 1
Equipment Class CW AHU Floor Area 15.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 113 113 7.56 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.3 Jul 1500 0.0 15.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-11 1 1.3 Jul 1500 113 0.0 15.0 7.56

Hourly Analysis Program 5.10 Page 314 of 340


Air System Design Load Summary for FCU-GF-11
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 21 m² 626 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 150 W 150 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 225 W 225 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 117 13 0% 0 0
>> Total Zone Loads - 1292 280 - 0 0
Zone Conditioning - 1250 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 113 L/s 0 - 113 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 113 L/s 5 - 113 L/s -5 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1255 280 - -5 0
Central Cooling Coil - 1255 282 - 0 0
>> Total Conditioning - 1255 282 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 315 of 340


Zone Design Load Summary for FCU-GF-11
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 15 m² 0 - 15 m² 0 -
Partitions 21 m² 626 - 21 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 150 W 150 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 225 W 225 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 117 13 0% 0 0
>> Total Zone Loads - 1292 280 - 0 0

Hourly Analysis Program 5.10 Page 316 of 340


Air System Sizing Summary for FCU-GF-12
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-12 Number of zones 1
Equipment Class CW AHU Floor Area 96.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 4.5 kW Load occurs at Jun 1500
Sensible coil load 4.3 kW OA DB / WB 45.4 / 29.0 °C
Coil L/s at Jun 1500 379 L/s Entering DB / WB 24.6 / 18.1 °C
Max block L/s 379 L/s Leaving DB / WB 15.2 / 14.6 °C
Sum of peak zone L/s 379 L/s Coil ADP 14.2 °C
Sensible heat ratio 0.938 Bypass Factor 0.100
L/(s kW) 83.4 Resulting RH 54 %
m²/kW 21.2 Design supply temp. 14.4 °C
W/m² 47.1 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.12 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 379 L/s Fan motor BHP 0.02 BHP
Standard L/s 379 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 3.93 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 317 of 340


Zone Sizing Summary for FCU-GF-12
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-12 Number of zones 1
Equipment Class CW AHU Floor Area 96.4 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 379 379 3.93 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 4.3 Jul 1500 0.0 96.4

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-12 1 4.3 Jul 1500 379 0.0 96.4 3.93

Hourly Analysis Program 5.10 Page 318 of 340


Air System Design Load Summary for FCU-GF-12
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.4 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 96 m² 0 - 96 m² 0 -
Partitions 45 m² 1318 - 45 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 964 W 964 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1446 W 1446 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 390 13 0% 0 0
>> Total Zone Loads - 4291 280 - 0 0
Zone Conditioning - 4241 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 379 L/s 0 - 379 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 379 L/s 18 - 379 L/s -18 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4259 280 - -18 0
Central Cooling Coil - 4259 282 - 0 0
>> Total Conditioning - 4259 282 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 319 of 340


Zone Design Load Summary for FCU-GF-12
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 96 m² 0 - 96 m² 0 -
Partitions 45 m² 1342 - 45 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 964 W 964 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1446 W 1446 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 392 13 0% 0 0
>> Total Zone Loads - 4317 280 - 0 0

Hourly Analysis Program 5.10 Page 320 of 340


Air System Sizing Summary for FCU-GF-13
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-13 Number of zones 1
Equipment Class CW AHU Floor Area 106.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 5.3 kW Load occurs at Jul 1600
Sensible coil load 5.0 kW OA DB / WB 45.6 / 28.9 °C
Coil L/s at Jul 1600 438 L/s Entering DB / WB 24.5 / 18.0 °C
Max block L/s 438 L/s Leaving DB / WB 15.1 / 14.5 °C
Sum of peak zone L/s 438 L/s Coil ADP 14.1 °C
Sensible heat ratio 0.947 Bypass Factor 0.100
L/(s kW) 83.2 Resulting RH 53 %
m²/kW 20.2 Design supply temp. 14.4 °C
W/m² 49.4 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.14 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 438 L/s Fan motor BHP 0.03 BHP
Standard L/s 438 L/s Fan motor kW 0.02 kW
Actual max L/(s·m²) 4.11 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 321 of 340


Zone Sizing Summary for FCU-GF-13
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:00PM

Air System Information


Air System Name FCU-GF-13 Number of zones 1
Equipment Class CW AHU Floor Area 106.7 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 438 438 4.11 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 5.0 Jul 1500 0.0 106.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-GF-13 1 5.0 Jul 1500 438 0.0 106.7 4.11

Hourly Analysis Program 5.10 Page 322 of 340


Air System Design Load Summary for FCU-GF-13
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 °C / 28.9 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 107 m² 0 - 107 m² 0 -
Partitions 57 m² 1693 - 57 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1067 W 1067 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1601 W 1600 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 453 13 0% 0 0
>> Total Zone Loads - 4987 280 - 0 0
Zone Conditioning - 4970 280 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 438 L/s 0 - 438 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 438 L/s 20 - 438 L/s -20 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 4990 280 - -20 0
Central Cooling Coil - 4990 281 - 0 0
>> Total Conditioning - 4990 281 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 323 of 340


Zone Design Load Summary for FCU-GF-13
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 107 m² 0 - 107 m² 0 -
Partitions 57 m² 1700 - 57 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1067 W 1067 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1601 W 1600 - 0 0 -
People 2 173 267 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 454 13 0% 0 0
>> Total Zone Loads - 4994 280 - 0 0

Hourly Analysis Program 5.10 Page 324 of 340


Air System Sizing Summary for FCU-PF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Air System Information


Air System Name FCU-PF-01 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1500
Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 168 L/s Entering DB / WB 24.5 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 168 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.816 Bypass Factor 0.100
L/(s kW) 73.4 Resulting RH 58 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.06 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.01 BHP
Standard L/s 167 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.06 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 325 of 340


Zone Sizing Summary for FCU-PF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Air System Information


Air System Name FCU-PF-01 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 168 168 9.06 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.9 Jul 1500 0.0 18.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-PF-01 1 1.9 Jul 1500 168 0.0 18.5 9.06

Hourly Analysis Program 5.10 Page 326 of 340


Air System Design Load Summary for FCU-PF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0
Zone Conditioning - 1856 420 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 168 L/s 0 - 168 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 168 L/s 8 - 168 L/s -8 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1864 420 - -8 0
Central Cooling Coil - 1864 420 - 0 0
>> Total Conditioning - 1864 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 327 of 340


Zone Design Load Summary for FCU-PF-01
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0

Hourly Analysis Program 5.10 Page 328 of 340


Air System Sizing Summary for FCU-PF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Air System Information


Air System Name FCU-PF-02 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1500
Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 168 L/s Entering DB / WB 24.5 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 168 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.816 Bypass Factor 0.100
L/(s kW) 73.4 Resulting RH 58 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.06 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.01 BHP
Standard L/s 167 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.06 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 329 of 340


Zone Sizing Summary for FCU-PF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

Air System Information


Air System Name FCU-PF-02 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 168 168 9.06 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.9 Jul 1500 0.0 18.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-PF-02 1 1.9 Jul 1500 168 0.0 18.5 9.06

Hourly Analysis Program 5.10 Page 330 of 340


Air System Design Load Summary for FCU-PF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:01PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0
Zone Conditioning - 1856 420 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 168 L/s 0 - 168 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 168 L/s 8 - 168 L/s -8 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1864 420 - -8 0
Central Cooling Coil - 1864 420 - 0 0
>> Total Conditioning - 1864 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 331 of 340


Zone Design Load Summary for FCU-PF-02
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0

Hourly Analysis Program 5.10 Page 332 of 340


Air System Sizing Summary for FCU-PF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Air System Information


Air System Name FCU-PF-03 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.3 kW Load occurs at Jul 1500
Sensible coil load 1.9 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 168 L/s Entering DB / WB 24.5 / 18.7 °C
Max block L/s 168 L/s Leaving DB / WB 15.3 / 14.7 °C
Sum of peak zone L/s 168 L/s Coil ADP 14.3 °C
Sensible heat ratio 0.816 Bypass Factor 0.100
L/(s kW) 73.4 Resulting RH 58 %
m²/kW 8.1 Design supply temp. 14.4 °C
W/m² 123.5 Zone T-stat Check 1 of 1 OK
Water flow @ 8.9 K rise 0.06 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 168 L/s Fan motor BHP 0.01 BHP
Standard L/s 167 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 9.06 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 333 of 340


Zone Sizing Summary for FCU-PF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Air System Information


Air System Name FCU-PF-03 Number of zones 1
Equipment Class CW AHU Floor Area 18.5 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 168 168 9.06 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 1.9 Jul 1500 0.0 18.5

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-PF-03 1 1.9 Jul 1500 168 0.0 18.5 9.06

Hourly Analysis Program 5.10 Page 334 of 340


Air System Design Load Summary for FCU-PF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0
Zone Conditioning - 1856 420 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 168 L/s 0 - 168 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 168 L/s 8 - 168 L/s -8 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 1864 420 - -8 0
Central Cooling Coil - 1864 420 - 0 0
>> Total Conditioning - 1864 420 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 335 of 340


Zone Design Load Summary for FCU-PF-03
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 19 m² 0 - 19 m² 0 -
Partitions 34 m² 1014 - 34 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 185 W 185 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 278 W 277 - 0 0 -
People 3 259 400 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 174 20 0% 0 0
>> Total Zone Loads - 1909 420 - 0 0

Hourly Analysis Program 5.10 Page 336 of 340


Air System Sizing Summary for FCU-RF-1
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Air System Information


Air System Name FCU-RF-1 Number of zones 1
Equipment Class CW AHU Floor Area 20.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 2.8 kW Load occurs at Jul 1500
Sensible coil load 2.7 kW OA DB / WB 46.0 / 29.0 °C
Coil L/s at Jul 1500 247 L/s Entering DB / WB 24.7 / 18.3 °C
Max block L/s 247 L/s Leaving DB / WB 15.6 / 15.0 °C
Sum of peak zone L/s 247 L/s Coil ADP 14.6 °C
Sensible heat ratio 0.956 Bypass Factor 0.100
L/(s kW) 86.6 Resulting RH 54 %
m²/kW 7.0 Design supply temp. 14.4 °C
W/m² 142.5 Zone T-stat Check 0 of 1 OK
Water flow @ 8.9 K rise 0.08 L/s Max zone temperature deviation 0.0 K

Supply Fan Sizing Data


Actual max L/s 247 L/s Fan motor BHP 0.01 BHP
Standard L/s 247 L/s Fan motor kW 0.01 kW
Actual max L/(s·m²) 12.34 L/(s·m²) Fan static 25 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s·m²) 0.00 L/(s·m²)

Hourly Analysis Program 5.10 Page 337 of 340


Zone Sizing Summary for FCU-RF-1
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

Air System Information


Air System Name FCU-RF-1 Number of zones 1
Equipment Class CW AHU Floor Area 20.0 m²
Air System Type SZCAV Location Dubai, United Arab Emirates

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load L/s Load L/s Airflow
Zone Name (L/s) (L/s) L/(s·m²) (kW) @ 11.1 K (kW) @ 11.1 K (L/s)
Zone 1 247 247 12.34 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (kW) Cooling Load (kW) (m²)
Zone 1 2.8 Jul 1500 0.1 20.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s·m²)
Zone 1
FCU-RF-1 1 2.8 Jul 1500 247 0.1 20.0 12.34

Hourly Analysis Program 5.10 Page 338 of 340


Air System Design Load Summary for FCU-RF-1
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:02PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 30 m² 170 - 30 m² 59 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 0 - 11 m² 0 -
Partitions 35 m² 1044 - 35 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 256 6 0% 0 0
>> Total Zone Loads - 2813 126 - 59 0
Zone Conditioning - 2711 126 - 3 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 247 L/s 0 - 247 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 247 L/s 11 - 247 L/s -11 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 2723 126 - -8 0
Central Cooling Coil - 2723 127 - 0 0
>> Total Conditioning - 2723 127 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.10 Page 339 of 340


Zone Design Load Summary for FCU-RF-1
Project Name: B-241 04/20/2023
Prepared by: EDMAC 05:03PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 °C / 29.0 °C HEATING OA DB / WB 12.2 °C / 7.4 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 30 m² 170 - 30 m² 59 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 11 m² 0 - 11 m² 0 -
Partitions 35 m² 1044 - 35 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 200 W 200 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 1000 - 0 0 -
People 2 144 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 256 6 0% 0 0
>> Total Zone Loads - 2813 126 - 59 0

Hourly Analysis Program 5.10 Page 340 of 340