Air System Name AHU-03 Number of zones 1 Equipment Class CW AHU Floor Area 532.0 m² Air System Type SZCAV Location Cairo, Egypt
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s Sum of space airflow rates Calculation Months Jan to Dec Space L/s Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 73.8 kW Load occurs at Jul 1500 Sensible coil load 45.4 kW OA DB / WB 40.5 / 25.0 °C Coil L/s at Jul 1500 3188 L/s Entering DB / WB 24.7 / 19.2 °C Max block L/s 3188 L/s Leaving DB / WB 12.8 / 12.3 °C Sum of peak zone L/s 3188 L/s Coil ADP 11.4 °C Sensible heat ratio 0.616 Bypass Factor 0.100 m²/kW 7.2 Resulting RH 61 % W/m² 138.7 Design supply temp. 12.8 °C Water flow @ 5.6 °K rise 3.18 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °K
Supply Fan Sizing Data
Actual max L/s 3188 L/s Fan motor BHP 5.94 BHP Standard L/s 3160 L/s Fan motor kW 4.43 kW Actual max L/(s-m²) 5.99 L/(s-m²) Fan static 750 Pa
Air System Sizing Summary for AHU-04 Project Name: FATHY PORTO 05/08/2012 Prepared by: SHAKER Consultancy Group 10:52AM
Air System Information
Air System Name AHU-04 Number of zones 1 Equipment Class CW AHU Floor Area 280.0 m² Air System Type SZCAV Location Cairo, Egypt
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s Sum of space airflow rates Calculation Months Jan to Dec Space L/s Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 43.8 kW Load occurs at Jul 1600 Sensible coil load 28.9 kW OA DB / WB 40.1 / 24.9 °C Coil L/s at Jul 1600 2414 L/s Entering DB / WB 22.6 / 17.8 °C Max block L/s 2414 L/s Leaving DB / WB 12.7 / 12.2 °C Sum of peak zone L/s 2414 L/s Coil ADP 11.5 °C Sensible heat ratio 0.659 Bypass Factor 0.100 m²/kW 6.4 Resulting RH 63 % W/m² 156.4 Design supply temp. 12.8 °C Water flow @ 5.6 °K rise 1.89 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °K
Supply Fan Sizing Data
Actual max L/s 2414 L/s Fan motor BHP 4.50 BHP Standard L/s 2393 L/s Fan motor kW 3.35 kW Actual max L/(s-m²) 8.62 L/(s-m²) Fan static 750 Pa
Air System Sizing Summary for AHU-05 Project Name: FATHY PORTO 05/08/2012 Prepared by: SHAKER Consultancy Group 10:52AM
Air System Information
Air System Name AHU-05 Number of zones 1 Equipment Class CW AHU Floor Area 429.0 m² Air System Type SZCAV Location Cairo, Egypt
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s Sum of space airflow rates Calculation Months Jan to Dec Space L/s Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 64.6 kW Load occurs at Jun 1400 Sensible coil load 41.8 kW OA DB / WB 39.5 / 24.9 °C Coil L/s at Jun 1400 3524 L/s Entering DB / WB 22.6 / 17.9 °C Max block L/s 3524 L/s Leaving DB / WB 12.7 / 12.3 °C Sum of peak zone L/s 3524 L/s Coil ADP 11.6 °C Sensible heat ratio 0.646 Bypass Factor 0.100 m²/kW 6.6 Resulting RH 64 % W/m² 150.7 Design supply temp. 12.8 °C Water flow @ 5.6 °K rise 2.78 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °K
Supply Fan Sizing Data
Actual max L/s 3524 L/s Fan motor BHP 6.56 BHP Standard L/s 3493 L/s Fan motor kW 4.89 kW Actual max L/(s-m²) 8.21 L/(s-m²) Fan static 750 Pa
Air System Sizing Summary for AHU-06 Project Name: FATHY PORTO 05/08/2012 Prepared by: SHAKER Consultancy Group 10:53AM
Air System Information
Air System Name AHU-06 Number of zones 1 Equipment Class CW AHU Floor Area 490.0 m² Air System Type SZCAV Location Cairo, Egypt
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s Sum of space airflow rates Calculation Months Jan to Dec Space L/s Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 91.6 kW Load occurs at Jul 1500 Sensible coil load 61.4 kW OA DB / WB 40.5 / 25.0 °C Coil L/s at Jul 1500 4246 L/s Entering DB / WB 24.5 / 18.5 °C Max block L/s 4246 L/s Leaving DB / WB 12.4 / 11.9 °C Sum of peak zone L/s 4246 L/s Coil ADP 11.1 °C Sensible heat ratio 0.670 Bypass Factor 0.100 m²/kW 5.3 Resulting RH 62 % W/m² 187.0 Design supply temp. 12.8 °C Water flow @ 5.6 °K rise 3.95 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °K
Supply Fan Sizing Data
Actual max L/s 4246 L/s Fan motor BHP 7.91 BHP Standard L/s 4209 L/s Fan motor kW 5.90 kW Actual max L/(s-m²) 8.67 L/(s-m²) Fan static 750 Pa