Air System Sizing Summary for AHU-03

Project Name: FATHY PORTO 05/08/2012


Prepared by: SHAKER Consultancy Group 10:50AM

Air System Information


Air System Name AHU-03 Number of zones 1
Equipment Class CW AHU Floor Area 532.0 m²
Air System Type SZCAV Location Cairo, Egypt

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 73.8 kW Load occurs at Jul 1500
Sensible coil load 45.4 kW OA DB / WB 40.5 / 25.0 °C
Coil L/s at Jul 1500 3188 L/s Entering DB / WB 24.7 / 19.2 °C
Max block L/s 3188 L/s Leaving DB / WB 12.8 / 12.3 °C
Sum of peak zone L/s 3188 L/s Coil ADP 11.4 °C
Sensible heat ratio 0.616 Bypass Factor 0.100
m²/kW 7.2 Resulting RH 61 %
W/m² 138.7 Design supply temp. 12.8 °C
Water flow @ 5.6 °K rise 3.18 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 3188 L/s Fan motor BHP 5.94 BHP
Standard L/s 3160 L/s Fan motor kW 4.43 kW
Actual max L/(s-m²) 5.99 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Sizing Summary for AHU-04
Project Name: FATHY PORTO 05/08/2012
Prepared by: SHAKER Consultancy Group 10:52AM

Air System Information


Air System Name AHU-04 Number of zones 1
Equipment Class CW AHU Floor Area 280.0 m²
Air System Type SZCAV Location Cairo, Egypt

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 43.8 kW Load occurs at Jul 1600
Sensible coil load 28.9 kW OA DB / WB 40.1 / 24.9 °C
Coil L/s at Jul 1600 2414 L/s Entering DB / WB 22.6 / 17.8 °C
Max block L/s 2414 L/s Leaving DB / WB 12.7 / 12.2 °C
Sum of peak zone L/s 2414 L/s Coil ADP 11.5 °C
Sensible heat ratio 0.659 Bypass Factor 0.100
m²/kW 6.4 Resulting RH 63 %
W/m² 156.4 Design supply temp. 12.8 °C
Water flow @ 5.6 °K rise 1.89 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 2414 L/s Fan motor BHP 4.50 BHP
Standard L/s 2393 L/s Fan motor kW 3.35 kW
Actual max L/(s-m²) 8.62 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Sizing Summary for AHU-05
Project Name: FATHY PORTO 05/08/2012
Prepared by: SHAKER Consultancy Group 10:52AM

Air System Information


Air System Name AHU-05 Number of zones 1
Equipment Class CW AHU Floor Area 429.0 m²
Air System Type SZCAV Location Cairo, Egypt

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 64.6 kW Load occurs at Jun 1400
Sensible coil load 41.8 kW OA DB / WB 39.5 / 24.9 °C
Coil L/s at Jun 1400 3524 L/s Entering DB / WB 22.6 / 17.9 °C
Max block L/s 3524 L/s Leaving DB / WB 12.7 / 12.3 °C
Sum of peak zone L/s 3524 L/s Coil ADP 11.6 °C
Sensible heat ratio 0.646 Bypass Factor 0.100
m²/kW 6.6 Resulting RH 64 %
W/m² 150.7 Design supply temp. 12.8 °C
Water flow @ 5.6 °K rise 2.78 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 3524 L/s Fan motor BHP 6.56 BHP
Standard L/s 3493 L/s Fan motor kW 4.89 kW
Actual max L/(s-m²) 8.21 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m²) 0.00 L/(s-m²)

Hourly Analysis Program v.4.4 Page 1 of 1


Air System Sizing Summary for AHU-06
Project Name: FATHY PORTO 05/08/2012
Prepared by: SHAKER Consultancy Group 10:53AM

Air System Information


Air System Name AHU-06 Number of zones 1
Equipment Class CW AHU Floor Area 490.0 m²
Air System Type SZCAV Location Cairo, Egypt

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 91.6 kW Load occurs at Jul 1500
Sensible coil load 61.4 kW OA DB / WB 40.5 / 25.0 °C
Coil L/s at Jul 1500 4246 L/s Entering DB / WB 24.5 / 18.5 °C
Max block L/s 4246 L/s Leaving DB / WB 12.4 / 11.9 °C
Sum of peak zone L/s 4246 L/s Coil ADP 11.1 °C
Sensible heat ratio 0.670 Bypass Factor 0.100
m²/kW 5.3 Resulting RH 62 %
W/m² 187.0 Design supply temp. 12.8 °C
Water flow @ 5.6 °K rise 3.95 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 4246 L/s Fan motor BHP 7.91 BHP
Standard L/s 4209 L/s Fan motor kW 5.90 kW
Actual max L/(s-m²) 8.67 L/(s-m²) Fan static 750 Pa

Outdoor Ventilation Air Data


Design airflow L/s 463 L/s L/s/person 2.36 L/s/person
L/(s-m²) 0.94 L/(s-m²)

Hourly Analysis Program v.4.4 Page 1 of 1