You are on page 1of 34

Air System Sizing Summary for Ac Auditorio

Project Name: Auditorio 06/30/2021


Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

Air System Information


Air System Name Ac Auditorio Number of zones 1
Equipment Class SPLT AHU Floor Area 5012.7 ft²
Air System Type VAV Location Diriamba, Nicaragua

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Peak zone sensible load
Sizing Data Calculated Space CFM Sizing Coincident space loads

Central Cooling Coil Sizing Data


Total coil load 15.6 Tons Load occurs at Jul 1200
Total coil load 186.9 MBH OA DB / WB 85.5 / 68.3 °F
Sensible coil load 186.9 MBH Entering DB / WB 79.1 / 75.1 °F
Coil CFM at Jul 1200 84915 CFM Leaving DB / WB 77.0 / 74.6 °F
Max block CFM at Aug 2300 118948 CFM Coil ADP 76.8 °F
Sum of peak zone CFM 118948 CFM Bypass Factor 0.100
Sensible heat ratio 1.000 Resulting RH 86 %
CFM/Ton 5452.8 Design supply temp. 77.0 °F
ft²/Ton 321.9 Zone T-stat Check 1 of 1 OK
BTU/(hr·ft²) 37.3 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise N/A

Supply Fan Sizing Data


Actual max CFM at Aug 2300 118948 CFM Fan motor BHP 0.00 BHP
Standard CFM 117672 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 23.73 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 4126 CFM CFM/person 13.75 CFM/person
CFM/ft² 0.82 CFM/ft²

Hourly Analysis Program 5.11 Page 1 of 34


Zone Sizing Summary for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

Air System Information


Air System Name Ac Auditorio Number of zones 1
Equipment Class SPLT AHU Floor Area 5012.7 ft²
Air System Type VAV Location Diriamba, Nicaragua

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Peak zone sensible load
Sizing Data Calculated Space CFM Sizing Coincident space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 118948 4126 23.73 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 127.1 Aug 2300 0.0 5012.7

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Auditorio de colegio 1 127.1 Aug 2300 118948 0.0 5012.7 23.73

Hourly Analysis Program 5.11 Page 2 of 34


Ventilation Sizing Summary for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2016
Design Condition Minimum flow (heating)
Occupant Diversity (D) 1.000
Uncorrected Outdoor Air Intake (Vou) 3301 CFM
System Ventilation Efficiency (Ev) 1.000
Outdoor Air Intake (Vot) 4126 CFM

2. Space Ventilation Analysis


Time People Breathing
Minimum Space Floor Area Outdoor Averaged Outdoor Air Air Space Zone Space
Supply Air Area Air Rate Occupancy Rate Distribution Outdoor Air Outdoor Air Ventilation
(CFM) (ft²) (CFM/ft²) (Occupants) (CFM/person) Effectiveness (CFM) (CFM) Efficiency
Zone Name / Space Name Mult. (Vpz) (Az) (Ra) (Pz) (Rp) (Ez) (Voz) (Vbz) (Evz)
Zone 1
Auditorio de colegio 1 4126 5012.7 0.06 300.0 10.00 0.8 4126 3301 1.000
Totals (incl. Space Multipliers) 4126 3301 1.000

Hourly Analysis Program 5.11 Page 3 of 34


Air System Design Load Summary for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1200 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.5 °F / 68.3 °F HEATING OA DB / WB 75.1 °F / 73.6 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 563 ft² 2503 - 563 ft² - -
Wall Transmission 2653 ft² -446 - 2653 ft² 0 -
Roof Transmission 5013 ft² 5261 - 5013 ft² 0 -
Window Transmission 563 ft² 471 - 563 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 145 ft² 61 - 145 ft² 0 -
Floor Transmission 5013 ft² 0 - 5013 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 5364 W 15169 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 7125 W 20929 - 0 0 -
People 300 54028 136500 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 9798 13650 0% 0 0
>> Total Zone Loads - 107773 150150 - 0 0
Zone Conditioning - 157006 150150 - 11725 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 84915 CFM 0 - 4126 CFM 0 -
Ventilation Load 4126 CFM 29867 -145179 4126 CFM -11725 -6926
Supply Fan Load 84915 CFM 0 - 4126 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 186873 4971 - 0 -6926
Central Cooling Coil - 186873 0 - 0 0
>> Total Conditioning - 186873 0 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 4 of 34


Zone Design Load Summary for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 60.2 °F / 59.7 °F HEATING OA DB / WB 75.1 °F / 73.6 °F
OCCUPIED T-STAT 78.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 563 ft² 15199 - 563 ft² - -
Wall Transmission 2653 ft² 3671 - 2653 ft² 0 -
Roof Transmission 5013 ft² 107101 - 5013 ft² 0 -
Window Transmission 563 ft² -4682 - 563 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 145 ft² -604 - 145 ft² 0 -
Floor Transmission 5013 ft² 0 - 5013 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 0W 1065 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 1150 - 0 0 -
People 0 11727 0 0 0 0
Infiltration - -19096 51283 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 11553 5128 0% 0 0
>> Total Zone Loads - 127085 56412 - 0 0

Hourly Analysis Program 5.11 Page 5 of 34


Space Design Load Summary for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

TABLE 1.1.A. Component Loads For Space "Auditorio de colegio" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 2300 HEATING DATA AT DES HTG
COOLING OA DB / WB 60.2 °F / 59.7 °F HEATING OA DB / WB 75.1 °F / 73.6 °F
OCCUPIED T-STAT 78.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 563 ft² 15199 - 563 ft² - -
Wall Transmission 2653 ft² 3671 - 2653 ft² 0 -
Roof Transmission 5013 ft² 107101 - 5013 ft² 0 -
Window Transmission 563 ft² -4682 - 563 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 145 ft² -604 - 145 ft² 0 -
Floor Transmission 5013 ft² 0 - 5013 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 0W 1065 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 1150 - 0 0 -
People 0 11727 0 0 0 0
Infiltration - -19096 51283 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 11553 5128 0% 0 0
>> Total Zone Loads - 127085 56412 - 0 0

TABLE 1.1.B. Envelope Loads For Space "Auditorio de colegio" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 904 0.333 - 806 - 0
WINDOW 1 223 0.600 0.685 -1857 4969 0
E EXPOSURE
WALL 388 0.333 - 1332 - 0
WINDOW 1 116 0.600 0.685 -969 5324 0
DOOR 48 0.300 - -201 - 0
S EXPOSURE
WALL 807 0.333 - 151 - 0
WINDOW 1 223 0.600 0.685 -1857 4906 0
DOOR 97 0.300 - -403 - 0
W EXPOSURE
WALL 553 0.333 - 1382 - 0
H EXPOSURE
ROOF 5013 0.421 - 107101 - 0

Hourly Analysis Program 5.11 Page 6 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: JANUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 47.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 44.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 42.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 40.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 39.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 38.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 39.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 42.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 46.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 52.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 59.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 67.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 75.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 81.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 85.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 86.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 85.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 81.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 76.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 70.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 64.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 58.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 54.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 50.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: FEBRUARY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 49.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 46.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 44.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 42.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 41.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 40.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 41.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 44.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 48.3 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 54.6 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 61.7 30181 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 69.9 56964 46.5 46.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 77.5 62511 92.0 92.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 83.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 87.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 88.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 87.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 83.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 78.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 72.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 66.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 60.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 56.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 52.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 7 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: MARCH


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 52.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 49.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 47.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 45.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 44.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 43.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 44.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 47.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 51.3 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 57.6 42983 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 64.7 63143 37.1 37.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 72.9 67633 83.3 83.3 0.0 0.0 0.0 0.0 0.0 0.0
1200 80.5 72011 127.9 127.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 86.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 90.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 91.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 90.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 86.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 81.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 75.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 69.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 63.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 59.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 55.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: APRIL


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 53.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 50.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 48.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 46.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 45.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 44.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 45.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 48.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 52.3 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 58.6 61687 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 65.7 65599 47.1 47.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 73.9 69849 93.1 93.1 0.0 0.0 0.0 0.0 0.0 0.0
1200 81.5 74028 137.5 137.5 0.0 0.0 0.0 0.0 0.0 0.0
1300 87.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 91.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 92.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 91.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 87.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 82.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 76.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 70.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 64.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 60.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 56.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 8 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: MAY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 54.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 51.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 49.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 47.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 46.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 45.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 46.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 49.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 53.3 22189 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 59.6 67178 23.6 23.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 66.7 70348 62.9 62.9 0.0 0.0 0.0 0.0 0.0 0.0
1100 74.9 74107 108.4 108.4 0.0 0.0 0.0 0.0 0.0 0.0
1200 82.5 77839 152.4 152.4 0.0 0.0 0.0 0.0 0.0 0.0
1300 88.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 92.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 93.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 92.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 88.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 83.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 77.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 71.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 65.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 61.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 57.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: JUNE


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 56.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 53.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 51.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 49.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 48.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 47.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 48.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 51.0 71341 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 55.3 72230 17.5 17.5 0.0 0.0 0.0 0.0 0.0 0.0
0900 61.6 73998 49.5 49.5 0.0 0.0 0.0 0.0 0.0 0.0
1000 68.7 76564 88.1 88.1 0.0 0.0 0.0 0.0 0.0 0.0
1100 76.9 79755 133.0 133.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 84.5 82967 176.3 176.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 90.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 94.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 95.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 94.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 90.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 85.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 79.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 73.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 67.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 63.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 59.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 9 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: JULY


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 57.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 54.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 52.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 50.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 49.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 48.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 49.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 52.0 75028 10.3 10.3 0.0 0.0 0.0 0.0 0.0 0.0
0800 56.3 74888 28.9 28.9 0.0 0.0 0.0 0.0 0.0 0.0
0900 62.6 76489 60.7 60.7 0.0 0.0 0.0 0.0 0.0 0.0
1000 69.7 78874 99.0 99.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 77.9 81877 143.7 143.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 85.5 84915 186.9 186.9 0.0 0.0 0.0 0.0 0.0 0.0
1300 91.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 95.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 96.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 95.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 91.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 86.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 80.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 74.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 68.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 64.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 60.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: AUGUST


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 57.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 54.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 52.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 50.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 49.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 48.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 49.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 52.0 73711 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 56.3 73687 25.7 25.7 0.0 0.0 0.0 0.0 0.0 0.0
0900 62.6 75352 57.6 57.6 0.0 0.0 0.0 0.0 0.0 0.0
1000 69.7 77828 96.0 96.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 77.9 80938 140.9 140.9 0.0 0.0 0.0 0.0 0.0 0.0
1200 85.5 84079 184.2 184.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 91.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 95.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 96.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 95.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 91.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 86.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 80.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 74.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 68.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 64.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 60.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 10 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: SEPTEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 55.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 52.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 50.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 48.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 47.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 46.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 47.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 50.0 7849 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 54.3 67185 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 60.6 69330 33.2 33.2 0.0 0.0 0.0 0.0 0.0 0.0
1000 67.7 72253 72.2 72.2 0.0 0.0 0.0 0.0 0.0 0.0
1100 75.9 75838 117.5 117.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 83.5 79425 161.3 161.3 0.0 0.0 0.0 0.0 0.0 0.0
1300 89.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 93.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 94.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 93.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 89.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 84.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 78.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 72.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 66.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 62.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 58.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: OCTOBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 53.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 50.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 48.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 46.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 45.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 44.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 45.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 48.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 52.3 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 58.6 61987 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 65.7 65809 47.6 47.6 0.0 0.0 0.0 0.0 0.0 0.0
1100 73.9 69998 93.5 93.5 0.0 0.0 0.0 0.0 0.0 0.0
1200 81.5 74134 137.8 137.8 0.0 0.0 0.0 0.0 0.0 0.0
1300 87.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 91.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 92.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 91.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 87.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 82.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 76.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 70.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 64.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 60.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 56.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 11 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

DESIGN MONTH: NOVEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 50.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 47.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 45.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 43.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 42.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 41.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 42.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 45.0 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 49.3 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 55.6 4126 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 62.7 51062 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 70.9 57349 51.7 51.7 0.0 0.0 0.0 0.0 0.0 0.0
1200 78.5 62873 97.2 97.2 0.0 0.0 0.0 0.0 0.0 0.0
1300 84.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 88.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 89.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 88.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 84.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 79.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 73.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 67.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 61.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 57.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 53.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DESIGN MONTH: DECEMBER


CENTRAL CENTRAL CENTRAL ZONE
OA SUPPLY COOLING COOLING HEATING PRECOOL PREHEAT TERMINAL TERMINAL HEATING
TEMP AIRFLOW SENSIBLE TOTAL COIL COIL COIL COOLING HEATING UNIT
Hour (°F) (CFM) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH) (MBH)
0000 48.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0100 45.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0200 43.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0300 41.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0400 40.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0500 39.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0600 40.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0700 43.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0800 47.3 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0900 53.6 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1000 60.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1100 68.9 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1200 76.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1300 82.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1400 86.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1500 87.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1600 86.1 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1700 82.7 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1800 77.5 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
1900 71.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2000 65.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2100 59.8 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2200 55.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
2300 51.2 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 12 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: JANUARY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 47.3 81.0 - 0.0 65090.7 0.0 0.0 0.0 0.0
0100 44.9 80.7 - 0.0 56858.9 0.0 0.0 0.0 0.0
0200 42.5 79.4 - 0.0 36075.9 0.0 0.0 0.0 0.0
0300 40.6 77.2 - 0.0 4312.0 0.0 0.0 0.0 0.0
0400 39.2 74.1 - 0.0 -36774.5 0.0 0.0 0.0 0.0
0500 38.7 70.4 - 0.0 -84655.0 0.0 0.0 0.0 0.0
0600 39.7 67.9 - 0.0 -114571.0 0.0 0.0 0.0 0.0
0700 42.0 67.3 - 0.0 -115687.5 0.0 0.0 0.0 0.0
0800 46.3 67.6 - 0.0 -106272.9 0.0 0.0 0.0 0.0
0900 52.6 68.4 - 0.0 -91253.1 0.0 0.0 0.0 0.0
1000 59.7 69.6 - 0.0 -72873.9 0.0 0.0 0.0 0.0
1100 67.9 71.0 - 0.0 -51322.4 0.0 0.0 0.0 0.0
1200 75.5 72.5 - 0.0 -29946.9 0.0 0.0 0.0 0.0
1300 81.2 73.8 - 0.0 -12929.8 0.0 0.0 0.0 0.0
1400 85.1 74.7 - 0.0 -1002.9 0.0 0.0 0.0 0.0
1500 86.5 75.2 - 0.0 4564.7 0.0 0.0 0.0 0.0
1600 85.1 75.2 - 0.0 2200.4 0.0 0.0 0.0 0.0
1700 81.7 74.6 - 0.0 -6152.5 0.0 0.0 0.0 0.0
1800 76.5 73.6 - 0.0 -20213.4 0.0 0.0 0.0 0.0
1900 70.2 74.5 - 0.0 -8069.0 0.0 0.0 0.0 0.0
2000 64.0 76.4 - 0.0 17143.9 0.0 0.0 0.0 0.0
2100 58.8 78.3 - 0.0 41290.6 0.0 0.0 0.0 0.0
2200 54.0 79.8 - 0.0 57374.3 0.0 0.0 0.0 0.0
2300 50.2 80.6 - 0.0 64709.7 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: FEBRUARY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 49.3 88.3 - 0.0 96066.6 0.0 0.0 0.0 0.0
0100 46.9 88.0 - 0.0 87811.3 0.0 0.0 0.0 0.0
0200 44.5 86.6 - 0.0 66676.9 0.0 0.0 0.0 0.0
0300 42.6 84.4 - 0.0 34316.0 0.0 0.0 0.0 0.0
0400 41.2 81.3 - 0.0 -7313.1 0.0 0.0 0.0 0.0
0500 40.7 77.6 - 0.0 -54638.6 0.0 0.0 0.0 0.0
0600 41.7 74.6 - 0.0 -89964.5 0.0 0.0 0.0 0.0
0700 44.0 73.1 77 4126.0 23865.2 128096.6 0.0 0.0 0.0
0800 48.3 74.1 81 4126.0 30171.7 113687.5 0.0 0.0 0.0
0900 54.6 76.0 85 4126.0 39866.1 94310.8 0.0 0.0 0.0
1000 61.7 78.2 79 30181.2 51732.7 72900.6 0.0 0.0 0.0
1100 69.9 78.4 79 56963.9 65574.8 84073.5 0.0 0.0 0.0
1200 77.5 78.4 79 62511.3 79732.7 96109.6 0.0 0.0 0.0
1300 83.2 81.0 - 0.0 19538.6 0.0 0.0 0.0 0.0
1400 87.1 81.9 - 0.0 30650.7 0.0 0.0 0.0 0.0
1500 88.5 82.4 - 0.0 35430.7 0.0 0.0 0.0 0.0
1600 87.1 82.2 - 0.0 32305.0 0.0 0.0 0.0 0.0
1700 83.7 81.6 - 0.0 23216.1 0.0 0.0 0.0 0.0
1800 78.5 80.6 - 0.0 8444.0 0.0 0.0 0.0 0.0
1900 72.2 81.5 - 0.0 22033.6 0.0 0.0 0.0 0.0
2000 66.0 83.4 - 0.0 47027.7 0.0 0.0 0.0 0.0
2100 60.8 85.4 - 0.0 71481.7 0.0 0.0 0.0 0.0
2200 56.0 86.8 - 0.0 88125.3 0.0 0.0 0.0 0.0
2300 52.2 87.7 - 0.0 95807.8 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 13 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: MARCH
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 52.3 90.5 - 0.0 109954.8 0.0 0.0 0.0 0.0
0100 49.9 90.1 - 0.0 100325.5 0.0 0.0 0.0 0.0
0200 47.5 88.7 - 0.0 78086.3 0.0 0.0 0.0 0.0
0300 45.6 86.4 - 0.0 45150.4 0.0 0.0 0.0 0.0
0400 44.2 83.4 - 0.0 3726.2 0.0 0.0 0.0 0.0
0500 43.7 79.8 - 0.0 -42242.6 0.0 0.0 0.0 0.0
0600 44.7 76.9 - 0.0 -76667.9 0.0 0.0 0.0 0.0
0700 47.0 75.3 76 4126.0 32893.4 124693.8 0.0 0.0 0.0
0800 51.3 76.4 79 4126.0 39112.2 110301.1 0.0 0.0 0.0
0900 57.6 78.3 82 42983.0 48814.1 89355.4 0.0 0.0 0.0
1000 64.7 78.4 82 63143.0 60751.8 97544.0 0.0 0.0 0.0
1100 72.9 78.5 82 67632.8 74702.0 108148.8 0.0 0.0 0.0
1200 80.5 78.5 82 72011.2 88984.7 119233.2 0.0 0.0 0.0
1300 86.2 83.0 - 0.0 32454.3 0.0 0.0 0.0 0.0
1400 90.1 84.0 - 0.0 43692.7 0.0 0.0 0.0 0.0
1500 91.5 84.5 - 0.0 48592.5 0.0 0.0 0.0 0.0
1600 90.1 84.4 - 0.0 45578.5 0.0 0.0 0.0 0.0
1700 86.7 83.8 - 0.0 36592.7 0.0 0.0 0.0 0.0
1800 81.5 82.8 - 0.0 22011.3 0.0 0.0 0.0 0.0
1900 75.2 84.2 - 0.0 42420.1 0.0 0.0 0.0 0.0
2000 69.0 86.2 - 0.0 67589.1 0.0 0.0 0.0 0.0
2100 63.8 88.1 - 0.0 90068.1 0.0 0.0 0.0 0.0
2200 59.0 89.4 - 0.0 104860.0 0.0 0.0 0.0 0.0
2300 55.2 90.2 - 0.0 110818.6 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: APRIL
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 53.3 90.9 - 0.0 109049.9 0.0 0.0 0.0 0.0
0100 50.9 90.3 - 0.0 97881.9 0.0 0.0 0.0 0.0
0200 48.5 88.9 - 0.0 75296.4 0.0 0.0 0.0 0.0
0300 46.6 86.6 - 0.0 43079.0 0.0 0.0 0.0 0.0
0400 45.2 83.6 - 0.0 3153.5 0.0 0.0 0.0 0.0
0500 44.7 80.2 - 0.0 -41062.1 0.0 0.0 0.0 0.0
0600 45.7 77.4 - 0.0 -74025.6 0.0 0.0 0.0 0.0
0700 48.0 75.9 76 4126.0 34887.5 122851.8 0.0 0.0 0.0
0800 52.3 77.0 79 4126.0 41148.6 108502.0 0.0 0.0 0.0
0900 58.6 78.4 84 61686.8 50916.0 94257.7 0.0 0.0 0.0
1000 65.7 78.5 84 65599.5 62936.2 103255.3 0.0 0.0 0.0
1100 73.9 78.5 84 69848.9 76974.8 113662.4 0.0 0.0 0.0
1200 81.5 78.6 84 74028.4 91345.7 124608.5 0.0 0.0 0.0
1300 87.2 83.4 - 0.0 36078.7 0.0 0.0 0.0 0.0
1400 91.1 84.5 - 0.0 47397.3 0.0 0.0 0.0 0.0
1500 92.5 85.0 - 0.0 52372.0 0.0 0.0 0.0 0.0
1600 91.1 84.9 - 0.0 49427.4 0.0 0.0 0.0 0.0
1700 87.7 84.4 - 0.0 40505.9 0.0 0.0 0.0 0.0
1800 82.5 84.0 - 0.0 34644.1 0.0 0.0 0.0 0.0
1900 76.2 85.6 - 0.0 56090.0 0.0 0.0 0.0 0.0
2000 70.0 87.4 - 0.0 79169.9 0.0 0.0 0.0 0.0
2100 64.8 89.0 - 0.0 97692.5 0.0 0.0 0.0 0.0
2200 60.0 90.1 - 0.0 108647.9 0.0 0.0 0.0 0.0
2300 56.2 90.7 - 0.0 111667.3 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 14 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: MAY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 54.3 91.5 - 0.0 110810.9 0.0 0.0 0.0 0.0
0100 51.9 90.9 - 0.0 99603.5 0.0 0.0 0.0 0.0
0200 49.5 89.5 - 0.0 77743.8 0.0 0.0 0.0 0.0
0300 47.6 87.4 - 0.0 47118.2 0.0 0.0 0.0 0.0
0400 46.2 84.6 - 0.0 9595.9 0.0 0.0 0.0 0.0
0500 45.7 81.3 - 0.0 -32341.4 0.0 0.0 0.0 0.0
0600 46.7 78.5 - 0.0 -66638.3 0.0 0.0 0.0 0.0
0700 49.0 76.9 74 4126.0 40758.1 122724.5 0.0 0.0 0.0
0800 53.3 78.2 77 22188.9 47023.5 105034.5 0.0 0.0 0.0
0900 59.6 78.5 85 67178.2 56743.9 107041.3 0.0 0.0 0.0
1000 66.7 78.5 86 70348.4 68671.8 114932.4 0.0 0.0 0.0
1100 74.9 78.6 86 74106.7 82593.4 124820.7 0.0 0.0 0.0
1200 82.5 78.6 86 77839.4 96838.0 135267.6 0.0 0.0 0.0
1300 88.2 84.3 - 0.0 42622.6 0.0 0.0 0.0 0.0
1400 92.1 85.4 - 0.0 53819.6 0.0 0.0 0.0 0.0
1500 93.5 85.9 - 0.0 58680.0 0.0 0.0 0.0 0.0
1600 92.1 85.8 - 0.0 55629.5 0.0 0.0 0.0 0.0
1700 88.7 85.3 - 0.0 46610.5 0.0 0.0 0.0 0.0
1800 83.5 85.3 - 0.0 45583.9 0.0 0.0 0.0 0.0
1900 77.2 86.8 - 0.0 65754.2 0.0 0.0 0.0 0.0
2000 71.0 88.5 - 0.0 86513.2 0.0 0.0 0.0 0.0
2100 65.8 90.0 - 0.0 102830.4 0.0 0.0 0.0 0.0
2200 61.0 90.9 - 0.0 111965.7 0.0 0.0 0.0 0.0
2300 57.2 91.4 - 0.0 113922.4 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: JUNE
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 56.3 92.6 - 0.0 117134.4 0.0 0.0 0.0 0.0
0100 53.9 92.2 - 0.0 106977.2 0.0 0.0 0.0 0.0
0200 51.5 90.9 - 0.0 86554.3 0.0 0.0 0.0 0.0
0300 49.6 88.9 - 0.0 57882.8 0.0 0.0 0.0 0.0
0400 48.2 86.3 - 0.0 22658.3 0.0 0.0 0.0 0.0
0500 47.7 83.2 - 0.0 -17713.3 0.0 0.0 0.0 0.0
0600 48.7 80.1 - 0.0 -55144.1 0.0 0.0 0.0 0.0
0700 51.0 78.5 66 71340.7 48653.6 119568.1 0.0 0.0 0.0
0800 55.3 78.6 78 72229.9 54913.2 119807.4 0.0 0.0 0.0
0900 61.6 78.6 88 73997.7 64652.6 124525.6 0.0 0.0 0.0
1000 68.7 78.6 88 76563.6 76575.8 131623.9 0.0 0.0 0.0
1100 76.9 78.7 87 79754.9 90476.2 140889.9 0.0 0.0 0.0
1200 84.5 78.7 87 82966.6 104690.6 150747.0 0.0 0.0 0.0
1300 90.2 85.7 - 0.0 52798.1 0.0 0.0 0.0 0.0
1400 94.1 86.8 - 0.0 63961.0 0.0 0.0 0.0 0.0
1500 95.5 87.3 - 0.0 68788.6 0.0 0.0 0.0 0.0
1600 94.1 87.3 - 0.0 65707.5 0.0 0.0 0.0 0.0
1700 90.7 86.7 - 0.0 56660.4 0.0 0.0 0.0 0.0
1800 85.5 86.6 - 0.0 53451.5 0.0 0.0 0.0 0.0
1900 79.2 88.0 - 0.0 72572.9 0.0 0.0 0.0 0.0
2000 73.0 89.7 - 0.0 92627.9 0.0 0.0 0.0 0.0
2100 67.8 91.1 - 0.0 108442.1 0.0 0.0 0.0 0.0
2200 63.0 92.1 - 0.0 117521.7 0.0 0.0 0.0 0.0
2300 59.2 92.6 - 0.0 119799.5 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 15 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 57.3 93.3 - 0.0 122192.1 0.0 0.0 0.0 0.0
0100 54.9 92.9 - 0.0 112728.9 0.0 0.0 0.0 0.0
0200 52.5 91.7 - 0.0 92794.0 0.0 0.0 0.0 0.0
0300 50.6 89.7 - 0.0 63925.3 0.0 0.0 0.0 0.0
0400 49.2 87.1 - 0.0 28313.9 0.0 0.0 0.0 0.0
0500 48.7 84.0 - 0.0 -12155.1 0.0 0.0 0.0 0.0
0600 49.7 80.9 - 0.0 -50336.8 0.0 0.0 0.0 0.0
0700 52.0 78.6 67 75028.3 51609.6 127340.6 0.0 0.0 0.0
0800 56.3 78.6 79 74888.4 57829.3 126955.3 0.0 0.0 0.0
0900 62.6 78.6 86 76488.7 67600.4 131411.5 0.0 0.0 0.0
1000 69.7 78.6 86 78873.9 79566.4 138281.1 0.0 0.0 0.0
1100 77.9 78.7 86 81876.6 93512.8 147339.5 0.0 0.0 0.0
1200 85.5 78.7 86 84915.0 107773.1 157005.9 0.0 0.0 0.0
1300 91.2 86.2 - 0.0 57102.6 0.0 0.0 0.0 0.0
1400 95.1 87.4 - 0.0 68306.8 0.0 0.0 0.0 0.0
1500 96.5 87.9 - 0.0 73172.6 0.0 0.0 0.0 0.0
1600 95.1 87.9 - 0.0 70126.7 0.0 0.0 0.0 0.0
1700 91.7 87.4 - 0.0 61111.8 0.0 0.0 0.0 0.0
1800 86.5 86.9 - 0.0 53618.5 0.0 0.0 0.0 0.0
1900 80.2 88.4 - 0.0 72894.3 0.0 0.0 0.0 0.0
2000 74.0 90.1 - 0.0 93964.7 0.0 0.0 0.0 0.0
2100 68.8 91.6 - 0.0 110882.8 0.0 0.0 0.0 0.0
2200 64.0 92.6 - 0.0 121138.1 0.0 0.0 0.0 0.0
2300 60.2 93.2 - 0.0 124296.2 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: AUGUST
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 57.3 93.4 - 0.0 124800.0 0.0 0.0 0.0 0.0
0100 54.9 93.0 - 0.0 114443.4 0.0 0.0 0.0 0.0
0200 52.5 91.6 - 0.0 92945.8 0.0 0.0 0.0 0.0
0300 50.6 89.5 - 0.0 61957.6 0.0 0.0 0.0 0.0
0400 49.2 86.7 - 0.0 23255.7 0.0 0.0 0.0 0.0
0500 48.7 83.3 - 0.0 -20009.0 0.0 0.0 0.0 0.0
0600 49.7 80.5 - 0.0 -54268.2 0.0 0.0 0.0 0.0
0700 52.0 78.6 67 73711.0 49380.2 123751.0 0.0 0.0 0.0
0800 56.3 78.6 80 73687.5 55649.9 123687.5 0.0 0.0 0.0
0900 62.6 78.6 86 75351.6 65434.0 128232.6 0.0 0.0 0.0
1000 69.7 78.6 86 77828.2 77466.2 135235.5 0.0 0.0 0.0
1100 77.9 78.7 86 80937.5 91513.7 144455.5 0.0 0.0 0.0
1200 85.5 78.7 86 84079.4 105892.0 154295.2 0.0 0.0 0.0
1300 91.2 86.0 - 0.0 55344.4 0.0 0.0 0.0 0.0
1400 95.1 87.2 - 0.0 66669.2 0.0 0.0 0.0 0.0
1500 96.5 87.7 - 0.0 71650.0 0.0 0.0 0.0 0.0
1600 95.1 87.7 - 0.0 68711.8 0.0 0.0 0.0 0.0
1700 91.7 87.2 - 0.0 59796.6 0.0 0.0 0.0 0.0
1800 86.5 86.6 - 0.0 50703.2 0.0 0.0 0.0 0.0
1900 80.2 88.1 - 0.0 71375.3 0.0 0.0 0.0 0.0
2000 74.0 90.0 - 0.0 94217.3 0.0 0.0 0.0 0.0
2100 68.8 91.6 - 0.0 112650.5 0.0 0.0 0.0 0.0
2200 64.0 92.8 - 0.0 123724.9 0.0 0.0 0.0 0.0
2300 60.2 93.3 - 0.0 127085.3 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 16 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: SEPTEMBER
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 55.3 92.4 - 0.0 120268.4 0.0 0.0 0.0 0.0
0100 52.9 91.8 - 0.0 107458.5 0.0 0.0 0.0 0.0
0200 50.5 90.2 - 0.0 82504.9 0.0 0.0 0.0 0.0
0300 48.6 87.7 - 0.0 47548.4 0.0 0.0 0.0 0.0
0400 47.2 84.5 - 0.0 4878.1 0.0 0.0 0.0 0.0
0500 46.7 80.9 - 0.0 -41480.9 0.0 0.0 0.0 0.0
0600 47.7 78.7 - 0.0 -67013.5 0.0 0.0 0.0 0.0
0700 50.0 78.0 73 7848.9 42846.9 112146.2 0.0 0.0 0.0
0800 54.3 78.5 77 67185.3 49068.6 107059.2 0.0 0.0 0.0
0900 60.6 78.5 85 69329.9 58699.6 112354.6 0.0 0.0 0.0
1000 67.7 78.6 85 72252.9 70610.1 119867.8 0.0 0.0 0.0
1100 75.9 78.6 85 75838.2 84568.8 129586.1 0.0 0.0 0.0
1200 83.5 78.6 85 79424.7 98881.9 139907.0 0.0 0.0 0.0
1300 89.2 84.8 - 0.0 45928.4 0.0 0.0 0.0 0.0
1400 93.1 85.9 - 0.0 57214.3 0.0 0.0 0.0 0.0
1500 94.5 86.4 - 0.0 62163.4 0.0 0.0 0.0 0.0
1600 93.1 86.3 - 0.0 59198.4 0.0 0.0 0.0 0.0
1700 89.7 85.8 - 0.0 50260.3 0.0 0.0 0.0 0.0
1800 84.5 85.3 - 0.0 42723.8 0.0 0.0 0.0 0.0
1900 78.2 87.0 - 0.0 65136.5 0.0 0.0 0.0 0.0
2000 72.0 88.9 - 0.0 89567.3 0.0 0.0 0.0 0.0
2100 66.8 90.7 - 0.0 109224.6 0.0 0.0 0.0 0.0
2200 62.0 91.8 - 0.0 120666.0 0.0 0.0 0.0 0.0
2300 58.2 92.4 - 0.0 123467.7 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: OCTOBER
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 53.3 91.2 - 0.0 113309.1 0.0 0.0 0.0 0.0
0100 50.9 90.4 - 0.0 98688.1 0.0 0.0 0.0 0.0
0200 48.5 88.7 - 0.0 71611.2 0.0 0.0 0.0 0.0
0300 46.6 86.0 - 0.0 34209.7 0.0 0.0 0.0 0.0
0400 45.2 82.6 - 0.0 -11270.0 0.0 0.0 0.0 0.0
0500 44.7 78.7 - 0.0 -60276.6 0.0 0.0 0.0 0.0
0600 45.7 76.9 - 0.0 -78317.0 0.0 0.0 0.0 0.0
0700 48.0 75.9 75 4126.0 37131.4 122979.2 0.0 0.0 0.0
0800 52.3 77.0 79 4126.0 43340.6 108710.7 0.0 0.0 0.0
0900 58.6 78.4 84 61987.2 52832.9 94929.8 0.0 0.0 0.0
1000 65.7 78.5 84 65809.1 64603.3 103753.1 0.0 0.0 0.0
1100 73.9 78.5 84 69998.2 78434.3 114041.2 0.0 0.0 0.0
1200 81.5 78.6 84 74134.3 92633.2 124896.1 0.0 0.0 0.0
1300 87.2 83.5 - 0.0 37221.4 0.0 0.0 0.0 0.0
1400 91.1 84.5 - 0.0 48416.2 0.0 0.0 0.0 0.0
1500 92.5 85.0 - 0.0 53283.6 0.0 0.0 0.0 0.0
1600 91.1 84.9 - 0.0 50245.2 0.0 0.0 0.0 0.0
1700 87.7 84.4 - 0.0 41240.9 0.0 0.0 0.0 0.0
1800 82.5 83.9 - 0.0 34363.7 0.0 0.0 0.0 0.0
1900 76.2 85.8 - 0.0 59263.4 0.0 0.0 0.0 0.0
2000 70.0 87.8 - 0.0 84636.0 0.0 0.0 0.0 0.0
2100 64.8 89.5 - 0.0 104466.7 0.0 0.0 0.0 0.0
2200 60.0 90.7 - 0.0 115341.2 0.0 0.0 0.0 0.0
2300 56.2 91.1 - 0.0 117426.5 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 17 of 34


Hourly Zone Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:22p. m.

ZONE: Zone 1
DESIGN MONTH: NOVEMBER
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 50.3 88.3 - 0.0 93792.1 0.0 0.0 0.0 0.0
0100 47.9 87.5 - 0.0 79943.0 0.0 0.0 0.0 0.0
0200 45.5 85.8 - 0.0 53775.6 0.0 0.0 0.0 0.0
0300 43.6 83.2 - 0.0 17201.2 0.0 0.0 0.0 0.0
0400 42.2 79.7 - 0.0 -28030.8 0.0 0.0 0.0 0.0
0500 41.7 75.7 - 0.0 -78628.0 0.0 0.0 0.0 0.0
0600 42.7 74.1 - 0.0 -93773.1 0.0 0.0 0.0 0.0
0700 45.0 73.3 78 4126.0 26194.4 124767.1 0.0 0.0 0.0
0800 49.3 74.4 81 4126.0 32434.8 110509.0 0.0 0.0 0.0
0900 55.6 76.2 86 4126.0 41895.0 91151.1 0.0 0.0 0.0
1000 62.7 78.3 85 51061.8 53620.5 72283.3 0.0 0.0 0.0
1100 70.9 78.4 85 57349.3 67405.5 84878.8 0.0 0.0 0.0
1200 78.5 78.4 85 62873.5 81561.2 96930.3 0.0 0.0 0.0
1300 84.2 81.1 - 0.0 22575.6 0.0 0.0 0.0 0.0
1400 88.1 82.1 - 0.0 33735.9 0.0 0.0 0.0 0.0
1500 89.5 82.5 - 0.0 38573.2 0.0 0.0 0.0 0.0
1600 88.1 82.4 - 0.0 35508.8 0.0 0.0 0.0 0.0
1700 84.7 81.9 - 0.0 26482.4 0.0 0.0 0.0 0.0
1800 79.5 80.9 - 0.0 12846.3 0.0 0.0 0.0 0.0
1900 73.2 82.8 - 0.0 39217.3 0.0 0.0 0.0 0.0
2000 67.0 84.8 - 0.0 64192.8 0.0 0.0 0.0 0.0
2100 61.8 86.4 - 0.0 84043.0 0.0 0.0 0.0 0.0
2200 57.0 87.5 - 0.0 95022.0 0.0 0.0 0.0 0.0
2300 53.2 88.0 - 0.0 97453.0 0.0 0.0 0.0 0.0

ZONE: Zone 1
DESIGN MONTH: DECEMBER
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 48.3 81.4 - 0.0 65757.7 0.0 0.0 0.0 0.0
0100 45.9 80.9 - 0.0 55066.5 0.0 0.0 0.0 0.0
0200 43.5 79.4 - 0.0 32113.7 0.0 0.0 0.0 0.0
0300 41.6 77.1 - 0.0 -1414.8 0.0 0.0 0.0 0.0
0400 40.2 73.9 - 0.0 -43982.4 0.0 0.0 0.0 0.0
0500 39.7 70.0 - 0.0 -93789.3 0.0 0.0 0.0 0.0
0600 40.7 68.1 - 0.0 -113867.4 0.0 0.0 0.0 0.0
0700 43.0 67.8 - 0.0 -111815.3 0.0 0.0 0.0 0.0
0800 47.3 68.2 - 0.0 -102441.5 0.0 0.0 0.0 0.0
0900 53.6 69.0 - 0.0 -87526.0 0.0 0.0 0.0 0.0
1000 60.7 70.1 - 0.0 -69200.2 0.0 0.0 0.0 0.0
1100 68.9 71.5 - 0.0 -47658.6 0.0 0.0 0.0 0.0
1200 76.5 73.1 - 0.0 -26265.3 0.0 0.0 0.0 0.0
1300 82.2 74.3 - 0.0 -9215.0 0.0 0.0 0.0 0.0
1400 86.1 75.3 - 0.0 2753.2 0.0 0.0 0.0 0.0
1500 87.5 75.8 - 0.0 8365.4 0.0 0.0 0.0 0.0
1600 86.1 75.7 - 0.0 6046.6 0.0 0.0 0.0 0.0
1700 82.7 75.2 - 0.0 -2261.6 0.0 0.0 0.0 0.0
1800 77.5 74.2 - 0.0 -16279.1 0.0 0.0 0.0 0.0
1900 71.2 75.6 - 0.0 2326.3 0.0 0.0 0.0 0.0
2000 65.0 77.5 - 0.0 26924.4 0.0 0.0 0.0 0.0
2100 59.8 79.3 - 0.0 48772.4 0.0 0.0 0.0 0.0
2200 55.0 80.5 - 0.0 62198.5 0.0 0.0 0.0 0.0
2300 51.2 81.2 - 0.0 67102.7 0.0 0.0 0.0 0.0

Hourly Analysis Program 5.11 Page 18 of 34


System Psychrometrics for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

July DESIGN COOLING DAY, 1200

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 85.5 0.01098 4126 400 29867 -145179
Vent - Return Mixing Outlet 79.1 0.01811 84915 1420 - -
Central Cooling Coil Outlet 77.0 0.01811 84915 1420 186873 0
Supply Fan Outlet 77.0 0.01811 84915 1420 0 -
Cold Supply Duct Outlet 77.0 0.01811 84915 1420 - -
Zone Air - 78.7 0.01849 84915 1472 157006 150150
Return Plenum Outlet 78.7 0.01849 84915 1472 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.068 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4695.7 BTU/(hr-CFM)
Site Altitude = 298.3 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 107773 Cooling 157006 78.7 84915 1472 0 0

Hourly Analysis Program 5.11 Page 19 of 34


System Psychrometrics for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 75.1 0.01770 4126 400 11725 6926
Vent - Return Mixing Outlet 75.1 0.01770 4126 400 - -
Central Cooling Coil Outlet 75.1 0.01770 4126 400 0 0
Supply Fan Outlet 75.1 0.01770 4126 400 0 -
Cold Supply Duct Outlet 75.1 0.01770 4126 400 - -
Zone Air - 72.4 0.01734 4126 400 -11725 0
Return Plenum Outlet 72.4 0.01734 4126 400 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.068 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4695.7 BTU/(hr-CFM)
Site Altitude = 298.3 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 0 Deadband -11725 72.4 4126 400 0 0

Hourly Analysis Program 5.11 Page 20 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for January

Total Cooling Total Heating


0.10
0.08
0.06
0.04
Load ( MBH )

0.02
0.00
-0.02
-0.04
-0.06
-0.08
-0.10
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for February

Total Cooling Total Heating


90

80

70

60
Load ( MBH )

50

40

30

20

10

0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 21 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for March

Total Cooling Total Heating


130
120
110
100
90
Load ( MBH )

80
70
60
50
40
30
20
10
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for April

Total Cooling Total Heating


140

120

100
Load ( MBH )

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 22 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for May

Total Cooling Total Heating

140

120

100
Load ( MBH )

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for June

Total Cooling Total Heating


180

160

140

120
Load ( MBH )

100

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 23 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for July

Total Cooling Total Heating


180
160
140
Load ( MBH )

120
100
80
60
40
20
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for August

Total Cooling Total Heating


180

160

140

120
Load ( MBH )

100

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 24 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for September

Total Cooling Total Heating


160

140

120
Load ( MBH )

100

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for October

Total Cooling Total Heating


140

120

100
Load ( MBH )

80

60

40

20

0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 25 of 34


Hourly Air System Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Data for November

Total Cooling Total Heating


100
90
80
70
Load ( MBH )

60
50
40
30
20
10
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Data for December

Total Cooling Total Heating


0.10
0.08
0.06
0.04
Load ( MBH )

0.02
0.00
-0.02
-0.04
-0.06
-0.08
-0.10
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day

Hourly Analysis Program 5.11 Page 26 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for January

Zone Sensible Zone Conditioning


60000

40000

20000

0
BTU/hr

-20000

-40000

-60000

-80000

-100000

00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: Zone 1
Data for February

Zone Sensible Zone Conditioning


120K
100K
80K
60K
40K
BTU/hr

20K
0
-20K
-40K
-60K
-80K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 27 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for March

Zone Sensible Zone Conditioning


120K

100K

80K

60K

40K
BTU/hr

20K

-20K

-40K

-60K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for April

Zone Sensible Zone Conditioning


120K

100K

80K

60K

40K
BTU/hr

20K

-20K

-40K

-60K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 28 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for May

Zone Sensible Zone Conditioning

120K

100K

80K

60K
BTU/hr

40K

20K

-20K

-40K

-60K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for June

Zone Sensible Zone Conditioning

140K

120K
100K

80K
BTU/hr

60K
40K

20K
0

-20K

-40K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 29 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for July

Zone Sensible Zone Conditioning


160K
140K
120K
100K
80K
BTU/hr

60K
40K
20K
0
-20K
-40K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for August

Zone Sensible Zone Conditioning

140K
120K
100K
80K
BTU/hr

60K
40K
20K
0
-20K
-40K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 30 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for September

Zone Sensible Zone Conditioning


140K
120K
100K
80K
60K
BTU/hr

40K
20K
0
-20K
-40K
-60K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for October

Zone Sensible Zone Conditioning


120K

100K

80K

60K

40K
BTU/hr

20K

-20K

-40K

-60K

-80K
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 31 of 34


Hourly Zone Design Day Loads for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Zone: Zone 1
Data for November

Zone Sensible Zone Conditioning


120K
100K
80K
60K
40K
BTU/hr

20K
0
-20K
-40K
-60K
-80K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: Zone 1
Data for December

Zone Sensible Zone Conditioning


60K

40K

20K

0
BTU/hr

-20K

-40K

-60K

-80K

-100K

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day

Hourly Analysis Program 5.11 Page 32 of 34


System Psychrometrics for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Location: Diriamba, Nicaragua


Altitude: 298.3 ft.
Data for: July DESIGN COOLING DAY, 1200
0.020
1. Outdoor Air 5
2. Mixed Air 34
3. Central Cooling Coil Outlet 2
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

1 0.012

0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 33 of 34


System Psychrometrics for Ac Auditorio
Project Name: Auditorio 06/30/2021
Prepared by: HVAC SIMPLIFIED AMK 02:23p. m.

Location: Diriamba, Nicaragua


Altitude: 298.3 ft.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Supply Fan Outlet
3. Room Air 12
3 0.018

0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 34 of 34

You might also like