Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
2ND-AUDITORIUM 1 163.7 Jul 1300 9744 20.8 3498.3 2.79
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 9744 CFM
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
2ND-AUDITORIUM ENTRANCE 1 8.7 Jul 1300 487 1.0 269.1 1.81
Zone 2
2ND-AUD.02-WAITING ROOM 1 75.6 Aug 1300 4235 8.8 1722.2 2.46
Zone 3
2ND-AUD.5-CONTROL 1 15.7 Jul 1300 880 0.5 139.9 6.29
Zone 4
2ND-MEP.6-ELEC ROOM 1 10.7 Jul 1300 598 0.3 75.3 7.93
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 902 CFM